Leader 3803, LG 3803 Instruction Manual

Page 1
LG 3803
8VSB/QAM SIGNAL GENERATOR
INSTRUCTION MANUAL
LEADER ELECTRONICS CORP.
Page 2
GENERAL SAFETY SUMMARY ............................................................................................. I
1. INTRODUCTION .............................................................................................................. 1-1
1.1 Scope of Warranty................................................................................................... 1-1
1.2 Operating Precautions............................................................................................. 1-1
1.2.1 Line Voltage and Fuse ................................................................................. 1-1
1.2.2 Maximum Input Voltage ............................................................................... 1-2
1.2.3 Reverse Voltage, Excessive Voltage ........................................................... 1-2
1.2.4 Backup of Control Settings .......................................................................... 1-2
1.2.5 Installation.................................................................................................... 1-3
1.2.6 Mechanical Shock........................................................................................ 1-3
1.2.7 About Network ............................................................................................. 1-3
2. SPECIFICATIONS ............................................................................................................ 2-1
2.1 Description .............................................................................................................. 2-1
2.2 Features .................................................................................................................. 2-1
2.3 Specifications .......................................................................................................... 2-2
2.3.1 Channel Coding Section.............................................................................. 2-2
2.3.2 RF Signal Generator.................................................................................... 2-2
2.3.3 Input/Output Signal Sources........................................................................ 2-2
2.3.4 C/N Generator Section ................................................................................ 2-3
2.3.5 BER Counter Section................................................................................... 2-3
2.3.6 External Interface......................................................................................... 2-4
2.3.7 Display Panel............................................................................................... 2-4
2.4 General Specifications............................................................................................. 2-4
3. PANEL DESCRIPTIONS .................................................................................................. 3-1
3.1 Front Panel.............................................................................................................. 3-1
3.2 Rear Panel .............................................................................................................. 3-4
4. LCD PANEL DESCRIPTION ............................................................................................ 4-1
4.1 Turning Power On and Starting Instrument ............................................................. 4-1
4.2 Screen Description.................................................................................................. 4-1
4.3 Menu ....................................................................................................................... 4-6
5. USING MENU...................................................................................................................5-1
5.1 CODING .................................................................................................................. 5-1
5.1.1 Source ......................................................................................................... 5-2
5.2 NOISE ..................................................................................................................... 5-4
5.3 CHANNEL ............................................................................................................... 5-5
Page 3
5.4 LEVEL ..................................................................................................................... 5-6
5.5 BER......................................................................................................................... 5-7
5.5.1 SETUP......................................................................................................... 5-8
5.6 UTILITY................................................................................................................... 5-9
5.6.1 CONFIG....................................................................................................... 5-10
5.6.2 TCP/IP ......................................................................................................... 5-11
5.6.3 GPIB ADDRESS.......................................................................................... 5-12
5.6.4 PRESET GROUP ........................................................................................ 5-13
5.6.5 CF ACCESS ................................................................................................ 5-14
6. PRESET, GROUP ............................................................................................................ 6-1
6.1 Preset...................................................................................................................... 6-1
6.2 GROUP ................................................................................................................... 6-1
7. REMOTE CONTROL........................................................................................................ 7-1
8. GPIB ................................................................................................................................ 8-1
8.1 Specifications .......................................................................................................... 8-1
8.2 Interface Function.................................................................................................... 8-1
8.3 Interface Message Function.................................................................................... 8-2
8.4 GPIB Address.......................................................................................................... 8-2
8.5 Clear, Reset............................................................................................................. 8-3
8.6 REMOTE/LOCAL .................................................................................................... 8-3
8.7 Multiline Message Command .................................................................................. 8-4
8.8 Program Message Format....................................................................................... 8-4
8.9 Program Message Terminator ................................................................................. 8-4
8.10 Program Code Format............................................................................................. 8-4
8.11 Program Code List .................................................................................................. 8-5
8.12 Detail Program Code............................................................................................... 8-7
9. ETHERNET ...................................................................................................................... 9-1
9.1 Connection .............................................................................................................. 9-1
9.2 Operating with Personal Computer ......................................................................... 9-1
10. MAINTENANCE ............................................................................................................... 10-1
Page 4
GENERAL SAFETY SUMMARY
To Avoid Personal Injury
It is recommended that only qualified personnel with technical knowledge use this instrument only after reading and fully understanding all functions of the instrument described this instruction manual. This instrument is not designed and manufactured for consumers. If you do not have enough knowledge on electricity, to avoid personal injury and prevent damage to this product, please be sure to use this product only under the su-pervision of an engineer who has sufficient knowledge about electronics.
Precautions on Contents
Should you find the contents in this manual and any of its technical terms confusing, please feel free to contact your local Leader agent.
Symbols and Terms
Following terms and symbols indicate necessary warnings and cautions used in this manual and on the product are there for safe operation.
Symbol
The sections where this symbol is marked in this manual or instrument, if not correctly performed or practiced, could result in personal injury or cause serious danger to the instrument. Misuse could also produce unintentional movement to create an operational impediment on the instrument or other products that might be connected to it. Be sure to refer to the safety precautions in this manual to safely use the part of the instrument where the symbol is marked.
Term
Warning statements identify warning conditions that if disregarded or not correctly performed or adhered to, could result in serious personal injury or even loss of life.
Term
Caution statements identify warning conditions if disregarded or not correctly performed or adhered to, could result in personal injury or damage to the instrument.
WARNING
CAUTION
I
Page 5
GENERAL SAFETY SUMMARY
Review the following safety precautions to avoid operator's injury and loss of life and prevent damage and deterioration to this instrument. To avoid potential hazards, use this product as specified.
WARNING
Warnings on the Cases and Panels of the Instrument
Operator should not remove any cases or panel for any reasons. If you touch inside the instrument it could result personal shock or fire hazard. Refrain from spilling any liquid on or inserting anything flammables or piece of metal into the ventilation of the instrument. Such actions could cause fire, shock, malfunction and be an accident hazard while the power is on.
Warnings on Power Line
Make sure to connect only to the rated power line voltage. Excess voltage may
cause fire.
Confirm the voltage of the commercial power line before connecting the AC power cord. The power frequency of the power line should be 50/60 Hz.
Warning on the Power Cord
Use only the optional power cord that is attached to this instrument. The use of the power cord other than that attached could cause fire hazard. If the attached cord is damaged stop using it and contact your local Leader agent. Should you use a damaged cord, it could cause a shock or create a fire hazard. When you pull out the cord be sure to hold it by plug and pull from the socket not by holding the cord wire.
Warning on Fuse
When the fuse is melted the instrument stops operation. If the fuse melted, turn off the power switch and disconnect the power plug from the socket. If you change the fuse while the cord is connected to the socket, it could cause a shock hazard. Only use the specified type and rated current and voltage fuses. If the cause for melting fuse is unclear or if you suspect there is damage to the instrument or if you have no proper fuse at hand please contact your local Leader agent.
II
Page 6
GENERAL SAFETY SUMMARY
WARNING
Warning on Installation Environments
About the Guaranteed Operating Temperature Range
Operate the instrument between the temperature range of 0 to 40 °C. Operating the instrument at higher temperatures could cause a fire hazard. Rapid changes of temperatures from cold to warm can create internal moisture or condensation and could damage the instrument. If there is a possibility of moisture condensation allow the instrument to sit for 30 minutes without the power on.
About the Guaranteed Operating Humidity Range
Operating humidity range is 85 % RH. Do not operate the instrument with wet hands, This could cause a shock and fire hazard.
About the Operation in the Presence of Gasses
Operating the instrument in and near the presence or storage locations of flammable, explosive gasses or fumes could create an explosion and fire hazard. Do not operate the instrument anywhere near such environments.
Avoid Insertions
Do not insert metals or flammable objects or drop liquid on or into the instrument. To do so could cause fire, shock, malfunction and create a dangerous accident hazard.
Warning while Operating
While operating the instrument in smoke, fire, or a bad smell, occurs, turn off the instrument at once for it could cause a fire hazard. When such a case occurs, turn off the power switch and pull the plug of the cord from the plug socket. Contact your local Leader agent after confirming there is no fire.
Warning about Ground
The instrument has a ground terminal to avoid electric shock hazard and to protect the instrument from damage. Ensure that the product is properly grounded for safe operation.
III
Page 7
GENERAL SAFETY SUMMARY
CAUTION
Caution on Input/Output Terminals
Input Terminals are rated with a maximum input. Do not supply an input over the specified rating in the standard section of the instruction manual. Also, do not supply external power to Output terminal, this could cause the instrument to malfunction.
Caution when Not to Using Instrument the for a Long Time
Make sure to disconnect the power cord from the socket when you do not use the instrument for a long time.
Calibration
This instrument is produced under the strictest quality controls at the factory, but accuracy may gradually deteriorate due to worn components. Therefore, periodic calibration should be performed. When service or calibration is required, contact your local Leader agent.
Routine Maintenance
Remove the power cord plug from the socket when cleaning the instrument. Avoid the use of thinner or benzene solvents for cleaning cases, panels and knobs since this might remove the paint or damage plastic surfaces. Wipe cases, panels, and knobs lightly with a soft cloth damped with neutral detergent. Do not allow water, detergent, or other foreign objects to enter the instrument while cleaning. If a liquid or metal object enters the instrument, it can cause electric shock or fire.
Please conform to the above warnings and cautions for safe operation. There are cautions in each area of in this instruction manual, so please conform to each caution. If you have any questions about this manual, please feel free to contact your local Leader agent.
IV
Page 8
1. INTRODUCTION
Thank you for purchasing Leader’s measuring instruments. Please read this instruction manual carefully to ensure correct and safe operation. If you have any difficulties or questions on how to use the instrument after you have read this manual, please feel free to contact your local Leader agent. After you have read the manual, keep the manual in a safe place for quick reference.
1.1 Scope of Warranty
This Leader instrument has been manufactured under the strictest quality control guidelines. Leader shall not be obligated to furnish free service during the warranty period under the following conditions.
1. Repair of malfunction or damages resulting from fire, natural calamity, or improper voltage applied by the user.
2. Repair of an instrument that has been improperly repaired, adjusted, or modified by personnel other than a factory-trained Leader representative.
3. Repair of malfunctions or damages resulting from improper use.
4. Repair of malfunctions caused by devices other than this instrument.
5. Repair of malfunctions or damages without the presentation of a proof of purchase or receipt bill for the instrument.
1.2 Operating Precautions
WARNING
1.2.1 Line Voltage and Fuse
Confirm that the power line voltage is correct before connecting the power cord. The voltage range and fuse rating are indicated on the rear panel. The instrument must be connected to the rated line voltage and line frequency of 50 Hz to 60 Hz. When replacing the fuse, turn the power switch off and disconnect the power cord from the outlet.
When replacing the fuse, use the correct fuse that matches the line voltage.
Voltage Range Fuse Rating Leader Parts Number
90 to 250 V 2 A, time-lag 436 3580 013
1-1
Page 9
CAUTION
1.2.2 Maximum Input Voltage
There is restriction when applying input signals. Applying excessive voltage to the connector may result instrument damage.
Connector Allowable Input Voltage
REMOTE CONTROL INC, DEC, RESET Pins
-0.5 V/+5.5 V
FREQ STD 10 MHz INPUT 2.5 Vp-p
SYNC, VALID, CLOCK, DATA -0.5 V/+5.5 V
CAUTION
1.2.3 Reverse Voltage, Excessive Voltage
Do not apply external voltage to the output connectors. If the cable touches such as DC power source, internal attenuator may be burned-out. Do not apply 5 Vp-p or greater signal to the output connector. If ±2V or greater DC component is superimposed, block it using a capacitor.
1.2.4 Backup of Control Settings
This instrument retains the panel settings even when the power is turned off. The setting can be recalled when the power is turned on. When the instrument is left for five years without supplying power, the stored data may be lost.
Notes on Backup Data
Data must be backed up properly since stored data may be lost or changed caused by incorrect operation, malfunction, or maintenance. A notepad may be helpful in some cases.
1-2
Page 10
1.2.5 Installation
Do not use the instrument in the following environments.
• High temperature environments Do not place the instrument under direct sunlight or near a heater (e.g., stove). Do not move the instrument from cold to warm environment abruptly, it may cause condensation.
Operating temperature range: 0 to 40 ˚C
5 to 40 ˚C (When Option 70 is installed.)
• High humidity environments Do not place the instrument in the high humidity environment (e.g., bathroom, near a humidor).
Operating humidity range: 85 % RH (without condensation)
• Dusty environments
1.2.6 Mechanical Shock
To prevent damage to the precise components used in this instrument, be careful not to expose the instrument to other forms of severe mechanical shock.
1.2.7 About Network
The remote control capability operation via the Ethernet is confirmed only under the local network environments; it is not guaranteed under other environments.
1-3
Page 11
2. SPECIFICATIONS
2.1 Description
The LG 3803 8VSB/QAM Signal Generator, conforms to 8VSB (digital terrestrial TV in USA System) and 64QAM/256QAM (CATV) standards, features a channel coding, modulation, C/N generator, and up converter in a single package. Consequently, the modulated signal covering VHF and UHF channels can be output. Providing pseudo random signal (PN) and BER counter can perform BER measurement of receivers and tuners with a signal unit. In addition to the internal TS signal, the external MPEG-2 TS can be used to evaluate video, and sound quality. Such powerful features are ideal for total evaluation of a reception system.
2.2 Features
• All-in-one This instrument features the signal generator capability and BER measurement capability in a single package. The BER function is used to measure the front-end section, the broadcasting MPEG-2 TS function is used to visually check entire system. In addition to the digital terrestrial TV broadcasting, this instrument can also be used for the CATV. Such features are ideal for the production line of STB and tuners.
• Arbitrary modulation system settings The modulation system can be arbitrary set via the front panel controls. The QVGA LCD graphically displays the setting conditions.
• Encoding/modulation MPEG-2 TS in realtime The MPEG-2 TS applied from the DVB-ASI or DVB-SPI connector can be encoded/modulated in realtime.
• 100 preset conditions Up to 100 preset conditions can be stored in the memory. Since the stored contents can be categorized into 10 groups, the preset mode is convenient for inspection applications.
• Various options
• LG 3803-OP70 Moving Picture Option (Factory option) With the HDD and DVD-ROM installed, a stream including HDTV content (i.e., requires large storage area) and long-time TS can be played back from the HDD.
• The BER measurement of Out Of Band in CATV systems can be performed by connecting the LG 3803-01 Out Of Band Generator (sold separately).
2-1
Page 12
2.3 Specifications
2.3.1 Channel Coding Section
(1) Broadcasting system Digital Terrestrial (ATSC A/53B)
CATV (ITU-T J.83 annex B)
(2) Modulation system 8VSB/64QAM/256 QAM
2.3.2 RF Signal Generator
(1) Frequency
Range 50 to 900 MHz Resolution 1 kHz, set in frequency Channel USA, KOREA Accuracy ±0.4 x 10
-6
(2) Output
Range -100 to +13 dBm (into 50 Ω) Resolution 0.1 dB Impedance 50 Level Accuracy ±1 dB (at 0 dBm, C/N off) Output Connector N type Harmonics -30 dBc Spurious -50 dBc
2.3.3 Input/Output Signal Sources
(1) Internal Signal
Pseudo Random Signal PN23 Still Picture Pattern Color bar, ramp, monoscope (*1) Screen Size 16:9 1920 x 1080i, 1280 x 720p, 704 x 480i (*1) 4:3 704 x 480i (*1) Sound (Tone) 1 kHz (LR), 400 Hz (LR), 1 kHz (L) + 400 Hz (R) (1)
1: Specifications are subject to change without notice.
(2) DVB-ASI Input
Input Connector BNC Input Impedance 75 Input Level 0.8 Vp-p Baud Rate 270 Mbps
(3) DVB-SPI Input
Input Connector 25-pin D-sub Input Impedance 100 differential input Input Level LVDS Input Format MPEG-2 TS or BER count input, automatic selection
2-2
Page 13
(4) ASI, SPI Input Specifications
Input Packet Format 188 bytes Applicable Stream MPEG-2 TS (ISO/IEC 13818-1) Input Data Rate 25 Mbps max.
(5) FREQ STD Input
Input Connector BNC Input Impedance 50 Input Level 0.8 Vp-p Input Frequency 10 MHz
(6) FREQ STD Output
Output Connector BNC Output Impedance 50 Output Level +4 dBm Output Frequency 10 MHz
(7) 4-Wire Serial BER Input
Input Connector BNC Input Level LVTTL 3.3 V Input Signal SYNC, VALID, CLOCK, DATA
(8) TS Clock Output
Output Connector BNC Output Impedance 50 Output Level TTL Output Frequency 8VSB 2.424083 MHz 64QAM 3.371294 MHz 256QAM 4.851338 MHz
2.3.4 C/N Generator Section
C/N Variable Range 0 to 31 dB Setting Resolution 0.1 dB On/Off Selectable
2.3.5 BER Counter Section
(1) Input Section
Packet Length 188 bytes Input Connector DVB-SPI connector, serial input
(2) GO/NO-GO Function
Threshold Settings Upper and lower limits of BER GO/NO-GO Indication Displays GO/NO-GO on the screen.
2-3
Page 14
2.3.6 External Interface
(1) Memory Card Interface
Memory Card Compact flash card (CFA TYPE-I) Function Updating firmware, changing internal TS-ROM
(2) ETHER Interface
Specifications 10BASE-T or 100BASE-TX Function Setting this instrument, reading status
(3) GPIB
Specifications ANSI/IEEE Std 488.1-1987. Function SH1, AH1, T8, L4, SR0, RL2, PP0, DC1, DT0, C0, E1
(4) USB Interface
Specifications USB1.1 Function For connection of external equipment for enhancing in the
future (Future support)
(5) Remote Control
Connector 24-pin Rectangular 57 LE-30240 (Amphenol) Remote Function Recalling of preset memory (INC/DEC) Input Level TTL
2.3.7 Display Panel
LCD 5.7” QVGA (320 x 240) TFT color
2.4 General Specifications
Environmental Conditions Operating Temperature 0 to 40°C 5 to 40°C (OP70 installed) Operating Humidity 85% RH (without condensation) Spec-Guaranteed Temperature 10 to 35°C Spec-Guaranteed Humidity 85% RH (without condensation) Operating Environment Indoor use Operating Altitude Up to 2000 m Overvoltage Category Pollution Degree 2 Power Requirements Voltage 90 to 250 VAC, 50/60 Hz Power Consumption 140 W max. Dimensions and Weight Dimensions 426 (W) x 150 (H) x 450 (D) mm Weight 14 kg approx. Accessory
Power cord..............................1
Instruction Manual ..................1
2-4
Page 15
3. PANEL DESCRIPTIONS
3.1 Front Panel
18
14
13
11
4
3
21
2
6
9
8
10
12
5
16
17
15
19
20
7
1
Figure 3-1 LG 3803 front panel
1 POWER switch
Push this switch in to apply power. Release this switch for turning power off. The setting conditions immediately before turning power off can be recalled.
2 LCD panel
Indicates the setting conditions in Graphical User Interface (GUI).
3 Function keys (F1 to F5)
Set functions. The functions are displayed on the LCD panel.
4 MENU keys
Set functions. Six keys are provided.
CODING Selects broadcasting system, input source, modulation parameter, etc. NOISE Selects noise signal on/off. Sets the CN value. CHANNEL Sets the RF output channel. The channel can also be set in frequency. LEVEL Sets the output level. BER Controls and sets the Bit Error Rate (BER). UTILITY Sets the various setting.
5 USB connector
USB 1.1 connector Connects an external equipment such as keyboards. (Future support)
6 Access lamp
Lights when this instrument is accessing the memory card
7.
3-1
Page 16
7 MEMORY CARD slot
Only used when the memory card contents are upgraded or updated.
8 UP MENU key
While displaying the setting screen, pressing this key enters the current data, then returns to the upper level by one. Holding down this key for at least one second enters the current setting, then returns to the top screen.
9 Ten key (0 to 9 . -)
Directly enter such numeric data as level, channel (frequency), CN. Press ENTER
10
key to enter data.
10 ENTER key
Enters numeric data set.
11 Arrow keys { ↑(INC), ↓(DEC), ← (BACK), → (NEXT)}
<, keys>
Increments and decrements numeric data {i.e., level, channel (frequency), CN}. Moves the arrow to the PID number to be selected in external input mode. Increments and decrements the PID value between 0 and F when data is input in
hexadecimal numbers.
Difference between Up (F2)/Down (F4) keys and ↑/↓ keys
F2, F4 keys Increments and decrements the value by preset step size. , keys Increments and decrements the value by preset step size. Holding down this key continuously changes the value.
< , keys>
Moves the arrow to the PID number to be selected in external input mode. When entering PID value (hexadecimal numbers):
pressing the → key enters the value at the current digit, then moves to the next digit. pressing the key cancels the value at the current digit, then returns to the previous digit.
12 ALL CLEAR key
Clears input data (i.e., numeric data, hexadecimal data).
13 PRESET display
Displays the last selected preset number.
14 ADDRESS key
Specifies the address to be stored or recalled.
15 STORE key
Stores the current setting in the address.
3-2
Page 17
16 RECALL key
Recalls the setting conditions in the specified address.
17 , key
Increments and decrements the specified address.
18 UNIT key (UNIT)
Selects either this instrument or OOB when the LG 3803-01 unit is connected.
19 REMOTE key (REMOTE)
Switches the remote control mode to local control mode. This key is disabled in local control mode.
20 RF OUTPUT connector CAUTION
Outputs RF signal. Refer to Section 2.3.2, "RF Signal Generator" for specifications.
21 Option compartment
Compartment to install the Moving Picture Option (OP70).
3-3
Page 18
3.2 Rear Panel
22 ○24
33
34
27
31
32
26
31
39
23
25
28 ○29
30
○35○
36
37
38
Figure 3-2 LG 3803 rear panel
22 FREQ STD 10 MHz INPUT connector
Accepts the external reference signal. Apply 10 MHz reference signal when operating this instrument in synchronized with the equipment connected.
23 FREQ STD 10 MHz OUTPUT connector
Synchronizes other equipment.
24 Serial BER CLOCK signal input connector (BER SERIAL INPUT CLOCK)
Used for BER measurement in serial connection.
25 Serial BER SYNC signal input connector (BER SERIAL INPUT SYNC)
Used for BER measurement in serial connection. This connector is only used when the "Serial (4 Wire)" is selected on the screen.
26 Serial BER DATA signal input connector (BER SERIAL INPUT DATA)
Used for BER measurement in serial connection.
27 Serial BER VALID signal input connector (BER SERIAL INPUT VALID)
Used for BER measurement in serial connection. This connector is only used when the "Serial (4 Wire)" is selected on the screen.
28 TS clock output connector
Outputs the TS clock to synchronize the external TS input.
29 TS INPUT DVB-ASI connector
Accepts the external TS signal. Apply the TS in DVB-ASI format.
30 TS INPUT DVB-SPI connector
Accepts the external TS signal. Apply the TS in DVB-SPI format.
3-4
Page 19
31 Cooling fans (Two places)
To prevent instrument damage due to overheating, do not block airflow through the ventilation holes. If the fan stops, the LCD panel displays alarm message. Turn the instrument power off immediately, then contact your local Leader agent in this case.
32 ETHER connector
Control connector for 10BASE-T or 100BASE-TX.
33 USB connector
Factory use only. Leave this connector open.
34 REMOTE CONTROL connector CAUTION
Used to up/down and return operations for the preset value. Refer to Chapter 7 "REMOTE CONTROL."
35 GPIB connector
GPIB interface connector.
36 AC INPUT
AC power inlet. The accessory power coed should be used. The AC voltage range is 90 to 250 V. Refer to Section 1.2.1, "Line Voltage and Fuse" for detail.
37 FUSE CAUTION
The mains fuse is installed. Use only the fuse of correct type and rating for replacement. Refer to Section 1.2.1, "Line Voltage and Fuse" for detail.
38 GND terminal
Grounding terminal connected to the chassis of this instrument
39 Serial number plate
Instrument serial number. Provide this number when contacting us.
3-5
Page 20
4. LCD PANEL DESCRIPTION
4.1 Turning Power On and Starting Instrument
Connect the accessory power cord between the AC inlet on the rear panel and the mains. Press the POWER switch to turn power on for starting the system. Whit for about 45 seconds until the top screen (Status screen) is displayed. The setting conditions immediately before turning power off will be recalled.
4.2 Screen Description
The screen display consists of the top screen and various setting screens. The followings describe the typical screens.
<Top Screen>
3
2
5
12
8
7
6
1
4
9
10
11
13
Figure 4-1 Top screen
1 Screen title Indicate the top (Status) screen.
2 Unit information Indicate the setting parameter of this instrument or OOB.
3 Group Displays the preset group number.
4 TS signal selection Selects the TS to be used.
5 Carrier modulation (Current) Displays the carrier modulation setting status.
6 Channel, frequency Displays the channel number when the RF signal is set in
channel. Displays the frequency in units of MHz when the RF signal is set in frequency.
7 Output level Displays the output level.
4-1
Page 21
8 BER result display Displays the Bit Error Rate (BER) measurement value
and GO/NO-GO results based on the threshold values.
9 Interleave Displays "- - -" when the carrier modulation is 8VSB.
Displays the interleave length when the 64QAM or
256QAM is selected.
10 Country Displays the channel table: USA or KOREA.
11 C/N level Display the C/N level. "- - -" is displayed when the C/N is
set off.
12 Key lock Displays the panel key lock status.
13 Alarm display Display alarm status for cooling fan, TS input, reference
signal and OOB.
<< Key lock >>
Restricts the front panel key operations.
Off Enables all keys. Part Disables all keys except the Address, ↑/(PRESET), and RECALL keys. All Disables all keys.
<<About top screen>>
• The top screen displays the titles. See each setting screen for detail.
• The top screen is displayed when one of the following operations are performed:
(1) Immediately after the power is turned on. (2) UP MENU key is held down for at least one second. (3) ADDRESS key is pressed. (4) Preset status is recalled by using the RECALL key, or or key in the
PRESET group.
<< Setting/controlling on the top screen >>
• The following operations can be performed on the top screen. Pressing the F5 key enables key lock mode. Pressing the F4 key can playback/stop the TS when the Moving Picture Option (OP70) is installed. For other items, press the menu key, then set as required on the appropriate setting screen.
4-2
Page 22
<<Alarm display on the top screen>>
• The following alarm message is displayed on the top screen. Message is displayed in red.
[FAN] Indicates cooling fan trouble. If this alarm is displayed, turn the
instrument power off, then contact your local Leader agent.
[TS IN] Monitors each input signal when SPI/ASI is selected as TS input. The
SPI input in BER measurement mode is also monitored. The alarm is displayed in the following status: (1) No signal is input. (2) When the signal other than transport stream (MPEG-2 TS) is input. (3) When five packets or more packets except 0x47 are continuously
received at the header byte position.
[F STD] Monitors the reference signal. The alarm is displayed in the following
status: (1) No signal is applied. (2) Input signal frequency exceeds the PLL lock range. (3) Input signal level is lower than the acceptable level range.
[OOB] In case of the LG 3803-01 is incorrectly connected.
4-3
Page 23
<Setting screen example "CODING">
14
15
16
18
17
16
15
14
16
18
17
Figure 4-2 Setting screen example (1)
14 Screen title, hierarchical layer display Displays the screen title and hierarchical layer from the top
menu.
15 Unit information Indicate the setting parameter of this instrument or OOB.
16 Selection status Use the corresponding key when changing the settings. The
selected item is displayed in white character on the blue background. Pressing the key sequentially selects the item.
17 Disabled function Items displayed in gray title is currently disabled or optional
functions.
18 Function Displays the functions assigned to the F1 to F5 keys.
When ">>>" is displayed on the bottom of the function display, use the next hierarchical layer for settings.
4-4
Page 24
<Setting screen example "LEVEL">
19
19
20
Figure 4-3 Setting screen example (2)
19 Numeric value display column Displays the current setting value.
When data is set by using the numeric keypad, the value is displayed in white on the black background. Press the ENTER key to enter data. The value is only entered when the value is within the acceptable range.
20 Step display The numeric value can be sequentially updated in preset
steps displayed in the step size column.
Pressing the F2 (Up) or F4 (Down) key increments/decrements the value preset by using the F3 key. The or ↓ key in the DATA ENTRY can also be used as well.
<Operation procedure> (1) Pressing either key in the MENU group enters the setting screen. (2) To return to the upper hierarchical layer, press the UP MENU key. Press this key
repeatedly to return to the uppermost hierarchical layer.
(3) Holding down the UP MENU key for at least one second any hierarchical layer returns
to the top menu.
(4) There are two setting methods:
For the items set on the CODING menu, data is entered when the UP MENU key is
pressed to return to upper hierarchical layer or to the top menu.
For other items {level, channel (frequency), C/N, etc.}, data is directly entered when
the value or settings are changed.
4-5
Page 25
4.3 Menu
The top screen only displays the current setting status; there is no setting items. When changing the setting status, press the MENU key to display the setting screen. The MENU key function is listed below:
CODING Selects the broadcasting system and modulation mode.
Selects the TS input source. Sets the Interleave. Selects the CW on/off. (Refer to Section 5.1.)
NOISE Sets the CN level value.
Sets the CN addition on/off. (Refer to Section 5.2.)
CHANNEL Sets the RF output channel (or RF frequency).
(Refer to Section 5.3.)
LEVEL Sets the output level.
(Refer to Section 5.4.)
BER Controls the BER measurement function.
Sets the threshold level for GO/NO-GO judgement. (Refer to Section 5.5.)
UTILITY Sets the various setting (Refer to Section 5.6.)
To return to the top menu, hold down the UP MENU key for at least one second.
4-6
Page 26
5. USING MENU
5.1 CODING
Pressing the CODING key in the MENU group enters setting screen.
Figure 5-1 Coding screen
This screen is used to select the modulation mode and TS signal, and to set items related to channel coding. To exit settings, press other key in the MENU, or hold down the UP MENU key to return to the top screen (status display).
• Source (F1) Selects the input source. (Refer to Section 5.1.1.)
• Modulation (F2) Selects the broadcasting system or modulation mode.
• Interleave (F3) Selects the interleave mode. This key is only enabled when the Modulation is set to 64QAM or 256QAM.
• CW (F5) Switches the output signal: modulated signal or carrier wave.
5-1
Page 27
5.1.1 Source
The TS source can be selected by pressing the Source (F1) key on the Coding (L-1) screen.
Notes on selecting TS_source
• The receiver is temporary unlocked when TS source (each pattern stored in the ROM, PN, SPI, ASI) is switched since the coding circuit is reset.
• When the external TS (SPI, ASI) is selected, reception capability is disabled if TS INPUT alarm lights on the top screen or TS exceeding allowable rate is input.
Figure 5-2 TS source selection screen
• TS Source (F2) Selects the TS input to be used.
PN Pseudo random signal in PN23 ROM
Modulates and outputs the video and sound signals stored in
the ROM. External <SPI> TS input to the SPI connector on the rear panel is used. External <ASI> TS input to the ASI connector on the rear panel is used. Internal TS of HDD on DVD is used when the Moving Picture Option
(OP70) is installed.
• Null Packet Filter (F4) This key is only enabled when the External (i.e., SPI, ASI) is selected. The packet with 0x1FFF PID is filtered off from the TS applied to the input connector. Various carrier modulation capabilities can be increased by removing surplus null packet.
• PCR Update (F5) Channel coding is performed for the external TS applied. The PCR should be rewritten to convert the rate. Set this function on in general. Up to eight PCRs are rewritable for the external TS.
5-2
Page 28
(1) Selecting PN
The random signal (PN23) can be output by setting the Source to PN on the TS Source (L-2) screen.
(2) Selecting ROM Pattern
The pattern stored in the ROM (called ROM pattern) can be selected by setting the Source to ROM on the TS Source (L-2) screen, then press the Pattern (F1) key.
Figure 5-3 ROM pattern selection screen
• Pattern (F3) Selects the video pattern.
Color Bar Eight-color full field color bar pattern Ramp Full field ramp pattern Monoscope Monoscope pattern
• Video Format (F4) Selects the size of patterns listed above.
1920 x 1080 (16:9) 1280 x 720p (16:9) 704 x 480i (16:9) 704 x 480i (4:3)
• Audio (F5) Selects the sound pattern.
1 kHz (L, R) Tone signal (1 kHz for both left and right) 400 Hz (L, R) Tone signal (400 Hz for both left and right) 1 kHz (L) + 400 Hz (R) Tone signal (1 kHz for left, 400 Hz for right)
The pattern, pattern size, and sound can arbitrary be combined.
(3) Selecting External <ASI or SPI>
The TS applied to the ASI or SPI connector is used by setting the TS Source to External on the Source (L-2) screen.
5-3
Page 29
5.2 NOISE
Figure 5-4 C/N setting screen
• Up (F2) Increments the C/N value by preset step size within the acceptable range.
• Step Size (F3) Sets the step size for Up and Down operations.
• Down (F4) Decrements the C/N value by preset step size within the acceptable range.
• C/N Addition (F5) Sets C/N on/off.
The C/N value can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
5-4
Page 30
5.3 CHANNEL
Figure 5-5 Channel or Frequency setting screen
• Country (F1) Selects the channel tables of USA or KOREA.
• Up (F2) Increments the channel or frequency by preset step size within the
acceptable range.
• Step Size (F3) Sets the steps for Up and Down operations.
(*Selectable only when frequency is set.)
• Down (F4) Decrements the channel or frequency by preset step size within
the acceptable range.
• Input Item (F5) Selects setting range and method of the RF frequency.
Air Channel Use to set channel directly.
USA: [2 to 83 ch], KOREA: [2 to 12, 21 to 83 ch]
CATV Channel Use to set CATV channel directly.
USA STD: [C2 to C135 ch] USA IRC: [C1 to C135 ch] USA HRC: [C1 to C135 ch] KOREA: [C1 to C41 ch]
Fequency Sets the CHANNEL in frequency.
The CHANNEL or FREQUENCY can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
5-5
Page 31
5.4 LEVEL
Figure 5-6 Level setting
• Up (F2) Increments the level value by preset step size within the
acceptable range.
• Step Size (F3) Sets the steps for Up and Down operations.
• Down (F4) Decrements the level value by preset step size within the
acceptable range.
The LEVEL can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
5-6
Page 32
5.5 BER
Figure 5-7 BER setting and measurement
• BER Setup (F1) Sets the BER measurement conditions. Refer to Section 5.5.1.
• Up (F2) Increments the C/N or output level value by preset step size within
the acceptable range.
• Step Size (F3) Selects the steps for C/N or output level.
• Down (F4) Decrements the C/N or output level value by preset step size
within the acceptable range.
• Select (F5) Selects the item by pressing the ↑,↓, up (F2) or Down (F4) keys
in the DATA ENTRY group. This function enables only when the C/N is set on.
The setting value can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
Notes on using BER function
The BER measurement mode is only enabled under the following conditions:
PN is selected for TS Source.
5-7
Page 33
5.5.1 BER SETUP
Figure 5-8 BER SETUP screen
• Interface (F2) Selects the TS input for BER measurement.
Parallel Use the SPI connector. Serial (2 Wire) Use both [CLOCK] and [DATA] connectors in the SERIAL
INPUT group.
Serial (4 Wire) Use all of four connectors in the SERIAL INPUT group.
• Value Input Select (F5) Selects the item to be set.
Upper Sets the upper threshold value (close to 0) in GO/NO-GO
judgement mode.
Lower Sets the lower threshold value (close to 1) in GO/NO-GO
judgement mode. (Settable range: 0.00E-0, 1.00E-9 to 9.99E-1)
Measurement Cycle The measurement cycle can be set in 0.1 second steps.
The values can be directly entered by using the numeric keypad.
(1) When no signal is input to the SPI connector or there is asynchronous error on the TS,
the alarm lights on the top screen.
(2) When measurement starts, the top screen and BER screen display the measurement
value. "GO" is displayed when measurement value is with the threshold value; "NO-GO" is displayed for outside the threshold.
5-8
Page 34
5.6 UTILITY
Figure 5-9 Utility screen
Software Version Displays the control software version. Provide the serial number
indicated on the rear panel and software number when contacting
us. TS ROM Version Displays the ROM pattern version. Installed Unit Displays the option installed.
• Config (F1)
Address of TCP/IP and GPIB is displayed. (Refer to Section 5.6.1)
• Pre. Group (F2)
There are 100 preset conditions (i.e., consisting of 10 groups, 10 conditions per group). The range can independently be incremented and decremented for each group.
(Refer to Section 5.6.4)
• OOB Unit (F4)
Sets the LG 3803-01 unit (OOB) to enable or disable.
• Freq. STD (F5)
Selects the reference signal.
5-9
Page 35
5.6.1 CONFIG
Figure 5-10 CONFIG screen
• TCP/IP (F1)
Sets the IP-Address, Subnet Mask and Default Gateway.
(Refer to Section 6.5.2)
• GPIB Adr. (F2)
Sets the GPIB Address. (Refer to Section 6.5.3)
5-10
Page 36
5.6.2 TCP/IP
Figure 5-11 TCP/IP screen
• Item Select (F5)
Selects the item that inputs the numeric value. The values can be directly entered by using the numeric keypad.
Notes on TCP/IP setting
The setting conditions will be recalled when the power is turned on.
5-11
Page 37
5.6.3 GPIB ADDRESS
Figure 5-12 GPIB ADDRESS screen
• GPIB Adr. Up (F2) Increments the GPIB ADDRESS within the acceptable range.
• GPIB Adr. Down (F4) Decrements the GPIB ADDRESS within the acceptable range.
The setting value can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
Notes on GPIB ADDRESS setting
The setting conditions will be recalled when the power is turned on.
5-12
Page 38
5.6.4 PRESET GROUP
Figure 5-13 PRESET GROUP screen
• CF Access (F1) Save the PRESET DATA to the memory card and load it from
the memory card. (Refer to Section 5.6.5)
• Group No. Up (F2) Increments the Group No. within the acceptable range.
• Group No. Down (F4) Decrements the Group No. within the acceptable range.
• Begin/End Select (F5) Selects the item that inputs the numerical value of the beginning
and the end number.
The setting value can be directly entered by using the numeric keypad, or changed by using the↑,↓,Up (F2) and Down (F4) keys.
5-13
Page 39
5.6.5 CF ACCESS
Figure 5-14 CF ACCESS screen
Status The operation status of SAVE/LOAD to the memory card is
displayed.
• Preset to CF (F1) Save the PRESET DATA to the memory card.
• CF to Preset (F2) Load the PRESET DATA from the memory card to internal
memory.
5.7 Internal Settings
5.7.1 Setting Calendar
Change to the super user, then login with telnet. The ID and password are lg3803. (Lowercase letters can only be used.)
data Enter month, date, hour, minute, and second as follows.
Example to set 2005/1/31 14:00:28
su (enter) root (enter) /work/script/hwdate 013114002005.28 (enter) hwclock -- systohc -- localtime (enter)
5-14
Page 40
6. PRESET, GROUP
6.1 Preset
Up to 100 setting conditions can be stored and recalled by using the front panel key.
• Storing Data (1) Set the CODING, CHANNEL, LEVEL, etc. (2) Press the ADDRESS key. The PRESET number LED brinks. (3) Specify the address to store data by pressing the or key in the PRESET
column, or enter address by using the numeric keypad.
(4) When the address is directly set by using the numeric keypad, press the ENTER
key.
(5) Pressing the STORE key stores data.
There are two methods to recall the setting conditions:
• Direct recall
To recall the desired memory number, press the or key in the PRESET group.
• Specifying address (1) Press the ADDRESS key. The PRESET number indicator LED brinks. (2) Specify the address to store data by pressing the or key in the PRESET
column, or enter address by using the numeric keypad. (3) Press the ENTER key to enter data. (4) Pressing the RECALL key recalls data.
6.2 GROUP
Up to ten groups can be set. Preset data can easily be used by incrementing or decrementing the preset range for each group.
• Setting group to be used (1) Press the Pre. Group (F1) key on the UTILITY screen to enter group setting
screen.
(2) Press the Preset Group (F5) key to select the desired group number.
• Setting preset range (1) Select the group number on the group setting screen. (2) Press the No. Input (F2) key to enter preset number setting screen, then set the
Begin and End numbers.
The End number must be larger than the Begin number.
• Recalling preset data (1) Press the ↑ or ↓ key, or the numeric keypad to specify the number to recall
data. Refer to Section 4.5.
Use the preset number within the specified range in the group being set.
Otherwise, the preset number is canceled.
6-1
Page 41
7. REMOTE CONTROL
This instrument can be remotely controlled (e.g., increments or decrements preset data) via the REMOTE CONTROL connector.
(1) Major Function Increment, decrement, returning group top (2) Connector 57LE-40240-7700 (DDK Ltd.) or equivalent (3) Input Level TTL (Pull up to +3.3 V) (4) Input Logic Negative logic (5) Output Level TTL (GO/NO-GO), open collector (Alarm) (6) Fan Out 1 each (7) Output Voltage +12 V (Alarm) (8) Output Logic Positive logic/negative logic (GO/NO-GO), negative logic (Alarm) (9) Pin Assignments See Table 7-1
Table 7-1 Pin assignments
No. Name Input/Output No. Name Input/Output
1 INC Input 13 GO (Positive logic) Output 2 DEC Input 14 GO (Negative logic) Output 3 RETURN Input 15 NO-GO (Positive logic) Output 4 Reserve 16 NO-GO (Negative logic) Output 5 Reserve 17 Alarm Output 6 Reserve 18 N. C. 7 Reserve 19 N. C. 8 Reserve 20 N. C.
9 N. C. 21 N. C. 10 N. C. 22 N. C. 11 GND GND 23 GND GND 12 GND GND 24 GND GND
About REMOTE CONTROL connector
• Do not apply external voltage to the output pins except Alarm pin.
• All pins are pulled up to +3.3 V. When externally control this instrument, do not apply voltage exceeding +5.0 V or negative voltages.
Recalling preset conditions via the REMOTE CONTROL connector
• The preset conditions between the Begin and End address can be recalled by using the INC/DEC pins. The INC, DEC, and RETURN pins are Low active. Assert for at least one second.
• After setting is performed, wait for at least one second for the next setting.
GO/NO-GO output pins
• Outputs TTL High or Low for GO/NO-GO judgement.
Alarm output pin
• Outputs OR of three types of alarms displayed on the top screen in negative logic. Since the open collector output is used, pull up the circuit for connection.
Operation while using GPIB and Ethernet
• The REMOTE CONTROL connector is enabled even when operating the instrument via the GPIB (in remote control mode) and Ethernet. When the REMOTE CONTROL connector is not used, disconnect any equipment from the connector.
7-1
Page 42
8. GPIB
Since this instrument provides the GPIB (IEEE 488) connector as standard, major functions can be remotely controlled via the GPIB interface.
Note
The GPIB capability of this instrument is confirmed by using the GPIB board (PCI-GPIB, PCMCIA-GPIB) manufactured by National Instruments Corporation (NI). If other than the board mentioned above is used, operation may differ from the instructions in this manual. Therefore, the board mentioned above should be used when controlling this instrument.
8.1 Specifications
Standard Conforms to ANSI/IEEE Std 488.1-1978 LSI Used TMS9914A or equivalent Code ASCII
8.2 Interface Function
Table 8-1 Interface function
Function Subset Description
Source Handshake SH1 All functions
Acceptor Handshake AH1 All functions
Talker T8 Basic talker function, canceling talker
specified by listener
Listener L4 Basic listener function, canceling listener
specified by MTA
Service Request SR0 No function
Remote/Local RL2 No LLO function
Parallel Poll PP0 No function
Device clear DC1 All function
Device trigger DT0 No function
Control C0 No function
E1 Open collector driver is used.
State driver is used for EOI and DAV, however.
8-1
Page 43
8.3 Interface Message Function
Table 8-2 Interface message and ASCII code
Upper 4 bits
0 1 2 3 4 5 6 7
Lower 4 bits
ASC MSG ASC MSG ASC MSG ASC MSG ASC MSG ASC MSG ASC MSG ASC MSG
0
NUL SPC 0 @ P ` p
1
GTL
! 1 A Q a q
2 " 2 B R b r
3 # 3 C S c s
4
SDC
DCL
$ 4 D T d t
5 % 5 E U e u
6 & 6 F V f v
7 ' 7 G W g w
8 ( 8 H X h x
9 ) 9 I Y i y
A
LF
* : J Z j z
B
+ ; K [ k {
C
, < L ¥ l |
D
CR
- = M ] m }
E . > N ^ n ~
F / ?
UNL
O _
UNT
o
Talk address
Listen address
Universal command group
Address command group
8.4 GPIB Address
Settable Range 1 to 30 Setting Procedure (Refer to Section 5.6.3)
8-2
Page 44
8.5 Clear, Reset
The Clear and Reset modes can be controlled by using the commands. The followings describe the reply for the clear and reset operations.
(1) IFC (Interface clear)
Reply of the universal command (IFC) is listed below.
• Cancels specified talker and listener.
• GPIB buffer and waiting command remain as is.
• Remote control conditions remain as is.
• Front panel control settings remain as is.
(2) DCL, SDC (Device clear)
Reply of the universal command (DCL) and address command (SDC) are listed below.
• Clears the GPIB buffer and waiting command.
• Interface conditions (specified talker and listener conditions) is remained.
• Enables the remote control mode.
• Front panel control settings remain as is.
(3) Returning power on
When the power is turned on again, the following operation is performed.
• Cancels specified talker and listener.
• Clears the GPIB buffer and waiting command.
• Enables the local control mode.
• Displays the top screen regardless of the display before turning power off.
8.6 REMOTE/LOCAL
The remote or local control mode can be selected by using the system controller and REMOTE key. Either remote or local control mode is always selected. Each status is described below.
(1) Local control mode
The local control mode is selected under the following conditions: (a) Power is turned on. (Immediately after the instrument starts.) (b) The REMOTE LED is turned off by pressing the REMOTE key. (c) When GTL command is received. (d) Remote control mode is canceled.
(2) Remote control mode
The remote control mode is enabled when the REN is in the truth state and this instrument is set to the listener. The REMOTE LED lights. In remote control mode, all front panel keys except the POWER switch and REMOTE key are disabled. The instrument can be controlled via the ETHER connector. The REMOTE CONTROL connector can also be used to control this instrument. When the GPIB capability is enabled, do not connect the equipment (e.g., personal computer) to the ETHER or REMOTE CONTROL connector.
8-3
Page 45
8.7 Multiline Message Command
Table 8-3 lists the multiline message command types and a reply to each command.
Table 8-3 Reply of multiline message command
Type Name Description Reply
DCL Clearing GPIB buffer Yes SPE Setting serial polling to State No SPD Clearing serial polling No PPU Clearing parallel polling No
Universal
Command
LLO
Setting all devices to local lockout status to inhibit manual operation
No
UNL Canceling specified listener Yes UNT Canceling specified talker Yes SDC Clearing GPIB buffer Yes
PPC
Enabling line assignments of specified parallel poll to listener in parallel polling
No
GTL Setting specified device to local Yes GET Triggering specified device No
Address
Command
TCT
When there are two controllers in the system, the controller specified to the talker operates as a master
No
8.8 Program Message Format
When controlling this instrument via the GPIB interface, send the program codes from the controller to this instrument. The program message consists of a single or multiple program codes. The program code consisting of up to 255 bytes (including delimiter) per each program message in ASCII code can be received. If the program code contains unspecified header or parameter outside the settable specified range, this program code is ignored even when the operation is performed.
8.9 Program Message Terminator
The terminator is used to delimit a program message. The following terminators CR can be used even if CR is attached.
(1) LF (2) LF+EOI (3) EOI
Separator for reply message ・・・";" (3Bh in ASCII code)
Terminator for reply message ・・・CR+LF+EOI
8.10 Program Code Format
The program code consists of header and data in accordance with requirements.
(1) Character
Use uppercase letters should be used for header and data.
(2) Delimiter between header and data
Insert a space (20h in ASCII code) between header and data. Also insert a space before "?" for query.
8-4
Page 46
(3) Program message unit separator
Use a semicolon ";" (3Bh in ASCII code) when transfers multiple messages simultaneously.
(4) Program data separator
Use a comma "," (2Ch in ASCII code) to delimit multiple parameters.
8.11 Program Code List
Table 8-4 Setting code list
Header Data Description Unit
1 SY n 0 to 2 Selecting modulation mode
n 0 to 5 Selecting TS input p 0 to 2 Type of TS input, or ROM video pattern q 0 to 3 ROM screen size
2 TS
r 0 to 2 ROM sound pattern 3 CO n 0 to 1 CN on (1), off (0) 4 CN i 0.0 to 30.0 Setting C/N value dB 5 CU CN value UP 6 CD CN value DOWN 7 CL n 0 to 2 Selecting digit of the C/N value to be set 8 BO n 0 to 1 Setting BER measurement on (1), off (0) 9 BU ne 0.00E-0 to 9.99E-1 Setting upper limit of BER threshold value
10 BL ne 0.00E-0 to 9.99E-1 Setting lower limit of BER threshold value 11 BI p 0.1 to 3600.0 Setting BER measurement interval 0.1 sec 12 CH n Setting channel CH 13 RF i 50.000 to 900.000 Setting RF frequency MHz 14 FU Frequency UP 15 FD Frequency DOWN 16 DF n 0 to 5 Selecting digit of the frequency to be set 17 LM i -100.0 to 13.0 Setting output level dBm 18 DU Output level UP 19 DD Output level DOWN 20 DL n 0 to 2 Selecting digit of the output to be set 21 CK n 0 to 1 Selecting reference signal 22 ST n 0 to 99 Setting address to store data 23 RC n 0 to 99 Setting address to recall data 24 RU Address increment 25 RD Address decrement 26 RR Returning to begin address 27 GR n 0 to 9 Selecting group
n
0 to 9
Setting begin and end addresses in each group
p 0 to 98 Setting begin address
28 GS
q 1 to 99 Setting end address
29 CW n 0 to 1 Setting modulation on (1), off (0)
8-5
Page 47
Table 8-5 Query code list
Header Data Description Reply 1 SY ? Reading modulation mode selected n 2 TS ? Reading signal selected to TS input n, p, q, r 3 CO ? Reading setting status of CN on (1), off (0) n 4 CN ? Reading setting status of C/N value i 5 CL ? Reading setting status of step to be set n 6 BO ? Reading setting status of BER measurement on (1), off (0) n 7 BR ? Reading BER value ne 8 BJ ? Reading judgement results ne, n 9 BU ? Reading setting status of upper limit for BER threshold value ne
10 BL ? Reading setting status of lower limit for BER threshold value ne 11 BI ? Reading setting status of BER measurement interval n, p 12 CH ? Reading setting status of channel n 13 RF ? Reading setting status of RF frequency i 14 DF ? Reading setting status of digit to be set n 15 LM ? Reading setting status of output level i 16 DL ? Reading setting status of digit to be set n 17 CK ? Reading selection status of reference signal n 18 GR ? Reading selection status of group n 19 GS n ? Reading setting status of begin and end addresses in each
group
n, p
20 CW ? Reading setting status of modulation n
Refer to each Option instruction manual for specified program code of option.
8-6
Page 48
8.12 Detail Program Code
This section describes the detail program codes listed in Section 8.11. Definition:
n, p, q, r, s 0 and natural number i Integer including decimal point ne Real number including exponential number _ Space (20h in ASCII code)
• Terminator is omitted for a syntax. Add the terminator at the end of the code (refer to Section 8.9).
• Header is not added for reply; the reply code consists of data only.
(1) Selecting modulation mode................... "SY"
Function Selecting and querying modulation mode. Syntax SY_n (Setting, reply) SY_? (Query)
n Modulation Mode Selection 0 8VSB 1 64QAM 2 256QAM
(2) Selecting TS input................................. "TS"
Function Selecting and querying TS for channel coding. Syntax TS_n (, p, q, r) (Setting, reply) TS_? (Query)
In this program code, the amount of consequent data depends on "n" selected.
n TS Input Selection 0 PN 1 External ASI 2 External SPI 3 Internal (OP70) 4 Reserve (Not used) 5 ROM
"3" is only enabled when the Moving Picture Option (OP70) is installed.
For external ASI or external SPI
p TS Type Selection 0 MPEG-2 TS 1 Reserve (Not used)
8-7
Page 49
For Internal (OP70 installed. Reply only; no setting is required.)
p Drive Used 0 HDD 1 DVD
For ROM
p Pattern Selection 0 Color Bar 1 Ramp 2 Monoscope
q Screen Size Selection 0 1920 x 1080i (16:9) 1 1280 x 720p (16:9) 2 704 x 480i (16:9) 3 704 x 480i (4:3)
r Sound Pattern 0 L: 1 kHz, R: 400 Hz 1 L, R: 1 kHz 2 L, R: 400 Hz
(1) For PN TS_0 (PN) (2) For ASI, SPI TS_1, 0 (ASI, MPEG-2 TS) (3) For ROM TS_5, 1, 0, 2 (Ramp, 1920x1080i, 400 Hz) (4) For Internal TS_3 (At setting) Reply for TS_? 3, 0
Setting of "n" and following data are ignored when they are not matched. When playing back TS from HDD or DVD, setting the TS command forcibly stops
playback operation.
8-8
Page 50
(3) Setting C/N on/off ............................... "CO"
Function Setting and querying C/N set in Step (4) on/off. Syntax CO_n (Setting, reply)
CO_? (Query)
n C/N On/Off 0 Off 1 On
(4) Setting and querying C/N value.......... "CN"
Function Setting and querying C/N value added. Syntax CN_i (Setting, reply)
CN_? (Query)
i C/N value: 0 to 31.0 (dB) Effective down to one digit after the decimal point
(5) Incrementing C/N value......................"CU"
Function Incrementing C/N value in current steps. Syntax CU (Setting)
(6) Decrementing C/N value .................... "CD"
Function Decrementing C/N value in current steps. Syntax CD (Setting)
(7) Setting preset steps for C/N value...... "CL"
Function Setting preset steps for incrementing and decrementing C/N value. Syntax CL_n (Setting, reply)
CL_? (Query)
n C/N Value Steps 0 0.1 1 1.0 2 10.0
(8) Setting BER measurement................."BO"
Function Setting and querying BER measurement. Syntax BO_n (Setting, reply)
BO_? (Query)
n BER Measurement 0 Off 1 On
Only when Source on the TS Source screen is set to PN, this program code is turned
on effectively and automatically.
8-9
Page 51
(9) Reading BER measurement value ....."BR"
Function Reading BER measurement value. Syntax ne (Reply)
BR_? (Query)
BER value ne: Replied in exponential format of 0.00E-0
This program code can only be used when the Source on the TS Source screen is set
to PN.
(10) Reading BER judgement results ........ "BJ"
Function Reading BER GO/NO-GO judgement results In accordance with
measurement value.
Syntax ne_n (Reply)
BJ_? (Query)
BER value ne: Replied in exponential format of 0.00E-0
n BER Measurement 0 NO-GO 1 GO
This program code can only be used when the Source on the TS Source screen is set
to PN.
(11) Setting upper limit of BER .................. "BU"
Function Setting and querying upper limit for GO/NO-GO judgement. Syntax BU_ne (Setting, reply)
BU_? (Query)
BER upper value ne: Exponential format of 0.00E-0
This program code can only be used when the Source on the TS Source screen is set
to PN.
When the value set is below the current lower limit, the value is ignored due to
handles as an error.
(12) Setting lower limit of BER..................."BL"
Function Setting and querying lower limit for GO/NO-GO judgement. Syntax BL_ne (Setting, reply)
BL_? (Query)
BER lower value ne: Exponential format of 0.00E-0
This program code can only be used when the Source on the TS Source screen is set
to PN.
When the value set is above the current upper limit, the value is ignored due to it is
handles as error.
8-10
Page 52
(13) Setting BER measurement interval .... "BI"
Function Setting and querying BER measurement interval. Syntax BI_p (Setting, reply)
BI_? (Query)
BER measurement interval p: 0.1 to 3600.0 sec.
Effective down to one digit after the decimal point.
The value set in second is converted into the number of packets ; it cannot be set in
number of packets.
Notes on program code for (8) to (13)
When TS input is set other then the PN, both setting and querying operations are disabled.
(14) Setting RF channel............................."CH"
Function Setting and querying RF channel (VHF, UHF, CATV). Syntax CH_n (Setting, reply)
CH_? (Query)
n RF channel VHF, UHF, CATV channel
n, STD STD setting of USA CATV channel
n, IRC IRC setting of USA CATV channel
n, HRC HRC setting of USA CATV channel
This program code is ignored when querying channel set in frequency.
(15) Setting RF frequency.........................."RF"
Function Setting and querying RF frequency. Syntax RF_i (Setting, reply)
RF_? (Query)
i RF frequency: 50.000 to 900.000 (MHz), effective down to three digits after
decimal point
This program code is ignored when querying channel set in channel.
(16) Incrementing frequency or channel .... "FU"
Function Incrementing frequency in current steps when RF is set in frequency.
Incrementing channel by one when RF is set in channel.
Syntax FU (Setting)
(17) Decrementing frequency or channel .."FD"
Function Decrementing frequency in current steps when RF is set in frequency.
Decrementing channel by one when RF is set in channel.
Syntax FD (Setting)
8-11
Page 53
(18) Setting frequency in current steps "DF"
Function Setting and querying increment/decrement of frequency in current
steps.
Syntax DF_n (Setting, reply)
DF_? (Query)
n Frequency Steps 0 0.001 1 0.01 2 0.1 3 1.0 4 10.0
This program code is ignored when frequency is set in channel.
(19) Setting output level............................."LM"
Function Setting and querying output level. Syntax LM_i (Setting, reply)
LM_? (Query)
i Output level: 13.0 to -100.0 (dBm) Effective down to one digit after the decimal point
(20) Incrementing output level ................... "DU"
Function Incrementing output level in current steps. Syntax DU (Setting)
(21) Decrementing output level.................."DD"
Function Decrementing output level in current steps. Syntax DD (Setting)
(22) Setting output level in current steps ... "DL"
Function Setting and querying increment/decrement of output level in current
steps.
Syntax DL_n (Setting, reply)
DL_? (Query)
n Output Level Steps 0 0.1 1 1.0 2 10.0
8-12
Page 54
(23) Selecting reference clock "CK"
Function Setting and querying reference clock. Syntax CK_n (Setting, reply)
CK_? (Query)
n Reference Clock 0 Internal 1 External input
(24) Writing preset memory ....................... "ST"
Function Storing current setting conditions to specified number. Syntax ST_n (Setting)
n Preset number 0 to 99
(25) Reading preset memory ..................... "RC"
Function Reading preset values of specified number. Syntax RC_n (Setting)
n Preset number 0 to 99
(26) Incrementing preset number .............."RU"
Function Incrementing preset number. Syntax RU (Setting)
(27) Decrementing preset number............."RD"
Function Decrementing preset number. Syntax RD (Setting)
(28) Preset return....................................... "RR"
Function Returning preset number to top. Syntax RR (Setting)
(29) Selecting group .................................."GR"
Function Setting and querying group. Syntax GR_n (Setting, reply) GR_? (Query)
n Group number 0 to 9
8-13
Page 55
(30) Setting group "GS"
Function Setting and querying group. Syntax GS_n, p, q (Setting, reply) GS_n_? (Query)
n Group number 0 to 9 p Begin address 0 to 98 q End address 1 to 99
The address numbers should be: begin address < end address.
(31) Setting modulation.............................. "CW"
Function Setting and querying modulation. Syntax CW_n (Setting, reply) CW_? (Query)
n Modulation 0 Modulation output 1 CW (carrier) output
8-14
Page 56
9. ETHERNET
9.1 Connection
When constructing the network system via the ETHER connector, use a STP cable conforming to 100BASE-TX standards. Use a straight cable when connecting the network via a hub. Use a cross cable when connecting a personal computer. Network manager should set the TCP/IP of this instrument according to your local network environments.
9.2 Operating with Personal Computer
Use the TELNET when remotely controlling the LG 3803 by using a commuter. To startup the TELNET, refer to the personal computer instruction manual.
Starting TELNET with the Windows 2000
Select TELNET from the START menu. When IP address assigned to the LG 3803 is "192.168.0.1," enter "TELNET
192.168.0.1."
The LG 3803 and TELNET is now connected.
When TELNET is started, "login:" is displayed. Enter "lg3803." When "Password" is displayed, enter "lg3803." The login name and password cannot be changed. Prefix "rem" to the command listed in Tables 8-4 and 8-5 for run the system. Attach "?" after the command to read setting value.
Example 1: When setting the frequency to 500 MHz, output level to -60 dBm,
proceed as follows:
rem RF 500 ENTER
rem LM -60 ENTER
is a space. Enter a space between header and data code.
Example 2: When reading the channel being set, proceed as follows:
rem CH ? ENTER Enter a space between header, data code, and "?."
Notes on using Ethernet
This instrument can be controlled via the Ethernet even when operating via the GPIB interface, or REMOTE CONTROL mode is in operation. When Ethernet is only used, disconnect other cables.
Windows is a registered trademark of Microsoft Corporation.
Operation of this instrument is confirmed by using Windows 2000 (SP2), however, the system may operate incorrectly depending on the personal computer environments.
9-1
Page 57
10. MAINTENANCE
The LG 3803 is designed to operate stably under normal handling. If you have questions regarding calibration and service, contact your local Leader agent.
Open Source
This instrument partially uses the open source distributed under the terms of the GNU General Public License. (http://www.gnu.org/copyleft/gpl.html)
When the source code is required, contact your local Leader agent.
[ NOTE ]
1. We do not guarantee and support software distributed under the terms of the GNU General Public License.
2. We are not responsible for modifying and distributing this program on your side.
3. You will be charged upon placing your order.
Jun. 3, 2005 05060.001K TS 1
10-1
Loading...