5. GENERAL CHARACTERISTICS (continued)
Packaged volume
4 141 55 4 141 56 4 141 85 4 141 83
Packaging per unit per unit
Volume (dm
3
0.5 0.2
Weight (g) 340 340
6. LEGRAND RECOMMENDATIONS
6.1 Protection of the DC part of the PV installation
To provide correct voltage surge protection of the DC part of the PV
installation, a PV SPD is recommended:
- On each inverter input
(1)
(in DC enclosures in accordance with guide
UTE C 15-712-1, SPD compulsory according to the type and location of
the installation to be protected, see UTE C 15-712-1)
- Close to the panels (in group junction boxes according to guide UTE C
15-712-1) when they are more than 10 m away from the inverter or the
DC enclosure
(2)
(1)
For multi-input or multi-MPPT inverters, it is advisable to use an SPD on
each input
(2)
PV generators with a Uocmax voltage of less than 600 V:
According to guide UTE C 15-712-1, this protection is only necessary if
Legrand 600 V SPDs are installed close to the inverters. This protection is
nonetheless recommended for widespread PV installations with very long
lines.
6.2 Protection of the AC part of the PV installation
Likewise, for correct protection of the AC part of the PV installation,
it is advisable to group the inverters together in the same equipment
room as the main panel (main LV distribution board) connecting the PV
installation to the LV grid. Thus a single AC SPD
(1)
is all that is needed
to protect the main LV distribution board (SPD compulsory according
to the type and location of the installation to be protected, see UTE C
15-712-1).
If the inverters are not installed in the equipment room in which the
main LV distribution board is located (or are installed outdoors) an
AC SPD is also necessary close to each inverter.
Recommended types of AC SPD:
PV installation
power
Main LV board
protection
Installations
with lightning
conductors
(3)
Main LV board
protection
Installations
without a lightning
conductor
Protection close
to inverters
(2)
P < 36 kWc
Type 1
(Iimp 12.5 kA)
SPD
protected
SPD
protected
P < 100 kWc
Type 1
(Iimp 25 kA)
Type 2
(Imax 70 kA)
Type 2
(Imax 15 kA)
P > 100 kWc
Type 1
(Iimp 25 kA)
Type 1
(Iimp 25 kA)
Type 2
(Imax 40 kA)
(1)
An additional AC SPD is also necessary close to each inverter that is more
than 10 m away from the main LV distribution board. This SPD must be the
same type as those used close to the inverters (see above table).
(2)
AC SPDs needed close to each inverter that is
- more than 10 m away from the main LV distribution board
- installed outdoors or outside the equipment room in which the main LV
distribution board is installed
(3)
When a PV installation is protected by lightning conductors, it is
advisable to create an isolated lightning protection system (isolated LPS)
as described in standard NF EN 62305, maintaining adequate separation
distances between the metal structures of the panels and the LPS (lightning
conductors and downcomers).
6. LEGRAND RECOMMENDATIONS (continued)
6.3 Protection of the AC part of the existing installation
(consumption part)
To ensure correct voltage surge protection of the whole installation
(PV installation and installation on the consumption side), it is advisable
to protect the AC installation on the consumption side so as to avoid
any possible risk resulting from voltage surges on the PV installation or
voltage surges from the grid.
Since both electrical installations usually have a common earthing
system, SPDs are recommended on both installations to avoid any
possible problem of equipotentiality or feedback from earth.
The SPDs must be the same type as the AC SPDs recommended for
AC protection of the PV installation (see section 6.2). SPDs for the
secondary enclosures must be the same type as those recommended
for protection close to the inverters (table above in section 6.2).
See also the technical data sheets for T1 and T2 SPDs for 230/400 V~
systems.
6.4 Guide UTE C 15-712-1
According to this guide, the use of PV SPDs for protection on the DC
side is compulsory:
- if lightning conductors are present
- depending on the lightning risk analysis* (according to the distance
between panels and inverter and the local lightning strike density)
(see article 13)
The use of AC SPDs is compulsory on the AC side:
- if lightning conductors are present
- if the local lightning strike density is greater than 2.5 (see NF C 15-100
article 443)
Note: The use of SPDs is usually also compulsory if a lightning risk
analysis has been carried out according to standard NF EN 62305
(IEC 62305). In this case, refer to section 6.2 and the previous table,
considering an installation equipped with lightning conductors and
incorporating all the necessary protection close to the equipment.
*Given the expense of panels and inverters, we strongly recommend that
SPDs are always installed.
7. CONFORMITY
Complies with standard NF EN 50539-11 and drafts PR NF EN 61643-31
and future standard IEC 61643-31.
Used to comply with the installation requirements and
recommendations in guides UTE C 15-712-1, TS 50539-12 and also
standards IEC 60364-7-712 and IEC 61643-32.
Conforms to Directive: 2014/35/EU
8. ACCESSORY
Replacement plug-in modules:
Plug-in module
Cat. No.
Voltage Associated base
4 141 85 600 VDC 4 141 55
4 141 86 1000 VDC 4 141 56
With LED indicator:
- Green: SPD operational
- Red: plug-in module needs to be replaced
Replacing plug-in modules: see section 4.7