Supplied with 2 sets of metal fixings: button for screwless fixing, or
standard screw-type brackets.
Single-phase 230V – 50/60 Hz or three-phase 380 V – 50/60 Hz power
supply
The range features three main product families:
- PDUs designed for horizontal installation (10’’ and 19’’ PDUs)
- PDUs designed for vertical installation (Zero-U PDUs)
- Accessories
PDUs designed for horizontal installation (10’’ and 19’’ PDUs)
10’’ PDUs to be installed on 10’’ mounting uprights and 19’’ PDUs to be
installed on 19’’ mounting uprights. 1U height casing for compactness.
Integrated cable guide. Screwless snap-on fixing. End pieces with 180°
reversible metal brackets for vertical mounting capability.
PDUs designed for vertical installation (Zero-U PDUs)
For vertical installation on the rear of cabinets to save 19’’ space within
it.
Cable inlet can be rotated 330° to ensure perfect alignment of the
power cable.
Accessories
- Replacement surge protection module to ensure continuity of service
- Locking caps for locking out the use of an outlet
See the detailed description of these accessories in the "Functions"
section.
Legrand's PDU offer is available as standard catalogue versions (see
the corresponding descriptions in the "Equipment and performance"
section) and as customized configurations.
1.2 Mechanical characteristics
- Casing: 6060 T5-R19 natural anodised aluminium
Dimensions in mm:
1U casing
23° view
44.3
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Depending on what equipment they comprise, the PDUs comply with
the current applicable standards below:
ApplicationStandard
French/Belgian standard plugs/outlets
German standard plugs/outlets
UK standard plugs/outlets + electrical accessories
Italian standard outlets
Swiss standard outlets
C13 and C19 connectors for electrical equipmentIEC 60320-2-2
Low voltage surge protection deviceIEC 6164-11
SwitchIEC 60058-1
MCBIEC 60898-1
RCBOIEC 61008-1
Thermal circuit breakerIEC 60730-2-9
Industrial plugIEC 60309-1
Information-processing equipmentIEC 60950-1
IP: IP40 for French/Belgian, German, Swiss, Italian and UK standards and
IP20 for electrical appliance connectors (C13 and C19)
IK07
Glow-wire flammability test: The various different standard outlets and
the other functions that equip the PDUs meet the requirements of their
respective standards relating to abnormal heat and fire resistance and
comply with the following thresholds:
- Plastic parts in contact with live parts: 750 °C
- Other plastic parts: 650 °C
IEC/TR 60083
Temperature rise: The PDUs are compliant with the standard
temperature rise limit of 45 °C for French/Belgian, German, Swiss and
Italian standards and electrical appliance connectors (C13 and C19) and
52 °C for the UK standard.
Final inspection: Compliant with European standard requirements and
Legrand's own manufacturing requirements, all products undergo
production tests, including:
- Electrical continuity to ensure the product is wired correctly
- Dielectric strength at 2000 V to ensure there is no leakage current
- Operating test
RoHS and REACH conformity: The PDUs comply with European
standards and therefore meet the requirements of the RoHS directive
(Restriction of Hazardous Substances) and REACH regulations
(Registration, Evaluation, Authorisation & restriction of CHemicals).
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Legrand PDUs can be delivered with custom configurations to meet
specific customer requirements. Contact your local sales representative
to discuss your requirements.
CONFIGURATION EXAMPLES
3m
Example:
19’’ PDU 1U with 2 x 2P+E French/Belgian standard outlets, 1 C19 socket
and 6 C13 sockets.
Supplied with 3 m cable and C20 plug
4.5 m
Example:
Zero-U PDU with 12 2P+E French/Belgian standard outlets.
Red strips for PDU identication purposes. Supplied with rotative
3. FUNCTIONS
3.1 Outlets
Legrand PDUs can be equipped with outlets of different standards.
C13 with cord locking system
2P+E 10 A
Outlet recess at 90° angle
Conforms to standard IEC 60320-2-2
C19 with cord locking system
2P+E 16 A
Socket recess at 90° angle
Conforms to standard IEC 60320-2-2
Cord locking system on C13/C19 sockets
The cord is locked mechanically into the outlet to prevent any
unintended disconnection (caused by maintenance, vibrations, etc.).
Pull-out force > 100 N
This universal solution is compatible with all standard cords available on
the market.
German
2P+E 16 A
Terminals equipped with protective shutters
Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
UK
2P+E 13 A
Terminals equipped with protective shutters
Outlet recess at 90° angle
Conforms to standard IEC 60320-2-2
3.2 LED switch
The LED switch is used to control the PDU power supply.
A white LED is lit when the PDU sockets are supplied
with power.
16 A switch
Transparent switch
3.3 Power indicator
A white LED on the power indicator shows that the product is supplied
with power.
3.4 Ammeter
The ammeter is used to measure consumption for enhanced installation
management.
Operation: 230 VAC 50Hz
Measured value: current (0 to 32 A)
Operates by measuring the current using a shunt
3-digit display "XX.X"
Rotatable display for legible readout regardless of whether the PDU is
mounted vertically or horizontally
French-Belgian
2P+E 16 A
Terminals equipped with protective shutters
Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Protection between Line and neutral of socket outlets connected
downstream against overloads generated by the electrical network
upstream of the surge protective device by creating a discharge current
on the network and/or earthing link.
To be used in combination with a voltage surge protector installed in
the panel..
D
TE
C
TE
O
PR
R
E
W
O
P
ON
ED
T
C
E
T
O
R
P
ER
W
PO
ON
A
Technical data
Number of poles2
Neutral systemT T - TNS
Mode of protectionMCB C16 and/or MCBO
Maximum continuous operating voltage U
300mA
CLN & N/PE 255V
L/PE 440V
Nominal sysem voltageU230 VAC
Assigned current of loadI
L16A
FrequencyF50/60 Hz
Open cicuit voltageU
Voltage protection levelU
OC10 kV
PL/N 1kV
L/PE & N/PE 1,2kV
Temporary overvoltage test valueU
T441V
Nominal discharge currentIn5kA
Maximum discharge currentImax10 kA
Current factor k1.6
TypeType 2 (T2) _ Type 3 (T3)
LocationIndoor
Temperature and humidity rangeNormal range : -5°C : +40°C
Mechanical characteristics
IP 20
B
ON
6 468 97
Operation
• Surge protective devices are designed to limit transient overvoltages
of atmospheric and industrial origin.
• They have a certain capacity to absorb energy and age with each
operation; it is therefore normal for them to be out-ot-order after a
certain number of operations. The imminent out-of-order status is
signalled and the draw-out module should be replaced.
• Surge protective devices are designed to be installed at use points and
are to be used in combination with the installation’s original modular
protection.
• They are not designed to provide sole protection for an installation
in a building likely to be hit by direct lightning strikes (e. g. buildings
equipped with lightning arresters). This would immediately put the
device out-of-order by exceeding its maximum discharge capacity.
• Overloads of atmospheric origin occur between the active wires and
the earth. They are highly charged and uncontrolled.
• Overloads of industrial origin occur between the active wires (L+N)
and are not so highly charged.
• The surge protective devices are equipped with an operation indicator
light (to be checked on a regular basis):
- Mains supply present and green indicator light on: operational
protection.
- Mains supply present and red indicator light on: change the module.
- Once the draw-out module is out-of-order the installation is no longer
protected but remains powered (including the withdrawn module).
Cleaning
Without cleaning
Replaceable element: Cassette Reference 6 468 9
Conformity
In compliance with the standard NF EN 61643-11 : 2014
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Protection devices are integrated in all standard catalogue PDUs and
customized PDUs.
- MCBs
For protecting equipment against short-circuits and overloads
407652 DX3 1P MCB 10 A 6000 A - 10 kA
407654 DX3 1P MCB 16 A 6000 A - 10 kA
409131 DX3 1P MCB 10 A 10000 A - 16k A
409133 DX3 1P MCB 16 A 10000 A - 16 kA
407698 DX3 1P+N MCB 10 A 6000 A - 10 kA
407700 DX3 1P+N MCB 16 A 6000 A - 10 kA
409150 DX3 1P+N MCB 10 A 10000 A - 16 kA
409152 DX3 1P+N MCB 16 A 10000 A - 16 kA
- RCBOs
For protecting equipment against short-circuits and overloads and
protecting people against leakage currents
410704 RCBO 10 A AC TYPE 4500 A - 6 kA - 30 mA
410705 RCBO 16 A AC TYPE 4500 A - 6 kA - 30 mA
410752 RCBO 10 A HPi AC TYPE 4500 A - 6 kA - 30 mA
410753 RCBO 16 A HPi AC TYPE 4500 A - 6 kA - 30 mA
For protecting equipment against short-circuits and overloads
Rating: 10 A and 16 A
Reset: The LED is lit during operation. When there is an overload, the
red button pops out of the module and the LED goes off. To reset the
breaker, press the red button until it clicks back into position; the LED
lights up again.
3.9 Colour-coding
The PDUs are colour-coded using coloured strips.
These strips clip onto the edge of the aluminium casing.
This solution is only compatible with Zero-U PDUs.
Extruded PVC plastic
Blue and red borders are available as standard, other colours are
available on request.
2 applications:
- For identifying circuits: one colour per circuit, to match the same
colour used on the circuit breaker
See section 2 "Equipment and performance" to see which protection
device is integrated in the standard catalogue products.
MCBs and RCBOs are installed on a projecting DIN rail support to avoid
unintended breaking. This support can be equipped with a transparent
cover by special request.
1 or 2-module support depending on the catalogue number
1-module support2-module support
No cover
3.7 Fuse (custom configured version)
For protecting equipment against short-circuits and overloads
Cartridge rating: 10 A and 16 A
1-module support
with cover
With transparent cover
- For identifying the source: whole PDU in one colour identifies whether
it is the primary or interruptible power source when there are 2 PDUs in
the rack
To replace the cartridge, use a screwdriver to lever open the
compartment containing the fuse.
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
Depending on the configuration, the PDUs can be connected in different ways.
1) Supplied with power cord
See section 2 "Equipment and performance" to see which standard catalogue products have an integrated cord.
2) Terminal block connection
Some products are supplied without a cable; they are designed to be wired on a terminal block.
See section 2 "Equipment and performance" to see which standard catalogue products have an integrated terminal block.
Example of terminal block connection for a Zero-U PDU with rotative cable entry
C
D
95/97/98/99
B
A
Cable ø13 min.
Cable ø20 max.
Cable ø7 min.
Cable ø15 max.
B
A
5G 2.5 mm2/5G 4 mm
120 mm
A
C
2
10 mm
3G 2.5 mm2/3G 6 mm
A
2
10 mm
120 mm
B
A
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
12/15
B
Page 13
10’’ PDUs
19’’ PDUs
Zero-U PDUs
3) Connection via fast connector or C20 connector (custom configured version)
Connectors mounted on the front panel of the PDU. The PDU is powered via a separate cable that plugs into these connectors.
Vertical mounting possible by turning the fixing brackets round and positioning them on the rear of the unit.
Mounting bracket dimensions
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
14/15
Page 15
10’’ PDUs
Standard xing bracket dimensions
19’’ PDUs
Zero-U PDUs
2) Zero-U
Zero-U PDUs are designed for vertical installation and supplied with 2 sets of fixing accessories:
- 2 button: for screwless fixing. The height of the fixing centre can be set at any point along the full height of the PDU by sliding the button slots into
the groove on the rear of the PDU. Tightened using a 2.5 mm Allen key.