Lab.gruppen C C 16 4, C C 28 4, C C 48 4, C C 68 4, C 68:4 Operation Manual

...
Rev. 2.0.3
Operation Manual
C Series:
Dedicated Installation Amplifiers
C 68:4
C 48:4
C 28:4
C 16:4
Item no. OM-CS
2 C Series C 68:4 , C 48:4, C 28 :4 and C 16:4 Operation Manual
1 CONTENTS .................................................................................................................................................2
2
APPROVALS ................................................................................................................................................4
3 WARNINGS .................................................................................................................................................4
3.1 Explanation of graphical symbols ........................................................................................................4
3.1.1 WARNING ................................................................................................................................4
3.1. 2 CAUTION ..................................................................................................................................4
3.2 Important Safety Instructions ..............................................................................................................4
3.3 User responsibility ...............................................................................................................................5
3.3.1 Mains connection grounding ....................................................................................................5
3.3.2 Speaker output hazard ..............................................................................................................5
3.3.3 Radio interference ....................................................................................................................5
3.3.4 Speaker damage .......................................................................................................................5
3.3.5 Maintenance .............................................................................................................................5
4
WELCOME ...................................................................................................................................................6
4.1 Introduction ..........................................................................................................................................6
4.2 Main Features ......................................................................................................................................6
4.2.1 Class TD amplifier and regulated switch-mode p ower supply ................................................. 6
4.2.2 Amplifier gain ...........................................................................................................................6
4.2.3 Voltage Peak Limiter (VPL) .......................................................................................................7
4.2.4 Protection and performance optimization .................................................................................7
4.2.5 NomadLink / Ethernet control and monitoring network ...........................................................7
5 INSTALLATION ...........................................................................................................................................8
5.1 Unpacking ............................................................................................................................................8
5.2 Mounting .............................................................................................................................................8
5.3 Cooling .................................................................................................................................................8
5.4 Operating voltage ................................................................................................................................8
5.5 Grounding ............................................................................................................................................9
6 QUICK GUIDE OVERVIEW .......................................................................................................................10
6.1 Front-Panel overview .........................................................................................................................10
6.1.1 Power on/off and remote switch ............................................................................................10
6.1.2 Front Panel LED’s ...................................................................................................................10
6.2 Rear-Panel overview ..........................................................................................................................11
6.2.1 The DIP-switch features .........................................................................................................11
6.3 NomadLink / Ethernet network setup ................................................................................................12
7 OPERATION AND PERFORM ANCE ........................................................................................................14
7.1 Introduction ........................................................................................................................................14
7.2 Operation precautions .......................................................................................................................14
7.3 Signal flow and headroom .................................................................................................................14
7.3.1 Signal flow blocks ...................................................................................................................14
7.3.2 Headroom, sensitivity and VPL / Gain settings ......................................................................15
7.4 Audio Input and Output connections, setup and features .................................................................16
7.4.1 Balanced / Unbalanced Input connection ...............................................................................16
7.4.2 Output operation and connection ...........................................................................................16
7.4.3 Output bridge mode ...............................................................................................................16
7.4.4 Amplifier Gain .........................................................................................................................17
7.4.4.1 Channel gain / Level (front-panel pots) .......................................................................... 17
7.4.4.2 Amplifier sensitivity ....................................................................................................... 17
7.4.5 Output Voltage Peak Limiter (VPL) .........................................................................................17
7.4.6 Constant Voltage 70 V and 100 V systems setup and operation ............................................ 18
7.4.7 Current Peak Limiter, (CPL) ....................................................................................................18
7.5 Protection, faults and warnings .........................................................................................................18
7.5.1 Int roduction ............................................................................................................................18
7.5.2 Safe Operating Area Detector (SOAD ) ...................................................................................18
7.5.3 Very High Frequency (VHF ) protection ...................................................................................18
7.5.4 DC protection .........................................................................................................................19
7.5.5 High-impedance war ning (open load) ....................................................................................19
7.5.6 Low-impedance protection (shor t circuit) ...............................................................................19
7.5.7 Temperature protection ..........................................................................................................20
7.5.8 Power Average Limiter (PAL) .................................................................................................20
7.5.9 Soft Start ................................................................................................................................20
7.6 Front-panel monitoring and adjustments ...........................................................................................21
7.6.1 Level indicators .......................................................................................................................21
7.6.2 Level adjust ............................................................................................................................21
7.6.3 Mute indication .......................................................................................................................21
7.6.4 Performance, Warning and Fault indicators ............................................................................22
7.7 NomadLink network and DeviceControl Software ............................................................................23
7.7.1 NomadLink network in the amplifiers ....................................................................................23
7.7. 2 Connection and setup .............................................................................................................23
7.7. 3 NomadLink network cable lengths .........................................................................................24
7.7. 4 Ethernet network cable lengths .............................................................................................25
7.7. 5 DeviceControl software .......................................................................................................... 25
8 APPENDIX .................................................................................................................................................26
8.1 M ai nte na nce ......................................................................................................................................26
8.2 FAQ ....................................................................................................................................................26
8.3 Additional documentation ..................................................................................................................27
8.4 Current Draw and Thermal Dissipation specifications .......................................................................28
9 TECHNICAL SPECIF ICATIONS ................................................................................................................30
10 WARRANTY ..............................................................................................................................................31
1 CONTENTs CONTENTs 1
4 C Series C 68:4 , C 48:4, C 28 :4 and C 16:4 Operation Manual
This equipment co nforms to the requirements of the EMC d irective 89/ 336/EE C, amended by 92/ 31/EEC and 93/ 68/ EEC and the requirements of the Low Vol tage Directive 73/ 23/EEC , amended by 93/ 68/EEC .
Standards appli ed: EMC Emission EN5 5103-1, E3 EMC Immunity EN 55103-2, E3, with S /N below 1% at normal ope ration level. Electrical Safet y EN6006 5, Class I
This equipment is tes ted and approved according to th e U.S. safety standard AN SI/ UL 600 65 and Canadian safety s tandard CSA C22.2 NO. 6 0065. ETL ma de the tests and they are a National ly Recognized Testing Labora tory (NRTL) .
3.1 Explanation of graphical symbols
The lightning symb ol within a triangle is intende d to alert the user to the presence of u n-insulated “dange rous voltage” within the amplifi er’s enclosure that may be of s ufficient magnitude to co nstitute a risk of electric shoc k to humans.
The exclamation po int within a triangle is intended to a lert the user to presence of impo rtant operating and ser vice instructions in the li terature accompanying th e product.
3.1.1 WARNING 3.1.2 CAUTION
3.2 Impor tant Safety Instructions
Before using your ampli fier, be sure to carefully read the appli cable items of these operatin g instructions and the safet y suggestions
Ke ep this manual for future reference. 1. H eed all warnings. 2. F ollow all instructions. 3. D o not use this unit near water. 4. D o not spill water or other liquids into o r on the unit. Do not operate the amp lifier while wet or standing in li quid. 5. C lean only with dry cloth.6. D o not block the air intake or exhaust p orts. Install the unit in ac cordance with the instruc tions. 7. D o not operate the amplifier near heat pro ducing devices such as radi ators, heat regi sters, stoves or other apparatus that produce heat. Always 8.
operate the unit with the chassis grou nd wire connected to the electrical safety ea rth. Do not defeat the safety purpose of a grounding -type plug. A grounding typ e plug has two pins and a third groundi ng prong. The third prong is provid ed for your safety. If the provided plug d oes not fit into your outlet, consult an el ectrician for replaceme nt of the obsolete outlet.
C onnect only to AC power outlets r ated 100-120 V or 200 -240 V, 50-6 0 Hz.9.
Do not use this amplifier if the power cord is broken or frayed. Protect the power cord from being walked upon or pinched particularly at the plugs 10. and the point where it exi ts from the apparatus. Only use accesso ries specified by the manufa cturer. 11. The unit is intended to use in a 19” rack. Follow the mounting instructions. When a rack on wheels is used, use caution when moving the loaded 12. rack to avoid injury fr om tipping over. Unplug this appar atus during lightning storms or w hen unused for long periods of t ime. 13. Do not connect an amplifier output in parallel or series with any other amplifier’s output. Do not connect the amplifier output to any other voltage 14. source, such as bat tery, mains source, or power suppl y, regardless of whether the ampli fier is turned on or off. Do not run the output of a ny amplifier back into another ch annel’s input.15. Refer all servicin g to qualified service pe rsonnel. Servicing is re quired when the apparatus ha s been damaged in any way such as :16.
Power-supply co rd or plug is damaged. • Liquid has been sp illed into the unit• An object has fall en into the unit• The unit has been exp osed to rain or moisture• The unit does not op erate normally• The unit was droppe d or the enclosure is damaged•
17. Do not remove top or bottom covers . Removal of the covers will expose h azardous voltages. The re are no user serviceable p arts inside and removal may void the warranty.
18. An experienced user shal l always supervise this profe ssional audio equipment, e specially if inexperienc ed adults or minors are using th equipment.
19. The mains plug is used as the dis connect device and shall rem ain readily operable. If the a mplifier mains plug is not read ily accessible due to mounting in a 19” rack, then the mains plu g for the entire rack must be readily o perable.
20. The US National Differe ncescl.16.3 requires that Noma dLinknetwork cables mu st be flame rated VW-1.
2 A PPROVAL s WARNINGs 3
3.3 User responsibility
3.3.1 Mains co nnection groundi ng
Your amplifier must be connected to a grounded socket outlet.
3.3.2 Speaker o utput hazard
Power amplifi ers are capable of producing
hazardous output voltages. To avoid electrical shock, do not touch any exposed speaker wiring while the amplifier is operating. The external wiring connected to the speaker terminals shall be installed by a trained and qualifi ed person, or ready-made leads or cords of appropriate c apacity shall be used.
3.3.3 Radio in terference
As the amplifier outputs produce high voltage,do
not connect or disconnect speaker cables when the mains power is on. Also, attach the safety cover on the speaker terminals for safe operation and to comply with electrical product approvals.
A sample of this product has b een tested and complies with the limits for the European Electro Magnetic Compatibility ( EMC) directive. This equipment has also been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference from electrical equipment. This product uses radio frequency energy and if not used or installed in accordance with these operating instructions, may cause interference to other equipment, such as radio receivers. However, there is no guarantee that inter­ference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be deter­mined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the antenna.• Increase the separation between the equip-
•
ment and receiver. Connect the equipment into an outlet on a • circuit different from that to which the receiver is connected .
Check if the affected unit complies with the • EMC limits for immunity, (CE -labeled). If not, address the p roblem with the m anufacturer or supplier. All electrical products sold in the EC must be approved for immunity against electromag­netic fields, high voltage flashes, and radio inter­ference. Consult the dealer or an experienced radio/• TV technician for help.
3.3.4 Speaker d amage
Your amplifier is very power ful and can be
potentially dangerous to both loudspeakers and humans alike. Many loudspeakers can be easily damaged or destroyed by overpowering, especially with the high power available from a bridg ed amplifier. Always check the speaker’s continuous and peak power capabilities. Even if though the amplifier’s front-panel attenuators can be used to reduce the gain, it is still possible to reach full output power if the input signal level is high enough.
3.3.5 Mainte nance
Fo r saf e an d rel iab le o pera tio n, t he du st c over s be hin d the front panel as well as the inside of the amplifier should be cleaned regularly. If the dust filters and inside are not maintained there will be safety risks. For example the amplifier can ignite the dust and a fire will occur due to high internal temperatures. There is also a risk that the amplifier will malfunction since the amplifier is dependent of constant airflow from front to rear. If the dust filters are not clean and the amplifier malfunctions, any resultant problems will not be covered by the warranty.
To reduce risk of fire or electr ic shock, do not expose this apparatus to rain or mo isture.
To reduce the risk of fire or elect ric shock, do not remove screws. No user-se rviceable parts i nside. Refer servicing to qualified ser vice personnel
3 WARNINGs
6 C Series C 68:4 , C 48:4, C 28 :4 and C 16:4 Operation Manual
4 WELCOME
4.1 Introduction
Thank you for choosing Lab.gruppen C Series power amplifiers for your sound reinforcement system installation. We are confident that you will be very pleased with the performance, configuration flexibility, reliability, and long-term durability offered by the C Series products.
This manual provides a comprehensive guide to the features and functionality of C Series model C 68:4, C 48 :4, C 28: 4 and C 16: 4 amplifiers. Please read through it in its entirely to bec ome fully acquainted with the many configuration options and multiple layers of protection circuitry.
To fa cil itat e ti mely ins tall ati on an d us e of t his C Ser ies product, we have included a Quick Guide Overview (section 6). This brief summary, in conjunction with Installation (section 5), contains the basic information needed to safely install the amplifier and place it in service. However, we highly recommend reading through this manual in its entirety, beginning with Main Features and Technologies and continuing through Operation and Performance. As you become thoroughly familiar with all aspects of operation, you may learn of features or options that will affect your choices on amplifier modes or loudspeaker system configuration.
Lab.gruppen C Series power amplifiers are designed and built specifically for the unique demands of permanent installation applications. C Series amplifiers offer the optimum combination of high­quality audio reproduction, flexible features, ease of installation, and 100% reliability in normal use.
By packing four or eight channels of reconfigurable power amplification into a 2U chassis, the C Series achieves unprecedented “power and channel den­sity.” The benefits of compact dimensions include reduced rack space requirements and minimal heat build-up. The flexible output stages enable each amplifier channel to be set for either low impedance or c ons tant vol tag e (7 0 V / 1 00 V ) mo de. Nom adLi nk, an easy-to-use network for monitoring and control, is implemented as a standard feature on all C Series amplifiers.
Although C Series features and facilities are tailored
to installation applications, at the heart of each amplifier is the same advanced technology that has made Lab.gruppen the benchmark of quality for touring concert systems: exceptional sonic performance, rugged construction, proven reliability, and protection features that anticipate every unwelcome possi­bility.
This manual is shipped with C Series ampli­fier models C 6 8:4, C 48: 4, C 28:4 and C 16:4. All references to “C Series” in this
manual apply to all four of these models. A different manual is shipped with models C 20:8X, C 10 :8 X, C 10: 4X a nd C 5: 4X. Refe renc es t o C Se rie s in this document may or may not apply to these C...X models.
4.2 Main Features
Thank you again for placing your confidence in Lab. gruppen power amplifiers.
Your new C Series amplifier incorporates a number of sophisticated technologies – many of them pro­prietary to Lab.gruppen – that are provided to ensure the best possible performance and many years of reliable operation. Familiarizing yourself with these technologies will prove invaluable in setting up and optimizing your loudspeaker system.
4.2.1 Class T D amplifier and regula ted switch-
mode power suppl y
Lab.gruppen’s patented Class TD technolog y com­bin es t he ex cept ion al ef fic ienc y of a Cla ss D amp lifie r with the high sonic quality associated with Class B designs. Class TD also incorporates the same basic concepts behind Class H designs, but here they are refined and pushed to a higher level to achieve much greater efficiency.
The Class TD output sections work in concert with Lab.gruppen’s unique, regulated switch-mode power supply (R.SMPS ) to create a superior overall power amplifier topolog y. This ensures st able, full output power over an extremely wide range of mains voltage levels. Sagging or fluctuating mains voltage will not affect the power output delivered to the loudspeak­ers.
4.2.2 Amplifi er gain
For greater flexibility in system integration, C Series amplifiers allow gain adjustment from +23 dB to +44 dB in 3 dB steps. This feature accommodates any combination of input device and loudsp eaker type. For example, if the input signal is weak, the gain can be boosted to maintain maximum power output while avoiding a poor signal-to-noise ratio. This gain adjust­ment feature makes it easier to achieve an optimal balance between headroom and noise floor.
4.2.3 Voltage Peak Limi ter (VPL)
The Voltage Peak Limiter (V PL) feature allows user adjustments that determine maximum voltage output, thus matching the amplifier to the connected speaker load. Whether the connected load is low impedance (2 to 16 ohms) or high impedance (70 V / 100 V), the VP L feature can be set to ensure that neither temperature nor current limitations are exceeded before reaching the desired voltage threshold.
4.2.4 Protec tion and performance optimizatio n
Appropriate and reliable power amplification is vital to any audio system. Inadequate or faulty power amplification could cause damage to the loudspeakers, or in some cases to the power amplifiers themselves. To prevent any damage or costly service interrup­tions, C Series amplifiers offer advanced features to protect both internal circuits and any connected loads. These features even protect the mains fuse that, in extreme cases, could be overloaded.
Following are short descriptions of standard built-in C Series protection features:
CPL•, (Current Peak Limiter) ensures that the
amplifier’s output does not exceed the safe current handling p arameters of amplifier components. Temperature pr otection• ensures that the amplifier will not be damaged by exceeding thermal limits.
PAL•, (Power Average Limiter) limits the
maximum average power consumption according to the power supply and mains-breaker capabili­ties.
VHF•, (Very High Frequency) protection
circuits mute the output of the amplifier when non-dynamic continuous signals above 10 kHz are detected.
DC protection• ensures destructive DC
signals will not appear at the amplifier outputs. If such conditions occur an internal fuse opens and fault indication is displayed.
Low impedance• ( short circuit) protection
provides a fault warning indication and shuts down the output stage when, for example, an input signal is present and a malfunctioning cable or driver is short circuiting the output. High impedance• warning repor ts an alert when, at the same time, output signal is high and no current draw is measured. This situation might occur when no speakers are connected, or when a driver is blown.
Low inrush current• ensures that the
mains breaker will not trip when several power amplifiers are turned on simultaneously.
4.2.5 NomadLi nk / Ethernet control a nd monitoring net work
The NomadLink network allows easy setup and control of C Series power amplifiers and other devices. The patented network topology allows automatic detection and addressing of multiple amplifiers, and is controlled from a PC via an NLB 60 E NomadLink Bridge & Network Controller using standard TCP/ IP communication. Phantom powering through the network cables allows the software to detect devices that are not currently turned on or connected to the mains. This ensures very high reliability and redun­dancy levels while allowing connected amplifiers to remain on standby with no power consumption.
Cable connections can be daisy- chained for easier system setup. This also reduces total component costs, simplifies installation, and makes daily opera­tion more convenient. There is no need to create a star topology using many switches as with, for example, an Ethernet system. Indiv idual amplifier addresses do not need to be manually entered: you will automatically know where an individual amplifier resides in the network.
A daisy chain network-loop, in combination with the automatic addressing of devices, enables Lab.gruppen’s proprietary DeviceControl software to aut oma tic ally cre ate a prec ise pic ture of al l co nne cted devices and their relative position in the chain. By quickly creating a clear overview of the entire system configuration, DeviceControl provides flexible control over very large amplifier systems. Set-up time is minimized, and critical information is readily available
WELCOME 4
8 C Series C 68:4 , C 48:4, C 28 :4 and C 16:4 Operation Manual
for monitoring performance and so lving problems during operation.
Via Noma dLink, you can monitor all metering d ata as well as all faults and warning indications simulta­neously. NomadLink also allows you to remotely control power on and power off, as well as engage Mute and Solo functions on individual channels.
5.1 Unpacking
Carefully open the shipping carton and check for any noticeable damage. Every Lab.gruppen amplifier is tested and inspected before leaving the factory and should arrive in perfect condition. If any damage is discovered, please notify the shipping company immediately. Only the consignee may institute a claim with the carrier for damage incurred during shipping. Save the carton and packing materials for the carrier ’s inspection. Should you ever need to ship the amplifier, always use the original packaging materials.
5.2 Mounting
The amplifier is two rack units high ( 2U) and will fit into a standard EIA 19” rack. The depth is 34 3 mm (13.5”). The weight is approximately 8, 5 kg (18.75 lbs.) depending on model type.
Free airflow from front-to-rear of the amplifier must be possible. Therefore, no doors or rack-lids should be mounted in front of or behind the amplifiers.
Amplifiers m ay be stacked directly on top of each other. There is no need for spacing in between units, though this might enable more convenient installation of cabling on the rear panel.
It is recommended that rear supports be mounted for maximum long-term stability.
5.3 Cooling
The amplifier uses a forced-air cooling system
with air flow from front-to -rear, maintaining a low operating temperature within defined limits. Front-to­rear airflow is preferred as cooler air is present at the front in nearly all installed applications. (This allows higher continuous power levels without encountering thermal problems. ) Never at tempt to reverse the airflow. The amplifier modules require a pressure chamber between the fans and heatsink, and this effect functions only in one direction. Ma ke su re th at t here is an ade qua te ai r su ppl y in f ront of the amplifier, and that the rear of the amplifier has sufficient space to allow the exhaust to escape. If the amplifier is rack-mounted, do not use covers or doors on the front or rear of the rack.
Should a heat sink overheat, the temperature sensing circuits will mute the overheating channel. If the power supply overheats, another sensing circuit will mute all output channels until the power sup ply coo ls to safe ope rati ng te mpe ratu re. A n ea rly warning before shut down will be indicated on the front-panel LEDs, and a warning will be sent through the NomadLink network.
Always make sure that the dust-filters behind the det ach abl e fro nt p anel are c lea n to e nsur e ma ximu m possible airflow.
If the amplifier malfunctions due to dirty dust-filters, any required repairs are not covered by the warranty.
To calculate the maximum heat emission value, when installing the amplifiers in rooms with an air-conditio­ning system, please refer to the Current Draw and Thermal Emissions specifications provided in the Appendix section.
5.4 Operating voltage
The lab el placed to the right of the mains
ca ble o n th e rea r of the a mpli fier ind icat es t he AC mains voltage for which the amplifier is wired and approved: 115 V or 230 V. Connect the p ower cable only to the AC source type referred to on the label. The warranty will not cover damage caused by connecting to an incorrect type of AC mains.
Lab.gruppen switch- mode amplifiers use primary switching. Bec ause the mains power is rectified
directly in front of the transformer, the amplifier is insensitive to mains frequency. It may be connected to 50 or 60 Hz sources, and actually will operate on line frequencies from DC to 400 Hz.
If the power plug mounted at the factory is not appropriate for your country, it can be removed and the proper connector wired in its place as follows:
BLACK or BROWN LIVE WHITE or BLUE NEUTRAL GREEN or GREEN/ YELLOW EARTH (GROUND)
If you are not 100% confident of your co mpe tenc e to rep lac e th e m ains plu g, eng age
qualified personnel to do the job.
Once a suitable AC supply is connected, the amplifier can be turned on using the front-panel power switch. The amplifier then goes through a soft-start sequence as it self-checks its circuits. The fans will blow at high speed before dropping to idle, and the “power” LED will illuminate.
Inrush power is controlled and limited during “soft start”, enabling multiple amplifiers to be powered up simultaneously.
5.5 Grounding
There is no ground lift switch or terminal on the C Series amplifiers. The signal ground is always floating, via a resistor, to chassis and therefore the grounding system is automatic.
In the interests of safety, never disconnect the earth (ground) pin on the AC power cord.
Use balanced input connections to avoid hum and interference.
5 INsTALL ATION INsTALL ATION 5
10 C Series C 68:4, C 4 8:4, C 28:4 and C 16:4 Operation M anual
6 QUICK GUIDE OVERVIEW QUICK GUIDE OVERVIEW 6
The amplifier’s front panel presents the performance and fault condition indicators, power and remote switches, and a removable dust-filter cover. Four level potentiometers located behind the cover provide individual at tenuation for the four amp lifier channels. Range is 0 dB to - infinit y. The 12 o’clock position indicates -10 dB attenuation. A label area is located beneath the LED display.
To remove the dust-filter cover, loosen the thumbscrew at the far left. This allows removal of the dust-filters for cleaning, and provides access to channel attenuation. The front cover may be made “tamper resistant” by replacing the thumbscrew with a Philips head or safety Torx screw. Thread size is M3.
Never operate the amplifier without the dust
-filters in place.
.
6.2.1 The DIP-s witch features
The following features may be adjusted using the DIP-switches on the rear-panel of the amplifier.
Gain - Set for all four channels from +23 dB to +44 dB in 3 dB steps.
Option acti ve - Available for future upgrades.
Fan Masked - When on, engages the intelligent fan
feature which lowers fan speed when no signal is present.
Bridged Mode - Switches the channel pairs (A+ B and/or C+D ) into bridged mode operation (automatic
-6 dB gain compensation) .
VPL - Voltage Peak Limiter adjustment is provided for 8 individual levels. Select the set ting most appropriate for connected speakers. See Appendix for details.
Mode - Select VPL mode to either Hard or Soft­operation. F or channels driving sub -woofers and low-frequency dr ivers, it is recommended to use the Hard setting for optimal operation. For mid- and high- frequency drivers, always select Soft.
Mains input 115 V
and 230 V operation
(Not selecta ble)
NomadLink
network In and Out
on EtherCon- housed
RJ45 connec tions
DIP-switches
for adjusting key
features
(See below)
3-pole Ph oenix-
type input
connectors
2-pole screw
terminal output
connections
6.2 Rear-Panel overview6.1 Front-Panel overview
Temperature mu te• (Yellow constant) VHF• (Very H igh Frequency) protection active
( output muted) (Yellow)
Mute• channel via NomadL ink network (2x Yellow) CPL• (Current Peak Limiter) active (O range flashing), CPL• constant ( output muted): Lo impedance / Short circuit
detec tion
Fault• (Yellow plus Orange ) VPL• (Volta ge Peak Limiter) active, VPL/ Clip (Red) 4 dB• signal level ( Green)
-10 dB• signal level (Green )
-40 dB• sig nal level (Green), Hi-Imp• open load detected ( Red)
Bridge mode• operation on (Yellow). Ch. A+ B or C+D
bridge d.
.
Power on (G reen) PAL (Power Average Limiter) active ( Red) Option acti ve (Yellow) Nomad Link network active (Blue).
PAL
When no VPL, CPL or PAL indicators are
illuminated, and the VPL DIP-switch is set to maximum at the specified nominal load, the amplifier channel is able to deliver maximum rated output power.
6.1.1 Power on/off and remote switc h
Th e Pow er o n/ off swi tch is lo ca ted o n th e ri ght s ide . A second switch, labeled “REMOTE,” is located above the Power switch. When the Remote switch is on, (with the mains connected and power switch turned on) the yel low L ED a bove it w ill i llum inat e in dica tin g tha t ex te r na l p ow er o n/ o ff c om ma n ds fr om th e No ma d Li nk network connection will switch the amplifier on or off. When Remote is activated the amplifier will not switch on until a “Power On” command is received from the network. When the remote switch is off, it is not possible to switch amplifier power on or off using NomadLink network control.
6.1.2 Front-panel LED’s
The front-panel LED area includes the following indicators per channel:
When the network is c on-
nected, the blue NomadLink
LED will illuminate even
when mains power is not connected. NomadLink receives phantom power from the net work supplied by the NLB 60E.
44dB 41dB 38dB 35dB 32dB 29dB 26dB 23dB
141V* 118V 100V** 85V
71V 59V 50V 42V
*100V
rms
**70V
rms
Ser. N:o
Removed!
SPEAKER OUTPUTS
BALANCED INPUTS
CH D
CH BCH C CH A
WIRING NORMAL: CLASS 2 BRIDGED: CLASS 3
PUSH PUSH
Must be grounded Made in Sweden
200-240VAC 50-60Hz :2300W
12 C Series C 68:4, C 4 8:4, C 28:4 and C 16:4 Operation M anual
6 QUICK GUIDE OVERVIEW
6.3 NomadLink / Ethernet network setup
Th e amp lifi er in clu des, as a stan dar d fea ture , int ern al facilities for the NomadL ink monitoring and control network. A ll features of the NomadLink network are accessible via a PC running Lab.gruppen’s pro ­prietary DeviceControl software. A single rackspace NLB 60E NomadLink Bridge & Network Controller, ac­ce pts t he TC P/ IP d ata stre am f rom t he c ompu ter and converts it to the NomadLink protocols. Even when no computer is connected, the NLB 60E can initiate stand-alone power on/off and muting functions, as well as report any fault or warning conditions.
The PC is connected to the NLB 60E using a standard Ethernet interface and a crossed Cat-5 cable (peer-to-peer setup). If a HUB or switch is in the network, standard “straight” Cat-5 cables must be used. T he front and rear Ethernet connections on the NLB 60E can be used individually, but only one PC at a time running DeviceControl can access the subnet.
Many newer laptop computers will allow peer-to-peer connection with the NLB 60E using a standard “straight” Cat-5 cable in­stead of a crossed cable.
The default fixed TCP/IP address of the NLB 60E is
192.168.1.166. The subnet mask is 255.255.255.0.
For further details, please refer to instructions sup ­plied with the NLB 60E unit.
The NomadLink connections use standard “straight” Cat-5/ RJ45 equipped cables. For a safer mechanical connection it is possible to use N eutrik EtherCon “XLR-type” housings on the cables.
US National Differences cl.16.3 requires that NomadL ink network c ables must be rated VW-1.
Th e OU T por t fr om t he NL B 6 0E m ust b e co nnec ted to the IN port of the first amplifier. T he OUT port from the first amplifier in turn connec ts to the next amplifier’s IN port to form a daisy chain The OUT port on the last amplifier is connected to the IN port on the NLB 60E to close the loop.
There are electrical limitations to cable lengths on a Nomad Link network, both in terms of total cable length in the loop and
between any two devices. Read the Operation and Performance chapter in this manual, or the instructions supplied with the NLB 60E, to ensure the network is configured within these constraints.
Although the network will function as an
open loop under most circumstances, it is
strongly recommended that the loop be
closed by connecting the l ast amplifier’s OUT p ort to the NLB 60E’s IN port. Doing so will improve redundancy and communication speed.
External contact closures and 24 V low/high triggers ca n be c onn ecte d to GPI c onn ecto rs o n the NLB 60 E for control of fire -alarm systems or external power sequencers. For more details read the instructions supplied with the NLB 60E.
IN OUT
NOMADLINK
IN OUT
NOMADLINK
NOMADLINK
IN OUT
ETHERNET
GENERAL PURPOSE INPUT, GPI
ETHERNET
"Crossed" RJ45 cable:
Between NLB 60E and PC.
"Straight" RJ45 cable: Between Ethernet switch or hub and NLB 60E.
"Straight" RJ45 cables: Between NLB 60E and amplifiers, and from amplifier to amplifier in a subunit.
NOTE: Connection can be made to either the front or rear panel or the NLB 60E. Although two computers may be connected to the NLB 60E simultaneously, only one is allowed access to the subnet at a time.
QUICK GUIDE OVERVIEW 6
14 C Series C 68:4, C 4 8:4, C 28: 4 and C 16:4 Operation Manual
7.1 Introduction
The following sections provide comprehensive infor­mation on amplifier connection, setup, operation, and performance. The detailed information included here is essential to realizing the full functionality of the C Series amplifiers.
7.2 Operation precautions
Ma ke su re th at t he Po wer swit ch a nd t he Re mot e
•
switch on the amplifier front- panel are set to “off” before making any input, output or network connections, and also before manipulating the DIP-switches on the rear-panel. Make sure that the AC mains voltage is correct • and matches the voltage printed on the rear-panel of the amplifier (115 V or 230 V). Make sure that no signal is present at the input • to the amplifi er when powering up. This could produce an unintentionally loud initial volume from the speakers.
7.3 Signal flow and headroom
7.3.1 Signal flow blo cks
All C Series amplifiers have the same signal flow and feature set. The only difference is the amplifier’s maximum output current per channel.
The input stage of all C Series amplifiers has a high sensitivity to provide ample system headroom. This in e ffe ct me ans that the inpu t st age is al mos t imp os­sible to clip.
Overall amplifier input gain is adjusted using the input stage DIP-switches. Please note that the gain setting is global, affecting all four channels. Following the input stage, the dedicated level control on each channel allows signal attenuation from 0 dB to minus infinity.
The CPL (Current Peak Limiter) section dynamically limits the input signal based on three parameters: sensed current level, feedback from the output stage, and sensed voltage clip from the VPL (and output amplifier voltage clip if “Soft Clip” activated). This ensures that power output is maintained within the design limits of the amplifier.
The adjustable VPL (Voltage Peak Limiter) sets the maximum output voltage and therefore also the maximum output power. Eight (8 ) different voltage stages are available using the DIP-switches on the rear-panel. See table in A ppendix section with VPL ratings at typical loads.
The sophisticated output section monitors faults and generates appropriate warnings, which are displayed on the amplifier front-panel and transmitted through the NomadLink network. These alerts allow the operator to adjust system settings and thereby avoid problems. In the rare event that conditions are extraordinarily severe, the amplifier will shut down until the fault or problem setting has b een rectified or adjusted. These sensing circuits are also employed to feed back voltage and current level information, via a side chain, to the limiters. Sensing circuits also transmit local amplifier module temperature and power supply temperature to the appropriate protection mechanisms. Read the Protection, Faults and Warnings section for further details.
The headroom available through the input stage to the clip limiter is shown by the dotted lines as +10 dB at 141 V peak and +20.4 dB at 42 V peak. These lines illustrate the additional signal level that can be ac cept ed at the inpu t be fore any s ign ific ant d isto rti on will appear at the input stage.
If you use the level potentiometer in the signal chain to reduce the level by an amount greater than the headroom relative to input
sensitivity, AND you drive the amplifi er to clip level, you are in danger of clipping the input stage before the current or voltage peak limiters are activated.
When bridging two channels, you must add
+6 dB to the input sensitivity to achieve
maximum output voltage due to the
automatic -6 dB gain compensation inserted by the amplifier.
7.3.2 Headro om, sensitivity an d VPL / Gain settings
The input amplifier and limiter system is designed to accommodate extremes of performance. Typically, exceeding maximum input by much as +10 dB will only result in a 1% increase in distortion. The following schematics illustrate how the adjusable VPL and Gain circuitry affect input sensitivity and output power:
The tab les to the left of the drawing below show input sensitivity for C 6 8:4 with an 8 ohm load and 141 V peak (max.) and 42 V peak (min.) respectively for the eight different gain stages between +23 dB and +44 dB. The resulting output power is displayed in dBu, Vrms and Watts in the tables to the far right. Complete input sensitivity tables for all VPL and Gain settings for all C Series models, can be found at www.labgruppen.com.
7 OPERATION AND PERFORMANCE OPERATION AND PERFORMANCE 7
C 68:4 V PL and GAIN settings
16 C Series C 68:4, C 4 8:4, C 28:4 and C 16:4 Op eration Manual
7.4 Audio Input and Output con­nections, setup and features
7.4.1 Balance d / Unbalanced Input c onnection
Two electronically balanced Phoenix-type inputs are available. Follow the +,– and Ground labels when connecting the input signal.
If an unbalanced connection is desired this can be achieved by summing the minus (“COLD”) and Ground terminals and using the + terminal as the “HOT” signal. For the best possible performance, the summing of ground and minus wires should be done at the source unit end of the cable (e.g. a CD player).
Four connectors are supplied for attaching cables to the inputs. The t ype of connector used is: P hoenix Contacts, Part number MSTB 2,5 /3-STZ-5, 08
When linking the same source signal to several input channels, be aware that there is a limit to the number of channels an
output source can “drive”. A typical output source (e.g. a DSP crossover unit) can drive up to 4 amplifier channels before line-drivers would b e required to buffer the signal.
7.4.2 Outpu t operation and conne ction
Screw-terminal connectors with + and – poles are provided at each channel output for connection of the speakers.
Make sure that the speaker cables are connected correctly and tightly, and that accurate polarity is maintained to all speakers in the system.
As the amplifier outputs produce high voltage,
do not connect or disconnect speaker cables when the mains power is on. Also, attach the safety cover on the speaker terminals for safe operation and to comply with electrical product approvals.
7.4.3 Outpu t bridge mode
It is possible to bridge channels in pairs of two (A+B and C+ D for example). When bridged, the input source must be connected to input A ( A+B) or C (C+D ) respectively. Output speaker cables must be connected to the plus pole on channel A or C and the minus pole on B or D.
The main benefit of bridging the output is a doubling of output voltage. Bridging c an be used to turn the amplifier into a three-channel amplifier with, for example, 2 x 1200 W and 1 x 2400 W at 4 ohms uti liz ing t he C 48 :4, or s imp ly to ach ieve an i mpr essi ve 200 Vrms supply per channel.
Most power amplifier designs, when bridged, automatically introduce a +6 dB input gain boost which can lead the user to conclude that said amplifier delivers “more than double the power” when in bridge mode. This is clearly not the case, as the gain boost artificially enhances perceived power at the cost of headroom. The C Series amplifiers work on globally set constant gain, and automatically compensate the input gain by -6 dB. For example, if the amplifier is configured in a three-channel mode, then the selected gain is maintained from input to output on all channels.
7.4.4 Amplifi er Gain
All C Series amplifiers feature adjustable input gain. Th is ve rsa tili ty e nab les t he a mpli fier to a cco mmod ate a multitude of system configurations with various input sources and speaker layouts.
Am plifi er g ain is se t glo bal ly fo r al l fou r ch anne ls. The range is +23 dB to +44 dB in 3 dB steps. Individual channel fine level adjustment is available using the potentiometers on the front panel.
The unique adjustable input gain feature of the C Se ries make s it easi er to att ain the o ptim um b ala nce between headroom and signal-to-noise ratio in the signal path. A weak signal at the input might require the gain to be raised in order to achieve maximum output power with the lowest signal-to-noise ratio. A “hot” input signal, however, would require a lowering of the gain to avoid sending the amplifier into Voltage or Current clipping.
See A ppendix to review the table containing Gain versus VPL setting implications for input sensitivity and output power.
Bridge mode operation automatically co mpen sat es by -6 dB, keep ing a ll c hann els at the same gain.
7.4.4.1 Channel gain/ Level (front-panel po ts)
Individual channel gain (level) may be adjusted using the potentiometers located on the front-panel behind the dust-filter cover. Range is from 0 dB to -infinity in 21 steps. The attenuation is logarithmic, with the 12 o’clock position indicating -10 dB.
Use your fingers or a screwdriver to adjust the potentiometers.
If the level c ontrol is used to attenuate to a lower level than the headroom relative to input sensitivity AND the amplifier input is
dri ven into clip , the re i s a da nge r of c lip ping the input stage before the current or voltage peak limiters are activated.
7.4.4.2 Amplifier sens itivity
Sensitivity is defined as how many volts ( rms) or dBu (referred to 0.775 Vrms) are required to achieve full (maximum) output power. As the output power varies with the load impedance, 4 ohms is usually
the common reference.
Since C Series amplifiers are capable of providing multiple maximum output power levels through use of the VPL feature, many sensitivity calculations may be required for a single amplifier. We recommend use of the DeviceControl software to simplify this process. DeviceControl’s Device View page, used in combination with the DIP-switch settings display, will automatically produce a sensitivity calculation from the given data (VPL, Gain and load ).
7.4.5 Outpu t Voltage Peak Limiter (VPL)
Voltage Peak Limiter ( VPL) is a unique feature in C Series amplifiers. It is used to select the maximum power available on each output channel. Eight levels can be set using the DIP-switches on the amplifier’s rear-panel.
V
peakVrms
141 100 118 84 100 70 85 60
71 50 59 42 50 35
42 30
The values for VPL are displayed as maximum voltage pe ak ( V pe ak) . To t rans lat e V p eak i nto Vrms , yo u mu st divide the Voltage Peak values by 1.41 (see table).
The V PL allows you to set the correct ma ximum output peak p ower for optimum performance with the con nec ted s pea kers . Th e co rrec t se tti ng d epen ds on the system type (low- or high-impedance) and the spec ific load connected to the channel. Since each channel can be configured to deliver either very high voltage peak power OR high current draw at low impedances, it is important to set the VPL correctly.
To configure an individual output channel for a constant voltage system, you simply adjust the DIP-switches to the desired voltage. However, when using an output for a low-impedance system (2, 4, 8 or 16 ohms), then sometimes you need to adjust the VPL to a lower setting to avoid either
7 OPERATION AND PERFORMANCE OPERATION AND PERFORMANCE 7
18 C Series C 68:4, C 4 8:4, C 28:4 and C 16:4 Operation M anual
delivering excessively high continuous power to the sp eake r or o ver heat ing of th e ou tput cha nne l thr oug h high current draw. For example, with a very “hot” continuous output signal, the temperature could rise to a critical level and activate Temp warning or even Temp Mute. Lowering the VPL setting normally will solve this situation.
If the Current Peak Limiter is active or indicates low impedance, lowering the VPL setting can rectify this situation as well.
7.4.6 Const ant Voltage 70 V and 100 V systems setup and ope ration
When using C Series amplifiers to drive constant vol tag e (h igh -im ped anc e) s pea ker s yste ms a t 70 V
rms
or 100 V
rms
, you can in most cases simply connect the speakers to the amplifier output terminals, select the correct VPL setting, and place the ampli fier in service.
7.4.7 Outpu t Current Peak Limiter ( CPL)
The Current Peak Limiter ( CPL) ensures that the amplifier will not be damaged by trying to deliver current to the outputs exceeding the physical limits of the transistors. The CPL keeps the amplifier within the Safe Operating Area. The CPL is non-adjustable and has different limit values depending on model type. The maximum output current values for the four C Series models are:
C 68:4, 24. 5 A•
rms per channel
C 48:4 , 17. 5 A•
rms per channel
C 28:4, A•
rms per channel
C 16:4, 8.5 A•
rms per channel
CPL activity is indicated by illumination of an orange LED for each channel on the front-panel. Warnings also are shown in the DeviceControl software’s GUI.
A steadily illuminated orange CPL LED indic ates a short circuit situation (or very low imped ance). The output will mute for 6 seconds before measuring the output impedance again. This will continue until the short circuit is fixed, at which time the output will automatically un-mute. An input signal must be present to allow detection of short circuit or low ­impedance conditions.
If the CPL LED is steadily illuminated orange while the output is muted and the - 4 dB signal LED is NOT on, then the amplifi er
output is detecting a short circuit or low impedance condition. The problem can be solved by checking input and output cables and examining the state of the loudspeaker load. If there is no short circuit present, then the c ondition may be rectified by lowering the VPL or input levels.
If the CPL and -4 dB indicators are lit simultaneously, then the amplifier is delivering excessive current and is being forced into a current limiting state ( output muted).
7.5 Protection, faults and
warnings
7.5.1 Introdu ction
The C Series amplifiers inc orporate a sophisticated and comprehensive set of protection features. Faults and warnings are indicated on the front- panel and reported via the NomadLink network for indication on the DeviceControl GUI.
7.5.2 Safe Ope rating Area Detec tor (SOAD)
Th e Saf e Op era ting Are a Det ect or ( SOA D) comp are s output voltage against output current to ensure that the output transistors are working inside their safe operating area.
The SOA D provides fault monitoring and input to the Current Peak Limiter (C PL). The SOAD has no dedicated indicator, and its operation is revealed only in conjunction with features such as the CPL.
7.5.3 Very High Freq uency protectio n
All C Series amplifiers include protection circuits that detect continuous Very High Frequency (VHF) content in the input signals. The detection begins at ap prox imat ely 10 kH z and move s up ward s to i ncl ude ultrasonic signals If VHF signals are detected, the output will mute for 6 seconds before re-measuring. Once no continuing VHF signal is detected, the output un-mutes and returns to normal operation.
This feature recognizes that continuous full-scale VHF
signals do not appear in “natural” sources such as mus ic. Any s uch sign als can t her efore be c ons ider ed as a fault when present. VHF protection is essential for avoiding damage to high frequency drivers.
The V HF protection operational area is dependent on output power level and frequency. The illustration below shows a decreasing threshold on the output power level, starting at ap proximately 10 kHz and ris ing wit h a - 6 dB slo pe. T his defi nes the V HF p rote c­tion area. When continuous output power above the threshold line is detected the VHF protection becomes active.
20 Hz 10 kHz 20 kHz
30 kHz
-6 dB slope
VHF protection operation area
Max. Peak output power
Max. Continous output power
Output power
Attack time
VHF protection
Slow
Fast
20 Hz 10 kHz 20 kHz
30 kHz
The Att ack time for the V HF protection is increa­singly shorter at higher frequencies. For example, an ultrasonic continuous signal will cause the outputs to mute rapidly, where it will take several milliseconds for a 10 kHz continuous signal to trigger the output mute. This is shown in the illustration above.
The V HF protection is NOT a limiter and does not alter the amplifier’s frequency response. It is imple­mented solely to detect continuous VHF content. The amplifier will always pass VHF peaks at full power, with no effect on musical “transients”.
The V HF protection is indicated by a yellow LED on the amplifier front-panel, with output muting for 6 seconds when in action. It is repor ted as a fault via the NomadLink network on the DeviceControl GUI.
If you bench test the amplifier using a continuous, full scale sine-wave input above 10 kHz, the VHF protection will activate and
prevent measurement of full peak output power. (Output will be muted long before maximum output power is attained.) To measure the true peak output power, use a burst signal.
7.5.4 DC prote ction
DC protection is implemented on eac h output to prevent damage to connected loudspeakers. DC present at the output will trigger muting and illuminate the fault LED indicator. A ny DC present at the output indicates a hardware malfunction that requires servicing of the amplifier.
7.5.5 High-i mpedance warning (o pen load)
A high-impedance (open load) condition is indicated when an input signal above approximately -29dB is detected and no functioning loudspeakers are connected to the amplifier. The fault in indicated by a red Sig /Hi-imp LED. The indicator is green when a valid load is present under the same input signal conditions
Since the High- impedance detection initially triggers only when the input signal rises above -29dB, it might cause the indicator to first turn green, and then red,
even in situations where no speaker is connected.
7.5.6 Low-imp edance protect ion (short ci rcuit)
A low- impedance or short circuit fault is detected when current draw is high (Current Peak Limiter active) and when, simultaneously, output signal is low (-4 dB LED does not illuminate). When this occurs, the amplifier protects the output stage from damage by muting the output signal and bypassing the circuits. Indication of this fault is a constant orange illumination of the Current Peak Limiter (CPL) LED on the front-panel. The protection will sequence at 6 second intervals to re- measure conditions. If the low-impedance fault is no longer detected, the amplifier will un-mute.
If the CPL turns constant orange, the output is muted, and the -4dB signal LED is ON, then the amplifier has gone into maximum
current protection. This situation is caused by an excessive input signal and is not due to a short circuit. Turn down the input signal to avoid or remedy this situation.
7 OPERATION AND PERFORMANCE OPERATION AND PERFORMANCE 7
20 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
7.5.7 Temperature pr otection
Thermal measurement points are provided on each output channel as well as on the power supply. If these sensors detect temperatures above the speci­fied maximums, a high temperature warning will be indicated by a flashing Temp LED on the front panel. The warning also will be transmitted to the Device Control GUI via the NomadLink network.
As the amplifier approaches a thermal protection threshold, the warning LED sequence will start with short “on-time” bursts. If the amplifier continues to overheat and approaches the temperature limit, the flashing sequence will be defined by longer and longer on -time bursts until the protection mode is activated.
If the temperature becomes too high to continue safe operation, the overheated output channel(s) will be muted until the temperature returns to an acceptable level.
Fully active temperature protection (with muting) is indicated by a constantly illuminated Temp LED. It will also b e indicated as a fault via the NomadLink network on the DeviceControl GUI.
Temperature measurements will continue at 6 second intervals. The output will un-mute when the channel or power supply returns to a safe operating temperature.
7.5.8 Power Average Limit er (PAL)
The Power Average Limiter (PAL) controls the current-drawing relationship between the power supply and the mains inlet. PAL limits the maximum average power consumption according to the power supply cap abilities, ensuring that the PSU will not overload. In addition, in the larger models that potentially could pull more current from the mains than the mains fuses are specified to handle (more than 16 A), PAL limits the amplifier’s maximum current draw to prevent blowing the mains fuse.
7.5.9 Soft-S tart
High p owered amplifiers with inadequate inrush limiting can pull considerable current from the mains at turn-on. This can result in fast acting mains breakers tripping. Such is not the case with C Series amplifiers. T he C Series amplifiers have ver y low inrush power as the capacitors are charged slowly
and in a controlled manner ensuring that breakers will not trip.
Several amplifiers will, under normal conditions, be able to be powered up simultaneously. If you do experience problems powering up multiple amplifiers simultaneously, use the NomadLink network and the NLB60E to establish a power sequence with pre-set delays between the start-up of each subsequent amplifier.
7.6 Front-panel monitoring and adjustments
7.6.1 Level indic ators
Four signal/level/clip LEDs per channel are contained on the C Series front-panels :
Orange• C PL (C urrent Peak Limiter) flashing
indicates signal exceeds the limits of the output devices and limiting is in effect.
Red• VPL/CLIP indicates that the signal has
exceeded maximum output voltage. (Maximum voltage is determined by rear-panel VPL set­tings.)
Green• - 4 d B in dic ates out put s ign al h as re ach ed
this level.
Green• - 10 dB i ndi cat es o utp ut s ign al ha s re ach ed
this level.
Si gna l / Hi -I mp• (Green/red) indicates an output
sig nal abo ve - 44 d B. I f it turn s RE D, th is in dic ate s that a high-impedance (“open” connection) has been detected at the output. This can be a fault such as a disconnected cable or malfunctioning loudspeaker driver. H owever, it could indicate acceptable high impedance, such as a sub-bass enclosure with high- impedance at a certain frequency. When the -10 dB sign al LED is on AND the Hi-Imp. LED turns red then the ampli­fier has detected an open load (no speaker is connected ).
For more detailed signal level indications use the DeviceControl software application.
7.6.2 Level adju st
Step Attenuation
1 (Min) -Inf. dB
2 -Inf. dB 3 - 50 dB 4 - 40 dB 5 - 35 dB 6 -21.5 dB 7 -21.5 dB 8 -14.7 dB
9 -12.9 dB 10 -11.4 dB 11 -10.0 dB 12 -8.7 dB 13 -7.4 dB 14 -6.0 dB 15 -4.5 dB 16 -2.7 dB 17 -0.6 dB 18 -0.3 dB 19 - 0.1 dB 20 0 dB
21 (Max) 0 d B
Level adjust potentiometers ( one per channel) are located behind the removable dust-filter cover on the amplifier’s front-panel. It is not possible to adjust the level settings with the cover in place.
The potentiometer’s operational range is 0 dB to
-infinity in 21 steps. Attenuation is logarithmic, with 12 o’clock position being -10 dB. See table to the right with increments.
It is not possible to adjust the indi vidual channel attenuation from the NomadLink network or elsewhere on the amplifier.
Use fingers or a screwdriver to adjust the potenti­ometers.
7.6.3 Mute ind ication
Individual channel Mute is indicated by illumination of the two yellow LEDs at the top of the channel’s LED bargraph. If both LEDs are illuminated and all other indications are normal, then the channel has been muted by a command from the NLB 60E front-panel or the DeviceControl application. Otherwise, a Mute could indicate a fault condition. (See below)
7 OPERATION AND PERFORMANCE OPERATION AND PERFORMANCE 7
22 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
7.6.4 Perfor mance, Warning and Fault indicators
Power on/off• (g ree n) i ndi cate s th at m ains pow er
is switched on.
NomadLink •(blue) indicates that the network
is connected. The NomadLink LED will light up even before the mains power is connected and swi tch ed on as i t tak es p hant om po wer from the network cable.
Bridge mode •(yellow) indic ates if t wo chan-
nels are bridged using the DIP-switch on the rear-panel.
CPL, •Cur rent Pea k Lim ite r (o rang e) , whe n fla sh-
ing indicates the maximum possible current draw has been reached. CPL, • Current Peak Limiter (orange), when con - stant indicates excessive current draw caused by a short circuit on the output or very low op­erational impedance. When detected, the output will mute for 6 seconds before re-measuring the output impedance. This will continue until the short circuit is removed. CPL remains constant orange in a fault condition only when an input signal is present. Temperature • (yellow) warning is indicated by a flashing LED. If the amplifier goes into thermal protect (output muted) the LED illuminates constant yellow. VHF, • Very High Frequency protection (yellow), indicates that potentially harmful continuous high frequencies have been detected on the input signal. The output is muted.
PAL•, Power Average Limiter (red), indic ates
that the amplifier is limiting because the power supply and/ or the mains inlet fuse has reached maximum capability.
Hardware fault •is i ndi cate d wh en b oth t he CP L
and VHF indicators light up simultaneously. The amplifier requires servicing before placing back in operation.
7.7 NomadLink network and DeviceControl software
7.7.1 NomadLink n etwork in the amplifie rs
All C Series amplifiers are equipped with the pro­prietary NomadLink network interface. This includes two Ether Con-housed RJ45 connections: one IN and one OUT.
Use standard straight Cat-5 Ethernet cables with RJ 45 c onn ecto rs to con nec t the amp lifie r to the N LB 60E or to daisy-chain multiple amplifiers.
It i s ve ry i mpor tan t th at tw o IN or t wo OU T ports are NEVER connected to each other. This will cause the NomadLink communi-
cation and DeviceControl software to exhibit erratic behavior and display inaccurate data. However, this situation will not damage the amplifier circuitry.
Up to 60 amplifiers can be connected to one NLB 60E in a daisy-chain or closed lo op.
When the NLB 60E is powered up, the NomadLink network receives phantom power. This c auses the blue Nomad Link LED on the amplifier front-panel and the NomadLink LED on the rear-panel to light up. Nom adL ink i s ac tive eve n whe n th e amp lifi er h as mains power disconnected or is not yet powered up.
The amplifier does not have a stand-by power supply for the network. The net work is solely powered from the NLB 60E. Should an amplifier fail or be inadvertently disconnected from the mains, network integrity is fully maintained and all amplifiers
7 OPERATION AND PERFORMANCE OPERATION AND PERFORMANCE 7
remain visible on the system.
7.7.2 Connec tion and setup
The No madLink network requires use of an NLB 60E N omadLink Bridge & Network Controller. The NomadLink network is established by connecting the NLB 6 0E OUT port to the first amplifier’s IN port. Then a daisy-chain is established by connecting the first amplifier’s OUT port to the next amplifier’s IN port, and so on. If a closed loop network is desired for improved redundancy (highly recommended), the last amplifier’s OUT port must be connected to the NLB 60E’s IN port.
For all connections, straight C at-5 RJ 45-equipped Ethernet cables should be used.
Optimal NomadLink performance can only be assured when using Cat-5 cables. However, as NomadLink is only using two
wires plus ground for communication and phantom power it is possible to create converters from RJ4 5 to, for example, XLR connectors using 2-wire shielded cable. The NomadLink network can then be operated using a stand ard tie- line in a multicore signal distribution system. See the drawing opposite for an example of how to create a converter.
If a ny c abl e for mat or co nne ctio n ot her t han
Cat-5 ( or better) and RJ45 is utilized, net-
work performance may be compromised.
In t his even t La b.gr upp en c ann ot gu ara ntee that the NomadLink network will be fully opera­tional.
24 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
7.7.4 Etherne t network cable len gths
The connection between the NLB 60E and your PC is a standard Ethernet network running the TCP /IP protocol. Cable distances between NLB 60E and your PC follow standard rules for Ethernet systems.
Contact your IT expert for more details.
7.7.5 DeviceC ontrol software
DeviceControl is Lab.gruppen’s proprietary software application for monitoring and controlling networked C Series power amplifiers. DeviceControl runs on a Windows P C, which connects via Ethernet to the NLB 60E. Device Control provides comprehensive monitoring of amplifier status as well as control of amplifier power on/ off and individual channel mute and solo functions.
Please review the DeviceControl Operation Manual for more detailed information.
OPERATION AND PERFORMANCE 77 OPERATION AND PERFORMANCE
7.7.3 NomadLink n etwork cable leng ths
In situations where the amplifiers and the NLB 60E will be positioned in different lo cations at some distance from each other, or where groups of amplifiers within a single subnet with up to 60 units will be installed with a distance in between, these general rules may be considered:
Below are typical examples of NomadLink network setups:
Rule 1: • The maximum cable length in between any two devices may not exceed 300 meters / 980 feet. Rule 2: • In a non-closed-loop daisy-chained subnet the total maximum cable length is 400 meters / 1300 feet. Rule 3: • In a closed-loop subnet the total maximum cable length is 700 meters / 2300 feet.
26 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
8 APPENDIX
8.1 Maintenance
During normal operation your C Series amplifier will provide trouble-free ser vice. The only user mainte ­nance required is to periodically vacuum clean the foam dust filters behind the front grille.
In some extreme cases it may be necessary for authorized service personnel to clean the inside of the amplifier. These conditions usually occur after prolonged use in extreme environments such as those using “cracked oil” smoke machines. If you are using your amplifier in a heavy duty application, it is recommended to have your amplifier ser viced every 3 years purely as a preventative action.
8.2 FAQ
Following are common questions asked about Lab.gruppen C Series power amplifiers together with helpful answers.
Q: What is the input sensitivity of the amplifiers? A: Input sensitivity is calculated from the amplifier
gain, maximum output voltage and load. As gain and output voltage is adjustable in C Series amplifiers, you need to look this information up in a table found in the Appendix section of this manual. Input sensitivity also is automatically calculated in the DeviceControl software application.
Q: What are the maximum cable lengths allowed when using the NomadLink network? A: NomadLink uses a daisy-chain topology to connect amplifiers and an NLB 60 E in a network. Standard RJ45-e quipped Cat- 5 cables are used throughout. The d aisy chain may be made into a closed -loop by connecting a return cable to the NLB 60E from the last amplifier.
General rules of cable lengths:
The maximum cable length in between any • two devices may not exceed 300 meters / 980 feet. In a non-closed -loop daisy-chained subnet • the maximum cable length is 400 meters / 1300 feet. In a closed-loop subnet the maximum cable
•
length is 700 meters / 2300 feet.
Exceeding these limits may result in lost contact with the devices, or loss of phantom powering due to cable resistance.
Q: How long can cable runs be on the Ethernet network connecting the NLB 60E to the PC? A: On the Ethernet side, normal Ethernet cable limits ap ply. T his is t ypi call y a m axi mum o f 80 mete rs / 300 feet between each device. Follow standard instal­lation procedures for Ethernet. Distances beyond 100 meters may require use of a repeater, a format converter, or optical cables.
Q: Why is the NomadLink network a closed-lo op topolog y? A: Technically speaking, the closed loop is optional. The purpose of closing the loop is primarily to provide a secondary path to the amplifiers. If cables are broken or disconnected in either direction, all amplifiers still may be addressed by the network.
Q: How can I be sure that no protection circuits or safety functions interfere with the output signal? A: If no Clip or Warning LEDs on the front-panel light up, you can be fully confident that the rated maximum output power in the full frequency range is available for your speakers. No limiting or gain-reduction takes place without a warning or fault indication.
8.3 Additional documentation
In case you didn’t find what you were looking for in this Operation Manual, check out the website at www.labgruppen.com, where you can find a multitude of additional documentation for C Series: Drawings, technical data sheets, tables with input sensitivity, background technology briefs and much more.
APPENDIX 8
28 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
8.5 Current Draw and Thermal Dissipation specifications
The following tables contain information on measured current consumption as well as calculated heat dissipation at three st ates: 1) Stand -by/idling; 2) Normal operation (1/8 of rated power); and 3) at extreme heavy duty operation (Max. power).
8 APPENDIX APPENDIX 8
C 68:4
Level Load Rated power Line Curre nt *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o ff via NomadLink 0 0 0 0 0
Powered on, idling. 133 0 133 454 114
Amp (I) Watt
Pink noise (1/8 ra te d p ow er )
8 Ω / Ch. 120 0 x 4
16.0 8.0 11 23 600 523 1784 450
16 Ω / Bridged 2400 x 2
4 Ω / Ch. 170 0 x 4
22.4 11.2 1 578 850 728 248 4 626
8 Ω / Bridged 3400 x 2
2 Ω / Ch. 120 0 x 4
21.2 10.6 1378 600 778 2655 669
4 Ω / Bridged 2400 x 2
100 V / Ch. 16 00 x 4
21.0 10. 5 14 63 800 663 2262 5 70
200 V / Bridged 3200 x 2
Pink noise (1/4 rated power) *3)
8 Ω / Ch. 120 0 x 4
32.6 16.3 2429 16 00 829 2829 713
16 Ω / Bridged 2400 x 2
4 Ω / Ch. 170 0 x 4
38.8 19.4 26 97 17 00 997 3402 857
8 Ω / Bridged 3400 x 2
4 Ω / Ch. 120 0 x 4
35.2 17.6 2296 1200 1096 3 740 942
8 Ω / Bridged 2400 x 2
100 V / Ch. 16 00 x 4
35.4 17.7 2605 1600 1005 3429 864
200 V / Bridged 3200 x 2
Mains connector, 230 V CE v ersion 16 A, CEE7
Mains connector, 115 V ETL version 20 A / 5-20P
*1) The amplifi er’s PSU operates as a non-r esistive load, so the c alculation “Volts x A mps = Watts” would not be c orrect. Instead, me asured and specifi ed here is what is known as the “Active Power” in th e amplifi er providing useful, real-wor ld values of power consu mption and heat dissi pation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measure d at maximum power before a mplifi er protection and limiter features are en gaged. Typically thi s is between 1/4 and 1 /3 of rated power. Note that the max. power c ondition is very ex treme and will not occu r during normal oper ation. Also note that th e mains breaker will not be tripped even if operati on is in excess of max. rati ngs.
C 28:4
Level Load Rated power Line Curre nt *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o ff via NomadLink 0 0 0 0 0
Powered on, idling. 123 0 123 420 106
Amp (I) Watt
Pink noise (1/8 ra te d p ow er )
8 Ω / Ch. 700 x 4
11.6 5.8 727 350 377 1286 324
16 Ω / Bridged 14 00 x 2
4 Ω / Ch. 700 x 4
13.0 6.5 775 350 425 145 0 365
8 Ω / Bridged 1400 x 2
2 Ω / Ch. 300 x 4
9.4 4.7 529 150 379 129 3 326
4 Ω / Bridged 600 x 2
100 V / Ch. 700 x 4
10.4 5.2 663 350 313 106 8 269
200 V / Bridged 140 0 x 2
Pink noise (1/4 rated power) *3)
8 Ω / Ch. 700 x 4
24.0 12.0 1589 933 656 2237 564
16 Ω / Bridged 14 00 x 2
4 Ω / Ch. 700 x 4
20.8 10.4 1359 700 659 2249 567
8 Ω / Bridged 1400 x 2
4 Ω / Ch. 300 x 4
14.0 7.0 843 300 543 185 3 467
8 Ω / Bridged 600 x 2
100 V / Ch. 700 x 4
21.4 10.7 145 8 933 525 179 0 451
200 V / Bridged 140 0 x 2
Mains connector, 230 V CE v ersion 16 A, CEE7
Mains connector, 115 V ETL version 20 A / 5-20P
*1) The amplifi er’s PSU operates as a non-r esistive load, so the c alculation “Volts x A mps = Watts” would not be c orrect. Instead, me asured and specifi ed here is what is known as the “Active Power” in th e amplifi er providing useful, real-wor ld values of power consu mption and heat dissi pation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measure d at maximum power before a mplifi er protection and limiter features are en gaged. Typically thi s is between 1/4 and 1 /3 of rated power. Note that the max. power c ondition is very ex treme and will not occu r during normal oper ation. Also note that th e mains breaker will not be tripped even if operati on is in excess of max. rati ngs.
C 48:4
Level Load Rated power Line Curre nt *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o ff via NomadLink 0 0 0 0 0
Powered on, idling. 123 0 123 420 106
Amp (I) Watt
Pink noise (1/8 ra te d p ow er )
8 Ω / Ch. 1000 x 4
13,8 6,9 945 500 445 1518 383
16 Ω / Bridged 2000 x 2
4 Ω / Ch. 120 0 x 4
17,4 8,7 117 1 600 571 1948 491
8 Ω / Bridged 2400 x 2
2 Ω / Ch. 600 x 4
12,4 6,2 769 300 469 1600 403
4 Ω / Bridged 1200 x 2
100 V / Ch. 900x 4
13,2 6,6 840 450 390 1331 335
200 V / Bridged 180 0 x 2
Pink noise (1/4 rated power) *3)
8 Ω / Ch. 1000 x 4
28,2 14,1 21 16 1333 783 2670 673
16 Ω / Bridged 2000 x 2
4 Ω / Ch. 1200 x 4
30,6 15,3 2168 1200 968 3303 832
8 Ω / Bridged 2400 x 2
4 Ω / Ch. 600 x 4
21,6 10, 8 13 68 600 768 2620 660
8 Ω / Bridged 1200 x 2
100 V / Ch. 900x 4
26,4 13,2 1827 1200 627 2139 539
200 V / Bridged 180 0 x 2
Mains connector, 230 V CE v ersion 16 A, CEE7
Mains connector, 115 V ETL version 20 A / 5-20P
*1) The amplifi er’s PSU operates as a non-r esistive load, so the c alculation “Volts x A mps = Watts” would not be c orrect. Instead, me asured and specifi ed here is what is known as the “Active Power” in th e amplifi er providing useful, real-wor ld values of power consu mption and heat dissi pation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measure d at maximum power before a mplifi er protection and limiter features are en gaged. Typically thi s is between 1/4 and 1 /3 of rated power. Note that the max. power c ondition is very ex treme and will not occu r during normal oper ation. Also note that th e mains breaker will not be tripped even if operati on is in excess of max. rati ngs.
C 16:4
Level Load Rated power Line Curre nt *2) Watt *1) Thermal Dissipation
115 VAC 230 VAC In Out Dissipated BTU/hr kCal/hr
Standby with remote power o ff via NomadLink 0 0 0 0 0
Powered on, idling. 129 0 129 440 111
Amp (I) Watt
Pink noise (1/8 ra te d p ow er )
8 Ω / Ch. 400 x 4
8.6 4.3 526 200 326 1112 280
16 Ω / Bridged 800 x 2
4 Ω / Ch. 300 x 4
8.2 4 .1 485 150 335 1143 288
8 Ω / Bridged 600 x 2
2 Ω / Ch. n.r.
4 Ω / Bridged n.r.
100V / Ch. 400 x 4
7.6 3.8 463 200 263 897 226
200V / Bridged 800 x 2
Pink noise (1/4 rated power) *3)
8 Ω / Ch. 400 x 4
16.2 8.1 1046 533 513 174 9 441
16 Ω / Bridged 800 x 2
4 Ω / Ch. 300 x 4
15.2 7. 6 953 400 553 1887 475
8 Ω / Bridged 600 x 2
2 Ω / Ch. n.r.
4 Ω / Bridged n.r.
100 V / Ch. 400x 4
14.4 7. 2 944 533 411 1401 353
200 V / Bridged 800 x 2
Mains connector, 230 V CE v ersion 16 A, CEE7
Mains connector, 115 V ETL version 15 A / 5-15P
*1) The amplifi er’s PSU operates as a non-r esistive load, so the c alculation “Volts x A mps = Watts” would not be c orrect. Instead, me asured and specifi ed here is what is known as the “Active Power” in th e amplifi er providing useful, real-wor ld values of power consu mption and heat dissi pation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measure d at maximum power before a mplifi er protection and limiter features are en gaged. Typically thi s is between 1/4 and 1 /3 of rated power. Note that the max. power c ondition is very ex treme and will not occu r during normal oper ation. Also note that th e mains breaker will not be tripped even if operati on is in excess of max. rati ngs.
30 C Series C 68: 4, C 48:4, C 28 :4 and C 16:4 Operation Manual
9 TEChNICAL sPECIFICATIONs
Following are the C Series technical specifications. These figures are accurate at the time of printing but please note that all figures are subject to change without notice. For the most accurate and current information available, please visit www.labgruppen.com.
Model
Number of channels
Peak total output all channels driven
Peak output voltage per cha nnel
Max. output current per c hannel
Max Output Po wer
16 ohms per ch. (all ch.’s driven)
8 ohms per ch. (all ch.’s driven)
4 ohms per ch. (all ch.’s driven)
2 ohms per ch. (all ch.’s driven)
Hi-Z per ch. (all ch.’s driven): 70 Vrms / 100 V peak
16 ohms Bridged per ch.
1)
8 ohms Bridged per ch.
1)
4 ohms Bridged per ch.
1)
2 ohms Bridged per ch.
1)
Hi-Z Bridged per ch.1): 140 Vrms / 200 V peak
Performan ce with Gain :
THD 20 Hz - 20 kHz for 1 W
THD at 1 kHz and 1 dB below clipping
Signal To Noise Ratio
Channel separation (Crosstalk) at 1 kHz
Frequency response (1 W into 8 ohms) +0/-3 dB
Input impedance
Input Common Mode Rejection, CMR
Output impedance @ 100 Hz
Voltage Peak Li miter (VPL), m ax. peak outp ut
VPL, selectable per ch.
3)
VPL, when bridged 3)
1)
Voltage Peak Limiter mode (per ch.)
Gain and Level
Amplifier gain selectable (all channels)
1)
– rear-panel switches
Default gain
Level adjustment (per ch.)
Connecto rs and switch es
Input connectors (per ch.)
Output connectors (per ch.)
Output bridge mode
High pass filter
NomadLink
®
network
Intelligent fans (on/off)
Power on/off and Remote enable on/off
Cooling
General Purpose Outputs (GPO)
General Purpose Inputs (GPI)
Front-panel indicators
Common
Per channel
Power
Operating voltage, 230 V / 115 V nominal
Minimum power-up voltage, 230 V / 115 V
Power Average Limiter (PAL)
2)
Soft-start / Inrush Current Draw
Mains connector
Dimension s (W/H/D)
Weight
Finish
Approvals
Note 1): Automatic -6 dB gain compensation when bridging channels. Ch.’s A+B and/or C+D, E+F, G+H, can be bridged individually.
Note 2): PAL can reduce the maximum output power to keep the power supply operating safely, and/or to prevent excessive current draw tripping the mains breaker. Refer to Operation Manual. Note 3): For sine waves, peak voltage output values translate to Vrms with the formula V/1.41 = Vrms. E.g. 100 V peak equals app. 70 V peak. Hence, outputs can be set for high-impedance loads without
requiring a transformer.
All specifications are subject to change without notice.
C 68:4 C 48:4 C 28:4 C 16:4 C 20: 8X C 10:8X C 10 :4X C 5:4 X
4 4 4 4 8 8 4 4
6800 W 4800 W 2800 W 1600 W 2000 W 1000 W 1000 W 500 W
141 V 141 V 141 V 141 V
100 V / 70 Vrms 100 V / 70 Vrms 100 V / 70 Vrms 100 V / 70 Vrms
24.5 Arms 17.5 Arms 12 Ar ms 8.5 Arms 8 Arms 5,6 Arms 8 Arms 5,6 Arms
650 W 6 25 W 60 0 W 400 W 250 W 125 W 250 W 125 W
1200 W 1000 W 700 W 400 W 25 0 W 125 W 250 W 125 W
1700 W 1200 W 700 W 300 W 25 0 W 125 W 250 W 125 W
1200 W 600 W 3 00 W n.r
4)
125 W 6 0 W 125 W 60 W
1600 W 900 W 7 00 W 400 W 250 W 125 W 250 W 125 W
2400 W 2000 W 1400 W 800 W 500 W 2 50 W 50 0 W 250 W
3400 W 2400 W 1200 W 600 W 500 W 2 50 W 50 0 W 250 W
2400 W 1200 W 600 W n.r
4)
250 W 125 W 25 0 W 125 W
n.r. n .r. n.r. n .r. n.r. n .r. n.r. n .r.
3200 W 180 0 W 1400 W 800 W 500 W 250 W 500 W 2 50 W
35 dB and VPL: 10 0 V 32 dB and VPL: 100 V
<0.1% <0.1%
<0.05% <0.05%
>112 dBA >112 dBA
>70 dB >70 dB
2.3 Hz - 56 kHz 2.3 Hz - 56 kHz
20 kOhm 20 kOhm
50 dB 50 dB
30 mOhm 48 mOhm
141, 118, 100, 85, 71, 59, 50, 42 V 100, 63, 45, 32 V
282, 236, 200, 170, 142, 118, 100, 84 V 200, 126, 90, 64 V
Hard / Soft Hard / Soft
23, 26, 29, 32, 35, 38, 41, 44 dB 29, 32, 35, 38 dB
35 dB 32 dB
Front-panel potentiometer, 21 position detented from -inf to 0 dB , hidden behind security panel/dust-filter grille
Front-panel potentiometer, 21 position detented from -inf to 0 dB , hidden behind security panel/dust-filter grille
3-pin Phoenix, electronically balanced 3-pin Phoenix, electronically balanced
Barrier strip 2-pole screw terminals Barrier strip 2-pole screw terminals
A+B and/or C+D, inputs A and C are input source A+B, C+D, E+F, G+H, inputs A, C, E, G are signal source
- Fixed at 35 Hz, switch able per channel
On board, 2 x RJ4 5 connectors IN and OU T On board, 2 x RJ4 5 connectors, IN and O UT
Yes, depending on presence of output signal Yes, depending on presence of output signal
Individual switc hes on front-panel Individual switc hes on front-panel
Two fans, front-to-rear airflow, temperature controlled speed Two fans, front-to-rear airflow, temperature controlled speed
- Contact Closure types, 2-pole Phoenix
- Contact Closure types, 2-pole Phoenix
NomadLink
®
Network; Power Average Limiter (PAL)2); Power on NomadLink® Network; Power Average Limiter (PAL)2); Power on
Signal present / High-impedance; -10 dB and -4 dB output signal;Voltage Peak Limiter (VPL); Current Peak Limiter (CPL): Very High Frequency (VHF); High temperature; Fault; Mute
Signal present / High-impedance; Voltage Peak Limiter (VPL); Current Peak Limiter (CPL): Very High Frequency (VHF); High temperature; Fault; Mute
130-265 V / 65-135 V 100-240 V
171 V / 85 V 80 V
Yes Yes
Yes / max. 5 A Yes / max. 5 A
230 V CE: 16 A, CEE7; 115 V ETL: 20 A / NEMA 5-20P IEC Inlet / NEMA 5-15P
W: 483 mm (19”), H: 88 mm (2 U), D: 343 mm (13.5”) W: 483 mm (19”), H: 88 mm (2 U), D: 343 mm (13.5”)
12 kg (26.4 lbs.) 8.5 kg (18.75 lbs.)
Black painted steel chassis with gray painted steel front Black painted steel chassis with gray painted steel front
CE, ANSI/UL 60065 (ETL), CSA C22.2 NO. 60065, FCC CE, ANSI/UL 60065 (ETL), CSA C22.2 NO. 60065, FCC
General
This product is manufactured by Lab.gruppen, and it is warranted to be free from any defects caused by components or factory workmanship, under normal use and service, for a period of six (6) years from date of purchase from an authorized Lab.gruppen dealer.
If the product fails to perform as specified during the warranty period, Lab.gruppen will undertake to repair, or at its option, replace this product at no charge to its owner, provided the unit is returned undamaged, shipping prepaid, to an authorized service facility or to the factory.
This warranty shall be null and void if the product is subjected to: repair work or alteration by a person other than those authorized by us; mechanical damage including shipping accidents; war, civil insur­rection, misuse, abuse; operation with incorrect AC voltage, incorrect connections or accessories; opera­tion with faulty associated equipment; or exposure to inclement weather conditions. Damage due to normal wear and tear is not covered by the warranty. Units on which the serial number has been removed or defaced will not be eligible for warranty service.
Lab.gruppen shall not be responsible for any incidental or consequential damages. Lab.gruppen’s responsibility is limited to the product itself. Lab.gruppen takes no responsibility for any loss due to cancellation of any events, or rent of replace­ment equipment or costs due to a third party’s or customer’s loss of profit, or any other indirect cost or losses however incurred. Lab.gruppen reserves the right to make changes or improvements in design or manufacturing without assuming any obligation to change or improve products previously manufactured.
This warranty is exclusive, and no other warranty is expressed or implied. This warranty does not affect the customer’s statutory rights.
Internationa l warranties
Please contact your supplier or distributor for this information, as rights and disclaimers may vary from country to country.
Technical assis tance and servic e
Internationa l
If your Lab.gruppen product requires repair, contact your Lab.gruppen dealer or distributor, or contact Lab.gruppen by fax or email to obtain the location of the nearest authorized service centre.
Factory ser vice
In the event Lab.gruppen produc t requires factor y service, you may contact Lab.gruppen’s service department for return instructions and a Return Authorization number. Please note for product return:
Use the original packing.1. Include a copy of the sales receipt, your name, 2. return address, phone and fax number, email address and description of the defect. Mark the Return Authorization number on the 3. outside of the packing. Ship the product prepaid to:4.
Lab.gruppen AB Faktorvägen 1 SE-4 34 37 Kungsbacka SWEDEN Phone: +46 30 0 56 28 00 Fax: +46 30 0 56 28 99
info@labgruppen.com www.labgruppen.com
WARRANTY 10
Lab .gruppen ab Sweden
internationaL contact info@Labgruppe n.com
uS contact infouS@tceLectronic.com
www.labgr uppen.com
Loading...