Lab.gruppen C 68:4, C 48:4, C 28:4, C 16:4 Operation Manual

Rev. 2.01
Operation manual
C Series:
Installation-Dedicated Amplifiers
C 68:4
C 48:4
C 28:4
C 16:4
Part no. UM-CS
1 CONTENTS .................................................................................................................................................2
2 APPROVALS ................................................................................................................................................4
3 WARNINGS .................................................................................................................................................4
3.1 Explanation of graphical symbols ........................................................................................................4
3.1.1 WARNING ................................................................................................................................4
3.1.2 CAUTION..................................................................................................................................4
3.2 Important Safety Instructions ..............................................................................................................4
3.3 User responsibility ...............................................................................................................................5
3.3.1 Mains connection grounding ....................................................................................................5
3.3.2 Speaker output hazard ..............................................................................................................5
3.3.3 Radio interference ....................................................................................................................5
3.3.4 Speaker damage .......................................................................................................................5
3.3.5 Maintenance .............................................................................................................................5
4 WELCOME ...................................................................................................................................................6
4.1 Introduction ..........................................................................................................................................6
4.2 Main Features ......................................................................................................................................6
4.2.1 Class TD amplifier and regulated switch-mode power supply .................................................6
4.2.2 Amplifier gain ...........................................................................................................................6
4.2.3 Voltage Peak Limiter .................................................................................................................7
4.2.4 Protection and performance optimization ................................................................................
7
4.2.5
NomadLink / Ethernet control and monitoring network ...........................................................7
5 INSTALLATION ...........................................................................................................................................8
5.1 Unpacking ............................................................................................................................................
8
5.2 Mounting .............................................................................................................................................8
5.3
Cooling .................................................................................................................................................8
5.4 Operating voltage ................................................................................................................................8
5.5 Grounding ............................................................................................................................................9
6 QUICK GUIDE OVERVIEW .......................................................................................................................
10
6.1 Front Panel overview .........................................................................................................................10
6.1.1 Power on/off and remote switch ............................................................................................10
6.1.2 Front Panel LED’s ...................................................................................................................10
6.2 Rear Panel overview ..........................................................................................................................11
6.2.1 The DIP switch features ......................................................................................................... 11
6.3 NomadLink / Ethernet network setup ................................................................................................12
7 OPERATION AND PERFORMANCE ........................................................................................................
14
7.1 Introduction ........................................................................................................................................14
7.2 Operation precautions .......................................................................................................................14
7.3 Signal flow and headroom .................................................................................................................14
7.3.1 Signal flow blocks ...................................................................................................................14
7.3.2 Headroom, sensitivity and VPL / Gain settings ......................................................................15
7.4 Audio Input and Output connections, setup and features .................................................................16
7.4.1 Balanced / Unbalanced Input connection ...............................................................................16
1 CONTENTs
C Series Operation Manual 3
7.4.2 Output operation and connection ...........................................................................................16
7.4.3 Output bridge mode ...............................................................................................................
16
7.4.4 Amplifier Gain .........................................................................................................................17
7.4.4.1 Channel gain / Level (front panel pots) ..........................................................................17
7.4.4.2 Amplifier sensitivity .......................................................................................................17
7.4.5 Output Voltage Peak Limiter (VPL) .........................................................................................17
7.4.6 Constant Voltage 70 V and 100 V systems setup and operation ............................................18
7.4.7 Current Peak Limiter, (CPL) ....................................................................................................18
7.5 Protection, faults and warnings .........................................................................................................
18
7.5.1 Introduction ............................................................................................................................18
7.5.2 Safe Operating Area Detector (SOAD) ...................................................................................18
7.5.3 Very High Frequency protection .............................................................................................18
7.5.4 DC protection .........................................................................................................................
19
7.5.5 Hi impedance warning (open load) .........................................................................................19
7.5.6 Lo impedance protection (short circuit) ..................................................................................19
7.5.7 Temperature protection ..........................................................................................................20
7.5.8 Power Average Limiter (PAL) .................................................................................................20
7.5.9 Soft Start ................................................................................................................................20
7.6 Front panel monitoring and adjustments ...........................................................................................21
7.6.1 Level indicators .......................................................................................................................21
7.6.2 Level adjust ............................................................................................................................21
7.6.3 Mute indication .......................................................................................................................21
7.6.4 Performance, Warning and Fault indicators........................................................................... 22
7.7 NomadLink network and PC editor ....................................................................................................23
7.7.1 NomadLink network in the amplifiers ....................................................................................23
7.7.2 Connection and setup.............................................................................................................23
7.7.3 NomadLink network cable lengths .........................................................................................24
7.7.4 Ethernet network cable lengths .............................................................................................25
7.7.5 DeviceControl editor ...............................................................................................................25
8 APPENDIX .................................................................................................................................................26
8.1 Maintenance ......................................................................................................................................
26
8.2 FAQ ....................................................................................................................................................26
8.3 Bench test the amplifier ....................................................................................................................26
8.4 Additional documentation ..................................................................................................................27
8.5 BTU specifications .............................................................................................................................28
9 TECHNICAL SPECIFICATIONS ................................................................................................................
30
10
WARRANTY ..............................................................................................................................................32
CONTENTs 1
This equipment conforms to the requirements of the EMC directive 89/336/EEC, amended by 92/31/EEC and 93/68/ EEC and the requirements of the Low Voltage Directive 7 3/23/EEC, amended by 93/68 /EEC.
Standards applied: EMC Emission EN 55103-1, E3 EMC Immunity EN55103-2, E3, with S/ N below 1% at normal operation level. Electrical Safety EN60065, Class I
This equipment is tested and approved according to the U.S . safety standard ANSI/ UL 60 065 and Canadian safety standard CSA C22. 2 NO. 60065. E TL made the tests and they are a Nationally Recognized Testing L aborator y (NRTL).
3.1 Explanation of graphical symbols
The lightning symbol within a triangle is intended to alert the user to the presence of un -insulated “dangerous voltage” within the amplifier’s enclosure that may be of suf ficient magnitude to constitute a risk of electric shock to humans.
The exclamation point within a triangle is intended to aler t the user to presence of impor tant operating and service instructions in the literature accompanying the product.
3.1.1 WARNING 3.1.2 CAUTION
3.2 Important Safety Instructions
Before using your amplifier, be sure to carefully read the applicable items of these operating instructions and the safety suggestions
Keep this manual for future reference. Heed all warnings. Follow all instructions. Do not use this unit near water. Do not spill water or other liquids into or on the unit. Do not operate the amplifier while wet or standing in liquid. Clean only with dr y cloth. Do not block the air intake or exhaust ports. Install the unit in accordance with the instructions. Do not operate the amplifier near heat producing devices such as radiators, heat registers, stoves or other apparatus that produce heat. Always
operate the unit with the chassis ground wire connected to the electrical safety earth. Do not defeat the safety purpose of a grounding-type plug. A grounding type plug has two pins and a third grounding prong. The third prong is provided for your safety. If the provided plug does not fit into your
outlet, consult an electrician for replacement of the obsolete outlet. Connect only to AC power outlets rated 100-120 V or 200-240 V, 50-60 Hz. Do not use this amplifier if the power cord is broken or frayed. P rotect the power cord from being walked upon or pinched particularly at the plugs
and the point where it exits from the apparatus. Only use accessories specified by the manufacturer. The unit is intended to use in a 19” rack. Follow the mounting instructions. When a rack on wheels is used, use caution when moving the loaded
rack to avoid injury from tipping over. Unplug this apparatus during lightning storms or when unused for long periods of time. Do not connect an amplifier output in parallel or series with any other ampli fier’s output. Do not connect the amplifier output to any other voltage
source, such as batter y, mains source, or power supply, regardless of whether the amplifier is turned on or of f. Do not run the output of any amplifier back into another channel’s input. Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way such as:
Power-supply cord or plug is damaged. Liquid has been spilled into the unit An object has fallen into the unit The unit has been exposed to rain or moisture The unit does not operate normally
The unit was dropped or the enclosure is damaged
17. Do not remove top or bottom covers. Removal of the covers will expose hazardous voltages. There are no user serviceable parts inside and removal may void the warrant y.
18. An experienced user shall always supervise this professional audio equipment, especially if inexperienced adults or minors are using th equipment.
19. The mains plug is used as the disconnec t device and shall remain readily operable. If mounted in a 19" rack causing the mains plug not being readily operable, the mains plug for the entire rack must be readily operable.
20. The US N ational Differencescl.16.3 requires that NomadLinknet work cables must be flame rated VW-1.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
2 APPROVALs
To reduce risk of fire or electric shock, do not expose this apparatus to rain or moisture.
To reduce the risk of fire or electric shock, do not remove screws. No user-serviceable parts inside. Refer servicing to qualified service personnel
3 WARNINGs
C Series Operation Manual 5
WARNINGs 3
3.3 User responsibility
3.3.1 Mains connection grounding
Your amplifier must be connected to a
grounded socket outlet.
3.3.2 Speaker output hazard
Power amplifiers are capable of producing
hazardous output voltages. To avoid electrical shock, do not touch any exposed speaker wiring while the amplifier is operating. The external wiring connected to the speaker terminals shall be installed by a qualified instructed person or ready-made leads or cords of appropriate capacity shall be used.
3.3.3 Radio interference
As the amplifier outputs produce high voltage,do
not connect or disconnect speaker cables when the mains power is on. Also, attach the safety cover on the speaker terminals for safe operation and to comply with electrical product approvals.
A sample of this product has been tested and complies with the limits for the European Electro Magnetic Compatibility (EMC) directive. This equipment has also been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference from electrical equipment. This product uses radio frequency energy and if not used or installed in accordance with these operating instructions, may cause interference to other equipment, such as radio receivers. However, there is no guarantee that inter­ference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be deter­mined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the antenna. Increase the separation between the equipment
and receiver.
Connect the equipmnt into an outlet on a
circuit different from that to which the receiver is connected.
Check if the affected unit complies with the EMC
limits for immunity, (CE-labeled). If not, address the problem with the manufacturer or supplier. All electrical products sold in the EC must be approved for immunity against electromag­netic fields, high voltage flashes, and radio inter­ference.
Consult the dealer or an experienced radio/T V
technician for help.
3.3.4 Speaker damage
Your amplifier is very powerful and can be
potentially dangerous to both loudspeakers and humans alike. Many loudspeakers can be easily damaged or destroyed by overpowering, especially with the high power available from a bridged amplifier. Always check the speaker’s continuous and peak power capabilities. Even if though the amplifier’s front panel attenuators can be used to reduce the gain, it is still possible to reach full output power if the input signal level is high enough.
3.3.5 Maintenance
For long-term and safe operation it is recommended that the amplifier dust filters on the front panel, as well as the inside of the amplifier is cleaned regularly. If the dust filters and inside are not maintained there will be safety risks. For example the amplifier can ignite the dust and a fire will occur due to high internal temperatures. There is also a risk that the amplifier will malfunction since the amplifier is dependent of constant airflow from front to rear. If the dust filters are not clean and the amplifier malfunctions, any resultant problems will not be covered by the warranty.
4 WELCOME
4.1 Introduction
Thank you for choosing Lab.gruppen C Series power amplifiers for your sound reinforcement system installation. We are confident that you will be very pleased with the performance, configuration flexibility, reliability, and long-term durability offered by the C Series products.
This manual provides a comprehensive guide to the features and functionality of C Series amplifiers. Please read through it in its entirely to become fully acquainted with the many configuration options and multiple layers of protection circuitry.
To facilitate timely installation and use of this C Series product, we have included a Quick Guide Overview (section 6). This brief summary, in conjunction with Installation (section 5), contains the basic information needed to safely install the amplifier and place it in service. However, we highly recommend reading through this manual in its entirety, beginning with Main Features and Technologies and continuing through Operation and Performance. As you become thoroughly familiar with all aspects of operation, you may learn of features or options that will affect your choices on amplifier modes or loudspeaker system configuration.
Thank you again for placing your confidence in Lab.gruppen power amplifiers.
Lab.gruppen C Series power amplifiers are designed and built specifically for the unique demands of permanent installation applications. C Series amplifiers offer the optimum combination of high­quality audio reproduction, flexible features, ease of installation, and 100% reliability in normal use.
By packing four channels of reconfigurable power amplification into a 2U chassis, the C Series achieves unprecedented “power density.” The benefits of compact dimensions include reduced rack space requirements and minimal heat build-up. The flexible output stages enable each amplifier channel to be set for either low impedance or constant voltage (70 V / 100 V) mode. NomadLink, an easy-to-use network for monitoring and control, is implemented as a standard feature on all C Series amplifiers.
Although C Series features and facilities are tailored to installation applications, at the heart of each amplifier is the same advanced technology that has made Lab.gruppen the benchmark of quality for touring concert systems: exceptional sonic performance, rugged construction, proven reliability, and protection features that anticipate every unwelcome possi­bility.
Read on to learn.
4.2 Main Features
Superficially, your new C Series amplifier may appear similar to other products made for the same purpose. On closer inspection, however, you will find a number of sophisticated technologies – many of them proprietary to Lab.gruppen – that are provided to ensure the best possible performance and many years of reliable operation. Familiarizing yourself with these technologies will prove invaluable in setting up and optimizing your loudspeaker system.
4.2.1 Class TD amplifier and regulated switch-
mode power supply
Lab.gruppen’s patented Class TD technology combines the exceptional efficiency of a Class D amplifier with the high sonic quality associated with Class B designs. Class TD also incorporates the same basic concepts behind Class H designs, but here they are refined and pushed to a higher level to achieve much greater efficiency.
The Class TD output sections work in concert with Lab.gruppen’s unique, regulated switch-mode power supply to create a superior overall power amplifier topology. The regulated PSU ensures stable, full output power over an extremely wide range of mains voltage levels. Sagging or fluctuating mains voltage will not affect the power output delivered to the loudspeakers.
4.2.2 Amplifier gain
For greater flexibility in system integration, C Series amplifiers allow gain adjustment from +23 dB to +44 dB in 3 dB steps. This feature accommodates any combination of input device and loudspeaker type. For example, if the input signal is weak, the gain can be boosted to maintain maximum power output while
C Series Operation Manual 7
avoiding a poor signal-to-noise ratio. This gain adjust
­ment feature makes it easier to achieve an optimal balance between headroom and noise floor.
4.2.3 Voltage Peak Limiting
The Voltage Peak Limiting (VPL) feature allows user adjustments that determine maximum voltage output, thus matching the amplifier to the connected speaker load. Whether the connected load is low impedance (8, 4 or 2 ohms) or high impedance (70 V / 100 V), the VPL feature can be set to ensure that neither temperature nor current limitations are exceeded before reaching the desired voltage threshold.
4.2.4 Protection and performance
optimization
Appropriate and reliable power amplification is vital to any audio system. Inadequate or faulty power amplification could cause damage to the loudspeakers, or in some cases to the power amplifiers themselves. To prevent any damage or costly service interrup­tions, C Series amplifiers offer advanced features to protect both internal circuits and any connected loads. These features even protect the mains fuse that, in extreme cases, could be overloaded.
Following are short descriptions of standard built-in C Series protection features:
CPL, Current Peak Limiter ensures that the
amplifier’s output does not exceed the safe current handling parameters of amplifier components.
Temperature protection ensures that the
amplifier will not be damaged by exceeding thermal limits.
PAL, Power Average Limiter limits the maximum
average power consumption according to the power supply and mains-breaker capabilities.
VHF, Very High Frequency protection circuits
mute the output of the amplifier when non­dynamic continuous signals above 10 kHz are detected.
DC protection ensures destructive DC signals
will not appear at the amplifier outputs. If such conditions occur an internal fuse opens and fault indication is displayed.
Low impedance (short circuit) protection
provides a fault warning indication and shuts down the output stage when, for example, an input signal is present and a malfunctioning cable or driver is short circuiting the output.
High impedance warning reports an alert when
at the same time output signal is high, simultane­ously, and no current draw is measured. This situation might occur when no speakers are connected, or when a driver is blown.
Low inrush current ensures that the mains
breaker will not trip when several power amplifiers are turned on simultaneously.
4.2.5 NomadLink / Ethernet control and monitoring network
The NomadLink network allows easy setup and control of C Series power amplifiers and other devices. The patented network topology allows automatic detection and addressing of multiple amplifiers, and is controlled from a PC via a bridge (NLB 60E) using standard TCP/IP communication. Phantom powering through the network cables allows the software to detect devices that are not currently turned on or connected to the mains. This ensures very high reliability and redundancy levels while allowing connected amplifiers to remain on standby with no power consumption.
Cable connections can be daisy-chained for easier system setup. This also reduces total component costs, simplifies installation, and makes daily operation more convenient. There is no need to create a star topology using many switches as with, for example, an Ethernet system. Individual amplifier addresses do not need to be manually entered. You will automatically know where an individual amplifier resides in the network.
A daisy chain network-loop, in combination with the automatic addressing of devices, enables Lab.gruppen’s proprietary DeviceControl editor software to automatically create a precise picture of all connected devices and their relative position in the chain. This is the key to creating a quick overview of the system layout, allowing simple operation of a large group of amplifiers. Installation time is kept to a minimum, and fast access is provided to monitor performance and solve problems during operation.
Via NomadLink, you can monitor all metering data as well as all faults and warning indications simulta­neously. NomadLink also allows you to remotely control power on and power off, as well as engage Mute and Solo functions on individual channels.
WELCOME 4
5.1 Unpacking
Carefully open the shipping carton and check for any noticeable damage. Every Lab.gruppen amplifier is tested and inspected before leaving the factory and should arrive in perfect condition. If any damage is discovered, please notify the shipping company immediately. Only the consignee may institute a claim with the carrier for damage incurred during shipping. Save the carton and packing materials for the carrier’s inspection. Should you ever need to ship the amplifier, always use the original packaging materials.
5.2 Mounting
The amplifier is two rack units high (2U) and will fit into a standard EIA 19” rack. The depth is 343 mm (13.5”). The weight is approximately 12 kg (26.4 lbs.) depen­ding on model type.
Free airflow from front to rear of the amplifier must be possible. Therefore, no doors or rack-lids should be mounted in front of or behind the amplifiers.
Amplifiers may be stacked directly on top of each other. There is no need for spacing in between units, though this might enable more convenient installation of cabling on the rear-panel.
It is recommended that rear supports be mounted for maximum long-term stability.
5.3 Cooling
The amplifier uses a forced-air cooling system with air flow from front to rear, maintaining a low operating temperature within defined limits. Front-to­rear airflow is preferred as cooler air is present at the front in nearly all installed applications. (This allows higher continuous power levels without encountering thermal problems.) Never attempt to reverse the airflow. The amplifier modules require a pressure chamber between the fans and heatsink, and this effect functions only in one direction.
Make sure that there is an adequate air supply in front of the amplifier, and that the rear of the amplifier has sufficient space to allow the exhaust to escape. If the amplifier is rack-mounted, do not use covers or doors on the front or rear of the rack.
Should a heat sink overheat, the temperature sensing circuits will mute the overheating channel. If the power supply overheats, another sensing circuit will mute all output channels until the power supply cools to safe operating temperature. An early warning before shut down will be indicated on the front panel LEDs, and a warning will be sent through the NomadLink network.
Always make sure that the dust-filters behind the detachable front panel are clean to ensure maximum possible airflow.
If the amplifier malfunctions due to dirty dust filters, any required repairs are not covered by the warranty.
To calculate the maximum heat emission value, when installing the amplifiers in rooms with an air-conditio­ning system, please refer to the BTU specifications provided in the Appendix section.
5.4 Operating voltage
The label placed to the right of the mains
cable on the rear of the amplifier indicates the AC mains voltage for which the amplifier is wired and approved: 115 V or 230 V. Connect the power cable only to the AC source type referred to on the label. The warranty will not cover damage caused by connecting to an incorrect type of AC mains.
Lab.gruppen switch mode amplifiers use primary switching. Because the mains power is rectified directly in front of the transformer, the amplifier is insensitive to mains frequency. It may be connected to 50 or 60Hz sources, and actually will operate on line frequencies from DC to 400 Hz.
If the power plug mounted at the factory is not appropriate for your country, it can be removed and the proper connector wired in its place as follows.
BLACK or BROWN LIVE WHITE or BLUE NEUTRAL
GREEN or GREEN/ YELLOW EARTH(GROUND)
Warning: If you are not 100% confident of your competence to replace the mains plug, engage qualified personnel to do the job.
Once a suitable AC supply is connected, the
5 INsTALLATION
C Series Operation Manual 9
amplifier can be turned on using the front panel power switch. The amplifier then goes through a soft-start sequence as it self-checks its circuits. The fans will blow at high speed before dropping to idle, and the “power” LED will illuminate.
Inrush power is controlled and limited during “soft start”, enabling multiple amplifiers to be powered up simultaneously.
5.5 Grounding
There is no ground lift switch or terminal on the C Series amplifiers. The signal ground is always floating, via a resistor, to chassis and therefore the grounding system is automatic.
In the interests of safety, never disconnect the earth (ground) pin on the AC power cord.
Use balanced input connections to avoid hum and interference.
INsTALL ATION 5
6 QUICK GUIDE OVERVIEW
The amplifier’s front panel presents the performance and fault condition indicators, power and remote switches ,and a removable dust-filter cover. Four level potentiometers located behind the cover provide individual attenuation for the four amplifier channels. Range is 0 dB to - infinity. The 12 o’clock position indicates -10 dB attenuation.
To remove the dust-filter cover, loosen the thumbscrew at the far left. This allows removal of the dust filters for cleaning, and provides access to channel attenuation. The front cover may be made “tamper resistant” by replacing the thumbscrew with Philips head or safety Torx screw. Thread size is M3.
6.1.1 Power on/off and remote switch
The Power on/off switch is located on the right side. A second switch, labeled “REMOTE,” is above the Power switch. When the Remote switch is on, the yellow LED above it will illuminate indicating that external power on/off commands from the NomadLink network connection will switch the amplifier on or off. When Remote is activated the amplifier will not switch on until a “Power On” command is received from the network. When the remote switch is off, it is not possible to switch amplifier power on or off using NomadLink network control.
6.1.2 Front panel LED’s
The front panel LED area includes the following indicators per channel:
Temperatur e warning ( Yellow flashing ) Temperatur e mute (Yellow co nstant) Very Hig h Frequency protection a ctive (outpu t muted) (Yell ow) Mute channel via Nom adLink net work (2x Yellow ) Current P eak Limiter ( CPL) act ive (Orang e flashin g), CPL con stant (outp ut muted): Lo impedance / Shor t circuit dete ction Fault ( Yellow plus Ora nge) Voltage Peak Limiter ( VPL) active, VPL/Clip (Red)
-4 dB s ignal level ( Green)
-10 dB signal l evel (Green)
-4 0 dB signal le vel (Green), Hi- Imp open lo ad detected ( Red)
Bridge mode o peration on (Yellow). Ch. A+B or C+D bridged.
When no VPL, CPL or PAL indicators are illuminated, the amplifier channel is able to deliver maximum rated output power.
Common LED’s on the front panel:
Power on (Green)
Power Average Limiter active (PAL) (Red)
Option active (Yellow)
NomadLink network active (Blue).
When the network is connected, the blue NomadLink LED will illuminate even when mains power is not connected. NomadLink receives phantom power from the network supplied by the NLB 60E.
PAL
6.1 Front Panel overview
C Series Operation Manual 11
QUICK GUIDE OVERVIEW 6
44dB 41dB 38dB 35dB 32dB 29dB 26dB 23dB
141V* 118V 100V** 85V
71V 59V 50V 42V
*100V
rms
**70V
rms
Ser. N:o
Removed!
SPEAKER OUTPUTS
BALANCED INPUTS
CHD
CHBCHC
CHA
WIRING NORMAL: CLASS 2 BRIDGED: CLASS 3
PUSH PUSH
Must be grounded
Made in Sweden
200-240VAC 50-60Hz :2300W
.
6.2.1 The DIP switch features
The following features may be adjusted using the DIP switches on the rear-panel of the amplifier.
Gain - Set for all four channels from +23 dB to +44 dB in 3 dB steps.
Option active - Available for future upgrades.
Fan Masked - When on, engages the intelligent
fan feature lowers fan speed when no signal is present.
Bridged A+B and C+D- Switches the channel pairs into bridged mode operation (automatic - 6 dB gain compensation).
VPL - Voltage Peak Limiter adjustment is provided for 8 individual levels. Select the setting most appropriate for connected speakers. See Appendix for details.
Mode - Select VPL mode between Hard and Soft. For channels driving sub-woofers and Lo-end frequen­cies, it is recommended to use the Hard setting for optimal operation. For mid and hi-end drivers, always select Soft.
Mains input 115V or 230V operation (Not selectable)
NomadLink network In and Out on EtherCon housed
RJ45 connections
DIP switches for adjusting key features
(See below)
3-pole Phoenix
input connectors
2-pole screw terminal output connections
6.2 Rear Panel overview
6 QUICK GUIDE OVERVIEW
6.3 NomadLink / Ethernet network setup
The amplifier includes, as a standard feature, internal facilities for the NomadLink monitoring and control network. All features of the NomadLink network are accessible via a PC running Lab.gruppen’s proprietary DeviceControl software. A single rackspace network bridge, the NLB 60E, accepts the TCP/IP data stream from the computer and converts it to the NomadLink protocols. Even when no computer is connected, the NLB 60E can initiate stand-alone power on/off and muting functions, as well as report any fault or warning conditions.
The PC is connected to the NLB 60E using a standard Ethernet interface and a crossed Cat5 cable (peer-to-peer setup). If a HUB or switch is in the network, standard “straight” Cat5 cables must be used. The front and rear Ethernet connections on the NLB 60E can be used individually, but only one PC at a time running DeviceControl can access the subnet.
The default fixed TCP/IP address of the NLB 60E is
192.168.1.166. The subnet mask is 255.255.255.0. For further details, please refer to instructions sup­plied with the NLB 60E unit.
The NomadLink connections use standard “straight” Cat5/RJ45 equipped cables. For a safer mechanical connection it is possible to use Neutrik EtherCon “XLR-type” housings on the cables.
US National Differences cl.16.3 requires that NomadLink network cables must be rated VW-1.
The OUT port from the NLB 60E must be connected to the IN port of the first amplifier. The OUT port from the first amplifier in turn connects to the next amplifier’s IN port to form a daisy chain The OUT port on the last amplifier is connected to the IN port on the NLB 60E to close the loop.
There are electrical limitations to cable lengths on a NomadLink network, both in terms of total cable length in the loop and between any two devices. Read the
Operation and Performance chapter in this manual, or the instructions supplied with the NLB 60E, to ensure the network is configured within these constraints.
Although the network will function as an open loop under most circumstances, it is strongly recommended that the loop be closed by connecting to the NLB 60E’s IN
por t. Doing so will improve redundancy and communication speed.
External contact closures and 24 V low/high triggers can be connected to GPI connectors on the NLB 60E for control of fire-alarm systems or external power sequencers. For more details read the instructions supplied with the NLB 60E.
IN OUT
NOMADLINK
IN OUT
NOMADLINK
NOMADLINK
IN OUT
ETHERNET
GENERAL PURPOSE
INPUT, GPI
ETHERNET
Crossed RJ45 Ethernet cable between bridge and PC. If bridge is connected to switch of HUB, use " straight " cable. PC can also be connected on front-panel.
" Straight " RJ45 cables between bridge and amplifiers.
C Series Operation Manual 13
7.1 Introduction
The following sections provide comprehensive infor­mation on amplifier connection, setup, operation, and performance. The detailed information included here is essential to realizing the full functionality of the C Series amplifiers.
7.2 Operation precautions
Make sure that the Power switch and the Remote
switch on the amplifier front panel are set to “off” before making any input, output or network connections, and also before manipulating the DIP switches on the rear-panel.
Make sure that the AC mains voltage is correct
and matches the voltage printed on the rear panel of the amplifier (115 V or 230 V).
Make sure that no signal is present at the input
to the amplifier when powering up. This will produce an unintentionally loud initial volume from the speakers.
7.3 Signal flow and headroom
7.3.1 Signal flow blocks
All C Series amplifiers have the same signal flow and feature set. The only difference is the amplifier’s maximum output current per channel.
The input stage of all C Series amplifiers has a high sensitivity to provide ample system headroom. This in effect means that the input stage is almost impos­sible to clip.
Hard/Sof
t switch
Gain select switches
Front panel
potentiometer
Dynamic
Ga
in red
uction
VP
L sele
ct switches
Class TD
Vo
ltageClip sensing
Current
cli
p s
ensin
g
MonitoringLeve
l
Temperature
Fault/Warning
Co
ntro
l Mu
te
Input Amplifier
Level control
Cl
ip Limiter Vo
ltage Pe
ak Limiter Output Power Amplifier
Overall amplifier input gain is adjusted using the input stage DIP switches. Please note that the gain setting is global, affecting all four channels. Following the input stage, the dedicated level control on each channel allows signal attenuation from 0 dB to minus infinity.
The Current Peak Limiter (CPL) section dynamically limits the input signal based on three parameters: sensed current level, feedback from the output stage, and sensed voltage clip from the VPL (and output amplifier voltage clip if “Soft Clip” activated). This ensures that power output is maintained within the design limits of the amplifier.
The adjustable Voltage Peak Limiter (VPL) sets the maximum output voltage and therefore also the maximum output power. Eight (8) different voltage stages are available using the DIP switches on the rear-panel. See table in Appendix section with VPL ratings at typical loads.
The sophisticated output section monitors faults and generates appropriate warnings, which are displayed on the amplifier front panel and transmitted through the NomadLink network. These alerts allow the operator to adjust system settings and thereby avoid problems. In the rare event that conditions are extraordinarily severe, the amplifier will shut down until the fault or problem setting has been rectified or adjusted. These sensing circuits are also employed to feed back voltage and current level information, via a side chain, to the limiters. Sensing circuits also transmit local amplifier module temperature and power supply temperature to the appropriate protection mechanisms. Read the Protection, Faults and Warnings section for further details.
7 OPERATION AND PERFORMANCE
C Series Operation Manual 15
The headroom available through the input stage to the clip limiter is shown by the dotted lines as +10 dB at 141 Vpeak and +20.4 dB at 42 Vpeak. These lines illustrate the additional signal level that can be accepted at the input before any significant distortion will appear at the input stage.
If you use the level potentiometer in the signal chain to reduce the level by an amount greater than the headroom relative to input sensitivity, AND you drive the amplifier to
clip level, you are in danger of clipping the input stage before the current or voltage peak limiters are activated.
When bridging two channels, you must ad +6 dB to the input sensitivity to achieve maximum output voltage due to the automatic -6 dB gain compensation
inserted by the amplifier.
7.3.2 Headroom, sensitivity and VPL / Gain settings
The input amplifier and limiter system is designed to accommodate extremes of performance. Typically, exceeding maximum input by much as +10 dB will only result in a 1% increase in distortion. The following schematics illustrate how the adjusable VPL and Gain circuitry affect input sensitivity and output power:
The tables to the left of the drawing below, show input sensitivity for C 68:4 with an 8 ohm load and 141 Vpeak (max.) and 42 Vpeak (min.) respectively for the eightdifferent gain stages between +23 dB and +44 dB. The resulting output power is displayed in dBu, Vrms and Watt in the tables to the far right. Complete input sensitivity tables for all VPL and Gain settings for all C Series models, can be found at www.labgruppen.com.
The headroom available through the input stage to the clip limiter is shown by the dotted lines as +10 dB at 141 Vpeak and +20.4 dB at 42 Vpeak. These lines illustrate the additional signal level that can be accepted at the input before any significant distortion will appear at the input stage.
Gainset to:
(DIP-switches)
+ 44
dB
+ 41
dB
+ 38
dB
+ 35
dB
+ 32
dB
+ 29
dB
+ 26
dB
+ 23
dB
Voltage Peak Limiter set to:
(DIP-switches)
141 V
peak
11
8 V
peak
100 V
peak
85 V
peak
71 V
peak
59 V
peak
50 V
peak
42
V
peak
Input
sensitiv
ity
dBu / V
rms
-2,0 /
0,6 1,0 / 0,9 4,0 / 1,2 7,0 / 1,7 10,0 / 2,5 13,0 / 3,5 16,0 / 4,9 19,0 / 6,9
Gain
set to:
(DIP-
switches)
+ 44dB + 41 d
B + 38dB + 35dB + 32
d
B + 29 d
B + 26dB + 23dB
Input
sensi
tivity
dBu / V
rms
-12,3 / 0,2
-9,3 /
0,3
-6,
3 /
0,4
-3,3 /
0,5
-0,3 /
0,7 2,7 / 1,1 5,7 / 1,5 8,7 / 2,1
V
PL s
e
t to 42
V
pe
ak
VPL set to 141 V
peak
*)Headro
m limited to +8d
B at Gain set
to +23 dB at Ma
x. VPL
Complete tables for all VPL settings can be
found at:
www.labgruppen.com
Hard/Soft switch
Gain
se
lectswit
ches
Front panel
pote
ntiomete
r
Dy
namic
Ga
in red
uction
VPL se
lect
switches
Class T
D
VoltageCli
p sens
ing
Curren
t c
lipsensing
Monito
ring
Level
Temperature
Fault/Warning
Control Mu
te
Input Amplifier
Level control
Clip Limiter Voltage Peak Limiter Output Power Amplifier
Output
power
dBu / V
rms
42,2 / 100
40,7 / 84 3
9,2 / 71
3
7,8 / 60 36,2 / 50 34,7 / 42 3
3,1 / 35
31,
8 / 30
Output
power
Watt
1200 W
880 W 6
30 W 440 W 310 W 220 W 1
60 W
110 W
+10 dB headr
oom to clip,
relati
ve
to input sensitivity
*)
+20,4 dB headroom to cl
ip,
relative to input sensitivity *)
OPERATION AND PERFORMANCE 7
7.4 Audio Input and Output con­nections, setup and features
7.4.1 Balanced / Unbalanced Input connection
Two electronically balanced Phoenix-type inputs are available. Follow the +,– and Ground labels when connecting the input signal.
If an unbalanced connection is desired this can be achieved by summing the minus (“COLD”) and Ground terminals and using the + terminal as the “HOT” signal. For the best possible performance, the summing of ground and minus wires should be done at the source unit end of the cable (e.g. a CD player).
Four connectors are supplied for attaching cables to the inputs. The type of connector used is: Phoenix Contacts, Part number MSTB 2,5/3-STZ-5,08
When linking the same source signal to several input channels, be aware that there is a limit to the number of channels an
output source can “drive”. A typical output source (e.g. a DSP crossover unit) can drive up to 4 amplifier channels before line-drivers would be required to buffer the signal.
7.4.2 Output operation and connection
Screw-terminal connectors with + and – poles are provided at each channel output for connection of the speakers.
Make sure that the speaker cables are connected correctly and tightly, and that accurate polarity is maintained to all speakers in the system.
As the amplifier outputs produce high voltage,
do not connect or disconnect speaker cables when the mains power is on. Also, attach the safety cover on the speaker terminals for safe operation and to comply with electrical product approvals.
7.4.3 Output bridge mode
It is possible to bridge channels in pairs of two (A+B and C+D for example). When bridged, the input source must be connected to input A (A+B) or C (C+D) respectively. Output speaker cables must be connected to the plus pole on channel A or C and the minus pole on B or D.
The main benefit of bridging the output is a doubling of output voltage. Bridging can be used to turn the amplifier into a 3 channel amplifier with, for example, 2x1200 W and 1x2400 W at 4 ohms utilizing the C 48:4, or simply to achieve an impressive 200 Vrms supply per channel.
Most power amplifier designs, when bridged, automatically introduce a +6 dB input gain boost which can lead the user to conclude that said amplifier delivers “more than double the power” when in bridge mode. This is clearly not the case, as the gain boost artificially enhances perceived power at the costof headroom. The C Series amplifiers work on globally set constant gain, and automatically compensate the input gain by -6 dB. For example, if the amplifier is configured in a three channel mode, then the selected gain is maintained from input to output on all channels.
7 OPERATION AND PERFORMANCE
C Series Operation Manual 17
7.4.4 Amplifier Gain
All C Series amplifiers feature adjustable input gain. This versatility enables the amplifier to accommodate a multitude of system configurations with various input sources and speaker layouts.
Amplifier gain is set globally for all four channels. The range is +23 dB to +44 dB in 3 dB steps. Individual channel fine level adjustment is available using the potentiometers on the front panel.
The unique adjustable input gain feature of the C Series makes it easier to attain the optimum balance between headroom and signal-to-noise ratio in the signal path. A weak signal at the input might require the gain to be raised in order to achieve maximum output power with the lowest signal-to-noise ratio. A “hot” input signal, however, would require a lowering of the gain to avoid sending the amplifier into Voltage or Current clipping.
See Appendix to review the table containing Gain versus VPL setting implications for input sensitivity and output power.
Bridge mode operation automatically compensates by -6 dB, keeping all channels at the same gain.
7.4.4.1 Channel gain/Level (front panel pots)
Individual channel gain (level) may be adjusted using the potentiometers located on the front panel behind the dust-filter cover. Range is from 0 dB to -Infinity in 21 steps. The attenuation is logarithmic, with the 12 o’clock position indicating -10 dB.
Use your fingers or a screwdriver to adjust the potentiometers.
If the level control is used to attenuate to a lower level than the headroom relative to input sensitivity AND the amplifier input is
driven into clip, there is a danger of clipping the input stage before the current or voltage peak limiters are activated.
7.4.4.2 Amplifier sensitivity
Sensitivity is defined as how many Volts (rms) or dBu (referred to 0.775 Vrms) are required to achieve full (maximum) output power. As the output power varies with the load impedance, 4 ohms is usually
the common reference.
Since C Series amplifiers are capable of providing multiple maximum output power levels through use of the VPL feature, many sensitivity calculations may be required for a single amplifier. We recom­mend use of the DeviceControl editor to simplify this process. DeviceControl’s device view page, used in combination with the DIP switch settings display, will automatically produce a sensitivity calculation from the given data (VPL, Gain and load).
7.4.5 Output Voltage Peak Limiter (VPL)
Voltage Peak Limiter (VPL) is a unique feature in C Series amplifiers. It is used to select the maximum power available on each output channel. Eight levels can be set using the DIP switches on the amplifier’s rear panel.
V
peak
V
rms
141 100 118 84 100 70
85 60 71 50 59 42 50 35 42 30
The values for VPL are displayed as maximum Voltage Peak. To translate Voltage Peak into V
rms
, you must
divide the Voltage Peak values by 1.41 (see table).
The VPL allows you to set the correct maximum output peak power for optimum performance with the connected speakers. The correct setting depends on the system type (lo-or hi-impedance) and the specific load connected to the channel. Since each channel can be configured to deliver either very high voltage peak power OR high current draw at low impedances, it is important to set the VPL correctly.
To configure an individual output channel for a constant voltage system, you simply adjust the DIP switches to the desired voltage. However, when using an output for a low impedance system (2, 4, 8 or 16 ohms), then sometimes you need to adjust the VPL to a lower setting to avoid either delivering excessively high continuous power to the
OPERATION AND PERFORMANCE 7
speaker or overheating of the output channel through high current draw. For example, with a very “hot” conti-nuous output signal, the temperature could rise to a critical level and activate Temp warning or even Temp Mute. Lowering the VPL setting normally will solve this situation.
If the Current Peak Limiter is active or indicates low impedance, lowering the VPL setting can rectify this situation as well.
7.4.6 Constant Voltage 70 V and 100 V systems
setup and operation
When using C Series amplifiers to drive constant voltage (hi-impedance) speaker systems at 70 V
rms
or 100 V
rms
, you can in most cases simply connect the speakers to the amplifier output terminals, select the correct VPL setting, and place the amplifier in service.
7.4.7 Output Current Peak Limiter (CPL)
The Current Peak Limiter (CPL) ensures that the amplifier will not be damaged by trying to deliver more current to the outputs than that physically possible for the transistors. The CPL keeps the amplifier within the Safe Operating Area. The CPL is non-adjustable and has different limit values depending on model type. The maximum output current values for the four C Series models are:
C 68:4, 24,5 A
rms
per channel
C 48:4, 17,5 A
rms
per channel
C 28:4, 12 A
rms
per channel
C 16:4, 8,5 A
rms
per channel
CPL activity is indicated by illumination of an orange LED for each channel on the front panel. Warnings also are shown in the DeviceControl software’s GUI.
A steadily illuminated orange CPL LED indicates a short circuit situation (or very low impedance). The output will mute for 6 seconds before measuring the output impedance again. This will continue until the short circuit is fixed, at which time the output will automatically un-mute. An input signal must be present to allow detection of short circuit or low impedance conditions.
If the CPL LED is steadily illuminated orange
while the output is muted and the -4 dB signal LED is NOT on, then the amplifier output is detecting a short circuit or low impedance condition. The problem can be solved by checking input and output cables and examining the state of the loudspeaker load. If there is no short circuit present, then the condition may be rectified by lowering the VPL or input lev­els.
If the CPL and -4 dB indicators are lit simultaneously, then the amplifier is delivering too high a current and is being forced into a current limiting state (output muted).
7.5 Protection, faults and warnings
7.5.1 Introduction
The C Series amplifiers incorporate a sophisticated and comprehensive set of protection features. Faults and warnings are indicated on the front panel and reported via the NomadLink network for indication on the DeviceControl GUI.
7.5.2 Safe Operating Area Detector (SOAD)
The Safe Operating Area Detector (SOAD) compares output voltage against output current to ensure that the output transistors are working inside their safe operating area.
The SOA detector provides fault monitoring and input to the Current Peak Limiter (CPL). The SOA detector has no dedicated indicator, and its operation is revealed only in conjunction with features such as the CPL.
7.5.3 Very High Frequency protection
All C Series amplifiers include protection circuits that detect continuous Very High Frequency content in the input signal. The detection begins at approximately 10 kHz and moves upwards to include ultrasonic signals If VHF signals are detected, the output will mute for 6 seconds before re-measuring. Once no continuing VHF signal is detected, the output un-mutes and returns to normal operation.
This feature recognizes that continuous full-scale VHF
7 OPERATION AND PERFORMANCE
C Series Operation Manual 19
signals do not appear in “natural” sources such as music. Any such signals can therefore be considered as a fault when present. VHF protection is essential in avoiding damage to high frequency drivers.
The VHF protection operational area is dependent on output power level and frequency. The illustration below shows a decreasing threshold on the output power level, starting at approximately 10 kHz and rising with a -6 dB slope. This defines the VHF protec­tion area. When continuous output power above the threshold line is detected the VHF protection becomes active.
20 Hz 10 kHz 20 kHz
30 kHz
- 6 dB slope
VHF protection
operation area
Max. Peak output power
Max. Continous output power
power
Attack time
VHF protection
Slow
Fast
20 Hz 10 kHz 20 kHz
30 kHz
The Attack time for the VHF protection is increa­singly shorter at higher frequencies. For example, an ultrasonic continuous signal will cause the outputs to mute rapidly, where it will take several milliseconds for a 10 kHz continuous signal to trigger the output mute. This is shown in the illustration above.
The VHF protection is NOT a limiter and does not alter the amplifier’s frequency response. It is imple­mented solely to detect continuous VHF content. The amplifier will always pass VHF peaks at full power, with no effect on musical “transients”.
The VHF protection is indicated by a yellow LED on the amplifier front panel, with output muting for 6 seconds when in action. It is reported as a fault via the NomadLink network on the DeviceControl GUI.
If you bench test the amplifier using a continuous, full scale sine-wave input above 10 kHz, the VHF protection will activate and
prevent measurement of full peak output power. (Output will be muted long before maximum output power is attained.) To measure the true peak output power, use a burst signal.
7.5.4 DC protection
DC protection is implemented on each output to prevent damage to connected loudspeakers. DC present at the output will trigger muting and illuminate the fault LED indicator. Any DC present at the output indicates a hardware malfunction that requires servicing of the amplifier.
7.5.5 Hi impedance warning (open load)
A high impedance (open load) condition is indicated when an input signal above approximately -29dB is detected and no functioning loudspeakers are connected to the amplifier. The fault in indicated by a red Sig/Hi-imp LED. The indicator is green when a valid load is present under the same input signal conditions
Since the Hi-impedance detection initially triggers only when the input signal rises above -29dB, it might cause the indicator to first turn green, and then red,
even in situations where no speaker is connected.
7.5.6 Lo-impedance protection (short circuit)
A lo-impedance or short circuit fault is detected when current draw is high (Current Peak Limiter active) and when, simultaneously, output signal is low (-4 dB LED does not illuminate). When this occurs, the amplifier protects the output stage from damage by muting the output signal and bypassing the circuits. Indication of this fault is a constant orange illumination of the Current Peak Limiter (CPL) LED on the front panel. The protection will sequence at 6 second intervals to re-measure conditions. If the low-impedance fault is no longer detected, the amplifier will un-mute.
If the CPL turns constant orange, the output
is muted, and the -4dB signal LED is ON, then the amplifier has gone into maximum current protection. This situation is caused
by an excessive input signal and is not due to a short circuit. Turn down the input signal to avoid or remedy this situation.
OPERATION AND PERFORMANCE 7
7.5.7 Temperature protection
Thermal measurement points are provided on each output channel as well as on the power supply. These indicators will, if the pre-specified temperature level is exceeded, give a high temperature warning. This warning condition is indicated by a flashing Temp LED on the front panel, and it is reported on the Device Control GUI via the NomadLink network.
As the amplifier approaches a thermal protection threshold, the warning LED sequence will start with short “on-time” bursts. If the amplifier continues to overheat and approaches the temperature limit, the flashing sequence will be defined by longer and longer on-time bursts until the protection mode is activated.
If the temperature becomes too high to continue safe operation, the overheated output channel(s) will be muted until the temperature returns to an acceptable level.
Fully active temperature protection (with muting) is indicated by a constantly illuminated Temp LED. It will also be indicated as a fault via the NomadLink network on the DeviceControl GUI.
Temperature measurements will continue at 6 second intervals. The output will un-mute when the channel or power supply returns to a safe operating temperature.
7.5.8 Power Average Limiter (PAL)
The Power Average Limiter (PAL) controls the current-drawing relationship between the power supply and the mains inlet. PAL limits the maximum average power consumption according to the power supply capabilities, ensuring that the PSU will not overload. In addition, in the larger models that potentially could pull more current from the mains than the mains-fuses are specified to handle (more than 16 A), PAL limits the amplifier’s maximum current draw to prevent blowing the mains fuse.
7.5.9 Soft Start
High powered amplifiers with inadequate inrush limiting can pull considerable current from the mains at turn-on. This can result in fast acting mains breakers tripping. Such is not the case with C Series amplifiers. The C Series amplifiers have very low inrush power as the capacitors are charged slowly
and in a controlled manner ensuring that breakers will not trip.
Several amplifiers will, under normal conditions, be able to be powered up simultaneously. If you do experience problems powering up multiple amplifiers simultaneously, use the NomadLink network and the NLB60E to establish a power sequence with a pre set delay between each amplifier start-up.
7 OPERATION AND PERFORMANCE
C Series Operation Manual 21
7.6 Front panel monitoring and adjustments
7.6.1 Level indicators
Four signal/level/clip LEDs per channel are contained on the C Series front panels :
Orange CPL (Current Peak Limiter) flashing indicates signal exceeds max. output current. Red VPL/CLIP indicates that the signal has exceeded maximum output voltage. This activity is governed by the rear panel VPL settings. Green - 4 dB indicates output signal has reached this level. Green - 10 dB indicates output signal has reached this level. Signal / Hi-Imp (Green/red) indicates an output signalabove -44 dB. If it turns RED, this indicates that a high impedance (“open” connection) has been detected at the output. This can be a fault such as a disconnected cable or the driver is not functioning properly. However, it could indicate acceptable high impedance, such as a sub-bass enclosure with high impedance at a certain frequency. When the -10 dB signal LED is on AND the Hi-Imp. LED turns red, then the amplifier has detected an open load no speaker is connected).
For more detailed signal level indications use the DeviceControl editor application.
1.
2.
3.
4.
5.
8.6.2 Level adjust
Step Attenuation
1 (Min) - Inf. dB
2 -Inf. dB 3 -50 dB 4 - 40 dB 5 -35 dB 6 -21.5 dB 7 -21.5 dB 8 -14.7 dB
9 -12.9 dB 10 -11.4 dB 11 -10.0 dB 12 -8.7 dB 13 -7.4 dB 14 -6.0 dB 15 -4.5 dB 16 -2.7 dB 17 -0.6 dB 18 -0.3 dB 19 - 0.1 dB 20 0 dB
21 (Max) 0 dB
Level adjust potentiometers (one per channel) are located behind the removable dust filter cover on the amplifier’s front panel. With the dust cover in place it is not possible to adjust the level settings.
The potentiometer’s operational range is 0 dB to
-Infinity in 21 steps. Attenuation is logarithmic, with 12 o’clock position being -10 dB. See table to the right with increments.
It is not possible to adjust the individual channel attenuation from the NomadLink network or elsewhere on the amplifier.
Use fingers or a screwdriver to adjust the potenti­ometers.
7.6.3 Mute indication
Individual channel Mute is indicated by illumination of the two yellow LEDs at the top of the channel’s LED bargraph. Mute/Un-mute can only be performed from the network using either the NLB 60E and/or the DeviceControl PC editor.
OPERATION AND PERFORMANCE 7
7.6.4 Performance, Warning and Fault indicators
Power on/off (green) indicates that mains power
is switched on.
NomadLink (blue) indicates that the network
is connected. The NomadLink LED will light up even before the mains power is connected and switched on as it takes phantom power from the network cable.
Bridge mode (yellow) indicates if two chan-
nels are bridged using the DIP switch on the rear-panel.
CPL, Current Peak Limiter (orange), when flashing
indicates the maximum possible current draw has been reached.
CPL, Current Peak Limiter (orange), when constant
indicates excessive current draw caused by a short circuit on the output or very low operational impedance. When detected, the output will mute for 6 seconds before re-measuring the output impedance. This will continue until the short circuit is removed. CPL remains constant orange in a fault condition only when an input signal is present.
Temperature (yellow) warning is indicated by a
flashing LED. If the amplifier goes into thermal protect (output muted) the LED illuminates constant yellow.
VHF, Very High Frequency protection (yellow),
indicates that potentially harmful continuous high frequencies have been detected on the input signal. The output is muted.
PAL, Power Average Limiter (red), indicates
that the amplifier is limiting because the power supply and/or the mains-inlet fuse has reached maximum capability.
Hardware fault is indicated when both the CPL
and VHF indicators light up simultaneously. The amplifier requires servicing before placing back in operation.
7 OPERATION AND PERFORMANCE
C Series Operation Manual 23
7.7 NomadLink network and PC editor
7.7.1 NomadLink network in the amplifiers
All C Series amplifiers are equipped with the pro­prietary NomadLink network interface. This includes two EtherCon housed RJ45 connections: one IN and one OUT.
Use standard straight Cat5 Ethernet cables with RJ45 connectors to connect the amplifier to the NLB 60E network bridge or to daisy-chain multiple amplifiers.
It is very important that two IN or two OUT
ports are NEVER connected to each other. This will cause the NomadLink communi-
cation and DeviceControl editor to exhibit erratic behavior and display inaccurate data. However, this situation will not damage the amplifier circuitry.
Up to 60 amplifiers can be connected to one NLB 60E in a daisy-chain or closed loop.
When the NLB 60E bridge is powered up, the NomadLink network receives phantom power. This causes the blue NomadLink LED on the amplifier front panel and the NomadLink LED on the rear-panel to light up. NomadLink is active even when the amplifier has mains power disconnected or is not yet powered up.
The amplifier does not have a stand-by power supply for the network. The network is solely powered from the NLB 60E. Should an amplifier fail or be inadvertently disconnected from the mains,
OPERATION AND PERFORMANCE 7
network integrity is fully maintained and all amplifiers remain visible on the system.
7.7.2 Connection and setup
The NomadLink network requires use of a NLB 60E. The NomadLink network is established by connecting the NLB 60E OUT port to the first amplifier’s IN port. Then a daisy-chain is established by connecting the first amplifier’s OUT port to the next amplifier’s IN port, and so on. If a closed loop network is desired for improved redundancy (highly recommended), the last amplifier’s OUT port must be connected to the NLB 60E’s IN port.
For all connections, straight Cat5 RJ45-equipped Ethernet cables should be used.
Optimal NomadLink performance can only be assured when using Cat5 cables. However, as NomadLink is only using two
wires + ground for communication and phantom power it is possible to create converters from RJ45 to, for example, XLR connectors using 2-wire shielded cable. The NomadLink network can then be operated using a standard tie-line in a multicore signal distribution system. See the drawing opposite for an example of how to create a converter.
If any cable format or connection other than
Cat5 (or better) and RJ45 is utilized, network
performance may be compromised. In this
event Lab.gruppen cannot guarantee that the NomadLink network will be fully operational.
7 OPERATION AND PERFORMANCE
7.7.3 NomadLink network cable lengths
In situations where the amplifiers and the NLB 60E will be positioned in different locations at some distance from each other, or where groups of amplifiers within a single subnet with up to 60 units will be installed with a distance in between, these general rules may be considered:
Below are typical examples of NomadLink network setups:
<300m/980ft
Amp. #1
IN
OUT
Amp. #60
IN
OUT
Example #1a: Daisy chain, total cable length max. 400m/1300ft
E.g., all amplifiers in one location or close to each other; NLB 60E in a different location.
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<300m/980ft
Amp. #4
IN
OUT
Amp. #60
IN
OUT
Example #2a, Daisy chain, total cable length max. 400m/1300ft
E.g., one group of amplifiers joined by the NLB 60E; more amplifiers in remote locations.
Amp. #5
IN
OUT
Amp. #6
IN
OUT
Amp. #1
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
Amp. #60
IN
OUT
Amp. #1
IN
OUT
Example #2b, Dual daisy chain, total cable length max. 700m/2300ft
E.g., groups of amplifiers in separate locations without interconnection; NLB 60E in a different location. Desirable where certain groups of amplifiers can physically not be connected.
Amp. #3
IN
OUT
Amp. #2
IN
OUT
Amp. #1
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
Example #1b: Closed loop, total cable length max. 700m/2300ft
E.g., all amplifiers in one location or close to each other; NLB 60E in a different location. Closing the loop via "return" cable provides extra redundancy and safer operation.
NLB 60E
IN
OUT
<300m/980ft
Amp. #1
IN
OUT
Amp. #60
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
NLB 60E
IN
OUT
<300m/980ft
NLB 60E
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
Ethernet / Cat5
Ethernet / Cat5
Ethernet / Cat5
Ethernet / Cat5
NLB 60E
IN
OUT
<300m/980ft
<300m/980ft
<100m/328ft total cable length for links in between amplifiers.
<300m/980ft
Amp. #1
IN
OUT
Amp. #60
IN
OUT
Example #1a: Daisy chain, total cable length max. 400m/1300ft
E.g., all amplifiers in one location or close to each other; NLB 60E in a different location.
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<300m/980ft
Amp. #4
IN
OUT
Amp. #60
IN
OUT
Example #2a, Daisy chain, total cable length max. 400m/1300ft
E.g., one group of amplifiers joined by the NLB 60E; more amplifiers in remote locations.
Amp. #5
IN
OUT
Amp. #6
IN
OUT
Amp. #1
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
Amp. #60
IN
OUT
Amp. #1
IN
OUT
Example #2b, Dual daisy chain, total cable length max. 700m/2300ft
E.g., groups of amplifiers in separate locations without interconnection; NLB 60E in a different location. Desirable where certain groups of amplifiers can physically not be connected.
Amp. #3
IN
OUT
Amp. #2
IN
OUT
Amp. #1
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
Example #1b: Closed loop, total cable length max. 700m/2300ft
E.g., all amplifiers in one location or close to each other; NLB 60E in a different location. Closing the loop via "return" cable provides extra redundancy and safer operation.
NLB 60E
IN
OUT
<300m/980ft
Amp. #1
IN
OUT
Amp. #60
IN
OUT
Amp. #2
IN
OUT
Amp. #3
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
NLB 60E
IN
OUT
<300m/980ft
NLB 60E
IN
OUT
<100m/328ft total cable length for links in between amplifiers.
Ethernet / Cat5
Ethernet / Cat5
Ethernet / Cat5
Ethernet / Cat5
NLB 60E
IN
OUT
<300m/980ft
<300m/980ft
<100m/328ft total cable length for links in between amplifiers.
Rule 1:
The maximum cable length in between any two devices may not exceed 300 meters / 980 feet.
Rule 2:
In a non-closed-loop daisy-chained subnet the total maximum cable length is 400 meters / 1300 feet.
Rule 3:
In a closed-loop subnet the total maximum cable length is 700 meters / 2300 feet.
C Series Operation Manual 25
7.7.4 Ethernet network cable lengths
The connection between the NLB 60E and your PC is a standard Ethernet network running the TCP/IP protocol. Cable distances between NLB 60E and your PC follow standard rules for Ethernet systems.
Contact your IT expert for more details.
7.7.5 DeviceControl editor
The DeviceControl editor is Lab.gruppen’s proprietary software application for monitoring and controlling networked C Series power amplifiers. DeviceControl runs on a Windows PC, which connects via Ethernet to the NLB 60E network bridge. DeviceControl provides comprehensive monitoring of amplifier status as well as control of amplifier power on/off and individual channel mute and solo functions.
Please review the DeviceControl user manual for more detailed information.
OPERATION AND PERFORMANCE 7
8 APPENDIX
8.1 Maintenance
During normal operation your C Series amplifier will provide trouble-free service. The only user mainte­nance required is to periodically vacuum clean the foam dust filters behind the front grille.
In some extreme cases it may be necessary for authorized service personnel to clean the inside of the amplifier. These conditions usually occur after prolonged use in extreme environments such as those using “cracked oil” smoke machines. If you are using your amplifier in a heavy duty application, it is recommended to have your amplifier serviced every 3 years purely as a preventative action.
8.2 FAQ
Following are common questions asked about Lab.gruppen C Series power amplifiers together with helpful answers.
Q: What is the input sensitivity of the amplifiers? A: Input sensitivity is calculated from the amplifier
gain, maximum output voltage and load. As gain and output voltage is adjustable in C Series amplifiers, you need to look this information up in a table found in the Appendix section of this manual. Input sensitivity also is automatically calculated in the DeviceControl editor software application.
Q: What are the maximum cable lengths allowed when using the NomadLink network? A: NomadLink uses a daisy-chain topology to connect amplifiers and an NLB 60E bridge in a network. Standard RJ45-equipped Cat5 cables are used throughout. The daisy chain may be made into a closed-loop by connecting a return cable to the NLB 60E from the last amplifier.
General rules of cable lengths:
The maximum cable length in between any
two devices may not exceed 300 meters / 980 feet.
In a non-closed-loop daisy-chained subnet the
maximum cable length is 400 meters / 1300 feet.
In a closed-loop subnet the maximum cable
length is 700 meters / 2300 feet.
Exceeding these limits may result in lost contact with the devices, or loss of phantom powering due to cable resistance.
Q: How long can cable-runs be on the Ethernet network connecting the NLB 60E to the PC? A: On the Ethernet side, normal Ethernet cable limits apply. This is typically a maximum of 80 meters / 300 feet between each device. Follow standard installation procedures for Ethernet. Distances beyond100 meters may require use of a repeater, a format converter, or optical cables.
Q: Why is the NomadLink network a closed-loop topology? A: Technically speaking, the closed loop is optional. The purpose of closing the loop is primarily to provide a secondary path to the amplifiers. If cables are broken or disconnected in either direction, all amplifiers still may be addressed by the network.
Q: How can I be sure that no protection circuits or safety functions interfere with the output signal? A: If no Clip or Warning LEDs on the front panel light up, you can be fully confident that the rated maximum output power in the full frequency range is available for your speakers. No limiting or gain-reduction takes place without a warning or fault indication.
8.3 Bench test the amplifier
All Lab.gruppen amplifiers are highly advanced devices which incorporate various features (e.g. VHF protection and Power Average Limiter) that make it impossible to verify maximum performance when performing a standard bench-test with continuous, full-scale sine-wave signals.
We therefore highly recommend that you take the time to read our document: “Amplifier testing procedure”, found at www.labgruppen.com under Technical Notes, before you bench-test a Lab.gruppen amplifier.
C Series Operation Manual 27
8.4 Additional documentation
In case you didn’t find what you were looking for in this Operation Manual, check out the website at ww w.labgruppen.com, where you can find a multitude of additional documentation for C Series: Drawings, technical data sheets, tables with input sensitivity, background technology briefs and much more.
APPENDIX 8
8.5 BTU specifications
The following tables contain information on measured current consumption as well as calculated heat dissipation at three states: 1) Stand-by/idling; 2) Normal operation (1/8 of rated power); and 3) at extreme heavy duty operation (Max. power).
115VAC 230VAC In Out Dissipated BTU/hr kCal/hr
0 0 0 0 0
133 0 133 454 114
8 / Ch. 1200
x4
16 / Bridged 2400
x2
4 / Ch. 1700
x4
8 / Bridged 3400
x2
2 / Ch. 1200
x4
4 / Bridged 2400
x2
100V / Ch. 1600
x4
200V / Bridged 3200
x2
8 / Ch. 1200
x4
16 / Bridged 2400
x2
4 / Ch. 1700
x4
8 / Bridged 3400
x2
4 / Ch. 1200
x4
8 / Bridged 2400
x2
100V / Ch. 1600
x4
200V / Bridged 3200
x2
Mains connector, 230 V CE version Mains connector, 115 V ETL version
800
663
3402
19,4
997
1700
2697
2262
Amp (I) *2)
21,0
10,5
1463
32,6
2829
16,3
829
1600
2429
857
38,8
W
450
22,4
11,2
1578
850
728
713
*2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
*1) The amplifier's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and specified here is what is known as the "Active Power" in the amplifier providing useful, real-world values of power consumption and heat dissipation.
*3) Figures measured at maximum power before amplifier protection and limiter features kicks in. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will never occour during normal operation. Also note that the mains breaker will not be tripped even it's in excess of max. ratings.
20 A / 5-20P
C 68:4
Level
Load
Rated power
Line Current
Watt *1)
Thermal Dissipation
Standby w. remote Power Off via NomadLink
Power On, Idling
1/8 of rated power
(Pink noise, 12 dB crest factor)
16,0
8,0
1123
600
523
1784
2484
626
21,2
10,6
1378
600
778
2655
669
570
Max.
power
*3)
(Pink noise, 6dB crest factor)
35,2
17,6
2296
1200
1096
3740
942
1005
3429
864
16 A, CEE7
35,4
17,7
2605
1600
115VAC 230VAC In Out Dissipated BTU/hr kCal/hr
0 0 0 0 0
123 0 123 420 106
8 / Ch. 1000
x4
16 / Bridged 2000
x2
4 / Ch. 1200
x4
8 / Bridged 2400
x2
2 / Ch. 600
x4
4 / Bridged 1200
x2
100V / Ch. 900
x4
200V / Bridged 1800
x2
8 / Ch. 1000
x4
16 / Bridged 2000
x2
4 / Ch. 1200
x4
8 / Bridged 2400
x2
4 / Ch. 600
x4
8 / Bridged 1200
x2
100V / Ch. 900
x4
200V / Bridged 1800
x2
Mains connector, 230 V CE version Mains connector, 115 V ETL version
*1) The amplifier's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and specified here is what is known as the "Active Power" in the amplifier providing useful, real-world values of power consumption and heat dissipation.
*3) Figures measured at maximum power before amplifier protection and limiter features kicks in. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will never occour during normal operation. Also note that the mains breaker will not be tripped even it's in excess of max. ratings.
*2) Current draw figures measured at 230V. 115V figures are 230V figures multiplied by two.
Standby w. remote Power Off via NomadLink
Amp (I) *2)
W
17,4
8,7
1171
600
571
C 48:4
Level
Load
Rated power
Line Current
Watt *1)
Thermal Dissipation
Power On, Idling
1/8 of rated power
(Pink noise, 12 dB crest factor)
13,8
6,9
945
500
445
1518
383
491
390
1331
335
1948
469
1600
403
12,4
6,2
769
13,2
6,6
840
450
300
Max.
power
*3)
(Pink noise, 6dB crest factor)
28,2
14,1
2116
30,6
15,3
2168
1333
783
2670
673
1200
968
16 A, CEE7
3303
832
21,6
10,8
1368
600
768
2620
660
20 A / 5-20P
627
2139
539
26,4
13,2
1827
1200
8 APPENDIX
C Series Operation Manual 29
115VAC 230VAC In Out Dissipated BTU/hr kCal/hr
0 0 0 0 0
123 0 123 420 106
8 / Ch. 700
x4
16 / Bridged 1400
x2
4 / Ch. 700
x4
8 / Bridged 1400
x2
2 / Ch. 300
x4
4 / Bridged 600
x2
100V / Ch. 700
x4
200V / Bridged 1400
x2
8 / Ch. 700
x4
16 / Bridged 1400
x2
4 / Ch. 700
x4
8 / Bridged 1400
x2
4 / Ch. 300
x4
8 / Bridged 600
x2
100V / Ch. 700
x4
200V / Bridged 1400
x2
Mains connector, 230 V CE version Mains connector, 115 V ETL version
*1) The amplifier's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and specified here is what is known as the "Active Power" in the amplifier providing useful, real-world values of power consumption and heat dissipation.
*3) Figures measured at maximum power before amplifier protection and limiter features kicks in. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will never occour during normal operation. Also note that the mains breaker will not be tripped even it's in excess of max. ratings.
*2) Current draw figures measured at 230V. 115V figures are 230V figures multiplied by two.
C 28:4
Rated power
Line Current
350
377
1286
Level
Load
Watt *1)
Thermal Dissipation
13,0
6,5
775
11,6
5,8
727
1450
150
379
1293
350
313
350
425
525
14,0
7,0
20,8
10,4
1359
700
656
843
1853
659
2249
2237
300
543
Power On, Idling
324
Standby w. remote Power Off via NomadLink
Amp (I) *2)
W
365
326
1/8 of rated power
(Pink noise, 12 dB crest factor)
1068
9,4
4,7
10,4
5,2
529
663
269
564
567
Max.
power
*3)
(Pink noise, 6dB crest factor)
24,0
12,0
1790
1589
933
16 A, CEE7
20 A / 5-20P
467
451
21,4
10,7
1458
933
115VAC 230VAC In Out Dissipated BTU/hr kCal/hr
0 0 0 0 0
129 0 129 440 111
8 / Ch. 400
x4
16 / Bridged 800
x2
4 / Ch. 300
x4
8 / Bridged 600
x2
2 / Ch. n.r. 4 / Bridged n.r. 100V / Ch. 400
x4
200V / Bridged 800
x2
8 / Ch. 400
x4
16 / Bridged 800
x2
4 / Ch. 300
x4
8 / Bridged 600
x2
2 / Ch. n.r. 4 / Bridged n.r. 100V / Ch. 400
x4
200V / Bridged 800
x2
Mains connector, 230 V CE version Mains connector, 115 V ETL version
*1) The amplifier's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and specified here is what is known as the "Active Power" in the amplifier providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw figures measured at 230V. 115V figures are 230V figures multiplied by two.
*3) Figures measured at maximum power before amplifier protection and limiter features kicks in. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will never occour during normal operation. Also note that the mains breaker will not be tripped even it's in excess of max. ratings.
C 16:4
Rated power
Line Current
200
326
1112
Level
Load
Watt *1)
Thermal Dissipation
8,2
4,1
485
8,6
4,3
526
1143
200
263
150
335
411
15,2
7,6
953
400
513
553
1887
1749
Power On, Idling
280
Standby w. remote Power Off via NomadLink
Amp (I) *2)
W
288
1/8 of rated power
(Pink noise, 12 dB crest factor)
897
7,6
3,8
463
226
441
475
Max.
power
*3)
(Pink noise, 6dB crest factor)
16,2
8,1
1401
1046
533
16 A, CEE7
15 A / 5-15P
353
14,4
7,2
944
533
APPENDIX 8
9 TEChNICAL sPECIFICATIONs
Following are the C Series technical specifications. These figures are accurate at the time of printing but please note that all figures are subject to change without notice. For the most accurate and current information available, please visit www.labgruppen.com.
Individual values for C Series amplifiers
C 68:4 C 48:4 C 28:4 C 16:4
Numb er of cha nnels p er amp lifier 4 4 4 4
Total Powe r Limit
680 0 W 480 0 W 28 00 W 1600 W
Max. o utput voltage p er chan nel
100 V
rms
100 V
rms
100 V
rms
100 V
rms
Max. o utput c urren t per channel
24,5 A
rms
17,5 A
rms
12 A
rms
8.5 A
rms
Max. c ontin uous output pow er all 4 ch annel s driven a t VPL: 141V and Gai n: 35dB
16 ohms (per ch.) 650 W 625 W 600 W 4 00 W
8 ohms (pe r ch.) 1200 W 100 0 W 700 W 400 W
4 ohms (pe r ch.) 1700 W 1200 W 600 W 300 W
2 ohms (pe r ch.) 1200 W 60 0 W 3 00 W n .r. 4)
Hi-Z : 70V/100 V (per ch.) 1600 W 90 0 W 70 0 W 4 00 W
16 ohms (br idged, per 2 ch.’s)
1)
240 0 W 200 0 W 1400 W 800 W
8 ohms (br idged, pe r 2 ch.’s)
1)
340 0 W 240 0 W 120 0 W 600 W
4 ohms (br idged, pe r 2 ch.’s)
1)
240 0 W 1200 W 6 00 W n.r. 4)
Hi-Z : 140V/2 00V (br idged, pe r 2 ch.’s)
1)
320 0 W 1800 W 14 00 W 80 0 W
Mains co nnector, 23 0V CE versio n 16A / C EE7 16A / CEE7 16 A / CEE7 16A / CEE7
Mains co nnector, 115V ETL version 20 A / 5-20P 20 A / 5-20P 20 A / 5-20P 15 A / 5-15P
Maximum mains curre nt consumption, 230 V version 11.2 A 8,7 A 6, 5 A 4. 3 A
Maximum mains curre nt consumption, 115V version 2 2.4 A 17,4 A 13 A 8.6 A
Note 1): Automatic -6 dB gain compensation when bridging two Channels. A+B and/or C+D can be bridged individually.
Note 2): PALTM reduces the maximum output power keeping the power supply in safe operating area and/or preventing excessive current draw tripping the mains breaker. Refer to user’s manual.
Note 3): The Voltage Peak output values translate to rms Voltage for a sine wave as: peak/1.41 = Vrms. E.g. 141V peak is 100V
rms
and 100V peak is 70V
rms
. This means that the outputs can be set for
high impedance loads without the use of an external transformer.
Note 4): Single channel operation at 2 ohms and bridged mode at 4 ohms are not recommended.
Note 5): Separate 230 V or 115 V versions available. Not selectable on the amplifier.
C Series Operation Manual 31
TEChNICAL sPECIFICATIONs 9
Common values for all C Series amplifiers
Perf ormance with Gain: 35d B and VPL: 141V
THD 20 H z - 20kHz for 1W 0.1%
THD at 1kHz a nd 1dB below clipping 0.05%
Signal To No ise Ratio 112 dBA
Channel separatio n (Crossta lk) at 1kHz 70 dB
Frequen cy response (1 W into 8 Ohm) +0/ -3dB 6.8 Hz - 3 4 kHz
Voltag e Peak Lim iter (V PL), max. p eak out put
VPL , selectab le per ch. ( V)
3)
141, 118, 100, 8 5, 71, 59, 5 0, 42 V
VPL , when bridg ed (V )
3), 1)
282, 2 36, 20 0, 170, 142, 118, 100, 8 4 V
Voltage Peak Limiter m ode (per ch .) Hard / Sof t
Gain a nd level
Ampli fier gain sel ectable ( all channels)
1)
Rear pan el switches: 2 3, 26, 29 , 32, 35, 3 8, 41, 44 dB
Default g ain 35dB
Level adj ustment (pe r ch.) Front p anel pot, 21 p osition dete nt -inf to 0 dB, .
hidden b ehind secur ity panel /dust filte r grille
Gene ral
Input co nnectors ( per ch.) 3- pin Phoeni x, electro nically b alanced
Output c onnector s (per ch.) Barrie r strip 2- pole screw ter minals
Output b ridge mod e A+B and/ or C+D, input s A and C are signal s ource
Nomad Link netwo rk On board, 2 x RJ45 E therCon c onnector s, IN and OUT
Intellig ent fans (on /off) Depending on presen ce of output s ignal
Power on /off and Remote enable on /off Indivi dual switch es on front pan el
Cooli ng Two fans, front to b ack airfl ow, temperatu re controlle d speed
Front panel in dicators:
Common NomadLink® Network; Power Average Limiter (PAL™) 2); Power on
Per channel Signal present / High impedance; -10 dB and -4 dB output signal;
Voltage Peak Limiter (VPL); Current Peak Limiter (CPL): Very High
Frequency (VHF); High temperature; Fault; Mute
Power
Operating voltag e, 230 V / 115 V nominal
5)
130 -265 V / 65 -135 V
Minimum p ower-up vo ltage, 23 0 V / 115 V 171 V / 85 V
Power Average Limiter
2)
Yes
Soft st art / Inrus h power Yes / max. 5A
Dime nsion s (W/H/D)
W: 48 3 mm (19”), H: 88 mm ( 2 U), D: 34 3 mm (13.5”)
Weigh t
12 kg (26.4 l bs.)
Fini sh
Black painted steel ch assis with g ray painted steel front
Appr ovals
CE 230V, ETL 115V/23 0V, FCC
32 C Series Operation Manual
General
This product is manufactured by Lab.gruppen, and it is warranted to be free from any defects caused by components or factory workmanship, under normal use and service, for a period of six (6) years from date of purchase from an authorized Lab.gruppen dealer.
If the product fails to perform as specified during the warranty period, Lab.gruppen will undertake to repair, or at its option, replace this product at no charge to its owner, provided the unit is returned undamaged, shipping prepaid, to an authorized service facility or to the factory.
This warranty shall be null and void if the product is subjected to: repair work or alteration by a person other than those authorized by us; mechanical damage including shipping accidents; war, civil insur­rection, misuse, abuse, operation with incorrect AC voltage, incorrect connections or accessories; opera­tion with faulty associated equipment; or exposure to inclement weather conditions. Damage due to normal wear and tear is not covered by the warranty. Units on which the serial number has been removed or defaced will not be eligible for warranty service.
Lab.gruppen shall not be responsible for any incidental or consequential damages. Lab.gruppen’s responsibility is limited to the product itself. Lab.gruppen takes no responsibility for any loss due to cancellation of any events, or rent of replace­ment equipment or costs due to a third party’s or customer’s loss of profit, or any other indirect cost or losses however incurred. Lab.gruppen reserves the right to make changes or improvements in design or manufacturing without assuming any obligation to change or improve products previously manufactured.
This warranty is exclusive, and no other warranty is expressed or implied. This warranty does not affect the customer’s statutory rights.
International warranties
Please contact your supplier or distributor for this information, as rights and disclaimers may vary from country to country.
Technical assistance and service
International
If your Lab.gruppen product requires repair, contact your Lab.gruppen dealer or distributor, or contact Lab.gruppen by fax or email to obtain the location of the nearest authorized service centre.
Factory service
In the event Lab.gruppen product requires factory service, you may contact Lab.gruppen’s service department for return instructions and a Return Authorization number. Please note for product return:
Use the original packing. Include a copy of the sales receipt, your name, return address, phone and fax number, email address and description of the defect. Mark the Return Authorization number on the outside of the packing. Ship the product prepaid to:
Lab.gruppen AB Faktorvägen 1 SE-434 37 Kungsbacka SWEDEN Phone: +46 300 56 28 00 Fax: +46 300 56 28 99
info@labgruppen.com www.labgruppen.com
1.
2.
3.
4.
10 WARRANTY
L a b . g r u p p e n a b S w e d e n & + 4 6 3 0 0 5 6 2 8 0 0
T C e L e C T r o n i C i n C
u S a & ( 8 1 8 ) 6 6 5 4 9 0 0
[
m a i l
]
i n f o @ L a b g r u p pe n . C o m
w w w . l a b g r u p p e n . c o m
Loading...