Lanair DHI 300 User Manual

DHI-300 DUCTABLE
WASTE OIL HEATER
Installation andOperating Instructions
Listed MH 14518 (N)
Lanair Waste Oil Heaters & Boilers
4109 Capital Circle
Janesville,Wisconsin 53546
www.lanair.com
BEFORE YOU BEGIN INSTALLATION...
IMPORTANT
Read and understand this manual completely before beginning installation.
• This heater is for commercial and industrial use only. This unit is not intended for residential
use.
This heater must be installed and/or inspected by a licensed heating contractor
before operation. Installer should be trained and thoroughly familiar with the installation and operation of oil-fired heaters.
• Installation of this unit must be made in accordance with state and local codes or authori­ties having jurisdiction over environmental control, fuel, fire and electrical safety.
• N.F.P.A. (National Fire Protection Association Publications for Heater Installation)
NFPA No. 30 Flammable and Combustible Liquids Code NFPA No. 31 Standard for the Installation of Oil Burning Equipment NFPA No. 70 National Electric Code NFPA No. 80 A&B Repair Garages and Parking Structures NFPA No. 211 Standard for Chimneys, Fireplaces,Vents, and
Solid Fuel Burning Appliances The above standards are available from the National Fire Protection Assn., Battery March Park, Quincey, MA 02269
• Read and familiarize yourself with these instructions and associated photos, diagrams and illustrations before beginning installation or operation.These instructions should be fol­lowed closely,to achieve the best possible results.
If you have questions or concerns at any time during the installation, stop the installation and contact a Lanair Service Representative.
• Check to make sure you have all the required components needed for proper installation and operation.
• Check each component for visible damage. If you find a damaged component, contact a Lanair Service Representative for a replacement. Do
• This heater is designed to provide economically and environmentally friendly disposal of waste oil. Due to the nature of the fuel used, this heater should not be relied upon as the sole source of heat.
• Read and understand the warranty. Fill out the enclosed warranty card and return within 10 days of purchase.
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
not install broken or damaged parts.
2
DHI-300 DUCTABLE WASTE OIL HEATER
Installation and OperatingInstructions
TableofContents:
RulesForSafe Installation and Operation ................................... page 2
Sec. 1 General Specificationsand Hazards .......................................... page 4
Sec. 2 Heater Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10
Sec. 3 Chimney/Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Sec. 4 Draft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ........................................ page 15
Sec. 5 Fuel SupplyTank /Piping Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............page 15
Sec. 6 Fuel SupplyPump/Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .................page 17
Sec. 7 CompressedAirInstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Sec. 8 Electrical Connections/WiringDiagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...page 20
Sec. 9 Controls . . . . . . . . . . . . . . . . . . ....................................................... page 23
Sec.10 PrimingFuel Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
Sec.11 Burner Start-UpProcedure . . . . . . . . . . . . . . . . . ...................................page 27
Sec.12 FlameAdjustment ........................ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Sec.13 Maintenance Schedule/Service Adjustments . . . . . . . . . . . . . .................page 32
Sec.14 Troubleshooting. . . . . . . . . ....................................................... page 44
Sec.15 Warranty Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
Sec.16 Burner ReferenceDiagram .................. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51
Visit our website at: www.lanair.com
3
Section 1 - General Specifications & Hazards
7
2
1
3
4
5
6
8
9
11
DHI Series Burner NOTE:This burner intended for use with DHI 300 Lanair Waste Oil-Fired Heater Only
No. Description
1 Mounting Plate 2 Ignitor Transformer 3 Fuel Line Inlet 4 Fuel Pressure Gauge 5 Combustion Air Baffle 6 View Port 7 Oil Primary Safety Control 8 Waste Oil/Fuel Oil Switch
9 Quick Disconnect Receptacle 10 Air Supply Inlet 11 Combustion Blower Motor
Burner Assembly­Performance Ratings
Voltage . . . . . . . . . . . . . . . . . . . . . . 115 vac
Cycles . . . . . . . . . . . . . . . . . . . . . . . . . . 60 hz
Total Operating Amperage . . . . . . . . 5.8
Weight . . . . . . . . . . . . . . . . . . . . . . . . .31 lbs
Oil Primary . . . . . . . . . . . . . . . . . . 0.2 amps
Pre-Heater Block . . . . . . . . . . . . .2.6 amps
Ignitor Transformer . . . . . . . . . . 0.3 amps
10
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
4
Section 1 - General Specifications & Hazards
9
2
2
2
1
3
6
4
5
No. Description
1 8" Chimney Exhaust 2 Mounting Holes 3 Fan Hi-Limit Switch 4 Flame View Port 5 Burner Assembly 6 Electrical Power Box 7 Electrical Panel Access 8 Clean-Out Port Access Panel
9 Blower Assembly
Visit our website at: www.lanair.com
8
7
5
Section 1 - General Specifications & Hazards
DHI-300 FRONT
DIMENSIONS:
DHI-300 Height: 61” Width: 43” Depth: 47” Weight: 370 LBS
FIRING CAPACITIES:
DHI-300 Nozzle @ 1.86 gallons/hour,No.2 fuel oil
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
6
8" exhaust
View port
Section 1 - General Specifications & Hazards
lower Moter
B
Assembly
ower Box
P
lectrical Access
E Panel
Fan Hi-Limit switch
Clean Out
Access Panel
LEFT SIDE
REAR
FRONT
Burner Assembly
RIGHT SIDE
Visit our website at: www.lanair.com
7
7
6
OPTIONAL J-PUMP
5
8
4
7
Section 1 - General Specifications & Hazards
2
8
3
9
6
No. Description
1 Pump Platform 2 Pump Motor 3 Pump Guard 4 Pump 5 Pressure Gauge port 6 Easy Flow Bleed Valve 7 1/4" NPT Inlet (1/2" J Pump) 8 1/8" NPT Outlet (1/4" J Pump) 9 Pump coupler
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
Pump Assembly­Performance Ratings
Voltage . . . . . . . . . . . . . . . . . . . . . . 115 vac
Cycles . . . . . . . . . . . . . . . . . . . . . . . . . . 60 hz
Weight . . . . . . . . . . . . . . . . . . . . . . . . . 24 lbs
Pump Motor . . . . . . . . . . . . . . . . . . 5 amps
1
8
Section 1 - General Specifications & Hazards
DIMENSIONS:
Height: 61” Width: 43” Depth: 47” Weight: 370 LBS
FIRING CAPACITIES:
DHI-300 Nozzle @ 1.86 gallons/hour,No.2 fuel oil
MINIMUM CLEARANCE TO COMBUSTIBLES:
Top . . . . . . . . . . . . . . . . . . . . . . . . 6” Chimney Connector . . . . .18”
Sides . . . . . . . . . . . . . . . . . . . . . .18” Rear . . . . . . . . . . . . . . . . . . . . . 6”
Front . . . . . . . . . . . . . . . . . . . . . .24” Bottom . . . . . . . . . . . . . . . . .18”
THIS HEATER IS DESIGNED TO BURN THE FOLLOWING APPROVED FUELS:
Used 5W through 50W Crankcase Oils Used Automatic Transmission Fluid No. 1 and No. 2 Fuel Oils
• The Lanair Heater provides the owner with a dependable, versatile and simple means of burning No. 1 and No. 2 fuel oils, 5W through 50W used crankcase oils, and used auto­matic transmission fluids. Maintained correctly, the heater will give you years of service. Please carefully read this owner’s manual. If in any case you have a problem with your heater,or its installation, you should contact the Lanair Customer Service Department at 1-800-753-1601.
• Do not attempt to start the burner when excess oil, oil vapor, or fumes have accumulat­ed! Never press the red button on the oil primary control more than twice! This could cause excess vapor, or fuel to ignite causing damage to the heater and/or chimney.
• Do not store or use gasoline, or any other flammable liquid and/or vapors near this heater.
• This heater is not designed for use in hazardous atmospheres such as: Paint Shops, Feed Mills, installations where explosive or flammable conditions are present or could occur.
WARNING! Lanair heaters rely on natural draft. Down drafts (positive pressures)
in the heaters chimney will occur in buildings where negative pressures are created by exhaust fans, (car exhaust, paint booths, etc). Do not try to use a power vent to
!
overcome a down draft (positive pressure). An adequate make-up air system is required when exhaust fans are used (consult your heating contractor).
Visit our website at: www.lanair.com
9
Section 2 - Heater Installation
TYPICAL INSTALLATION:
HEATER/CHIMNEY PACKAGE
Through the wall installation
Figure 1
1. Chimney Cap
2. Chimney Pipe
3. Clean-out Tee
4. Wall Thimble
5. Barometric Damper
6. Black Pipe
7. Burner
8. Blower Assembly
9. Secondary Air Regulator
10. Primary Air Regulator
11. Duct Connectors
12. Fuel Line
13. By-pass Regulator
14. Oil Strainer
15. Pump Assembly
16. Oil Storage Tank
17. Thermostat
18. Power Supply
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
10
Section 2 - Heater Installation
General Requirements
1. Do not install the heater on a combustible surface of any kind. For minimum clearance to
combustible material (see Page 9)
2. Install the heater in a location to utilize total heat throw.
3. Install the heater in a location to permit a correct outdoor chimney exit to eliminate
down drafts, and provide easy chimney installation and maintenance. Class A chimney MUST be used when passing through any wall or ceiling. See Section 3 Chimney Installation
4. Install the heater in a location to permit the fuel supply to be as close as possible.
5. Do not install the heater more than 10 feet above the top of the fuel supply tank.
6. Before suspending the heater check the supporting structure and reinforce if necessary
to support the weight of the heater/system.
7. Use 3/8” steel threaded rod to suspend the heater from a capable load carrying ceiling
structure when not using the Lanair Waste Oil Storage Tank.
8. The heater must be suspended level for proper operation. A heater that is not level could
cause a hazardous situation in which personal injury or property damage may result.
CAUTION: DUCT WORK RUNS MUST BE DESIGNED AND INSTALLED BY A LISCENSED HEATING CONTRACTOR
!
Visit our website at: www.lanair.com
11
Section 3 - Chimney/Vent System
Figure 2 - Typical Chimney Installation
NOTE: Class "A" compo­nents require a 2" clear­ance from combustible materials. All other chimney components require a minimum 18" clearance from com­bustible materials
General Requirements
1. Safe operation of any gravity vented heating appliance requires a proper air make-up
system to prevent the heater exhaust gases from being drawn into the building.These gases could cause death, serious injury, and/or property damage.Exhaust fans, paint booths may cause draft problems.
2. Never vent this heater into another heating appliances chimney. Never vent into ‘Class B”
chimney.Gas heaters use “Class B” chimney, it is rated for a much lower temperature than is required for your waste oil furnace.This heater must have its own separate “Class A” chimney.
3. Inspect and maintain the chimney on an annual basis.
FAILURE TO PROVIDE PROPER VENTING OF THE HEATER EXHAUST GASES COULD RESULT IN DEATH, SERIOUS INJURY, AND/OR PROPERTY
!
DAMAGE. FOLLOW CHIMNEY MANUFACTURERS INSTRUCTIONS.
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
12
Section 3 - Chimney/Vent System
DO NOT INSTALL CHIMNEY IN FRONT OF THE HEATER (in air stream of fan)
!
Barometric Damper Position
ORIZONTAL
H
General Requirements (cont.)
4. Install a U.L. listed barometric damper in the chim-
ney. Do not reduce or enlarge the vent pipe.
5. Each 90° elbow equals a 10’ run of chimney.The
maximum run for the chimney connector is 30’ (See illustrations on pp. 12 & 14).
6. To prevent the drawing of exhaust gases into the
building, keep the barometric draft control at least 24” from the heater,exhaust fan etc..
7. Position the draft control as shown. Barometric
Damper gate pins must be horizontal (Level or parallel to the floor) for proper operation.
8. Secure all connections in the chimney connector with 3 screws per joint.
9. The chimney connector clearance to any combustible material is 18”. The “Class A”
chimney clearance to any combustible is 2”. Follow the chimney manufacturer’s instruc­tions.
10. Do not install heat re-claimers, manual draft controls, or any other type of restrictive
control in the chimney.
11. Install clean out tee with a cap, at the transition of the chimney. FOLLOW CHIMNEY
MANUFACTURERS INSTRUCTIONS.
NOTE: Barometric Damper may
be mounted horizontally or vertically. Angle gate pins must be horizontal (level or parallel to floor) for proper operation.
VERTICAL
12. Use “Class A” insulated chimney pipe to vent exhaust gases through wall, ceilings, attics,
roofs, combustibles, etc. Class A chimney must be used for the entire run once passing through a wall of ceiling.
13. Vent chimney at least 3 feet above the roof and at least 3 feet higher than any portion
of the building, roof, or obstruction within 10 feet of the chimney.
14. The chimney cap should be at least 3’ above the chimney exit through the roof.
15. Do not use a rotating chimney cap. Use a non-restrictive “Class A”cap made for the type
“Class A”chimney you are using. Follow chimney manufacturer’s instruction.
16. The chimney must be capable of producing a negative -.02 W.C. draft when cold and -
.06 W.C. draft when hot. Refer to Section 5 Draft Instructions.Refer to Section 3.10 for typical Chimney Installation.
Visit our website at: www.lanair.com
13
Section 3 - Chimney/Vent System
17. If you are unable to attain the proper draft,check for exhaust fans in the building.To test
if there is a problem, open an overhead door and see if you now have the proper draft. You may have to add one or more sections of “Class A” chimney to the roof to get the proper draft.
18. The heater and chimney must be installed in accordance with all state and local codes.The heater must be installed in accordance with the specifications listed in this manual.The chimney must be installed per the chimney manufacturer’s instruction. Use “Class A”chimney only.
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
14
Section 4 - Draft
The Lanair heater should have a (negative) -.02 draft reading when cold, and a (negative) -.06 when hot. Check the heater when it is running after 45 minutes. If the reading is not what it should be, adjust the barometric damper according to the instructions provided with the damper.The draft reading should be taken with a manometer. Consult your heating contrac­tor, or a manometer can be purchased from the Lanair Customer Service Department .
Section 5 - Fuel Supply Tank Installation
Figure 3
NOTE: For illustrative purpose only.Individual tank installations will vary.
Visit our website at: www.lanair.com
15
Section 5 - Fuel Supply Tank Installation
If using a Lanair supply tank follow instructions included with the tank.
!
General Requirements
1. The fuel supply tank and supply lines must be installed in accordance with the National
Fire Protection Association requirements, as well as State and Local ordinances.
2. Regulations require oil storage tanks located inside not too exceed 275 gallons individu-
ally, and are not to exceed a total capacity of 550 gallons in one building. Check State and Local codes.
3. Locate the fuel supply tank inside the building as close to the heater as possible. It
should be no further than 25 feet from the heater to avoid oil flow problems.
4. The fuel supply tank must be mounted below the level of the burner and the by-pass
regulator.Mounting the fuel supply tank above the burner will create head pressure and over-fire the burner voiding the warranty.
5. Pitch the fuel supply 2º with the drain valve at the lowest end to drain off water and
sludge. Sludge may have to manually be removed.
6. Some ordinances may require the fuel supply tank to be vented to outside, and above
the roofline. Check State and Local codes. Keep the vent clear.
7. Install the fuel tank fill pipe at the end of the tank and above the drain.
8. Label the fuel tank for the recommended fuels.
9. Strain all fuel with a 50 X 50 mesh strainer before putting fuel into the tank.
10. When filling the fuel tank with a motorized pump, never leave unattended to prevent
over filling and/or spillage.
11. Keep cap on the fuel tank when not filling.
For optimum performance, the waste oil pump manufacturer recom­mends that multi-weight oils such as 5W-30W be maintained at 32˚ F
!
minimum and straight weight oils such as 40W and 50W be maintained at 50˚ F minimum.
QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST
16
Loading...
+ 36 hidden pages