Legrand 291-H-BTC User Manual

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Core drill hole.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each 65 sq. ft. [6 sq. m] of floor area in each span.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall
or pillar to leave enough room for poke-thru cover assembly.
Step 3. Carpet Option.
RC9FFS, RC9AFFTC, 291-H/BTC, 292-H/BTC, RC91GHBTC, RC92GHBTC, and RC9CFFTC
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 997 R2 – Updated July 2005
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL listed. Made for interior use only and should be installed in conformance with current local and/or the National Electrical Code.
24" [610mm] Min Center – Center
3" Diameter Core Drill
3 1/16" [78mm] Actual Diameter
RC91GHBTC, RC92GHBTC, 291-H/BTC, 292-H/BTC Style Service Heads (Carpet Only)
RC9AFFTC, RC9CFFTC 6 1/2" [165mm] Diameter Cutout (Carpet Only)
Make Concentric with Intended Core Hole
IMPORTANT: Please read all instructions
before beginning.
Step 4. Tile Option.
For RC9CFFTC and RC9AFFTC, cut a clearance hole in tile floor covering between 3 1/16" [78mm] and 4" [102mm] diameter.
NOTE: If installing poke-thru cover assembly over grout line on tile floor covering, apply a silicon bead to underside
of poke-thru flange or service head gasket.
Installing RC92GHBTC, RC91GHBTC, 291-H/BTC, and 292-H/BTC Style Service Heads:
Step 1. Install stem into core-drilled hole and then Step 2. Attach base to poke-thru stem using
remove disposable plate. Retain the four four #6-32 screws provided. screws for use when installing service head of choice.
CAUTION: Poke-thru stem cannot be rotated after insertion.
2
Cutout in Tile to be Between 3 1/16" [78mm] Min. Diameter to 4" [102mm] Max. Diameter
Flange
RC91GHBTC, RC92GHBTC, 291-H/BTC, 292-H/BTC Style Service Heads – Core Drill a 3" Diameter Through Both Tile and Concrete
3/4" [19.1mm] Maximum Tile Thickness
Factory Installed Gasket (Sets on Top of Tile Floor Covering)
RC91GHBTC and 291-H/BTC
Carpet Covered Floor
Tile Covered Floor
RC92GHBTC and 292-H/BTC
Remove Disposable Plate
Push Down