Lambda UF1500 Series Installation Manual

INSTALLATION MANUAL
ULTRAFLEX
POWER SUPPLY
UF1500 Series
3055 Del Sol Blvd.
San Diego, CA 92154
Phone: (619) 575-4400
Fax: (619) 429-1011
TABLE OF CONTENTS
INTRODUCTION 4
CERTIFICATION 4
WARRANTY 4
APPLICABILITY 4
INSTALLATION MANUAL 4
SAFETY AGENCY APPROVALS 4
GENERAL SAFETY INSTRUCTIONS 5
INPUT FUSE 6
RECEIPT AND UNPACKING 6
MOUNTING REQUIREMENTS AND COOLING 7
INPUT POWER CONNECTIONS 7
AC INPUT AND OUTPUT POWER RATINGS 7
EMI 8
INPUT TRANSIENT/ESD PROTECTION 8
REMOTE SENSE 8
OUTPUT VOLTAGE ADJUSTMENT (TRIMMING) 9
CURRENT LIMIT PROTECTION 9
OVERVOLTAGE PROTECTION (OVP) 9
OUTPUT LOAD REGULATION 9
OUTPUT LINE REGULATION 9
HOLD UP TIME AFTER POWER LOSS 9
REV C Page 2 of 17
TURN-OFF/TURN-ON 9
TURN ON TIME 9
NOISE AND RIPPLE 9
DYNAMIC LOAD TRANSIENT RESPONSE 10
DYNAMIC CROSS REGULATION 10
TEMPERATURE COEFFICIENT 10
NO LOAD OPERATION 10
OVER TEMPERATURE SHUTDOWN 10
OPERATING ENVIRONMENT 10
SIZE AND WEIGHT 10
COOLING 11
SHOCK & VIBRATION 11
PACKAGE DROP 11
RELIABILITY PREDICTION 11
MATING SIGNAL & CONTROL CONNECTOR INFORMATION 11
GLOBAL SIGNALS 11
OUTPUT MODULE SIGNALS & FEATURES 12
MODULE RATING WITH MODEL NUMBERS: UE Z 1 - X X X X X X 14
NOTE: ENERGY HAZARDS 15
THERMAL DERATING GUIDELINE 15
MAXIMUM POWER VS. AC LINE 15
LABEL / CONNECTION DIAGRAM 17
REV C Page 3 of 17
LAMBDA
Power Supply
Installation Manual
INTRODUCTION
The “UltraFlex” is a product family of fan-cooled, multi-output, power factor corrected switch mode power supplies. The flexible design offers a high quality, cost-effective solution for the high volume OEM market.
CERTIFICATION
Lambda certifies that this product meets published specifications at the time of shipment from the factory.
WARRANTY
This power supply is warranted against defects in material and workmanship for a period of three years from date of shipment. During this period Lambda will either repair or replace this product at the discretion of Lambda . No other warranty is implied or given.
APPLICABILITY
This manual applies to the UltraFlex UF1500 Series power supply. Manual part no. IMUE1500.
PART NUMBER CONFIGURATION
UEZ1-_______
UltraFlex Case Code
Global Signals Output Module Codes [SEE PAGE 14]
EN55022 Level B, FCC20780 Class A Cond. EMI
INSTALLATION MANUAL
This manual contains important information regarding the proper installation and operation of the power supply mounted inside the host equipment.
SAFETY AGENCY APPROVALS
The UltraFlex power supply series complies with the following regulatory specifications: UL1950, IEC950, CSA 22.2 No.950, EN60950. This product is certified and allowed to carry UL combined Canada/U.S. Recognized Component Mark, DEMKO. CE Marked in accordance with the Low Voltage directive (73,23/EEC) as amended by the CE Marking directive (93/68/EEC). NOTE: CE Mark does not include compliance to either EMC or medical device directives.
PLEASE READ THE SAFETY AND INSTALLATION INSTRUCTIONS BEFORE INSTALLATION OR USE OF THIS PRODUCT.
REV C Page 4 of 17
SAFETY SYMBOL:
This symbol indicates dangerous voltages present within the power supply. Isolation transformers should be used between the AC mains and the power supply if work is to be carried out with the safety covers removed.
GENERAL SAFETY INSTRUCTIONS
The UltraFlex power supply series is designed for use within other equipment or enclosures. Access is restricted to authorized personnel only.
For safe installation and operation of this product, carefully follow the instructions below:
A. Do not install, operate or test this product near water, and do not spill any liquid on it.
B. Do not touch the product when the input supply is connected.
C. Do not operate this product unless it is in a secure position.
D. When cleaning the product, make sure the input supply is disconnected and use only a
damp cloth.
E. Never push objects of any kind into the product through slots in its case, as this could
result in electric shock or a fire hazard.
F. Slots in the product case are designed for ventilation and must not be obstructed when
the product is installed and/or operated.
G. Make sure the unit is supplied only by a power source of the type indicated on its label.
H. When securing the product, do not use screws that infringe the maximum penetration
depth specified on the mechanical drawing within this handbook.
I. The unit covers are designed only to protect skilled personnel from hazards. They must
not be used as part of the external covers of any equipment where they may be accessible to operators, since, under full load conditions, parts of the unit chassis may reach temperatures in excess of those considered safe for operator access.
J. All servicing, repair and testing of this product must be carried out by competent
personnel who are familiar with the hazards of AC/DC line operated equipment and with the particular dangers associated with switched mode power supplies.
K. AFTER DISCONNECTING THE AC SOURCE, ALLOW 5 MINUTES BEFORE
TOUCHING THE UNIT TO ALLOW CAPACITORS WITHIN THE UNIT TO DISCHARGE.
L. The low-voltage output from the power supply unit shall not be user-accessible as
defined in EN 60950.
REV C Page 5 of 17
M. A protective earth must be provided for safety in accordance with EN60950.
WARNING: It is essential that the earth grounding terminal of this product be securely connected to earth (hard-wired) by the end user.
N. PREVENTION OF ACCESS BY THE USER: This apparatus is intended to be
accessible to authorized personnel only. Ensure that user access to this product, when installed in a host equipment, complies with EN60950. Failure to do this will invalidate the approval given to this apparatus.
O. WARNING: All outputs used are SELV as defined in EN60950 Clause 2.3. As such, all
outputs must only be connected to circuits compliant with the requirements of SELV complying EN60950 Clause 2.3. circuits. Other usage will invalidate any approval given to this apparatus.
P. EARTH TERMINAL MARKING:
IMPORTANT: If in the end use equipment the incoming mains cable earth wire connects directly to the "GND" connection on the UltraFlex unit without being interrupted or junctioned on its way to that connection, then this connection is the main protective earth of the system. To comply with EN60950, UL1950, and CSA-22.2-950
requirements, this terminal must be marked with as defined in IEC417 No. 5019a. The customer should therefore affix an adhesive label which will pass the 15 second rub test (IEC950 section 1.7.15) showing the above symbol adjacent to the earth connection. This symbol must only be used at the first interruption/connection of the incoming earth wire.
INPUT FUSE
The AC power source line is protected by an internal ceramic body fuse contained within the power supply enclosure located in the neutral side. Only qualified service personnel should replace the internal fuse (no user access).
Notes:
1. Replace the input fuse in the unit with same type and rating. Fusing requirements are shown in Table #1. Caution: Primary fuse is located in the neutral side.
2. Additional customer supplied fuse is required in the “Line side”, same as in Table #1.
3. Internal fuses (no user access) F506, F601, rated 4A/250v Very Fast-Acting Type.
TABLE #1
MODEL OUTPUT
FUSE VALUE NOTES
POWER
UF1500 1500W 25A/600V Bussmann fast
acting KTK-25 or equivalent
RECEIPT AND UNPACKING
On receipt, the unit should be unpacked carefully and checked for transit damage. If the unit is damaged, do not apply power or install the unit--seek specialist advice. Read the rating label located on the power supply to verify that the unit has the correct input and output ratings and