Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.
From branch circuitfrom Poke-Thru receptacleFrom branch circuitfrom Poke-Thru receptacle
HITE or NEUTRAL WHITE W/ BLUE STRIPEWHITE or NEUTRAL WHITE W/ BLUE STRIPE
W
From branch circuitfrom Poke-Thru receptacleFrom branch circuitfrom Poke-Thru receptacle
GREEN or GROUND GREEN W/ YELLOW STRIPEISOLATED GROUND GREEN W/ YELLOW STRIPE
rom branch circuitfrom Poke-Thru receptacleFrom branch circuitfrom Poke-Thru receptacle
F
System Ground
GREEN or GROUND
rom branch circuitfrom Poke-Thru
GREEN (jumper wire)
from Poke-Thru
junction box
F
System Groundjunction box
WARNING: Ground wire from junction box must be connected to system ground.
CAUTION: Receptacle mounting means not grounded. Grounding wire connection required. For isolated ground
wiring, connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d).
If necessary remove Feed Plates to pull communications wires through Poke-Thru device.
Replace Feed Plates when finished pulling wires.
Catalog Nos. 8ATCP, 8ATP
GREEN (jumper wire)
CAUTION: To maintain fire classification, Feed Plates must be installed.
2
Page 3
Step 2If circuit is connected to an isolated
ground, apply IG icon on receptacle
plate as shown.
or Carpet or Surface Mounted Tile Installation
F
Step 3Place appropriate gasket around
poke thru and slide under flange.
Use flat foam gasket for surface
ile applications or use round
t
neoprene gasket for carpet
applications. For the flush tile
applications no gasket is needed.
NOTE: The orange triangle shall only be placed
on devices that are wired for isolated
ground. See NEC 250-146(d).
Step 4Push Poke-Thru into floor.
Step 5Installation complete.
For Flush Tile Installation (Start with Steps 1 & 2 on previous page.)
Step 3Place shims around bottom of flange to
Step 4Use grout and/or silicone caulk
match thickness of tile. Flange is 1/8"
thick. (2) 1/8" shims and (2) 1/16" shims
are provided. Push Poke-Thru into floor.
between edges of flange and tile.
NOTE: If more shims are required, use Cat. No 8TS.
3
Page 4
INSTALLING STEM ASSEMBLY AND SEPARATE COVER
Step 1Insert Stem Assembly into core hole.
INSTALLING DIVIDERS
Step 1Slide divider into slots in body of Poke
Thru. Two sets of slots are provided.
Either set may be used.
Step 2Remove disposable plate and (2) plate clips by
removing the 8-32 screws. Install Flange using
the (2) 8-32 x 1/2” Cap Head screws provided
with the cover assembly.
Step 2Two dividers are provided for the bottom of
the Poke Thru. Use the shorter divider on top
of Wire Tunnel. Use the longer divider when
separating channels without the Wire Tunnel.
To install, turn divider at an angle to place
inside the Feed Housing. Once inside, twist the
divider to align with holes in the Feed Housing.
Attach using (2) # 8-32 screws.
4
Page 5
INSTALLING DEVICE PLATES
Half Gang Plates
Step 1Install plates using (2) 6-32 x 1/2" screws.
provided)
(
NEMA 1 Gang Device
Step 1Screw receptacle into tabs using (2) 6-32
screws provided with the receptacle.
Step 2Install plates using (2) 6-32 x 1/2" screws.
(provided)
1.5 Gang Data/AV Plates
Step 1Install device plate using (2) 6-32 x 1/2" screws. (provided)
5
Page 6
Carpet Cutout Template
Carpet Cutout
1/2" [216mm]
8
CAUTION: When printing copies of this
template please be sure template
is scaled correctly and is the
correct size once it is printed.
6
Page 7
Core Hole
(See chart below for
Core Hole dimensions.)
FLOORCORE CORE
TYPESIZE (Min.)SIZE (Max.)
Covered Floors8"[203mm]8 1/8" [206mm]
(Carpet, Tile or
Wood)
Bare Concrete8 1/16" [205mm]8 1/8" [266mm]
or Terrazzo
7
Page 8
CONFIGURING FEED PLATES
Step 1Remove cover assembly from Poke Thru
y removing (2) 8-32 screws and lifting
b
cover off.
Step 1Remove (2) 8-32 screws and pull off Feed
Plate or housing.
Step 2Remove Poke Thru from floor by bending tabs
nward and pulling unit up.
i
Step 2Use (2) 8-32 screws to install new Feed Plate
or housing
CAUTION: To maintain fire classification, Feed Plates must
be installed.
CAUTION: To maintain fire classification, Feed Plates must
be installed.
8
Page 9
WIRE TUNNEL REMOVAL
Step 1Remove Feed Housing from center and side
without J-box.
Step 2Pull wires out of wire tunnel.
Step 3Slide wire tunnel out of
remaining Feed Housing.
Step 4Rotate center housing and reattach with
(4) 8-32 screws.
80°
1
Step 5Reattach side Feed Housing and feed plate with (2) 8-32 screws.
CAUTION: To maintain fire classification, Feed
9
Plates must be installed.
Page 10
I
N
S
T
A
L
L
I
N
G
D
E
V
I
C
E
S
I
N
D
E
V
I
C
E
P
L
A
T
E
S
8
T
R
A
C
,
8
S
E
R
,
8
A
C
T
6
A
(
D
e
v
i
c
e
s
n
o
t
i
n
c
l
u
d
e
d
)
(
I
n
c
l
u
d
e
s
2
A
b
8
M
A
A
P
,
8
A
A
P
,
6
8
M
A
A
(
D
e
v
i
c
e
s
n
o
t
i
6
8
2
A
e
z
e
l
s
.
D
e
v
i
c
e
s
n
o
t
i
n
c
P
n
c
l
u
d
e
d
)
l
u
d
e
d
)
10
Page 11
Evolution Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards to the
ollowing conditions:
f
The 8STC Poke-Thru Stem with the 8CTC or 8CT Service Head Fitting, and the 8ATCP, 8ATP, 8ATC or 8AT factory assembled
Poke-Thru devices are for use with 1-, 1 1/2-, or 2- hour rated unprotected reinforced concrete floors and 1-, 1 1/2-, or 2- hour
rated floors employing unprotected steel floor units and concrete topping (D900 Series Designs), or concrete floors with suspended
ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling area below the PokeThru fittings).
The assembled Poke-Thru stem and service fitting will not reduce the ratings of the floor assembly when the thickness and type
f concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified:
o
1. Spacing – Minimum of 2' [610mm] OC and not more than one unit per 65 sq. ft. [6 m
2
] of floor area in each span.
2. Concrete – Minimum thickness of structural concrete topping of 2 1/4" [57mm] over metal deck or a minimum 3" [76mm]
thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.
3. Installation – Mounted in a 8" [203mm] diameter hole in concrete per installation instructions accompanying
the fittings. For use with power circuits, data and/or audio/visual cables as tabulated below:
COPPER CROSS-SECTION
OUTER CENTER
CHANNELSCHANNEL
Max Copper .0154 sq. in. .0775 sq. in.
X-Section[9.9mm2][16.6 mm2]
Max #(3) 12 AWG(24) 14 AWG
Conductors
NOTE:When using conductor sizes other than listed above, the aggregate cross-sectional area of
the copper conductors shall not exceed the cross-sectional areas listed.
The “TC” suffix letters indicate that the device may be installed on tile or carpet covered concrete floors. The “T” suffix letter
indicates that the device is intended to be installed on a concrete floor, embedded into the tile covering.
Copper Cross Sectional Area
of Commonly Used Conductors
SizeSolid
#24 .00032 sq. in. [.20645mm2]
#22 .00050 sq. in. [.32258mm2]
#14 .00323 sq. in. [2.08386mm2]
#12 .00512 sq. in. [3.30321mm2]
#10 .00815 sq. in. [5.25805mm2]
#8 .01296 sq. in. [8.36127mm2]
NOTE: Use above values for solid or stranded conductors.
CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring.
Contact manufacturer for replacement. Field modifications will void UL Listing
and Classification. Replacement receptacle is limited to this manufacturers'
Catalog No 68REC.
11
Page 12
Wiremold
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251