LEGRAND GFCI Installing And Testing

• To prevent severe shock or
electrocution, always turn the power OFF at the service panel before working with wiring.
• Use this GFCI receptacle with copper or copper-clad wire. Do not use it with aluminum wire.
• For installation in wet locations, protect the GFCI receptacle with a weatherproof cover that will keep both the receptacle and any plugs dry.
• Must be installed in accordance with national and local electrical codes.
3. Should you install it?
Installing a GFCI receptacle can be more complicated than installing a conventional receptacle.
Make sure that you:
• Understand basic wiring principles and techniques.
• Can interpret wiring diagrams.
• Have circuit wiring experience.
• Are prepared to take a few minutes to test your work, making sure that you have wired the GFCI receptacle correctly.
6. Identify cables/wires
IMPORTANT:
Do not install the GFCI receptacle in an electrical box containing (a) more than 4 wires (not including the grounding wires) or (b) cables with more than two wires (not including the grounding wire). Contact a qualified electrician if either (a) or (b) is true.
• If you are replacing an old receptacle, pull it out of the electrical box without disconnecting the wires.
• If you see one cable (2-3 wires), it is the LINE cable. The receptacle is probably in position C (see diagram to the right). Remove the receptacle and go to step 7A.
• If you see two cables (4-6 wires), the receptacle is probably in position A or B (see diagram to the right). Follow steps a-e of the procedure to the right.
Procedure: box with two cables (4-6 wires)
(a)   Detach one cable’s white and  hot 
wires from the receptacle and cap each one separately with a wire connector. Make sure that they are from the same cable.
(b) Re-install the receptacle in the
electrical box, attach the faceplate, then turn the power ON at the service panel.
(c) Determine if power is flowing to the
receptacle. If so, the capped wires are the LOAD wires. If not, the capped wires are the LINE wires.
(d) Turn the power OFF at the service
panel, label the LINE and LOAD wires, then remove the receptacle.
(e) Go to step 7B.
Placement in circuit:
The GFCI’s place in the  circuit  determines if it protects other receptacles in the circuit.
Sample circuit:
Placing the GFCI in position A will also provide protection to “load side” receptacles B and C. On the other hand, placing the GFCI in position C will not provide protection to receptacles A or B. Remember that receptacles A, B, and C can be in different rooms.
1. What is a GFCI?
A GFCI receptacle is different from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.
Definition of a ground fault:
Instead of following its normal safe path, electricity passes through a person’s body to reach the  ground.  For example, a defective appliance can cause a ground fault.
A GFCI receptacle does not protect against circuit overloads, short circuits, or shocks. For example, you can still be shocked if you touch bare wires while standing on a non-conducting surface such as a wood floor.
Self-Test GFCI Receptacle with SafeLock Protection
This is a Self-Test GFCI Receptacle with SafeLock™ Protection; it
conducts an automatic test every three seconds, ensuring it’s always ready  to protect. If the device fails the test, the indicator light flashes to signal that the GFCI should be replaced. It also has our proven SafeLock Protection feature: if critical components are damaged and protection is lost, power to this receptacle, and any downstream receptacles, will be disconnected.
5. Turn the power OFF
Plug an electrical device, such as a lamp or radio, into the receptacle on which you are working. Turn the lamp or radio on. Then, go to the service panel. Find the breaker or fuse that protects that receptacle. Place the breaker in the OFF position or completely remove the fuse. The lamp or radio should turn OFF.
Next, plug in and turn ON the lamp or
radio at the receptacle’s other  outlet 
to make sure the power is OFF at both outlets. If the power is not OFF, stop work and call an electrician to complete the installation.
2. The GFCI’s features
ABC
LINE
LOAD
Service
Panel
LOAD
LINE LINE
FRONT VIEW
Screw (terminal) colors: Green = grounding terminals Silver = white terminals Brass = hot terminals
BACK VIEW
Installing and
Testing a
GFCI Receptacle
!
CAUTION
P.O. Box 4822 (800) 223-4185 Syracuse, NY 13221 www.legrand.us
For covering patents, see www.legrand.us/patents Nº 341082
Please read this leaflet
completely before
getting started.
Receptacle
Outlet
Reset button: See step 8
Indicator Light
TEST button: See step 8
Outlet
Mounting bracket
LINE
Hot terminal
(Brass):
Connection
for the LINE
cable’s black 
wire
LOAD
Hot terminal
(Brass):
Connection
for the LOAD
cable’s black 
wire
A yellow sticker covers the LOAD terminals. Do not remove the sticker at this time.
Grounding terminal (Green): Connection for bare copper or green wire
LINE White terminal (Silver): Connection
for the LINE cable’s 
white wire
LOAD White terminal (Silver): Connection
for the LOAD cable’s 
white wire
4. LINE vs. LOAD
A cable consists of 2 or 3 wires.
LINE cable:
Delivers power from the service panel (breaker panel or fuse box) to the GFCI. If there is only one cable entering the electrical box, it is the LINE cable. This cable should
be connected to the GFCI’s  LINE 
terminals only.
LOAD cable:
Delivers power from the GFCI to another receptacle in the circuit. This cable should be connected to the
GFCI’s LOAD terminals only. The 
LOAD terminals are under the yellow sticker. Do not remove the sticker at this time.
About wire connections:
Connect the LINE cable wires to the LINE terminals:
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the LOAD cable wires to the LOAD terminals:
• Remove the yellow sticker to reveal the LOAD terminals
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the grounding wires as shown above (only if there is a grounding wire):
• Connect a 6-inch bare copper (or green) 12 or 14 AWG wire to the grounding terminal on the GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires to
the LINE and LOAD cable’s  bare copper (or green) wire  using a wire connector. 
If these wires are already in place, check the connections.
Complete the installation:
• Fold the wires into the box, keeping the grounding wire away from the White and Hot terminals. Screw the receptacle to the box and attach the faceplate.
• Go to step 8.
A: One cable (2 or 3 wires) entering the box B: Two cables (4 or 6 wires) entering the box
OU
About wire connections:
Connect the LINE cable wires to the LINE terminals:
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the grounding wire (only if there is a grounding wire):
• For a box with no grounding terminal (diagram not shown): Connect the LINE
cable’s bare copper (or green)  wire directly to the grounding  terminal on the 
GFCI receptacle.
• For a box with a grounding terminal (diagram shown above): Connect a 6-inch bare copper (or green) 12 or 14 AWG wire to the grounding terminal on the GFCI. Also connect a similar wire to the grounding terminal on the box. Connect the ends of these wires  to the LINE cable’s bare  copper (or green) wire using  a wire connector. If these wires are already in place, check the connections.
Complete the installation:
• Fold the wires into the box, keeping the grounding wire away from the White and Hot terminals. Screw the receptacle to the box and attach the faceplate.
• Go to step 8.
8. Test your work
Why perform this test?
• If you miswired the GFCI, it may not prevent personal injury or death due to a ground fault (electrical shock).
Procedure:
(a) Turn the power ON at the service panel. Press the RESET button
fully. The RESET button should stay in. If the RESET button does not stay in, go to Troubleshooting. If the RESET button stays in, plug a lamp or radio into the GFCI (and leave it plugged in) to verify that the power is ON. If there is no power, go to Troubleshooting.
(b) Press the TEST button in order to trip the device. This should
stop the flow of electricity, making the radio or lamp shut OFF and the GFCI’s red Indicator  Light (if present) come on.  Note  that the RESET button will pop-out. If the power stays ON, or the red Indicator Light stays off, go to Troubleshooting. If the power goes OFF, and the red Indicator Light comes on, you have installed the GFCI receptacle correctly. To restore power, press the RESET button.
(c) If you installed your GFCI using step 7B, plug a lamp or radio into
surrounding receptacles to see which one(s), in addition to the GFCI, lost power when you pressed the TEST button. Do not plug life saving devices into any receptacles that lost power. Place a “GFCI Protected” sticker on every receptacle that lost power.
(d) Press the TEST button (then RESET button) every month to assure proper operation. (e) This is a Self-Test GFCI Receptacle with SafeLock Protection™; it conducts
an automatic test every three  seconds, ensuring it’s always ready  to protect. If 
the device fails the test, the indicator light flashes to signal that the GFCI should be replaced. It also has our proven SafeLock Protection feature: if critical components are damaged and protection is lost, power to this receptacle, and any downstream receptacles, will be disconnected.
7. Connect the wires (choose A or B)… only after reading other side completely
Screw Terminal
Wire
1 inch
Side Wire
Clockwise, 2/3 of the way around screw
LINE cable brings power to the GFCI
Grounding connection to box (if box has a grounding terminal)
Wire
connector
Electrical
box
LOAD cable
feeds power to
other receptacles
Screw Terminal
Wire
1 inch
Back Wire Holes
Wire
.5 inch
Back Wire Holes
Wire
.5 inch
TROUBLESHOOTING
Turn the power OFF and check the wire connections against the appropriate wiring diagram in step 7A or 7B. Make sure that there are no loose wires or loose connections. Also, it is possible that you reversed the LINE and LOAD connections. LINE/LOAD reversal will be indicated by no power at the GFCI and by the RESET button not staying
in when pressed, or by the red Indicator Light remaining off after you press the GFCI’s
TEST button. Reverse the LINE and LOAD connections if necessary. Start the test from the beginning of step 8 if you rewired any connections to the GFCI.
Side Wire
Clockwise, 2/3 of the way around screw
Back Wire
2. Securely tighten screw beneath wire hole to retain inserted wire.
1. Insert wire to bottom of hole.
Back Wire
2. Securely tighten screw beneath wire hole to retain inserted wire.
1. Insert wire to bottom of hole.
LIMITED ONE YEAR WARRANTY
Pass & Seymour will remedy any defect in workmanship or material in Pass & Seymour products which may develop under proper and normal use within one year from date of purchase by a consumer:
(1) by repair or replacement, or, at Pass &  Seymour’s option, (2) by return of an amount equal  to consumer’s purchase price. 
Such remedy is IN LIEU OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Such remedy by Pass & Seymour does not include or cover cost of labor for removal or reinstallation of the product. ALL OTHER FURTHER ELEMENTS OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES) FOR BREACH OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXCLUDED HEREBY. (Some states do not allow disclaimers or exclusion or limitation of incidental or consequential damages, so the above disclaimer and limitation or exclusion may not apply to you.) ANY IMPLIED WARRANTIES INCLUDING WHERE REQUIRED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED TO THE ONE YEAR PERIOD SET FORTH ABOVE. (Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.)
To insure safety, all repairs to Pass & Seymour products must be made by Pass & Seymour, or under its specific direction. Procedure to obtain performance of any warranty obligation is as follows: (1) Contact Pass & Seymour, Syracuse, New York 13221, for instructions concerning return or repair; (2) return the product to Pass & Seymour, postage paid, with your name and address and a written description of the installation or use of the Pass & Seymour product, and the observed defects or failure to operate, or other claimed basis for dissatisfaction.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Ratings: 15A 125V 60Hz 20A 125V 60Hz
LINE cable brings power to the GFCI
Grounding connection to box (if box has a grounding terminal)
Wire
connector
Electrical
box
Yellow sticker remains in place to cover the LOAD terminals
Loading...