Legrand FS User Manual

FlameStopper
Thru-Wall & Thru-Floor Fittings
INSTALLATION INSTRUCTIONS
Installation Instruction No.: INS0010R2 – Updated January 2007
Wiremold / Legrand Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold / Legrand electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local building codes and/ or the National Electrical Code.
1. Determine location and drill pilot hole thru wall or floor.
Drill hole using 4 3/4" [120mm] for FS4R and 2 1/4" [58mm] for FS2R.
NOTE: Use core drill when going
through concrete or block walls or floors.
2. Measure wall or floor thickness. Cut EMT Sleeve to length.
3. Peel off backing for adhesive.
1. Insert EMT into Box.
Wall or Floor Thickness
Wall or Floor Thickness + 1 5/8" [41mm]
4. Stick on Wall or floor (Make sure wall or floor is clean and dust-free).
NOTE: Do not force EMT through
intumescent material.
NOTE: Do not over tighten.
2. Tighten Clamp.
5. Install cabling then adjust sliding doors to be snug around cables by turning side screws.
4.
Products Covered: FS2R, FS4R, FS2RHS, FS4RHS, FS2RWP8, FS4RWP12
6. Ground in accordance with National Electrical Codes.
7. Fill out and place label on wall or floor near FlameStopper.
Minimum Spacing
CAT NO. MINIMUM SPACING
FS4R 6 1/8" [155MM]
FS2R 3 7/8" [98MM]
FS2R, FS4R INSTALLATION – Thru-Wall & Thru-Floor:
3.
1. Peel off backing for adhesive.
2. Stick on Wall or floor.
3. Tighten Clamp.
2
1. Wall Assembly – The 1, 2, 3 or 4 hr fire-rated gypsum board/stud wall assembly shall
be constructed of the materials and in the manner described within the individual U300, U400 or V400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs – Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. [51 by 102 mm] lumber spaced max 16 in. [406 mm] OC. Steel studs to be min 1-5/8 in. [41 mm] wide and spaced max 24 in. [610 mm] OC.
B. Gypsum Board* – Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Diam of opening shall be 2-1/4 in. [57 mm] and 4-3/4 in. [121 mm] for the nom 2 in. [51 mm] and 4 in. [102 mm] sleeves (Item 2), respectively.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Metallic Sleeve – Nom 2 in. [51 mm] or 4 in. [102 mm] diam electrical metallic tubing
(EMT), dependent on the size of the firestop device (Item 4). The sleeve is to extend a nom 3/4 in. beyond both surfaces of wall. The annular space between the sleeve and the periphery of opening shall be min 0 in. (continuous point contact) to max 1/4 in. [6 mm].
3. Cables – Aggregate cross-sectional area of cables in the EMT sleeve to be 0% to max
60% of the aggregate cross-sectional area of the EMT sleeve. When there is no cable fill, device cover is to be tightly closed. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Single conductor No. 18 AWG (or smaller) RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
B. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diameter of 5/8 in. [16 mm].
C. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) or plenum rated jacketing and insulation.
D. Max 4/C No. 2 AWG (or smaller) copper conductor cable with XLPE/PVX insulation and PVC jacket.
E. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
F. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
G. Max 8/C 12 AWG (or smaller) copper conductor steel Metal-Clad or Armored-Clad cable.
The hourly T Rating of the firestop system is equal to the F Rating when no cable fill is used or when cables A or B are used. The hourly T Rating is equal to the F Rating up to 3 hr when cable C is used. The hourly T Rating is 1 hr when cable D is installed in 2, 3 or 4 hr rated walls, 1/2 hr in 1 hr rated walls. The hourly T Rating is 1 hr when cable E is installed in 4 hr rated walls and 0 hr in 1, 2 or 3 hr rated walls. The hourly T Rating is 3/4 hr when cable F is installed in 2, 3 or 4 hr rated walls, 0 hr in 1 hr rated walls. The hourly T Rating is 1/4 hr when cable G is installed in 2, 3 or 4 hr rated walls, 0 hr in 1 hr rated walls.
The L Rating at ambient and 400°F with no cable fill is 2.6 CFM and 1.9 CFM, respectively. The L Rating at ambient and 400°F with cable fill is 2.8 CFM and 1.3 CFM, respectively.
4. Firestop Device – Device to be installed in accordance with the accompanying installation
instructions. Device to be installed and secured to the EMT sleeve both sides of wall.
THE WIREMOLD COMPANY – FS2R FlameStopper, FS4R FlameStopper
*Bearing the UL Classification Mark
1. Floor & Wall Assembly – Min 4-1/2 in. [114 mm] thick reinforced lightweight or normal
weight (100-150 pcf or 1600-2400 kg/m3) concrete floor or wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Maximum diameter of opening is 4-1/2 in. [114 mm].
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
*4-Hour Rated Assemblies (System No. W-J-3154): for concrete wall installation, minimum
6 in. [152mm] thick, reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete wall.
2. Metallic Sleeve – Nom 2 in. [51 mm] or 4 in. [102 mm] diameter electrical metallic tubing
(EMT), dependent on the size of the firestop device (Item 4). The sleeve is to extend a nom 5/8 in. [16mm] beyond both surfaces of floor or wall. The annular space between the sleeve and the periphery of opening shall be min 0 in. (continuous point contact) to max 1/4 in. [6 mm].
3. Cables – Aggregate cross-sectional area of cables in the EMT sleeve to be 0% to max 60%
of the aggregate cross-sectional area of the EMT sleeve. When there is no cable fill, device cover is to be tightly closed. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Single conductor No. 18 AWG (or smaller) RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
B. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diameter of 5/8 in. [16 mm].
C. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) or plenum rated jacketing and insulation.
D.
Max 4/C No. 2 AWG (or smaller) copper conductor cable with XLPE/PVX insulation and
PVC jacket.
E. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
F. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
G. Max 8/C 12 AWG (or smaller) copper conductor steel Metal-Clad or Armored-Clad cable.
The hourly T Rating is 3 hr when no cable fill is used or when cables A, B or C are used. The hourly T Rating is 3/4 hr when cable D is used. the hourly T Rating is 1 hr when cables E and F are used. The hourly T Rating is 1/4 hr when cable G is used.
4. Firestop Device – Device to be installed in accordance with the accompanying installation
instructions. Device to be installed and secured to the EMT sleeve both sides of wall or floor.
THE WIREMOLD COMPANY – FS2R FlameStopper, FS4R FlameStopper
*Bearing the UL Classification Mark
u
UL Certification
From UL Fire Resistance Directory
Through-penetration Firestop Systems
System No. W-L-3300
December 28, 2005
Ratings – 1, 2, 3 and 4 Hr (See Item 1)
T Ratings – 0, 1/4, 1/2, 3/4, 1, 2, 3, and 4 Hr (See Item 3)
L Rating at Ambient – 2.6 CFM and 2.8 CFM (See Item 3)
L Rating at 400°F – 1.9 CFM and 1.3 CFM (See Item 3)
Through-penetration Firestop Systems
System No. C-AJ-3271
January 12, 2006
F Rating – 3 Hr*
T Ratings – 1/4, 3/4, 1, & 3 (See Item 3)
L Rating at Ambient – 2.6 CFM and 2.8 CFM (See Item 3)
L Rating at 400°F – 1.9 CFM and 1.3 CFM (See Item 3)
FIRESTOP DEVICE FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY
D
E
I
F
I
S
S
A
L
C
1A
3
2
1B
4
3
2
1
4
3
Measure pipe length.
Break Off.
A.
B.
C.
A.
Install Heat Shield around Product.
B. Tighten Clamp.
A.
B.
FS2RHS, FS4RHS HEAT SHIELD INSTALLATION:
NOTE: Heat Shield is only required if conduit extends out from the wall more than 7/8" [22mm]. Add-On Kit used to retrofit Flamestopper Thru-Wall Fitting onto existing 2" trade size or 4" trade size EMT pipe.
Use FS2RHS – 2" trade size EMT with FS2R. Use FS4RHS – 4" trade size EMT with FS4R.
1. Remove any existing firestop material from
within end of EMT Pipe.
3. Remove Top and Front Door and
drop Cables into Fitting.
5. Move Sliding Doors to be snug around
Cables by turning Side Screws.
6.
4.
2.
NOTE: Pipe cannot exceed 6" [152mm].
NOTE: Make sure Heat Shield
is tight to wall.
Ground in accordance with National Electrical Codes.
Fill out and place label on wall near FlameStopper.
PIPE HEAT SHIELD
LENGTH CUT LENGTH
1/2" – 7/8" No Shield Needed 7/8" – 1" 1
1" – 2" 2 2" – 3" 3 3" – 4" 4 4" – 5" 5 5" – 6" No EMT
1.
2.
3.
4.
5.
Cut Length
Loading...
+ 5 hidden pages