Lancer 1300 Operators Manual

INSTALLATION AND SERVICE MANUAL
FOR
PURE LINK WATER SYSTEMS
LANCER SERIES 1300
DATE: 06/17/03 P.N. 28–0461/03
This Manual supersedes the Installation and Service Manual 28-0461/02, dated 04/23/03
6655 LANCER BLVD. • SAN ANTONIO, TEXAS 78219 USA • (210) 310-7000
FAX SALES • USA-CANADA – 210-310-7250
Warranty / Technical Support - Field • 800-729-1500
Customer Service • Domestic / International – 800-729-1500
SPECIFICATIONS
DIMENSIONS
WIDTH 18 3/4 Inches (47.63 cm)
DEPTH 4 5/8 Inches (11.75 cm)
HEIGHT (with Boost Pump 29 Inches (73.66 cm)
and Transformer)
WEIGHT
Shipping (with Boost and 33.60 pounds (15.24 kg)
Delivery Pump, Transformer, and two Modules)
Gross Operating (with Boost and 60.60 pounds (24.79 kg)
Delivery Pump, Transformer, and two Modules)
ELECTRICAL REQUIREMENTS (Only when Booster Pump is included)
100V/50-60Hz 1.2 Amps
115V/60Hz 0.8 Amps
230V/50-60Hz 0.4 Amps
WATER REQUIREMENTS
Potable Water Supply
STORAGE CAPACITY
Storage Unit 4.00 Gallons (15.14 Liters)
One (1) Membrane Unit 4.00 Gallons (15.14 Liters)
Two (2) Membrane Unit 4.00 Gallons (15.14 Liters)
PRODUCTION RATE, WITH BOOST PUMP (@ 60psi, 77°F INLET)*
One (1) Membrane Unit 170.85 GPD* (646.7 LPD)
Two (2) Membrane Unit 269 GPD (1018.3 LPD)
*Gallons per Day
(Continued on inside cover page)
Please refer to the Lancer web site (www.lancercorp.com) for information relating to Lancer Installation and Service Manuals, Instruction Sheets, Technical Bulletins, Service Bulletins, etc.
System Tested and Certified by
NSF International against
NSF/ANSI 58 for the reduction of
Barium, Hexavalent Chromium,
Radium 226/228, TDS, and Cysts.
(Continued from cover page)
WORKING PRESSURE
Minimum 30 psi (206.8 KPa)
Maximum 120 psi (827.4 KPa)
Maximum inlet pressure 80 psi (551.6 KPa) (with boost pump)
OPERATING TEMPERATURE
Minimum 40°F (4.4°C)
Maximum 113°F (45°C)
FLOW RESTRICTOR RATIO (REJECT PRODUCT)
One (1) Membrane Unit 3:1
Two (2) Membrane Unit 2:1
Efficiency rating, as verified by testing in accordance with NSF/ANSI 58:
One Membrane 16.96%
Two Membrane 18.46%
Efficiency rating means the percentage of the influent water to the system that is available to the user as reverse osmosis treated water under operating conditions that approximate typical daily usage.
NOTES:
This system conforms to NSF/ANSI 58 for the specific performance claims as verified and substantiated by test data.
*Testing was performed under standard laboratory conditions - actual performance may vary.
PERFORMANCE DATA
This system has been tested according to NSF/ANSI 58 for reduction of the substances listed below. The concentration of the indicated substances in water entering the system was reduced to a concentration less than or equal to the permissible limit for water leaving the system, as specified in NSF/ANSI 58.
Substance Influent Challenge Maximum Permissible
concentration mg/L Product Water
Concentration mg/L
Barium 10.0 + 10% 2.0
Chromium (hexavalent) 0.3 + 10% 0.1
Radium 226/228 25 pCi/L +
10% 5 pCi/L
Total Dissolved Solids (TDS) 750 + 40 mg/L 187
i
Substance Influent Challenge Reduction Requirement
Concentration
Cyst Minimum 50,000/ml 99.95%
TABLE OF CONTENTS
SPECIFICATIONS......................................................................................................................................Cover
PERFORMANCE DATA ......................................................................................................................................i
TABLE OF CONTENTS .....................................................................................................................................ii
1. INSTALLATION ...........................................................................................................................................1
1.1 RECEIVING .................................................................................................................................................1
1.2 UNPACKING ......................................................................................................................................1
1.3 SELECTING INSTALLATION LOCATION..........................................................................................1
1.4 FILTERING THE WATER SUPPLY ....................................................................................................2
1.5 CONNECTING UNIT TO DRAIN........................................................................................................2
1.6 INSTALLING OVERFLOW.................................................................................................................2
1.7 CONNECTING UNIT TO POINT OF USE (POU)..............................................................................2
1.8 CONNECTING UNIT TO WATER SUPPLY .......................................................................................3
1.9 TURNING WATER ON .......................................................................................................................3
1.10 CONNECTING UNIT TO ELECTRIC POWER SUPPLY (IF EQUIPPED WITH
POWER SUPPLY)..............................................................................................................................3
1.11 BOOST PUMP BYPASS PRESSURE SETTING (IF SO EQUIPPED) ..............................................3
1.12 SANITIZING AND PURGING SYSTEM UPON INSTALLATION .......................................................4
2. INSTALLATIONS .........................................................................................................................................5
2.1 TYPES OF EQUIPMENT TO BE CONNECTED ...............................................................................5
2.2 INSTALLATION OF A FOUR (4) GALLON STORAGE UNIT TO SYSTEM (PN 85-1330) ................5
2.3 INSTALLATION OF OPTIONAL EQUIPMENT...................................................................................5
3. CLEANING AND MAINTENANCE ..............................................................................................................6
3.1 FILTER REPLACEMENT ...................................................................................................................7
3.2 WATER QUALITY ..............................................................................................................................7
4. MEMBRANE REPLACEMENT INSTRUCTIONS .......................................................................................7
5. REPLACING THE STORAGE BAG............................................................................................................8
5.1 PURE LINK SYSTEM WITH 4 GALLON STORAGE BAG ................................................................8
5.2 PURE LINK SYSTEM WITH 38.5 GALLON STORAGE BAG ...........................................................8
6. TROUBLESHOOTING.................................................................................................................................8
6.1 UNIT IS NOT MAKING WATER .........................................................................................................8
6.2 BOOSTER PUMP IS NOT RUNNING ...............................................................................................8
6.3 PRODUCTION RATE OF PURE WATER SEEMS TO BE SLOWING DOWN..................................8
6.4 NO WATER OR VERY LITTLE WATER FLOWING TO DRAIN ........................................................8
6.5 SYSTEM CANNOT KEEP UP TO HOST UNIT, ICE MAKER, COFFEE MAKER, ETC....................9
6.6 BOOSTER PUMP WILL NOT SHUT OFF ONCE THE BAG IS FULL OR WATER
FLOWS OUT OF OVER FLOW DEVICE AT TOP OF UNIT..............................................................9
6.7 SYSTEM CHATTER PRIOR TO SHUT OFF .....................................................................................9
TUBE CONNECTIONS ....................................................................................................................................10
7. ILLUSTRATIONS, PARTS LISTINGS, AND WIRING DIAGRAMS ..........................................................11
7.1 LANCER PURE LINK REVERSE OSMOSIS (RO) SYSTEM.....................................................11-12
7.2 LANCER PRE-FILTER KIT, TWIN-PAC, 5 MICRON (10” AND 20”)
(OPTIONAL EQUIPMENT)...............................................................................................................13
7.3 LANCER PURE LINK DELIVERY PUMP KIT, PN 82-3202 (OPTIONAL EQUIPMENT).................13
7.4 LANCER PURE LINK DELIVERY PUMP, PN 86-0139 (OPTIONAL EQUIPMENT) .......................14
7.5 LANCER PURE LINK DELIVERY PUMP, PN 86-0132 (OPTIONAL EQUIPMENT) .......................14
TEST EQUIPMENT (AVAILABLE THROUGH LANCER CUSTOMER SERVICE).........................................15
LANCER PURE LINK WATER UNITS ............................................................................................................16
CERTIFICATE OF WARRANTY ......................................................................................................................17
ii
Pure Link
Return Water -
Optional Ice Maker
Vent
Assembly
1/4"
Tube
OD
To
Drain
Brine Water To Drain
Product Water To Carbonator,
Point Of Use, Or Delivery Pump
Carbonated
Water Out
Filtered Water To
Booster Pump Inlet
CAUTION
MUST have Carbon Pre-Filter
5 Micron Carbon Block NSF
Pure Link Installation With Delivery And Booster Pump
Tee Must Be Left
Open at Top
Filtered Water to Inlet
for Units Without
Water Booster Pump
Siphon
Break
(See Detail Drawing)
1
1. INSTALLATION
1.1 RECEIVING
A. Each unit is completely tested and thoroughly inspected before shipment. At the time of
shipment, the carrier accepts the unit and any claim for damage(s) must be made with the carrier. Upon receiving units from the delivering carrier, carefully inspect carton for visible indication(s) of damage. If damage exists, have carrier note same on bill of lading and file a claim with the carrier.
1.2 UNPACKING
A. Remove the unit from carton. B. Remove inner carton pads and plastic bag. C. Remove Installation Kit of Loose parts. D. Inspect for concealed damage(s); if evident, notify delivering carrier and file claim against same.
Installation Diagram
Figure 1
Air Gap
Figure 1a
1.3 SELECTING INSTALLATION LOCATION (SEE FIGURE 1)
A. The Pure Link unit is designed to attach to a vertical wall that
must be capable of supporting a minimum weight of 61 pounds (27.7 kg). Select a location that is close to a drain, a municipal water supply, and an electrical outlet (if required). If the unit does not have a delivery pump, it should be mounted high enough on the wall to allow gravity feed to the point of use.
NOTE: Lancer recommends installation height seven (7) feet (top of unit) for gravity feed units. A minimum height of seven (7) feet is
required for use with the optional 38.5 Gallon Pure Storage unit. If the building does not have a pre-filter and a carbon filter on the incoming water supply to the unit, then allow enough space to mount a dedicated pre-filter and a carbon filter.
B. Mount unit to wall in desired location. Ensure that unit is properly
secured based on operating weight.
Drain
1/4" Brine Water from Pure Link
1" (Minimum)
Refer to Local Plumbing Code for Specific Requirement
2
1.4 FILTERING THE WATER SUPPLY
The Pure Link System is intended for use with potable water only. Excessive levels of chlorine, bacteria, iron, turbidity, and/or hardness may affect the RO membranes or other components and may require additional pre-filtration of the incoming water supply.
A. Water supplied to the Pure Link unit must first pass through a maximum 5 micron pre-filter and
then through a maximum 5 micron carbon block filter. The pre-filter removes suspended solids
and protects the carbon block filter from premature failure. The carbon block filter removes chlorine and some organic compounds from the incoming water supply which can damage the module.* The building must
have an adequate filtering system if a dedicated filter system is not
provided to the Pure Link unit. A Block Carbon pre-filter is required; otherwise, granular carbon
filters will release salt and carbon fines that will cause the booster pump to fail and not build pressure.
* Not performance tested or certified by NSF.
CAUTION
FAILURE TO PROPERLY MAINTAIN AND CHANGE FILTER CARTRIDGES IN A TIMELY MANNER WILL CAUSE THE PURE LINK UNIT TO REDUCE PRODUCTION AND/OR FAIL TO OPERATE.
B. In the event the building is not equipped with these filters, then a suitable pre-filter and a
carbon block filter must be installed and maintained at proper intervals. For selection of the
proper filtration system, refer to your Lancer Catalog or contact Lancer Customer Service.
Overflow Assembly
Installation
Figure 3
Siphon Break
Installation
Figure 2
1.7 CONNECTING UNIT TO POINT OF USE (POU)
NOTE:
For selection of the proper filtration system, refer to your Lancer Catalog or contact Lancer Customer Service.
The Pure Link unit has a connection on the bottom of the unit (marked “Product Water Out”) which is the gravity feed port. For gravity feed applications, connect 3/8” OD tubing to port and to the POU.
A. For Pressure Applications, connect 3/8” OD tubing to appropriate
Remote Delivery Pump.
B. Ensure that the Delivery pump is properly sized to meet the demand of
the Point(s) of Use (POU). Refer to Delivery Pump installation instructions for proper installation.
Connect to Drain
1.5 CONNECTING UNIT TO DRAIN
The module drain is located on the bottom left hand side of the unit, marked “DRAIN”. Install the siphon break (included in the Installation Kit) to the “Drain port” of the unit (see Figure 2). Using 1/4” OD tubing, connect the siphon break to the nearest suitable drain. Follow local plumbing codes for air gap requirements (see Figure 1a).
1.6 INSTALLING OVERFLOW
A. The only time any water will vent from the overflow is if there is a
failure of the shut off valve to operate correctly and the unit continues to produce water and overfills the storage bag causing the overflow valve to vent water.
B. Insert six (6) inch length of 1/4” tubing (supplied with the Install Kit) into
the overflow valve on top right of unit (at location marked”VENT”). Install the supplied 1/4”tee to tubing, as shown in Figure 3.
CAUTION
FAILURE TO PROPERLY INSTALL THE OVERFLOW ASSEMBLY OR PLUMB IT TO THE DRAIN COULD RESULT IN WATER DAMAGE.
C. Plumb the overflow valve to drain (see Figure 3). Make sure that the
top of the tee is open to prevent siphoning of water from the storage bag or backflow into the storage bag.
3
C. For High Volume Applications, connect to optional storage unit. D. When used with the optional 38.5 Gallon Pure Storage unit, the Delivery Pump must be installed
below the tank level to ensure proper operation..
1.8 CONNECTING UNIT TO WATER SUPPLY
A. The water inlet connection for units without
a water boost pump is on the top left hand side of
the unit. Connect to filtered water source using 3/8” OD tubing.
B. The water connection port, for units equipped with a water boost pump, is the inlet port on the
pump (see Figure 1). Connection can be accomplished using 3/8” OD tubing. As an alternative, the Installation Kit contains an adaptor with a 3/8” barbed fitting. This allows the use of 3/8” ID beverage tubing as the inlet water tube.
C. Use cold water supply ONLY.
CAUTION
THE UNIT COVER MUST BE PROPERLY INSTALLED ON UNIT DURING OPERATION WITH ALL FIVE (5) SCREWS IN PLACE. FAILURE TO PROPERLY SECURE COVER TO UNIT WILL RESULT IN FAILURE OF THE UNIT TO SHUT OFF AND/OR BOOST PUMP WILL OPERATE CONTINUOUSLY IN BY-PASS.
1.9 TURNING WATER ON
Turn water on to unit and check for leaks. Membrane will begin to produce water to fill storage bag. The time required to fill the bag is dependent upon the Pure Link model.Water production can be verified by observing flow rate to drain. If equipped with internal delivery pump, disconnect 3 pin pump connector from power supply. Follow Sanitizing Instructions in Section 1.12. Allow unit to fill with water, then reconnect delivery pump.
1.10 CONNECTING UNIT TO ELECTRIC POWER SUPPLY (IF EQUIPPED WITH POWER SUPPLY)
W
ARNING
THIS UNIT MUST BE PROPERLY ELECTRICALLY GROUNDED TO AVOID POSSIBLE FATAL ELECTRICAL SHOCK OR SERIOUS INJURY TO THE OPERATOR. THE POWER CORD IS PROVIDED WITH A THREE PRONG GROUNDED PLUG. IF A THREE HOLE GROUNDED ELECTRICAL OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD TO GROUND THE UNIT.
DO NOT USE EXTENSION CORDS WITH THIS UNIT. DO NOT “GANG” TOGETHER WITH OTHER ELECTRICAL DEVICES ON THE SAME OUTLET.
Plug unit power cord into transformer control box and into the proper electrical outlet. The water boost pump will begin to operate. Product water will begin to fill the product water storage bag. The boost pump will shut off when the storage bag is full.
1.11 Boost Pump Bypass Pressure Setting (if so equipped)
A. Install pressure gauge (0-160 psi) on outlet side of boost pump (PN 86-0112). Connect feed
water line from Pure Link unit to other side of gauge. B. Turn on water supply. C. Connect unit to electrical supply. D. With boost pump operating, insert 1/16" hex key into bypass adjustment screw on pump head.
Turn clockwise to increase bypass setting, or turn counterclockwise to decrease bypass setting.
Set to 110 psi. E. Disconnect electrical supply. F. Turn off water supply. G. Remove gauge and reconnect feed water line from Pure Link to boost pump outlet. H. Turn on water supply and connect unit to electrical supply. Check for pump operation and leaks.
NOTE:
Pressure Test Gauge is available through Lancer Customer Service.
Loading...
+ 14 hidden pages