Legrand 881FC User Manual

Wiremold/ Legrand electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Wiremold/ Legrand electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
Fire Classified Floor Boxes
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 007 939 – July 2008
IMPORTANT: Please read all instructions
before beginning.
Step 1 MEASURE AND LOCATE BOX.
Box must be located over deck valley directly above thickest region of concrete.
Step 2 PREASSEMBLY
Secure box to mounting plate with cable ties or wire. Loosely insert adapters and conduit elbows into box.
Offset displaced downward
Plug
Second PVC Elbow (Optional)
1" Trade Size PVC Elbow
Step 3 CUT OPENINGS INTO DECK
Measure to the outside edge of the 1" trade size PVC elbow to the box centerline. Cut a 2" [51mm] tangent to this dimension. Repeat on opposite side if both PVC elbows are required.
2"
[51mm]
Cut ø 2" [51mm] Hole through Deck
Distance to outside edge of elbow
Step 4 ATTACH MOUNTING PLATE & GLUE
Secure mounting plate to deck by welding or screws. Glue elbow(s) and adapter(s) in place. Seal any unused hub with hub plug provided. Offset in mounting plate is positioned downward. Seal off any excessive gaps around elbows with duct tape.
Secure to Deck with Screws or weld
1" Trade Size PVC Elbow
Seal opening end with Duct Tape
Step 5 SECURE CONCRETE
COVER & POUR
Insert body spacer and concrete cover in box. Do not remove intumescent pads. Pour concrete to requires height.
Concrete Cover
Intumescent Pads – Do not Remove
Step 6 CUT BOX TO
REQUIRED HEIGHT
After concrete has cured, saw off the remainder of the box at floor level using a wood saw. If the final floor covering is a thick carpet, leave enough of the box protruding above the floor to compensate.
Step 7 CUT CARPET OR FLOOR
COVERING AROUND BOX
After upper section of box is removed, cut the carpet or floor covering as indicated.
ø 5"
[127mm]
Wiremold / Legrand
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251 Canada: 570 Applewood Crescent • Vaughan, Ontario L4K 4B4 1-800-723-5175 • FAX 905-738-9721
1 007 939 0708
© Copyright 2008 Wiremold / Legrand All Rights Reserved
Type 881FC outlet box for use with 1-, 11/2- or 2-hour rated unprotected reinforced concrete floors, floors employing unprotected steel floor units and concrete toppings (D900 Series Designs) or concrete floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the outlet boxes.)
The assembled outlet boxes will not reduce the ratings of the floor assembly when the thickness and type of concrete (required for specific ratings) are within the specified limits and the fittings are installed as specified.
1. Concrete – Minimum thickness of structural concrete topping of 3 1/4" [83mm] on steel deck. Unit weight of concrete to be 100 to 155 pcf.
2. Installation – Mounted on 2" or 3" [51mm or 76mm] deck. For use with up to (4) 12 AWG Type THHN power conductors or (48) 23 AWG tele/data conductors.
Outlet Boxes and Fittings Classified for Fire Resistance Wiremold/ Legrand (R8209)
COVER PLATES
Adapter Duplex GFCI
Dual Rectangular
Flip Lid Flip Lid
Brass 895 895GFI
Aluminum 895TCAL 895GFICAL
Nonmetallic 881ADP
881FC
881FC: Complete activation following instructions provided with Adapter
(Cat. No. 881ADP) and cover plate. See list below for available options.
CAUTION: Wiring capacity is reduced by 9.0 cu.in. than stated by graduations
on box due to intumescent pads.
Step 8 ACTIVATION