Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
Model XCR
Model XCR is a direct drive ceiling
exhaust fan designed for clean
air applications where low sound
levels are required. Many options
and accessories are available such
as lights, motion detectors, ceiling radiation dampers
and speed controls. Capacities range from 25 to 1,600
cfm (42 to 2,718 m
Licensed for Sound and Air Performance.
ENERGY STAR® Certified models include:
XCR-A, 50, 70, 90, 200, 250, 290 and 410;
XCR-B, 50, 70, 80 and 90.
To reduce the risk of fire, electric shock, or injury to persons,
observe the following:
• Suitable for use with solid state speed controls.
• Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
• Before servicing or cleaning unit, switch power off at service panel
and lock service disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
• Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) and the local code authorities.
• When cutting or drilling into wall or ceiling, do not damage
electrical wiring or other hidden utilities.
• Acceptable for use over a bathtub or shower when installed
in a GFCI protected branch circuit. (Up through size SP-A390)
• Never place a switch where it can be reached from a tub or
shower.
• Ducted fans must always be vented to the outdoors.
• These fans are not recommended for cooking exhaust
applications. They are designed primarily for low temperature,
clean air applications only. The diagram shows the minimum
distance these fans should be placed in relation to cooking
equipment.
• Fan/Light
insulated to a value greater than R40.
• For general ventilating use only. Do not use to exhaust hazardous
or explosive materials and vapors.
combination not to be installed in a
3
/hr) and 1 in. wg (248 Pa). AMCA
WARNING!
ceiling thermally
CAUTION!
Model XIR
Model XIR is a direct drive inline
exhaust fan designed for clean
air applications where low sound
levels are required. Capacities
range from 70 to 3,800 cfm (119 to
6,456 m
AMCA Licensed for Air Performance.
Pour réduire le risque d’incendie, de choc électrique ou de
blessure corporelle, respecter cd qui suit:
• Appareil pouvant être utilisé avec un régulateur de vitesse à semi-
• Utiliser cet appareil exclusivement comme prévu par le fabricant. En
• Avant tout entretien ou nettoyage de l’appareil, couper l’alimentation
• La pose et le câblage électrique doivent être effectués par des
• Une quantité d’air suffisante est nécessaire pour la bonne combustion
• Lors de la découpe ou du perçage de murs ou plafonds, ne pas
• Pose admissible au-dessus d’une baignoire ou d’une douche sous
• Ne jamais placer d’interrupteur à un emplacement à portée d’une
• Les caissons d’extraction à gaine doivent toujours être évacués vers
• Ces caissons ne sont pas conseillés pour les applications
• Le combiné ventilateur/luminaire ne devra pas être installé dans un
• À utiliser pour la ventilation générale uniquement. Ne pas utiliser
3
/hr) and 1 in. wg (248 Pa).
AVERTISSEMENT!
conducteurs.
cas de questions, communiquer avec le fabricant à l’adresse ou au
numéro de téléphone figurant dans la garantie.
sur le tableau électrique et verrouiller le dispositif de sectionnement
pour empêcher toute mise sous tension accidentelle. Si le dispositif
de sectionnement ne peut pas être verrouillé, attacher un moyen
de mise en garde bien visible, tel qu’un panonceau, au tableau
électrique.
personnes qualifiées en conformité avec les codes et normes en
vigueur, y compris pour la résistance au feu du bâtiment.
et l’extraction des gaz brûlés par le conduit d’évacuation (cheminée)
d’appareils à combustible afin d’éviter le refoulement. Veiller à suivre
les indications du fabricant du matériel de chauffe, les normes de
sécurité telles que celles publiées par la National Fire Protection
Association (NFPA) et l’American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE) et la réglementation en
vigueur.
endommager les câbles électriques et autres conduites masquées.
réserve de raccordement à un circuit de dérivation à protection GFCI
(disjoncteur différentiel). (Jusqu’à la taille SP-A390 incluse)
baignoire ou d’une douche.
l’extérieur.
d’aspiration de vapeurs de cuisson. Ils sont conçus essentiellement
pour l’aspiration d’air propre à basse température. Le schéma
indique la distance minimale de placement de ces caissons par
rapport à l’équipement de cuisson.
plafond ayant une isolation thermique d’une valeur supérieure à R40.
ATTENTION!
pour l’aspiration de matières et vapeurs dangereuses ou explosives.
Ceiling Exhaust and Inline Fans1
Page 2
Prepare the fan
Power Assembly
If power assembly (motor, wheel, and scroll) is not
installed in housing, insert the electrical plug into fan
socket, then slide scroll end of power assembly into
fan housing. Attach by using two sheet metal
screws provided.
B Model
A Model
Fan Rotation
To rotate from horizontal to vertical discharge
A-Models Only
Remove Wiring Knockout
Remove either top or side wiring knockout,
depending on wiring
direction, by
bending it back
E
lectrical
A
cce
P
ane
ss
l
and forth to
break tabs.
K
nockout
s
Ductwork
Check ductwork to see if the fan’s discharge requires
rotation from horizontal to vertical discharge.
Airflow
Airflow
A-50-500, 710, 780 Models
Remove the two screws holding the power assembly
in and pull power assembly out. Rotate power
assembly 180 degrees and put back into fan. Use
the same screws to reattach power assembly to fan
housing. Flip fan over and remove the four screws
holding the discharge duct and damper assembly.
Exchange the assembly with plate mounted on top of
fan, as shown in these illustrations.
A-700, 900-1500 Models
Remove the eight screws
holding the access panel or
collar as shown in picture.
Rotate the fan housing so
the discharge is facing up.
Replace access panel or
collar and screws.
Access
Panel
Access
Panel
Ceiling Exhaust and Inline Fans2
Page 3
Ceiling Radiation Damper (CRD)
A
A
If fan is to be used in a fire resistive membrane
ceiling, a ceiling radiation damper must be used.
If the ceiling radiation damper is already mounted to
the fan from the factory, proceed to Install the Fan.
To mount the ceiling radiation damper to fan, make sure
grille attachment tabs are facing down. Then place the inlet
part of the fan into the ceiling radiation damper collar, and
use self-tapping sheet metal screws (by others) to screw
through the damper collar and into the fan housing. If the
fan/light combination is being used, make sure ceiling
radiation damper has
an electrical plug in it.
The electrical plug must
be inserted into the fan.
Make sure the electrical
wire will not interfere with
damper operation as
shown in figure below.
Wires to ceiling fan
Attachment Tabs
A-50-510, 710, 780 Models
B-Models
Discharge Installation XCR-A 50-90 Models
12
Insert plastic duct tab into XCR-A box slots.
XCR-A Box
XCR-A Box Slot
Plastic XCRDuct Adapter Tabs
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Plastic XCRDuct Adapter (PN 473322)
3
Install screws provided to secure discharge.
A-700, 900-1550 Models
Rotate plastic XCR-A duct adapter (PN 473322)
until the screw tabs meets XCR-A box.
XCR-A Box
Plastic XCR-A
Duct Adapter (PN 473322)
Do not allow
interference
Wires from lighted grille
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Screw Tabs
in this area
Screw holes
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Ceiling Exhaust and Inline Fans3
Page 4
Discharge Installation XCR/XIR-B 50-200 Models
X
12
Insert XCR-B box scroll tab into XCR-B
box scroll slots.
XCR-B
Box Scroll Tabs
XCR-B
Box Scroll Slots
Rotate plastic XCR-B duct adapter (PN 474433)
until the two XCR-B mounting tabs fully engage
into the two XCR-B box mounting slots.
XCR-B
Box Mounting Slots
CR-B
Box Mounting Tabs
TR 6x4 Pin
3
TR 6x4
(PN 473324)
OPTIONAL
Align the pins on the TR 6x4 adaptor to the
duct pin hole on the XCR-B 6-inch duct. Push
until the adaptor snaps into place.
XCR-B
Plastic Duct Pin Hole
XCR-B
6-inch
Plastic Duct
(PN 474433)
Ceiling Exhaust and Inline Fans4
Page 5
Install the Fan
1. For best
performance,
choose a location
with the shortest
possible duct run
and minimum
number of elbows.
Do not mount near
cooking equipment, as
shown in Fig. 1.
2. Attach adjustable
mounting brackets
to fan, but leave the
screws loose until
proper height is
determined, shown
in Fig. 2. Cut hole to
dimensions shown
in table below:
45°45°
Bottom Mount
Bottom Mount
Top Mount
Do not install
fan in this area
Brackets can be
used in either
position to adapt to
most mounting
situations
Fig. 1
Fig. 2
For Frame Construction:
Position unit between
joists. Position brackets
such that bottom
edge of housing will
be flush with finished
ceiling, and tighten the
adjustable mounting
brackets, shown in
Fig. 3.
For Hanging
Installations:
Use Manufacturer’s
optional vibration
isolator kit Part Number
VI Kit. Using the fan’s
standard adjustable
mounting brackets and
10 by 32 threaded rod
(by others), hang unit as
shown in Fig. 4.
Fig. 4
Slots in the
brackets
allow fine
adjustment
for flush
fit with
wall/ceiling
opening
Fig. 3
Ceiling Openings
SizesFan or Fan/LightFan/CRD
XCR-A50, A70, A90
XCR-A110, A125, A190
XCR-A200, A250, A290, A390121⁄8
XCR-A700233⁄4
XCR-A410, A510, A710, A780143⁄4
XCR-A900, A1050, A1410,
A1550
XCR-B 50 - 200141⁄8
7
⁄8
x 133⁄8
10
x 141⁄4
x 113⁄4
x 183⁄8
3
⁄4
x 24147⁄8
14
x 113⁄4
111⁄8
121⁄4
241⁄8
147⁄8
143⁄8
x 137⁄16
x 143⁄8
x 121⁄4
x 187⁄16
x 241⁄8
x 121⁄4
NOTE
Model XCR-A 50-90 are standard with a round duct.
Should Model XCR-A 110-190 require a round duct,
Model RDC (Round Duct Connector) may be ordered
from Manufacturer for field installation.
Wire the Fan
1. Remove wiring cover.
If fan/light combination
is being used, make
sure the fan plug is
connected to the fan
receptacle and the light
plug is connected to the
light receptacle, shown
in Fig. 6. Using proper
Fig. 6
wire connectors, wire
the fan as shown in Fig. 7a.
For wiring of light proceed to Fig. 7b.
2. Push all wiring into the unit’s cover and replace
wiring cover.
Fan
Light
Light Outlet (bottom)
Fan Outlet (top)
3. Installation of ductwork
is critical to the performance
of the fan, shown in Fig. 5.
Straight ductwork (1) or
ductwork that turns in
the same direction as the
Fig. 5
2
(GOOD)
1
(GOOD)
AIRFLOW
3
(POOR)
wheel (2) is recommended.
Ductwork turning opposite
the wheel direction (3) will
cause turbulence and back
pressure resulting in poor
performance.
4. Slide ductwork over the fan’s discharge collar and
securely attach it with sheet metal screws.
Make sure the screws do not interfere with damper
operation. Check damper to make sure it opens freely.
Fig. 7aFig. 7b
115 & 277 Volt
Black wire is “Hot”
White wire is “Neutral”
Green wire is “Ground”
220 - 240 Volt
Black wire is “Hot”
White wire is “Hot”
Green wire is “Neutral/Ground”
Ceiling Exhaust and Inline Fans5
Page 6
Attach the Grille
1. If lighted grille is being used, plug wire into fan
socket.
If lighted grille and ceiling radiation damper are
being used, plug wire from lighted grille into ceiling
radiation damper socket. Do not plug wire directly
into the fan socket. Make sure the wire does not
interfere with the ceiling radiation damper operation.
2. Attach grille with two screws provided. Make sure
not to over tighten; over tightening will damage
grille.
3. Slide attachment screw covers over the attachment
screws, shown in Figure 8 and 9.
4. If lighted grille is being used, install light bulb(s) into
light socket(s). For incandescent lights, use maximum
100 watt bulb (by others). For fluorescent lights, use
27W GU24 bulbs. Manufacturer has replacement
27W GU24 bulbs call 1-800-355-5354 to order.
5. If lighted grille is being used, snap lens into place, by
pushing on the outside edges of lens, shown in Fig.9.
To remove lens, use small screw driver and pry on
one side of lens.
6. Turn on power and check fan and light operation.
Fig. 8
Fig. 9
Squeeze
tabs to
insert/remove lens
Converting from ceiling to cabinet design for Model XCR fans
All XCR convertible sizes will be shipped with grille and duct collar cover.
Conversion Kit Parts List
• Qty. of 1 Blower Box Cover
Tools Required
• Phillips Head Screwdriver
Step 1: Remove grille (A) by removing the two
grille screws (B).
Step 2: Remove duct collar cover (C) by
removing the four duct collar screws (D).
Step 3: Discard grille (A), two grille screws (B),
and duct collar cover (C).
Step 4: Remove the six (6) tinnerman clips (E)
by twisting them to one side and pulling
straight out. Discard two of the six
tinnerman clips.
Step 5: Insert the remaining four tinnerman clips
(E) on grille opening side.
Step 6: Place blower box cover (F) over tinnerman clips
(E), which were inserted in step 5.
Step 7: Screw the blower box cover (F) into place with
four blower box cover screws (D).
C
D
B
A
E
D
F
E
XCR/XIR models shown are
UL and cUL listed E 33599
Ceiling Exhaust and Inline Fans6
Page 7
Other Installation Considerations
Ductwork and Noise
Fiberglass ductboard is a better choice than metal
ductwork for reducing fan noise and is highly
recommended for low sound applications. Where metal
duct is used, sound transmission can be reduced with
flexible duct connections between the fan and the duct.
Sound and Location
The location of these fans must be taken into
consideration before installation. In critical sound
installations, insulated ductwork, flexible duct
connections or placing the fan in a remote section of
ductwork are solutions to meeting the required fan
sound levels.
Filters
The addition of an intake filter is highly recommended
for these fans, even in clean air environments excess
dirt can accumulate on wheels and motors causing
reduced performance and imbalance.
Filters, once installed, should be checked and cleaned
periodically to maintain performance.
Manufacturer offers washable aluminum mesh filters
specifically designed for these fans. Contact your
Accurex representative for more information.
XIR and XCR-C
Converted
to Inline
Fiberglass
Ductboard
Correct Low
Sound Installation
Remote
Mounted
Flex Duct
Connections
XCR and XCR-C
Mounted Directly
Overhead
Incorrect
XCR/XIR models shown are
UL and cUL listed E 33599
General Maintenance Suggestions
Model XCR/XIR ceiling exhaust fans require very little maintenance. But since small problems over time left
unchecked could lead to loss of performance or early motor failure, we do recommend that the unit be inspected
periodically (once or twice a year).
The fan motor and wheel should be checked for dust and dirt accumulations. Dirt buildup can lead to loss of
performance and motor overheating. Cleaning can be accomplished by brushing off any dust that may have
accumulated. Even filtered units can accumulate build-up and should be checked when cleaning filters.
The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole
provided. A few drops of all purpose oil (SAE 20) will be sufficient.
Ceiling Exhaust and Inline Fans7
Page 8
Typical Installation
INSULATION*
(Place around and over Fan Housing.)
FAN HOUSING
POWER CABLE*
Seal gaps around
Housing.
ROUND
DUCT*
Seal duct joints
with tape.
*Purchase separately.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in damper)
Keep duct runs short.
WALL CAP*
(with built-in damper)