Lancer IBD30 Installation Manual

LANCER INSTALLATION SHEET
ICE BEVERAGE DISPENSERS - SERIES 4500
DATE: 03/15/01 P.N. 28–0483
6655 LANCER BLVD. • SAN ANTONIO, TEXAS 78219 USA • (210) 310-7000
"Lancer" is the registered trademark of Lancer • Copyright — 2001 by Lancer, all rights reserved.
1. INSTALLATION
WARNING
IBD UNITS ARE EQUIPPED WITH AUTOMATIC AGITATION. THE UNIT MAY ACTIVATE UNEXPECTEDLY. DO NOT PLACE HANDS, OR FOREIGN OBJECTS INTO THE ICE STORAGE COMPARTMENT.
WHEN UNIT IS BEING SERVICED, CLEANED, OR SANITIZED, UNPLUG DISPENSER FROM THE POWER SOURCE.
1.1 RECEIVING
Each unit is completely tested under operating conditions and thoroughly inspected before shipment. At time of shipment, carrier accepts the unit and any claim for damage(s) must be made with carrier. Upon receiving units from the delivering carrier, carefully inspect carton for visible indication(s) of damage. If damage exists, have carrier note same on bill of lading and file a claim with the carrier.
1.2 UNPACKING
A. Set shipping carton upright on the floor. Cut band and remove. Open top of carton and remove interior packing. B. Lift carton up and off of the dispenser. Remove wood shipping base from the bottom of the dispenser. (Support dispenser while
removing shipping base to prevent damage to the dispenser.) C. Remove installation parts kits from the ice compartment. D. Inspect unit and parts for concealed damage(s). If damage exists, notify delivering carrier and file claim against same.
1.3 SELECTING THE LOCATION
A. Select a level, well ventilated, accessible location (convenient to water, soda, and syrup lines and open type drain), a properly
grounded electric supply and ensure sufficient clearance for air circulation. Sufficient clearance must be provided, if an ice maker is
not installed, to allow filling the ice compartment from a five gallon bucket (a minimum of 16 inches is recommended). Lancer does
not
recommend the use of shaved, flake, nugget, or pellet ice in the dispenser. Dispenser will only operate properly with cube ice.
B. The selected location should be able to support the weight of the dispenser, ice and possibly an ice maker being installed after
counter cut out is made. Total weight (with ice maker) for the IBD22 unit, IBD25 unit, IBD30 unit, or IBD44 unit could exceed
800 pounds (363.6kg). C. Unit may be installed directly on the countertop or on legs supplied with the unit. If installed directly on the counter, the unit must be
sealed to the countertop with an FDA approved sealant. If an ice maker is to be mounted on top of dispenser, do not
install dispenser
on legs.
1.4 CONNECTING TO ELECTRICAL POWER
WARNINGS
THIS UNIT MUST BE PROPERLY ELECTRICALLY GROUNDED TO AVOID POSSIBLE FATAL ELECTRICAL SHOCK OR SERIOUS INJURY TO THE OPERATOR. THE POWER CORD IS PROVIDED WITH A THREE PRONG GROUNDED PLUG. IF A THREE-HOLE GROUNDED ELECTRICAL OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD TO GROUND THE UNIT.
BE SURE TO FOLLOW LOCAL ELECTRICAL CODES WHEN MAKING ALL CONNECTIONS. EACH DRINK DISPENSER MUST BE SUPPLIED WITH A SEPARATE ELECTRICAL CIRCUIT. DO NOT USE EXTENSION CORDS WITH THIS UNIT. DO NOT “GANG” TOGETHER WITH OTHER ELECTRICAL DEVICES ON THE SAME OUTLET.
THE KEY SWITCH DOES NOT DISABLE THE LINE VOLTAGE TO THE TRANSFORMER PRIMARY. ALWAYS DISCONNECT ELECTRICAL POWER TO THE UNIT TO PREVENT PERSONAL INJURY BEFORE ATTEMPTING ANY INTERNAL MAINTENANCE. ONLY QUALIFIED PERSONNEL SHOULD SERVICE INTERNAL COMPONENTS OF ELECTRICAL CONTROL HOUSING. MAKE SURE THAT ALL WATER LINES ARE TIGHT AND UNITS ARE DRY BEFORE MAKING ANY ELECTRICAL CONNECTIONS!
A. Check the dispenser serial number plate for correct electrical requirements of unit. Do not plug into wall electrical outlet unless the
current shown on the serial number plate agrees with local current available.
B. Route the power supply cord to a grounded electrical outlet of the proper voltage and amperage rating, and plug in the unit.
1.5 CONNECTING TO WATER SUPPLY LINES
CAUTION
USE A SHARP KNIFE, RAZOR BLADE, OR TUBE CUTTER TO CUT TUBING. TUBING CUT WITH A SAW WILL RESULT IN PLASTIC SHAVINGS WHICH WILL PLUG THE FLOW CONTROLS IN THE DISPENSING VALVE. A FILTER IN THE WATER
This basic Installation Sheet is an initial release.
If a complete Installation and Service Manual (for the unit being installed) is required or needed, please refer to the Lancer web site (www.lancercorp.com). All Lancer Manuals and Instruction Sheets are being made available for immediate access on the web site. Or contact Lancer Customer Service for assistance as required.
LINE MUST BE USED IF THE WATER SUPPLY CONTAINS ANY APPRECIABLE AMOUNT OF SILT, SAND, OR ANY OTHER DEBRIS. FAILURE TO DO SO CAN RESULT IN EQUIPMENT DAMAGE.
FAILURE TO LIMIT WATER PRESSURE TO 50 PSI (3.52 KG/CM
2
) WILL RESULT IN IMPROPER PERFORMANCE OF THE
DISPENSER - INSTALL WATER REGULATOR IF NECESSARY.
THE WATER SUPPLY MUST BE PROTECTED BY MEANS OF AN AIR GAP, A BACKFLOW PREVENTION DEVICE (LOCATED UPSTREAM OF THE CO2 INJECTION SYSTEM) OR ANOTHER APPROVED METHOD TO COMPLY WITH NSF STANDARDS. A LEAKING INLET WATER CHECK VALVE WILL ALLOW CARBONATED WATER TO FLOW BACK THROUGH THE PUMP (WHEN IT IS SHUT OFF), AND CONTAMINATE THE WATER SUPPLY. A BACKFLOW PREVENTION DEVICE MUST COMPLY WITH ASSE AND LOCAL STANDARDS. IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE COMPLIANCE.
A SCREEN OF AT LEAST 100 MESH [100 STRANDS PER 25MM (ONE INCH)] SHALL BE INSTALLED IMMEDIATELY UPSTREAM OF ALL CHECK VALVE TYPE BACKFLOW PREVENTERS USED FOR WATER SUPPLY PROTECTION. THE SCREEN SHALL BE ACCESSIBLE AND REMOVABLE FOR CLEANING OR REPLACEMENT.
A FILTER IN THE WATER LINE MUST BE USED IF THE WATER SUPPLY CONTAINS ANY APPRECIABLE AMOUNT OF SILT, SAND, OR ANY OTHER DEBRIS. FAILURE TO DO SO CAN RESULT IN EQUIPMENT DAMAGE.
DO NOT OPERATE CARBONATOR PUMP WITH WATER SUPPLY SHUT OFF.
A. An adequate potable water supply must be provided. The water supply line must be at least a 3/8 inches (9.525 mm) pipe with a
minimum of 20 PSI line pressure, but not exceeding a maximum of 50 PSI. Water pressure exceeding 50 PSI must be reduced to 50 PSI with a pressure regulator.
1. Water pipe connections and fixtures directly connected to a potable water supply must all be sized, installed, and maintained according to Federal, State, and Local laws.
2. Off tastes and excessive silt, sand, or iron require that a water filter be installed in the water supplying the Carbonator. The water filter should be checked periodically, as required by local conditions.
3. Do not connect to a heated (hot) water source or a water source supplying soft water. This will cause excessive foaming.
B. The Carbonator Pump is equipped with a Strainer and a Tee on the outlet side for a plain water Valve (if required), but a water supply
containing any appreciable quantity of silt, fine sand, or other debris requires a Filter ahead of the Unit. The Filter cartridge must be cleaned periodically, depending upon the condition of the water. Failure to do so may starve the Pump and cause it to burn out; thereby, voiding the equipment warranty.
1.6 INSTALLATION OF THE UNIT
A Inspect the counter location where the unit is to be installed. Verify that the counter is strong enough to safely support the weight of
the unit being installed (see Section 1.3), after the cutout for the unit is made. B. Remove Splash Plate and Top Cover. C. Remove Cover Plate at rear of unit if not a “through the counter” installation. D. Connect soda and water supply lines to 3/8 inch barb fittings at the front of the unit. Check for leaks. (If dispenser is to operate with
all soda valves, connect water line into one of the soda supply lines.) E. Connect syrup supply lines to the 3/8 inch barb inlet fittings at the front of the unit. Check for leaks. F. Install the ice bin drain hose; connect the 90° elbow or straight fitting underneath the unit’s base. The ice bin drain is located towards
the front of the bin and slightly to the right. Screw the elbow or straight fitting into the cold plate; uncoil and connect the hose. Extend
the hose to an open type drain. G. Connect the hose to the Drip Tray fitting, install the Drip Tray, and extend hose to open type drain. H. Both drain lines must be insulated with a closed cell insulation. Insulation must cover the entire length of the drain hose, including
fittings. The drain should be installed in such a manner that water does not collect in sags or other low points, as condensation will
form.
I. Install Cup Rest and Splash Plate. J. Connect Power Cord to grounded electrical outlet. K. Test Motor operation by pushing Ice Chute. L. Clean and sanitize dispenser (see Section 3). M. Fill unit approximately half full with ice. Push Chute and check for ice delivery. N. Finish filling the unit with ice and install Top Cover. O. Set brix ratio for beverage dispensing valves according to manufacturer’s instructions.
1.7 CONNECTING CO
2
WARNINGS
CARBON DIOXIDE (CO2) DISPLACES OXYGEN. STRICT ATTENTION MUST BE OBSERVED IN THE PREVENTION OF CO
2 GAS LEAKS IN THE ENTIRE CO2 AND SOFT DRINK SYSTEM. IF A CO2 GAS LEAK IS SUSPECTED,
IMMEDIATELY VENTILATE THE CONTAMINATED AREA BEFORE ATTEMPTING TO REPAIR THE LEAK.
CO
2 IS A HEAVIER THAN AIR, COLORLESS, NONCOMBUSTIBLE GAS WITH A FAINTLY PUNGENT ODOR. HIGH PER-
CENTAGES OF CO2 MAY DISPLACE OXYGEN IN THE BLOOD, PROLONGED EXPOSURE TO CO2 MAY BE HARMFUL. PERSONNEL EXPOSED TO HIGH CONCENTRATIONS OF CO
2 GAS WILL EXPERIENCE TREMORS WHICH ARE
FOLLOWED RAPIDLY BY LOSS OF CONSCIOUSNESS AND SUFFOCATION.
UNDER NO CIRCUMSTANCE SHOULD CO
2 PRESSURE EXCEED 80 PSI (5.6 KG/CM
2
). PRESSURE ABOVE THIS LIMIT WILL RESULT IN DAMAGE TO THE SYRUP PUMPS. SHOULD REMOTE SYRUP PUMPS FAIL TO OPERATE PROPERLY AT 70 PSI (4.9 KG/CM2), THE CO2 PRESSURE MAY BE REDUCED TO A MINIMUM PRESSURE OF 60 PSI (4.2 KG/CM2), BUT NO LOWER. TO AVOID POSSIBLE PERSONAL INJURY OR PROPERTY DAMAGE, DO NOT ATTEMPT TO REMOVE
2
Loading...
+ 2 hidden pages