LEGRAND 1.1KVA, 1.5KVA, 2KVA, 3KVA, 1KVA Series User Manual

...
Line Interactive Sinewave UPS
1.1KVA | 1.5KVA | 2KVA | 3KVA Models
Uninterruptible Power Supply System
User Manual
2
Table of Contents
Important Safety Warnings ......................................................................................................3
Transportation and Storage ................................................................................................................................................. 3
Preparation ......................................................................................................................................................................... 3
Installation .......................................................................................................................................................................... 3
Operation ............................................................................................................................................................................ 4
Maintenance, Service and Faults ........................................................................................................................................ 4
Avertissements de sécurité importants ....................................................................................5
Transport et stockage .......................................................................................................................................................... 5
Préparation ......................................................................................................................................................................... 5
Installation .......................................................................................................................................................................... 6
Fonctionnement .................................................................................................................................................................. 6
Maintenance, Service et Défauts ........................................................................................................................................ 7
1. Installation and Setup ..........................................................................................................9
Unpacking and Inspection ................................................................................................................................................... 9
Rear Panel ......................................................................................................................................................................... 10
Operating Principle ........................................................................................................................................................... 11
Installing The UPS .............................................................................................................................................................. 11
Setting Up the UPS ............................................................................................................................................................ 13
Battery Replacement ......................................................................................................................................................... 15
Replacement Battery Assembly ........................................................................................................................................ 16
2. Operations .......................................................................................................................... 18
Button Operations ............................................................................................................................................................. 18
LCD Panel .......................................................................................................................................................................... 19
Audible Alarms .................................................................................................................................................................. 20
LCD Panel Index ................................................................................................................................................................. 21
Operating Mode Descriptions ........................................................................................................................................... 21
UPS Settings ...................................................................................................................................................................... 22
Fault Reference Codes ....................................................................................................................................................... 25
Warning Indicators ............................................................................................................................................................ 25
4. Troubleshooting ................................................................................................................. 26
5. Maintenance and Storage ................................................................................................... 27
Maintenance ..................................................................................................................................................................... 27
Storage .............................................................................................................................................................................. 27
6. Specifications ..................................................................................................................... 28
Input .................................................................................................................................................................................. 28
Output ............................................................................................................................................................................... 28
Efficiency ........................................................................................................................................................................... 28
Battery ............................................................................................................................................................................... 28
Protection.......................................................................................................................................................................... 28
Alarm ................................................................................................................................................................................. 29
Physical .............................................................................................................................................................................. 29
Environment ...................................................................................................................................................................... 29
Management ..................................................................................................................................................................... 29
Expandable Battery Box Specification ............................................................................................................................... 30
3
Important Safety Warnings
Comply with all warnings and operating instructions in this manual and save it for future reference. Do not operate this unit before carefully reading through all safety information and operating instructions.
Transportation and Storage
Transport the UPS system only in the original package to protect against shock and impact.
The UPS must be stored in a ventilated and dry room.
Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environments. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to adjust to the environment.
Do not install the UPS system near water or in damp environments.
Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
Do not block ventilation holes on the UPS housing.
Installation
Do not connect appliances or devices to the UPS output sockets or terminal that would over load the UPS.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
Connect the UPS system only to a grounded, shockproof outlet, which must be easily accessible and close to the UPS system.
Use only a VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 Vac models) mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Use only VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 Vac models) power cables to connect the loads to the UPS system.
When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.
Temperature Rating: Units are considered acceptable for use in a maximum ambient environment of 104°F (40°C).
For Pluggable Equipment: The socket-outlet shall be installed near the equipment and shall be easily accessible.
The unit is heavy. Lifting the unit requires a minimum of two people.
4
Operation
Do not disconnect the ground conductor cable on the UPS or the building wiring terminals at any time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries), therefore, the UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button, and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The EPO, RS-232 and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.
Maintenance, Service and Faults
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet); components inside the UPS system are still connected to the battery and are electrically live and dangerous.
Before performing any service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists on the terminals of the high capability capacitor, such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source and load prior to installing or maintaining the battery.
Remove battery grounds during installation and maintenance to reduce likelihood of shock. Remove the
connection from ground if any part of the battery is determined to be grounded.
5
When changing batteries, install the same number and same type of batteries or battery packs.
For UPS with internally mounted battery:
Instructions shall have sufficient information to enable the replacement of the battery with a suitable
manufacturer and catalogue number.
Safety instructions to allow access by Service Personnel shall be stated in the installation/service
handbook.
If batteries are to be installed by Service Personnel, instructions for interconnections, including terminal
torque, shall be provided.
Do not attempt to dispose of batteries by burning them. This could cause an explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Only replace the fuse with the same type and amperage to avoid fire hazards.
Do not disassemble the UPS system.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
This is a product for commercial and industrial applications. In second environment installations, restrictions or additional measures may be needed to prevent disturbances.
Avertissements de sécurité importants
Respectez tous les avertissements et consignes d'utilisation de ce manuel et conservez-le pour référence ultérieure. Ne faites pas fonctionner cet appareil avant de lire attentivement toutes les informations de sécurité et les instructions d'utilisation.
Transport et stockage
Transportez le système UPS uniquement dans son emballage d'origine pour le protéger contre les chocs.
L'onduleur doit être stocké dans une pièce ventilée et sèche.
Préparation
De la condensation peut se produire si le système UPS est directement déplacé d'un environnement froid à un environnement chaud. Le système UPS doit être absolument sec avant d'être installé. Veuillez prévoir au moins deux heures pour que le système d'ASI s'adapte à l'environnement.
N'installez pas l'onduleur à proximité d'eau ou dans un environnement humide.
6
N'installez pas le système UPS à un endroit exposé à la lumière directe du soleil ou à proximité d'un appareil de chauffage.
Ne bloquez pas les trous de ventilation sur le boîtier de l'onduleur.
Installation
Ne connectez pas de périphériques à la sortie de l'onduleur ou à un terminal susceptible de surcharger l'onduleur.
Placez les câbles de manière à ce que personne ne puisse marcher dessus ou trébucher dessus.
Ne connectez pas d'appareils domestiques tels que des sèche-cheveux aux prises de sortie de l'ASI.
Ne connectez le système ASI qu'à une prise de terre protégée contre les chocs, qui doit être facilement accessible et proche du système ASI.
Utilisez uniquement un câble d'alimentation certifié VDE, marqué CE (par exemple, le câble d'alimentation de votre ordinateur) pour connecter le système UPS au câblage du bâtiment sortie (sortie antichoc).
Utilisez uniquement des câbles d'alimentation VDE, marqués CE pour connecter les charges au système UPS.
Lors de l'installation de l'équipement, assurez-vous que la somme du courant de fuite de l'onduleur et des périphériques connectés ne dépasse pas 3.5 mA.
Température nominale: Les unités sont considérées acceptables pour une utilisation dans un environnement ambiant maximal de 40°C (104°F).
Pour les équipements enfichables: La prise de courant doit être installée près de l'équipement et doit être facilement accessible.
L'unité est lourde. Le levage de l'unité nécessite un minimum de deux personnes.
Fonctionnement
Ne déconnectez pas le câble du conducteur de mise à la terre de l'onduleur ou des bornes de câblage du bâtiment car cela annulerait la mise à la terre de protection de l'onduleur et de toutes les charges connectées.
Le système ASI dispose de sa propre source de courant interne (batteries). Par conséquent, les prises de sortie ou les borniers de sortie de l'ASI peuvent être sous tension même si le système ASI n'est pas connecté à la sortie du bâtiment.
Pour déconnecter complètement le système UPS, appuyez d'abord sur le bouton "OFF", puis débranchez le secteur.
Assurez-vous qu'aucun liquide ou autre corps étranger ne puisse pénétrer dans le système ASI.
Les circuits EPO, RS-232 et USB sont des circuits de très basse tension de sécurité (TBTS) CEI 60950-1. Ce circuit doit être séparé de tout circuit de tension dangereux par une isolation renforcée.
7
Maintenance, Service et Défauts
Le système UPS fonctionne avec des tensions dangereuses. Les réparations ne peuvent être effectuées que par du personnel de maintenance qualifié.
Risque de choc electrique. Même après que l'appareil est déconnecté du secteur (prise de câblage du bâtiment); les composants à l'intérieur du système UPS sont toujours connectés à la batterie et sont sous tension et dangereux.
Avant d'effectuer toute opération de maintenance, déconnectez les batteries et vérifiez qu'il n'y a pas de courant et qu'aucune tension dangereuse n'existe sur les bornes du condensateur haute capacité, telles que les condensateurs BUS.
Seules des personnes connaissent bien les batteries et, avec les mesures de précaution requises, peuvent les remplacer et superviser les opérations. Les personnes non autorisées doivent être tenues à l'écart des batteries.
Risque de choc electrique. Le circuit de la batterie n'est pas isolé de la tension d'entrée. Des tensions dangereuses peuvent se produire entre les bornes de la batterie et le sol. Avant de toucher, vérifiez s'il n'y a pas de tension.
Ne jetez pas les piles dans un feu. Les piles peuvent exploser.
N'ouvrez pas et ne mutilez pas les piles. L'électrolyte libéré est nocif pour la peau et les yeux. Cela peut être toxique.
Les batteries peuvent provoquer un choc électrique et un courant de court-circuit élevé. Veuillez prendre les mesures de précaution suivantes et toutes les autres mesures nécessaires lorsque vous travaillez avec des batteries:
• Retirez les montres, bagues ou autres objets métalliques.
Utilisez des outils avec des poignées isolées.
• Portez des gants et des bottes en caoutchouc.
Ne posez pas d'outils ou de pièces métalliques sur les batteries.
Débranchez la source de charge avant d'installer ou de maintenir la batterie.
Retirez les masses de la batterie pendant l'installation et la maintenance afin de réduire les risques de
choc. Retirez la connexion de la masse si une partie de la batterie est déterminée pour être mise à la terre.
Lorsque vous changez les piles, installez le même numéro et le même type de piles ou de batteries.
Pour onduleur avec batterie interne:
Les instructions doivent contenir suffisamment d'informations pour permettre le remplacement de la
batterie par un fabricant et un numéro de catalogue appropriés.
Les instructions de sécurité pour permettre l'accès au personnel de service doivent être indiquées dans
le manuel d'installation/d'entretien.
Si des batteries doivent être installées par le personnel de service, des instructions pour les
interconnexions, y compris le couple aux bornes, doivent être fournies.
N'essayez pas de vous débarrasser des piles en les brûlant. Cela pourrait provoquer une explosion.
Ne pas ouvrir ou détruire les piles. L'électrolyte qui s'échappe peut causer des blessures à la peau et aux yeux. Cela peut être toxique.
8
Ne remplacez le fusible que par le même type et le même ampérage pour éviter les risques d'incendie.
Ne démontez pas le système UPS.
Cet équipement a été testé et déclaré conforme aux limites d'un appareil numérique de classe A, conformément à la partie 15 des règles de la FCC. Ces limites sont conçues pour fournir une protection raisonnable contre les interférences nuisibles lorsque l'équipement est utilisé dans un environnement commercial. Cet équipement génère, utilise et peut émettre de l'énergie radiofréquence et, s'il n'est pas installé et utilisé conformément au manuel d'instructions, peut causer des interférences nuisibles aux communications radio. L'utilisation de cet équipement dans une zone résidentielle est susceptible de provoquer des interférences nuisibles, auquel cas l'utilisateur devra corriger les interférences à ses propres frais.
Les changements ou modifications non expressément approuvés par la partie responsable de la conformité pourraient annuler l'autorité de l'utilisateur à utiliser l'équipement.
Ceci est un produit pour les applications commerciales et industrielles. Dans les installations du deuxième environnement, des restrictions ou des mesures supplémentaires peuvent être nécessaires pour éviter les perturbations.
9
1. Installation and Setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
Please keep the original package in a safe place for future use.
Unpacking and Inspection
Unpack your products and inspect the contents. The contents should include the following supplied components and hardware.
1.1, 1.5, 2, or 3KVA UPS Unit
User Manual
USB Cable
(2x) UPS Mounting Brackets and Screws
(4x) Foot
NOTE:
Rail Slider is provided. For more information, refer to the 2U Rackmount Rail Slider instruction sheet (I-00888.pdf).
Before installation, inspect all supplied components and hardware to ensure nothing was damaged during transportation. If you notice any damaged or missing parts, do not turn on the unit and notify the carrier and utilize the support reference number provided on your unit. Please keep the original package in a safe place for future use.