LEGRAND 10 PDUs, Zero-U, 19 PDUs User Manual

Page 1
128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex - France Tel: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 www.legrand.com
10’’ PDUs 19’’ PDUs Zero-U PDUs
1. GENERAL CHARACTERISTICS
1.1 Presentation
Legrand PDUs are designed for supplying power to equipment in 19’’ enclosures.
They comprise:
- an aluminium casing
- socket modules
- additional functions
- a termination solution
- a mounting solution
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/20/
21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
CONTENTS Page
1. GENERAL CHARACTERISTICS .............1
2. EQUIPMENT AND PERFORMANCE ........3
3. FUNCTIONS..............................8
4. DIMENSIONS ...........................11
5. INSTALLATION ..........................12
Supplied with 2 sets of metal fixings: button for screwless fixing, or standard screw-type brackets.
Single-phase 230V – 50/60 Hz or three-phase 380 V – 50/60 Hz power supply
The range features three main product families:
- PDUs designed for horizontal installation (10’’ and 19’’ PDUs)
- PDUs designed for vertical installation (Zero-U PDUs)
- Accessories
PDUs designed for horizontal installation (10’’ and 19’’ PDUs) 10’’ PDUs to be installed on 10’’ mounting uprights and 19’’ PDUs to be
installed on 19’’ mounting uprights. 1U height casing for compactness. Integrated cable guide. Screwless snap-on fixing. End pieces with 180° reversible metal brackets for vertical mounting capability.
PDUs designed for vertical installation (Zero-U PDUs) For vertical installation on the rear of cabinets to save 19’’ space within
it. Cable inlet can be rotated 330° to ensure perfect alignment of the
power cable.
Accessories
- Replacement surge protection module to ensure continuity of service
- Locking caps for locking out the use of an outlet See the detailed description of these accessories in the "Functions"
section.
Legrand's PDU offer is available as standard catalogue versions (see the corresponding descriptions in the "Equipment and performance" section) and as customized configurations.
1.2 Mechanical characteristics
- Casing: 6060 T5-R19 natural anodised aluminium Dimensions in mm:
1U casing
23° view
44.3
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
1/15
Page 2
10’’ PDUs
51.
1U casing
Ze
19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
- Outlet modules: PC/ABS CW507L (CuZn 36) brass
- Fixing brackets: DC01-A-m galvanised steel
ro-U casing
1
View from above
End viewSide viewEnd view
52
1.3 Standards, regulations and tests
Depending on what equipment they comprise, the PDUs comply with the current applicable standards below:
Application Standard
French/Belgian standard plugs/outlets
German standard plugs/outlets
UK standard plugs/outlets + electrical accessories
Italian standard outlets
Swiss standard outlets
C13 and C19 connectors for electrical equipment IEC 60320-2-2
Low voltage surge protection device IEC 6164-11
Switch IEC 60058-1
MCB IEC 60898-1
RCBO IEC 61008-1
Thermal circuit breaker IEC 60730-2-9
Industrial plug IEC 60309-1
Information-processing equipment IEC 60950-1
IP: IP40 for French/Belgian, German, Swiss, Italian and UK standards and IP20 for electrical appliance connectors (C13 and C19)
IK07
Glow-wire flammability test: The various different standard outlets and the other functions that equip the PDUs meet the requirements of their respective standards relating to abnormal heat and fire resistance and comply with the following thresholds:
- Plastic parts in contact with live parts: 750 °C
- Other plastic parts: 650 °C
IEC/TR 60083
Temperature rise: The PDUs are compliant with the standard temperature rise limit of 45 °C for French/Belgian, German, Swiss and Italian standards and electrical appliance connectors (C13 and C19) and 52 °C for the UK standard.
Final inspection: Compliant with European standard requirements and Legrand's own manufacturing requirements, all products undergo production tests, including:
- Electrical continuity to ensure the product is wired correctly
- Dielectric strength at 2000 V to ensure there is no leakage current
- Operating test
RoHS and REACH conformity: The PDUs comply with European standards and therefore meet the requirements of the RoHS directive (Restriction of Hazardous Substances) and REACH regulations (Registration, Evaluation, Authorisation & restriction of CHemicals).
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
2/15
Page 3
10’’ PDUs 19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
2. EQUIPMENT AND PERFORMANCE
2.1 Composition of each catalogue number
10" PDUs
6 468 98 6 468 00 6 468 01
Number of phases 1 1 1
Input voltage 230 V 230 V 230 V
Input current 16 A 16 A 16 A
Maximum power 3.7kW 3.7kW 3.7kW
Termination method Cord Cord
Cable length 1 m 1 m
Cable material PVC HO5VVF PVC HO5VVF
Cable cross-section 3G 1.5 3G 1.5
Plug type Schuko/UTE Schuko/UTE
Cable retention method Cableclamp + guide Cableclamp + guide
Number and type of outlets 4 French/Belgian 4 German
Outlets colour Black Black
Angle of outlets 55° 55°
Number of circuits per phase 1 1
Casing Zero-U aluminium 1U aluminium 1U aluminium
Fixings (included) 19’’ reversible bracket + snap-on fixing 19’’ reversible bracket + snap-on fixing 19’’ reversible bracket + snap-on fixing
19" PDUs
6 468 05 6 468 06 6 468 07 6 468 09 6 468 10 6 468 11 6 468 12 6 468 13 6 468 14
Number of phases 1 1 1 1 1 1 1 1 1
Input voltage 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V
Input current 16 A 16 A 16 A 16 A 16 A 16 A 16 A 13 A 16 A
Maximum power 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3kW 3.7kW
Termination method Cord Cord Terminal
Cable length 3 m 3 m 3 m 3 m 3 m 3 m
Cable material PVC
HO5VVF
Cable cross-section 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5
Plug type Schuko/
UTE
Cable retention method Cable
clamp +
guide
Number and type of outlets* 6 French/
Belgian
Outlet colour Black Black Black Black Black Red Black Black Black
Angle of outlets 55° 55° 90° 90° 55° 55° 55° 90°
Number of circuits per phase 1 1 1 1 1 1 1 1 1
Additional functions
Casing 1U
aluminium
Fixings (included) 19’’ reversible bracket + snap-on fixing
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
6 German 6 C19 with
1U
aluminium
block**
Cable
clamp +
guide
locking
1U
aluminium
Terminal
block**
Cable
clamp +
guide
6 C13 + 2 C19 with
locking
1U
aluminium
Cord Cord Cord Cord Terminal
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
9 French/
Belgian
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
9 French/
Belgian
tamper-
proof
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
9 German 8 UK 10 C13
1U
aluminium
PVC
HO5VVF
BS 1363
Cable
clamp +
guide
1U
aluminium
clamp +
aluminium
block**
Cable
guide
locking
* Outlets are equally distributed on each circuit ** Maximum capacity of terminal block 6 mm²
with
1U
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
3/15
Page 4
10’’ PDUs 19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
19" PDUs (continued)
6 468 15 6 468 18 6 468 19 6 468 20 6 468 21 6 468 22 6 468 23 6 468 24 6 468 30
Number of phases 1 1 1 1 1 1 1 1 1
Input voltage 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V
Input current 16 A 16 A 16 A 16 A 16 A 16 A 16 A 13 A 16 A
Maximum power 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3kW 3.7kW
Termination method Cord Cord Cord Cord Cord Cord Cord Cord Cord
Cable length 3 m 3 m 3 m 3 m 3 m 3 m 3 m 3 m 3 m
Cable material PVC
HO5VVF
Cable cross-section 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5
Plug type IEC 60309
16 A 2P+E
Cable retention method Cable
clamp +
guide
Number and type of outlets* 12 C13
with
locking
Outlet colour Black Black Black Black Black Black Black Black Black
Angle of outlets 90° 90° 90° 55° 55° 55° 55° 55°
Number of circuits per phase 1 1 1 1 1 1 1 1 1
Additional functions Power
Casing 1U
aluminium
Fixings (included) 19’’ reversible bracket + snap-on fixing
PVC
HO5VVF
T23 SEV
1011
Cable
clamp +
guide
12 T13
Swiss
standard
1U
aluminium
PVC
HO5VVF
T23 SEV
1011
Cable
clamp +
guide
12 T23
Swiss
standard
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
9 French/
Belgian
indicator
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
9 German 8 French/
Power
indicator
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
Belgian
Luminous
switch
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
8 German 6 UK 6 French/
Luminous
switch
1U
aluminium
PVC
HO5VVF
BS 1363 Schuko/
Cable
clamp +
guide
Luminous
switch
1U
aluminium
HO5VVF
Cable
clamp +
guide
Belgian
1P MCB
C16 6 kA
Cat.No.
4 136 06
aluminium
* Outlets are equally distributed on each circuit
PVC
UTE
1U
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
4/15
Page 5
10’’ PDUs 19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
19" PDUs (continued)
6 468 31 6 468 32 6 468 33 6 468 35 6 468 36 6 468 40 6 468 41 6 468 42 6 468 43
Number of phases 1 1 1 1 1 1 1 1 1
Input voltage 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V
Input current 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Maximum power 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW 3.7kW
Termination method Cord Cord Cord Cord Cord Cord Cord Cord Terminal
Cable length 3 m 3 m 3 m 3 m 3 m 3 m 3 m 3 m
Cable material PVC
HO5VVF
Cable cross-section 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5 3G 1.5
Plug type Schuko/
UTE
Cable retention method Cable
clamp +
guide
Number and type of outlets* 6 German 9 German 6 French/
Outlet colour Black Black Black Black Black Black Black Black Black
Angle of outlets 55° 55° 55° 55° 55° 55° 55° 90° 90°
Number of circuits per phase 1 1 1 1 1 1 1 1 1
Additional functions 1P MCB
C16 6 kA
Cat.No.
4 136 06
Casing 1U
aluminium
Fixings (included) 19’’ reversible bracket + snap-on fixing
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
1P MCB
C16 6 kA
Cat.No.
4 136 06
2x1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
Belgian
1P RCBO C16 6 kA
30 mA
AC type C
curve
Cat.No.
4 107 05
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
6 French/
Belgian
Surge
protection
module
Luminous
switch
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
6 German 6 French/
Surge
protection
module
Luminous
switch
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
Belgian
Ammeter Ammeter Ammeter Ammeter
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
6 German 6 German/
1U
aluminium
PVC
HO5VVF
Schuko/
UTE
Cable
clamp +
guide
Italian
1U
aluminium
block**
Cable
clamp +
guide
6 C13 with
locking
1U
aluminium
* Outlets are equally distributed on each vertical PDU circuit ** Maximum capacity of terminal block 6 mm²
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
5/15
Page 6
10’’ PDUs 19’’ PDUs Zero-U PDUs
19” PDUs (continued)
6 468 44 6 468 45 6 468 99
Number of phases 1 1 1
Input voltage 230 V 230 V 230 V
Input current 16 A 16 A 16 A
Maximum power 3.7kW 3.7kW 3.7kW
Termination method Terminal
block**
Cable length
Cable material
Cable cross-section
Plug type
Cable retention method Cable
clamp +
guide
Number and type of outlets* 6 C19 with
locking
Outlet colour Black Black
Angle of outlets 90° 90°
Number of circuits per phase 1 1
Additional functions Ammeter Ammeter
Casing 1U
aluminium
Fixings (included) 19’’ reversible bracket + snap-on fixings
* Outlets are equally distributed on each vertical PDU circuit ** Maximum capacity of terminal block 6 mm²
Terminal
block**
Cable
clamp +
guide
6 C13 + 1 C19 with
locking
1U
aluminium
Zero-U
aluminium
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
Zero-U PDUs
646850 646851 646852 646853 646854 646856
Number of phases 1 1 1 1 1 1
Input voltage 230 V 230 V 230 V 230 V 230 V 230 V
Input current 32 A 32 A 32 A 32 A 32 A 32 A
Maximum power 7.4kW 7.4kW 7.4kW 7.4kW 7.4kW 7.4kW
Termination method Terminal block** Cord Terminal block** Cord Terminal block** Terminal block**
Cable length 3 m 3 m
Cable material Rubber HO7RNF Rubber HO7RNF
Cable cross-section 3G 4 3G 4
Plug type IEC 60309 32 A
Cable retention method Cable clamp +
rotatative system
Number and type of outlets* 24 French/Belgian 24 French/Belgian 24 German 24 German 24 UK 24 C13 with
Outlet colour Black Black Black Black Black Black
Angle of outlets 55° 55° 55° 55° 55° 90°
Number of circuits per phase 2 2 2 2 2 2
Identification of circuits (colour-code) Blue/Red Blue/Red Blue/Red Blue/Red Blue/Red Blue/Red
Additional functions 1P+N MCB C16
10 kA
Cat.No. 4 077 00
Casing Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium
Fixings (included) 2 button + 2 standard brackets, 2 Minkels brackets + 2 screws
2P+E
Cable clamp +
rotatative system
1P+N MCB C16
10 kA
Cat.No. 4 077 00
Cable clamp +
rotatative system
1P+N MCB C16
10 kA
Cat.No. 4 077 00
IEC 60309 32 A
2P+E
Cable clamp +
rotatative system
1P+N MCB C16
10 kA
Cat.No. 4 077 00
Cable clamp +
rotatative system
1P+N MCB C16
10 kA
Cat.No. 4 077 00
Cable clamp +
rotatative system
locking
1P+N MCB C16
10 kA
Cat.No. 4 077 00
** Maximum capacity of terminal block 6 mm²
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
6/15
Page 7
10’’ PDUs 19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
Zero-U PDUs (continued)
646857 646859 646860 646861 646865 646870
Number of phases 1 1 1 1 1 3
Input voltage 230 V 230 V 230 V 230 V 230 V 400 V
Input current 32 A 32 A 32 A 32 A 32 A 16 A
Maximum power 7.4kW 7.4kW 7.4kW 7.4kW 7.4kW 11kW
Connection method Cord Cord Terminal block** Cord Terminal block** Cord
Cable length 3 m 3 m 3 m 3 m
Cable material Rubber HO7RNF Rubber HO7RNF Rubber HO7RNF Rubber HO7RNF
Cable cross-section 3G 4 3G 4 3G 4 5G 2.5
Plug type IEC 60309 32 A
2P+E
Cable retention method Cable clamp +
rotative system
Number and type of outlets* 24 C13 with
locking
Outlet colour Black Black Black Black Black Black
Angle of outlets 90° 90° 90° 90° 90° 90°
Number of circuits per phase 2 2 2 2 2 1
Identification of circuits (colour-code) Blue/Red Blue/Red Blue/Red Blue/Red Blue/Red
Additional functions 1P+N MCB C16
10 kA
Cat.No. 4 077 00
Casing Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium Zero-U aluminium
Fixings (included) 2 button + 2 standard brackets, 2 Minkels brackets + 2 screws
IEC 60309 32 A
2P+E
Cable clamp +
rotative system
24 German/Italian 20 C13 + 4 C19
1P+N MCB C16
10 kA
Cat.No. 4 077 00
Cable clamp +
rotative system
with locking
1P+N MCB C16
10 kA
Cat.No. 4 077 00
IEC 60309 32 A
2P+E
Cable clamp +
rotative system
20 C13 + 4 C19
with locking
1P+N MCB C16
10 kA
Cat.No. 4 077 00
Cable clamp +
rotative system
20 C13 + 4 C19
with locking
1P+N MCB C16
10 kA
Cat.No. 4 077 00
1 ammeter per
circuit
IEC 60309 16 A
3P+N+E
Cable clamp +
rotative system
18 C13 + 6 C19
with locking
1P MCB C16 10 kA
Cat.No. 4 076 54
646875
Number of phases 3
Input voltage 400 V
Input current 16 A
Maximum power 11kW
Connection method Cord
Cable length 3 m
Cable material Rubber HO7RNF
Cable cross-section 5G 2.5
Plug type IEC 60309 16 A
Cable retention method Cable clamp +
Number and type of outlets* 18 C13 + 6 C19
Outlet colour Black
Angle of outlets 90°
Number of circuits per phase 1
Identification of circuits (colour-code)
Additional functions 1P MCB C16 10 kA
Casing Zero-U aluminium
Fixings (included) 2 button + 2
3P+N+E
rotative system
with locking
Cat.No. 4 076 54
1 ammeter per
circuit
standard brackets, 2 Minkels brackets
+ 2 screws
* Outlets are equally distributed on each circuit ** Maximum capacity of terminal block 6mm²
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
7/15
Page 8
10’’ PDUs
cable entry, 4.5 m cable and IEC 60309 16 A plug
m
A p
19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
2.2 Customized products
Legrand PDUs can be delivered with custom configurations to meet specific customer requirements. Contact your local sales representative to discuss your requirements.
CONFIGURATION EXAMPLES
3m
Example: 19’’ PDU 1U with 2 x 2P+E French/Belgian standard outlets, 1 C19 socket and 6 C13 sockets. Supplied with 3 m cable and C20 plug
4.5 m
Example: Zero-U PDU with 12 2P+E French/Belgian standard outlets. Red strips for PDU identication purposes. Supplied with rotative
3. FUNCTIONS
3.1 Outlets
Legrand PDUs can be equipped with outlets of different standards.
C13 with cord locking system
2P+E 10 A Outlet recess at 90° angle
Conforms to standard IEC 60320-2-2
C19 with cord locking system
2P+E 16 A Socket recess at 90° angle
Conforms to standard IEC 60320-2-2
Cord locking system on C13/C19 sockets
The cord is locked mechanically into the outlet to prevent any unintended disconnection (caused by maintenance, vibrations, etc.).
Pull-out force > 100 N This universal solution is compatible with all standard cords available on
the market.
German
2P+E 16 A Terminals equipped with protective shutters Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
UK
2P+E 13 A Terminals equipped with protective shutters Outlet recess at 90° angle
Conforms to standard IEC 60320-2-2
3.2 LED switch
The LED switch is used to control the PDU power supply. A white LED is lit when the PDU sockets are supplied
with power. 16 A switch Transparent switch
3.3 Power indicator
A white LED on the power indicator shows that the product is supplied with power.
3.4 Ammeter
The ammeter is used to measure consumption for enhanced installation management.
Operation: 230 VAC 50Hz Measured value: current (0 to 32 A) Operates by measuring the current using a shunt 3-digit display "XX.X"
Rotatable display for legible readout regardless of whether the PDU is mounted vertically or horizontally
French-Belgian
2P+E 16 A Terminals equipped with protective shutters Outlet recess at 55° angle
Conforms to standard IEC 60320-2-2
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
B
A
mA p
Amp
Amp
8/15
Page 9
10’’ PDUs
PR
OTEC
T
E
D
P
O
W
ER
P
ROTE
C
T
ED
PO
WE
R
P
ROTECTED
P
O
WER
P
ROTECTED
P
O
WER
19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
3.5 Surge protection and replacement module
Protection between Line and neutral of socket outlets connected downstream against overloads generated by the electrical network upstream of the surge protective device by creating a discharge current on the network and/or earthing link.
To be used in combination with a voltage surge protector installed in the panel..
D TE
C TE O PR
R
E
W O P
ON
ED T
C E T O R P
ER
W PO
ON
A
Technical data
Number of poles 2
Neutral system T T - TNS
Mode of protection MCB C16 and/or MCBO
Maximum continuous operating voltage U
300mA
C LN & N/PE 255V
L/PE 440V
Nominal sysem voltage U 230 VAC
Assigned current of load I
L 16A
Frequency F 50/60 Hz
Open cicuit voltage U
Voltage protection level U
OC 10 kV
P L/N 1kV
L/PE & N/PE 1,2kV
Temporary overvoltage test value U
T 441V
Nominal discharge current In 5kA
Maximum discharge current Imax 10 kA
Current factor k 1.6
Type Type 2 (T2) _ Type 3 (T3)
Location Indoor
Temperature and humidity range Normal range : -5°C : +40°C
Mechanical characteristics
IP 20
B
ON
6 468 97
Operation
• Surge protective devices are designed to limit transient overvoltages of atmospheric and industrial origin.
• They have a certain capacity to absorb energy and age with each operation; it is therefore normal for them to be out-ot-order after a certain number of operations. The imminent out-of-order status is signalled and the draw-out module should be replaced.
• Surge protective devices are designed to be installed at use points and are to be used in combination with the installation’s original modular protection.
• They are not designed to provide sole protection for an installation in a building likely to be hit by direct lightning strikes (e. g. buildings equipped with lightning arresters). This would immediately put the device out-of-order by exceeding its maximum discharge capacity.
• Overloads of atmospheric origin occur between the active wires and the earth. They are highly charged and uncontrolled.
• Overloads of industrial origin occur between the active wires (L+N) and are not so highly charged.
• The surge protective devices are equipped with an operation indicator light (to be checked on a regular basis):
- Mains supply present and green indicator light on: operational protection.
- Mains supply present and red indicator light on: change the module.
- Once the draw-out module is out-of-order the installation is no longer protected but remains powered (including the withdrawn module).
Cleaning
Without cleaning Replaceable element: Cassette Reference 6 468 9
Conformity
In compliance with the standard NF EN 61643-11 : 2014
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
9/15
Page 10
10’’ PDUs 19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
3.6 Protection devices
Protection devices are integrated in all standard catalogue PDUs and customized PDUs.
- MCBs
For protecting equipment against short-circuits and overloads 407652 DX3 1P MCB 10 A 6000 A - 10 kA 407654 DX3 1P MCB 16 A 6000 A - 10 kA 409131 DX3 1P MCB 10 A 10000 A - 16k A 409133 DX3 1P MCB 16 A 10000 A - 16 kA 407698 DX3 1P+N MCB 10 A 6000 A - 10 kA 407700 DX3 1P+N MCB 16 A 6000 A - 10 kA 409150 DX3 1P+N MCB 10 A 10000 A - 16 kA 409152 DX3 1P+N MCB 16 A 10000 A - 16 kA
- RCBOs
For protecting equipment against short-circuits and overloads and protecting people against leakage currents
410704 RCBO 10 A AC TYPE 4500 A - 6 kA - 30 mA 410705 RCBO 16 A AC TYPE 4500 A - 6 kA - 30 mA 410752 RCBO 10 A HPi AC TYPE 4500 A - 6 kA - 30 mA 410753 RCBO 16 A HPi AC TYPE 4500 A - 6 kA - 30 mA
3.8 Thermal overload breaker (custom configured version)
For protecting equipment against short-circuits and overloads Rating: 10 A and 16 A
Reset: The LED is lit during operation. When there is an overload, the red button pops out of the module and the LED goes off. To reset the breaker, press the red button until it clicks back into position; the LED lights up again.
3.9 Colour-coding
The PDUs are colour-coded using coloured strips. These strips clip onto the edge of the aluminium casing.
This solution is only compatible with Zero-U PDUs. Extruded PVC plastic Blue and red borders are available as standard, other colours are
available on request.
2 applications:
- For identifying circuits: one colour per circuit, to match the same colour used on the circuit breaker
See section 2 "Equipment and performance" to see which protection device is integrated in the standard catalogue products.
MCBs and RCBOs are installed on a projecting DIN rail support to avoid unintended breaking. This support can be equipped with a transparent cover by special request.
1 or 2-module support depending on the catalogue number
1-module support 2-module support
No cover
3.7 Fuse (custom configured version)
For protecting equipment against short-circuits and overloads Cartridge rating: 10 A and 16 A
1-module support with cover
With transparent cover
- For identifying the source: whole PDU in one colour identifies whether it is the primary or interruptible power source when there are 2 PDUs in the rack
To replace the cartridge, use a screwdriver to lever open the compartment containing the fuse.
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
10/15
Page 11
10’’ PDUs
1
All 10’’ catalogue numbers
To be equipped catalogue number
52
All 19’’ catalogue numbers
To be equipped catalogue
C
BFA
19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/19/
20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
3.10 Locking caps
For locking out the use of a socket. Require a key to unlock access. Products comprise a set of 6 locking caps + 1 key.
Cat.No 646890: For French/Belgian, German and Italian standard sockets (P40)
Cat.No 646892: For UK standard sockets Cat.No 646894: For C13 standard sockets Cat.No 646895: For C19 standard sockets
ABS plastic Light grey RAL 7035
Operating principle
2
45
3
6
4.1 10’’ PDUS
excluding 6 468 98
214
237
4.2 19’’ PDUS
excluding 6 468 99
442
465
4.3 ZEROU PDUS
D
E
52.5
6 468 98
214
52.5
44.3
180
237
52.5
number 6 468 99
44.3
Cat. No
6 468 50 1250 129452 52.5 87 1262-1292
6 468 51 1250 129452 52.5 87 1262-1292
6 468 52 1250 129452 52.5 87 1262-1292
6 468 53 1250 129452 52.5 87 1262-1292
6 468 54 1466 151052 52.5 87 1478-1508
6 468 56 1034 107852 52.5 87 1046-1076
6 468 57 1034 107852 52.5 87 1046-1076
6 468 60 1070 111452 52.5 87 1082-1112
6 468 61 1070 111452 52.5 87 1082-1112
6 468 65 1160 120452 52.5 87 1172-1202
6 468 70 1340 138452 52.5 87 1352-1382 6 468 75 1475 151952 52.5 87 1487-1517
1: Total height with standard bracket (screw-xing) 2: Total depth at circuit breaker slot
Height Width Depth
(1)
AB
442
405
465
CDE
(2)
Fixing centres
(min.-max.)
52.5
52
(1)
F
4. DIMENSIONS
Data sheet: S000093176EN-05 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
11/15
Page 12
10’’ PDUs
L2
L3
N
L2
L3
N
L2
L3
L2
L3
N
L2
L3
N
10
mm
19’’ PDUs Zero-U PDUs
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
5. INSTALLATION
5.1 TERMINATION
Depending on the configuration, the PDUs can be connected in different ways.
1) Supplied with power cord
See section 2 "Equipment and performance" to see which standard catalogue products have an integrated cord.
2) Terminal block connection
Some products are supplied without a cable; they are designed to be wired on a terminal block. See section 2 "Equipment and performance" to see which standard catalogue products have an integrated terminal block. Example of terminal block connection for a Zero-U PDU with rotative cable entry
C
D
B
A
Cable ø13 min. Cable ø20 max.
Cable ø7 min.
Cable ø15 max.
B
A
5G 2.5 mm2/5G 4 mm
120 mm
A
C
2
10 mm
3G 2.5 mm2/3G 6 mm
A
2
10 mm
120 mm
B
A
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
12/15
B
Page 13
10’’ PDUs 19’’ PDUs Zero-U PDUs
3) Connection via fast connector or C20 connector (custom configured version)
Connectors mounted on the front panel of the PDU. The PDU is powered via a separate cable that plugs into these connectors.
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
C20
Type Male Female Female
Nominal current 16 A 16 A 25 A
Voltage 250 VAC 250 VAC 250 VAC
IP 20 20 20
4) Explanation of 19’’ cable entry, rotative cable input, input with cable gland
The end piece on 19’’ PDUs integrates a cable guide.
Zero-U PDUs integrate a rotative cable input (330°).
Wieland GST18 Wago
C20 Wieland GST18 Wago
330º
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
13/15
Page 14
10’’ PDUs 19’’ PDUs Zero-U PDUs
PDUs can be supplied with a cable input via cable gland by special request (input on front face or on the end).
5.2 MOUNTING SOLUTIONS
1)10’’ and 19’’
Horizontal mounting with snap-on fixing (for square holes 9.5 x 9.5). Snap-on fixing system included
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
Snap-on xing
Vertical mounting possible by turning the fixing brackets round and positioning them on the rear of the unit.
Mounting bracket dimensions
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016
CONTENTS
14/15
Page 15
10’’ PDUs
Standard xing bracket dimensions
19’’ PDUs Zero-U PDUs
2) Zero-U
Zero-U PDUs are designed for vertical installation and supplied with 2 sets of fixing accessories:
- 2 button: for screwless fixing. The height of the fixing centre can be set at any point along the full height of the PDU by sliding the button slots into the groove on the rear of the PDU. Tightened using a 2.5 mm Allen key.
Cat. Nos: 6 468 00/01/05/06/07/09/10/11/12/13/14/15/18/1
9/20/21/22/23/24/30/31/32/33/35/36/40/41/42/43/44/
45/50/51/52/53/54/56/57/59/60/61/65/70/75/90/92/94/
Button dimensions
x2
B
B
C
2.5
- 2 standard fixing brackets: for screw-fixing (screws not included)
x2
A
A
- 2 Minkels brackets + 2 screws
x2
Data sheet: S000093176EN-04 Updated: 29/03/2018 Created: 25/10/2016