LAKOS CSX Separator User Manual

Maintenance / Purging Installation Instructions
LAKOS
1365 N. Clovis Ave
Fresno Ca, 93727
559-255-1601
WWW.Lakos.com
1. Lakos CSX Separator must be
purged continuously to remove separated solids from the collection chamber.
2. The CSX has a recommended
purge flow of 3% - 5% of inlet flow.
3. Purge piping is to be sized in a
manner that the velocities are able to keep purge line clear of fines. Length should also be a part of this calculation.
4. Purge lines should not be sized
smaller than 3/4". Purge lines should also run at shortest length possible. Extended runs of pipe can cause clogging if not sized properly. Purge should
not run uphill unless factory consulted.
5. Manual isolation valve should
be placed at the end of the purge line. Isolation valve may be used to control flow when applicable to the situation. Manually controlled flow should be opened completely once a week for flushing of valve and line.
6. Manual bypass should be placed
on the separator in the case of purge blockages. Blockages may occur due to improper piping or unforeseen process issues.
1. Lakos CSX Separators are shipped on skids or in wooden creates. Support eyes are provided
for hanging separator.
2. A suitable support is required to accommodate the Lakos Separator's weight with liquid. If a
suitable support from building structure is not available, other means of support must be obtained. CSX separators are designed to hang from lifting lugs or by clamp (Separator should not be hung via piping). If this is not possible, consult factory before purchase.
3. Prior to installation, inspect the inlet & outlet for foreign material that may have entered in
shipment or storage.
4. Inlet and outlet pipe connections to the Lakos Separator should have a straight run of at least
five times the pipe diameter. This is to minimize turbulence that may occur within the separator and enhance performance. Properly sized spools can be purchased.
5. Proper piping for purging is critical to the operation of the separator. Proper purging also
improves the performance of your Lakos separator. See Maintenance / Purging (at left) for details on purge piping.
6. Lakos Separators are designed to operate within a prescribed flow range. Pipe size is not a
factor in model selection. Properly sized hardware is required for inlet, outlet, & purge of separator.
7. Lakos Separators are to be installed on the discharge side of a pump. Lakos Separators will
not separate properly if plumbed to the intake of a pump.
8. Inlet pressure to the Lakos Separator must be at least equal to or greater than the anticipated
pressure loss through the separator plus 15 psi, plus whatever downstream pressure is required. A pressure chart is available with these instructions.
9. Pressure gauges should also be placed on the inlet and outlet of the separator to monitor
pressure loss and separator performance.
10. After proper installation of the separator, sanitation is to be performed. Sanitation is not to be
less than normal sanitation procedures for the facility or system installed.
7. Blockages should be cleaned
only after a safe temperature is obtained. Separator should be bypassed immediately when a blockage occurs to minimize the extent of the blockage.
Improper installation does not constitute a failure on the part of LAKOS. Separator performance can be altered due to improper installation. Performance is not warranted under manufacture defects.
LS-672
Loading...