Type C1 Biosafety Cabinet Models
30441 30448
30461 30468
Labconco Corporation
8811 Prospect Avenue
Kansas City, MO 64132-2696
800-821-5525, 816-333-8811
FAX 816-363-0130
E-MAIL labconco@labconco.com
HOME PAGE www.labconco.com
Axiom Technical Manual and Specifications
2
Labconco Training Programs:
In order to assist technicians gain a better understanding of our products,
Labconco Corporation offers Training Seminars at our Kansas City Facility on
a regular basis. For further details about these training programs, contact
Labconco's Product Service Department at 800-821-5525, or (816) 333-8811
from 7:30 a.m. to 5:30 p.m. C.S.T.
Additional Copies:
Additional copies of this document can be downloaded from Labconco’s
website at www.labconco.com. Electronic copies are available to members of
the service community free of charge. Please request electronic copies by
contacting our Product Service Department.
All Rights reserved. No part of this document may be translated or
reproduced in any form without written permission from Labconco
Corporation, 8811 Prospect, Kansas City, Missouri, 64132, U.S.A.
While the advice and information offered in this document are believed to be
true and accurate at the date of going to press, neither the author, nor
Labconco Corporation can accept any legal responsibly for any errors or
omissions that may be made.
P/N 3849911
Rev. G, ECO J633
Product Service 1-800-522-7658
3
Table of Contents
Introduction 7
Contacting Labconco 7
Section One – Background Information
QuickStarts 8
What’s the password for the Axiom? 9
How do I calibrate blower speed, filter life & airflow sensor? 10-11
How do I see the current settings? 12
How do I change the configuration? 13-14
How do I run a diagnostic on the: Sash position switches? 15
Keypad, relays and contact? 16
Inlet Relief Valve? 17
Airflow Sensor? 18
How do I set up automatic operation of the blower & lights? 19
Axiom Filter Life Gauge Operation and Resetting for Local Conditions 20
QuickCharts
Axiom Type C1 Purifiers 21-23
Identifying Axiom Models 24
Serial Number Tags 25
Model Numbering System 26
Axiom Data Plate 27
Final Inspection and Test Report 28
Theory of Operation Background 29
Airflow Patterns and Features 29
Chem-ZoneTM Directly Exhausted Work Zone 30
Inlet Relief Valve 31
Exhaust System 31
Exhaust System Alarm 32
Airflow Patterns of Axiom 33
ECM Motor 34-35
Electronics 35-36
Section Two – Installation Requirements
Prerequisites 37
Space Requirements 37
Clearance 37
Location Requirements 38
If You Intend to Connect the Axiom to an Exhaust System 39-41
Electrical Requirements 42
Service Line Requirements 43
Product Service 1-800-522-7658
4
Section Three – Installation 45
Unpacking the Biosafety Cabinet 46
Preparing the Biosafety Cabinet for operation 46
Moving and Lifting the Cabinet 47
Installing the Biosafety Cabinet on an Existing Work Surface 47
Installing the Cabinet on a Labconco Base Stand 48
Telescoping Base Stands 48
Manual or Electric Lift Base Stands 48
SoLo Electric Hydraulic Lift Base Stands 48
Optional Exhaust System Connection Requirements 49
Configuring for an Exhaust System Connection 50-53
Disconnecting the Axiom from an Exhaust System to Operate in
Recirculation 54-56
Connecting the Biosafety Cabinet to Utility Service Lines 57
Optional Vacu-Pass Cord and Cable Portal 58
Drain Valve Installation (optional) 59
Section Four – Initial Operation of the Axiom
System Reset Switch 61
Information Center 62
Alarm Screens 63
Operating the Sliding Sash 64
Starting the Biosafety Cabinet 64
The Axiom Touchpad 65
Navigating the Axiom Menu Screens 66
Navigating the MyLogic Menu Screens 67-69
Setting the Clock 67
Configuring the Axiom 68-69
Navigating the Settings Menu Screens 69-71
Display Options
Units of Measure 69
Startup Tone 70
Security Lock 70
RS-232 Output 70
UV Settings
UV Lamp Hour meter 71
Reset UV Lamp Hour Meter 71
Change UV Lamp Life 71
Timer Operation Interval Timer Operation 72
Stopwatch Timer Operation 72
If An Airflow Alert Activates 72
Resetting the Airflow Alert System 72
Product Service 1-800-522-7658
5
Section Five – Certification Procedures for the Axiom
Accessing the Certifier’s Menu73
Adjusting the Inflow, Downflow and Filter Life Gauges 73-74
Axiom Filter Life Gauge Operation and Resetting for Local Conditions 75
HEPA Filter Leak Test Information Supply HEPA Filter Leak Test 76
If the Axiom is contaminated 77
Supply HEPA Filter Leak Test Specifications 77
If the Axiom is uncontaminated 77-79
Exhaust HEPA Filter Leak Test 80-81
Exhaust HEPA Filter Leak Test Specifications 80
Downflow Velocities 81-82
Circuit Breaker Resetting a circuit breaker 117
Circuit breaker specifications 117-18
Testing a circuit breaker 118
Replacing a circuit breaker 118
Power Supply Board Service Operations Fuse Testing & Replacement 119
Display Board Service Operations 120
Touchpad Connections 120
Diagnostic Operations 121
Motor Service Operations Motor Testing 121-23
Motor Output Signal Testing 124
Wiring Diagrams 125-26
Section Eight – Purifier Axiom Accessories
Air Flow Sensor Kit 127-30
Service Fixture Kit 131-32
U.V. Lamp Kit 133-35
I.V. Bar Kit 136
Vacu-Pass Cord & Cable Portal 137
RS-232 Connection Kits 138-40
Using the RS-232 Receptacle 141
Connection for Computer Interface 141
Optional Axiom RS-232 Data Output 142-43
Axiom Relay Contact Outputs 144-48
Section Nine - Miscellaneous
Troubleshooting 149-52
Purifier Logic Replacement Parts 153
Dimensions 154-55
Product Service 1-800-522-7658
7
INTRODUCTION
This text is designed for you, the Biohazard Cabinet Certifier. Based on
your suggestions, comments, and ideas, Labconco has compiled this
information for you to use in the certification or servicing of our
Purifier Axiom Biosafety Cabinets.
When you use this document in your office or in the field, we would
appreciate your input so that we can make further improvements to
future editions.
As always, we at Labconco want to assist you in having a better
understanding of our products and their operation; if you have any
questions, or need additional information, please contact us.
Thanks again for all your support in the past, and in the future.
Labconco
CONTACTING LABCONCO
Labconco’s Address is:
LABCONCO Corporation
8811 Prospect
Kansas City, MO 64132
Our hours of operation are from 07:30 - 17:30 CST, Monday through Friday,
except national holidays
We can be reached at the following numbers:
(800) 821-5525
(816) 333-8811
Our Fax numbers are:
(816) 444-5343
(816) 363-0130
Should you require Technical Assistance, Service Parts, or have general
questions regarding the Purifiers, please direct them to our Product Service
Department, so that your call can be properly routed and answered.
Product Service 1-800-522-7658
8
SECTION ONE –
Background Information
Quickstart
The Axiom is a significant step forward in Biosafety Cabinet technology. While many
internal components are the same or similar to our Logic+-platform products, its
operation and certification are different. The
show you how to answer the questions asked in each case. Keystrokes are shown in
bold blue italics
, while screen selections are shown in
Quickstarts
that follow will help you
green italics
.
Product Service 1-800-522-7658
9
Quickstart
What’s the password for the Axiom?
Like the Logic, the Axiom models password protects the user from entering the
Calibration
the airflow sensor readings. New to the Axiom is a
Configuration
connection status, whether its sash height is 8” or 10” and airflow sensor optionsthere is more on this in the Quickstart “How do I change the BSC configuration?”
The password for all protected screens is:
1. Light
2. UV Light
3. Timer
4. Timer
5. OK/Mute
menu to prevent them from adjusting the blower speed, filter gauge or
Service
; entering this option allows you to configure the Axiom’s exhaust
menu selection entitled
Product Service 1-800-522-7658
10
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to r eturn
Current Settings
Restore Default
Diagnostics
Configuration
Calibration
Service
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Calibration
OK to proceed, MENU to return
PASSWORD:
Calibration
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
9. If the password is properly entered, the first certification screen
will display the supply blower motor’s PWM setting. Press the ▲
or ▼ button to increase or decrease the blower speed as
needed. When the speed is set properly, press the
button to lock the new blower speed setting, and continue to the
filter life screen.
Menu
OK/Mute
OK/Mute
warning screen
OK/Mute
then
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Calibration
option is highlighted (it
to start the calibration procedure.
alerting you that you are about to
to input the password.
Light, UV light
OK/Mute
.
OK/Mute
,
Product Service 1-800-522-7658
11
Quickstart
The Inflow displayed
value is: 102 FPM
Calibration
Inflow Display
or to change display value,
UV Light to reset to 105 FPM,
OK to select, MENU to finish
Calibration
Supply Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Reset Filter Gauge to 100%
Leave Gauge unchanged
Set Gauge to new setting
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Exhaust Fan Speed
or to change motor speed,
OK to select, MENU to escape
10. If this is an initial certification or a recertification after supply
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
11. The next certification screen will display the exhaust blower motor’s PWM setting. Press the ▲ or ▼ button to increase or
decrease the blower speed as needed. When the speed is set
properly, press the
OK/Mute
speed setting, and continue to the filter life screen.
12. If this is an initial certification or a recertification after exhaust
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
13. If the unit is has no airflow sensor, after the filter gauge option
is selected and you press
down, and then restart with the new settings. If the Unit has an
airflow sensor, you will then be asked to calibrate the inflow
sensor to match the value you obtained when you measured the
inflow. After the inflow is calibrated, and you press
the Axiom will power down, and then restart with the new
settings.
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
.
button to lock the new blower
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
OK/Mute
, the Axiom will power
.
OK/Mute
. If
.
Set
. If
.
Set
,
Product Service 1-800-522-7658
12
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to return
Current Settings
Restore Default
Diagnostics
Calibration
Configuration
Service
Current Settings
Supply System
or to change, OK to return
The ECM setting is: 65
The current RPM is: 0
The average RPM is: 0
The new filter RPM is: 1450
C1, with afs, with UV
10484 -
Current Settings
Exhaust System
or to change, OK to return
The ECM setting is: 65
The current RPM is: 0
The average RPM is: 0
The new filter RPM is: 1450
C1, with afs, with UV
10484 -
How do I see the Current Settings of the Axiom?
1. Press the
2. Press the ▼ button until the
turn yellow). Press
screen.
3. Press the ▼ button until the
highlighted (it will turn white). Press
configuration.
4. The first screen shows the current settings of the supply blower
system.
5. By pressing the ▲ or ▼ button, you can see the current
settings of the exhaust blower system. If you are recertifying the
unit, you may want to record the data on this screen. The
firmware revision is shown in the bottom right corner as a -, or
as a letter.
Menu
button.
OK/Mute
Services
option is highlighted (it will
to enter the Services menu
Current Settings
OK/Mute
option is
to see the
Product Service 1-800-522-7658
13
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to return
Current Settings
Restore Default
Diagnostics
Calibration
Configuration
Service
Configuration
PASSWORD:
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Configuration
OK to proceed, MENU to return
How do I change the Configuration of the Axiom?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
(it will turn white).
5. Press
6. You will see a alter the BSC’s settings.
7. Press
8. When requested for the password press
Timer, Timer
Menu
OK/Mute
OK/Mute
warning screen
OK/Mute
then
button.
Services
to enter the Services menu screen.
Configuration
to alter the configuration.
alerting you that you are about to
to input the password.
OK/Mute
.
option is highlighted (it will
option is highlighted
Light, UV light
,
Product Service 1-800-522-7658
14
This cabinet is not configured
for a UV light
If you want to install a UV
light, contact Labconco Product
Service at 800-821-5525
Attention
MENU to return
Configuration
Type C Configuration
This cabinet has:
an
or to choose,
OK t o select , MENU to escape
no exhaust connect ion
exhaust connection
Configuration
Type C Configuration
If there is an exhaust system
failure, Active protection should
last:
or to choose,
OK t o select , MENU to escape
0 Seconds
The sash height is:
or to choose,
OK to select, MENU to escape
8 inches
10 inches
NOTE: If you change the sash
height, you must recertify
airflows.
Sash Height Settings
This Logic has:
or to choose,
OK to select, MENU to escape
a UV light
NO UV light
UV Settings
Quickstart
How do I change the Configuration of the Axiom? – continued
9. The first screen allows you to decide if the cabinet is connected to
an exhaust system or not. When the unit is configured for no
exhaust connection, the Axiom will ignore the inlet relief valve
sensor’s status. Selecting connected to an exhaust system
activates the sensor; if the valve is open, the unit operates
normally, if closed, an exhaust alarm is activated. Use the ▲or▼
buttons to select the exhaust configuration, and then press
OK/Mute.
10. If the unit is configured to be connected to an exhaust system,
then the next screen allows you to program the amount of time
interval of Active Protection. Active Protection will allow the Axiom
blowers to continue to operate after the detection of an exhaust
system failure. This will maintain a safe inflow to allow the user a
programmed time interval to secure any hazardous materials in
the cabinet before the BSC shuts off.
11. This screen configures the sash height. After your selection is
chosen, and you press OK/Mute.
12. This screen configures the unit for a UV light or not. After your
selection is chosen, and you press OK/Mute, the unit will shut off
and then reset in the new configuration.
13. If the unit is configured to NOT have a UV light, and the user
presses the UV Light button, they will get this message.
Product Service 1-800-522-7658
15
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
Diagnostics
Test the alarm by closing the
inlet valve.
Note the alarm status below:
Open
OK to return
How do I run a diagnostic on the sash position switches?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
highlighted (it will turn white). Press
7. Lower the sash, and note the status line – it should properly
report the sash as open too high, open, nearly closed or closed
when the sash is in the corresponding position.* Press
OK/Mute
Menu
button.
OK/Mute
OK/Mute
to enter the Services menu screen.
to enter the Diagnostic submenu.
to exit the diagnostic.
Services
option is highlighted (it will
Diagnostic
OK/Mute
option is highlighted (it
Sash sensors
.
option is
Product Service 1-800-522-7658
16
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
How do I run a diagnostic on the keypad, relays and contacts?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
(it will turn white). Press
7. Press any button on the keypad (except
display.
How do I run a diagnostic on the Inlet Relief Valve?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
is highlighted (it will turn white). Press
7. The display shows the status of the Inlet Relief Valve. During
normal operation, it will be open, and during an exhaust alarm,
it will be closed. NOTE: The inlet relief valve function is
OPPOSITE OF THE MAGNETIC SWITCH FUNCTION! – WHEN
THE INLET VALVE IS OPEN, THE MAGNETIC SWITCH IS
CLOSED.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Inlet Relief Valve
OK/Mute
.
Product Service 1-800-522-7658
option
18
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to choose,
OK to select, MENU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
Quickstart
How do I run a diagnostic on the Airflow Sensor?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
highlighted (it will turn white). Press
7. The display shows the status of the airflow sensor. Its current
output, alarm setting and zero point in Millivolts, along with the
corrected Inflow velocity currently being displayed.
Quickstart
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Airflow Sensor
OK/Mute
.
Product Service 1-800-522-7658
option is
19
How do I set up automatic operation of the blower and lights?
1. Press the
2. Press the ▼ button until the
turn blue).
3. Press
Menu
OK/Mute
button.
MyLogic
to enter the MyLogic menu screen.
option is highlighted it will
4. Press the ▼ button until the option
option is highlighted (it will turn white).
5. Press the ▼ button to select either Smart-Start or manual
operation of the cabinet blower. (In Smart-Start, the cabinet
blower will automatically start every time the sash is opened.
6. Press the ▼ button to select either Smart-Start or manual
operation of the fluorescent lights.
7. Press the ▼ button to select either Night-Smart or manual
operation of the cabinet blower. (In Night-Smart, the cabinet
blower will automatically operate at idle every time the sash is
closed.
8. Press the ▼ button to select either Night-Smart or manual
operation of the UV Light.*
9. Press the ▼ button to select the time interval the UV light will
operate for until it automatically shuts off.*
* - These screens will only appear if the unit is configured for a UV light.
configure my Logic for use
Axiom Filter Life Gauge Operation and Resetting
for Local Conditions
Product Service 1-800-522-7658
20
The filter life gauge calculates the remaining filter life by measuring and comparing
the current motor speed to the initial speed noted at the factory during assembly,
and the calculated maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left
max. speed-original speed
So
anything
Blocking the grille.
Raising the air temperature.
Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic
dampening of the gauge will limit the change in readings to approximately
1%/minute.
Axiom Biosafety Cabinets being installed at altitudes or operating at temperatures
significantly different from those at the time of manufacture (900 +/- 500 ft above
sea level, 75o +/- 5o F)
conditions. Failure to do so will result in the users noticing a steady drop in Percent
(%) Filter Life remaining as the unit operates. Below are the instructions on how to
correct the Filter Life Gauge for local conditions.
that changes the motor’s current speed, like:
must
have their filter life gauge recalibrated for local
1. Ensure to correct all measurement equipment for local conditions
(temperature, absolute pressure). Anemometers may not have this
ability and might have to be done manually; whereas, a
ShortRidgeTM instrument has a setting to correct for local conditions.
2. As the elevation or the ambient temperature rises, the motor power
factor will have to be reduced to compensate. For an initial
certification, the motor speed should be reduced until it equals the
Axiom’s“Initial Motor Speed”as reported on the unit’s test sheet,
plus approximately 10-15 RPM per each additional 1000 feet of
elevation.
3. The Axiom MUST be recertified using instruments corrected for local
conditions.
4. When the unit is recertified, and operating properly, the certifier
MUST RESET THE FILTER LIFE GAUGE, INDICATING A NEW FILTER
HAS BEEN INSTALLED.
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND
RECERTIFIED FOR ITS LOCAL CONDITION, will the filter life gauge
register 100% (+/- 2%) during operation. As the Filters then load,
the filter life gauge will then begin to drop as appropriate.
Product Service 1-800-522-7658
21
QuickChart – Axiom Type C1 BSCs – Imperial Units
Model
30441
30448
30461
30468
Type
C1
C1
C1
C1
Cabinet Size (in feet)
4 4 6
6
Sash Opening (inches)
10 8 10
8
Starting Serial #
1503_
1503_
1503_
1503_
Downflow Data
Nominal Avg. Downflow (FPM)
65+/-5
65+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
24 (3x8)
24 (3x8)
36(3x12)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
6.0
Distance between rows
5.55
5.75
5.55
5.75
Distance between columns
5.21
5.21
5.50
5.50
Inflow Data
Nominal Average Inflow (FPM)
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
3.37
2.69
5.03
4.03
Nominal Avg. Exhaust Vol. (CFM)
354
283
529
423
Avg. Exhaust Vol. Range (CFM)
337-371
269-296
503-553
403-443
Secondary Inflow Data
Sash Opening Template
1
4+
4+
6+
6+
Sensor distance (inches)2
3.25
3.25 4 4
# of Test points
8 8 12
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
354
283
289
231
Avg. Inflow Vel. Range (FPM)
312-344
249-274
252-277
202-222
Correction Factor (CF)
1.08
1.08 2 2
Avg. Inflow Volume (CFM)
337-371
269-296
503-553
403-443
Sash Open Area (Sq. Ft)
3.37
2.69
5.03
4.03
Inflow Velocity Range (FPM)
100-110
100-110
100-110
100-110
Supply HEPA Data
Air Displacement (CFM)
530
530
660
660
Laskin Nozzles needed
1 1 1
1
Theoretical aerosol conc. (ug/l)3
25
25
20
20
Width x Depth x Height (in.)4
48x18x3.06
48x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
445
445
665
665
Performance (Pressure in. H2O)
<.45”
<.45”
<.42”
<.42”
Labconco P/N
3838401
3838401
3838403
3838403
Exhaust HEPA Data
Air Displacement (CFM)
354
283
529
423
Laskin Nozzles needed
1 1 1
1
Theoretical aerosol conc. (ug/l)3
38
48
26
32
Width x Depth x Height (in.)
4
26x18x5.88
26x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
354
354
529
52
Performance (Pressure in. H2O)
<0.3
<0.3
<0.3
<0.3
Labconco P/N
3838501
3838501
3838503
3838503
Exhaust Volume Data
DIM Exhaust Volume (CFM)5
400
323
570
463
Traverse Exhaust Volume (CFM)6
480
387
684
556
Differential Pressure (in. H20)7
0.3
0.3
0.3
0.3
IRV Inflow Range (CFM)8
20-100
20-100
20-100
20-100
Nominal IRV Slot Velocity (FPM)
240-260
240-260
240-260
240-260
Nominal IRV Slot Volume (CFM)
50
50
50
50
Supply Motor/Blower Data
Motor HP
1/3
1/3
1/3
1/3
Exhaust Motor/Blower Data
Motor HP
1/3
1/3
1/3
1/3
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Product Service 1-800-522-7658
22
QuickChart – Axiom Type C1 BSCs – Metric Units
Model
30441
30448
30461
30468
Type
C1
C1
C1
C1
Cabinet Size (in m)
1.22
1.22
1.83
1.83
Sash Opening (mm)
254
203
254
203
Starting Serial #
1503_
1503_
1503_
1503_
Downflow Data
Nominal Avg. Downflow (FPM)
65+/-5
65+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
24 (3x8)
24 (3x8)
36(3x12)
36(3x12)
Grid distance from back & sides (mm)
152
152
152
152
Distance between rows (mm)
141
146
141
146
Distance between columns (mm)
132
132
140
140
Inflow Data
Nominal Average Inflow (m/s)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
Sash Open Area (Sq. m)
.313
.250
5.03
4.03
Nominal Avg. Exhaust Vol. (m3/s)
354
283
.468
.374
Avg. Exhaust Vol. Range (m3/s)
337-371
269-296
503-553
403-443
Secondary Inflow Data
Sash Opening Template
1
4+
4+
6+
6+
Sensor distance (mm)2
83
83
102
102
# of Test points
8 8 12
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (m/s)
1.80
1.44
1.47
1.17
Avg. Inflow Vel. Range (m/s)
1.71-1.88
1.37-1.50
1.40-1.53
1.12-1.23
Correction Factor (CF)
.0929
.0929
.1700
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.159-.175
.127-.140
.238-.261
.190-.209
Sash Open Area (Sq. m)
.313
.250
.468
.374
Inflow Velocity Range
(AIV / Sash open area)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
Supply HEPA Data
Air Displacement (m3/s)
.250
.250
.311
.311
Laskin Nozzles needed
1 1 1
1
Theoretical aerosol conc. (ug/l)3
25
25
20
20
Width x Depth x Height (in.)4
48x18x3.06
48x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
445
445
665
665
Performance (Pressure in. H2O)
<.45”
<.45”
<.42”
<.42”
Labconco P/N
3838401
3838401
3838403
3838403
Exhaust HEPA Data
Air Displacement (m3/s)
.167
.134
.250
.200
Laskin Nozzles needed
1 1 1
1
Theoretical aerosol conc. (ug/l)3
38
48
26
32
Width x Depth x Height (in.)
4
26x18x5.88
26x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
283
283
423
423
Performance (Pressure in. H2O)
<0.3
<0.3
<0.3
<0.3
Labconco P/N
3838501
3838501
3838503
3838503
Exhaust Volume Data
DIM Exhaust Volume (m3/s)5
.189
.152
.269
.219
Traverse Exhaust Volume (m,3/s)6
.227
.183
.323
.262
Differential Pressure (Pascal)7
75
75
75
75
IRV Inflow Range (m/s)
.010-.047
.010-.047
.010-.047
.010-.047
Nominal IRV Slot Velocity (m/s)
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
Nominal IRV Slot Volume (m3/s)
.235
.235
.235
.235
Supply Motor/Blower Data
Motor HP
1/3
1/3
1/3
1/3
Exhaust Motor/Blower Data
Motor HP
1/3
1/3
1/3
1/3
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Product Service 1-800-522-7658
23
QuickChart – Axiom/Cell Axiom Type C1 BSCs footnotes
Axiom Model Identification
The primary serial tag is on the lower right edge of the front dress panel.
The secondary serial tag is located on the front of the electronics module on the top
right side of the cabinet.
The first two digits of the serial number are the year of production; the next two are
the month. The next 5 digits are the sequence of production, and the letter following
the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow.
All tests performed as described in ANSI/NSF Standard 49:2012.
UV Lamp, IV bar and all other accessories must be removed before measuring
downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2012.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal
anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the
side wall and subsequent test points every 9 holes until the number of test points
marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points).
Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. Without gasket
Aerosol generator should be placed in the left rear corner of the work area, pointing
toward the rear grille.
For uncontaminated units, the upstream concentration can be sampled from the
tube located under the work surface.
Metric calculation of concentration is:
# of Laskin nozzles @ 138K Pascal x 6.372/Volume of air in m3/sec. = Conc.
In ug/l
Exhaust Data
5. Total Exhaust Volume; The sum of the inflow and air drawn into the Inlet Relief
6. Measured as per ASHRAE methodology for measuring air volume in round ducts.
7. Measured at the exhaust transition sampling point, relative to atmosphere.
8. IRV = Inlet Relief Valve.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
For all 115/230 VAC models, the ballast assembly is Labconco part number 3829901.
For all 100 VAC models, the ballast assembly is Labconco part number 3830600. The
Valve.
1271300.
The ballast is Robertson part number PSM2GPH18MVW.
ballast is Robertson part number RSO1GPH30100.
Product Service 1-800-522-7658
24
IDENTIFYING AXIOM MODELS
The Axiom platform Biosafety Cabinet can be identified readily by several
external features, as shown in Figure 1-1:
Model number Stars with 304xxxxxx
Serial number beginning with 1503xxxxx.
Exhaust System Cover.
Segmented Work Surfaces.
Figure 1-1
Exhaust System Cover
Axiom Logo
Segmented Work
Surfaces
Product Service 1-800-522-7658
25
SERIAL NUMBER TAGS
The model/serial number tag is located on the bottom right edge of the
dress panel. A second tag is located on the front of the electronics module
on the top of the unit. This tag includes the unit’s operating voltage and
amperage. The model and serial numbers of each unit are also recorded on
the unit test report attached beneath the front dress panel. These items are
shown graphically in the figures 1-3 to 1-5 below:
Figure 1-3
Primary Serial Tag
Figure 1-4
Secondary Serial Tag
Figure 1-5
Final Inspection and Test Report Form
Obviously, you can get confirmation of the Biosafety Cabinet's model by
contacting Labconco's Product Service Department, and providing us with
the serial number. From this number, we can tell the date of production and
its model.
Product Service 1-800-522-7658
26
AXIOM MODEL NUMBERING SYSTEM
Axiom units’ model numbers define the configuration of the cabinet. The first
five digits define the unit's configuration, while the last four are assigned
based on the unit's options and electrical configuration. Thus, a model
number of:
30448xxxx
Labconco Product Group
3=Laminar Flow Products
Indicates the Product Family
0= Logic
1= PuriCare
2-4= Cell Logic
The Axiom Data Plate contains much of the information required to certify
the unit. Information on the plate includes nominal inflow and downflow
velocity settings, a description of how to establish the downflow grid and the
secondary inflow methodology are also included on the data plate, as shown
below. The plate is located in the upper left corner of the dress panel.
Figure 1-6
Product Service 1-800-522-7658
28
Final Inspection and Test Report Form
A copy of the Final Inspection Test Report is attached to the blower plenum
cover, beneath the front dress panel. The report contains initial setup
information on inflow and downflow velocities, and the initial blower torque
setting. A copy of the report is shown in Figure 1-7, below
Figure 1-7
Model/Serial
Numbers
HEPA Filter
Information
Test Results
Downflow Test
Results
Product Service 1-800-522-7658
29
Theory of Operation
Background
The Axiom Type C1 BSC was the result of a customer request for a Type B
(directly exhausted) cabinet that could operate at a constant exhaust system
vacuum of only 0.25 inches of H2O. Realizing that this was impossible for
existing Type B technologies, Labconco developed a new type of BSC; The
proposed Type C1.
Figure 1-8
Airflow Patterns and Features
The overall airflow pattern in the Type C1 is similar to a Type B1, with three
important differences:
1. In the C1, the directly exhausted portion of downflow air is
taken from the center of the work area (The Chem-ZoneTM).
2. An inlet relief valve, unique to the Axiom, stabilizes the inflow
as exhaust system airflows fluctuates, and closes during an
exhaust system failure, signaling the Axiom to initiate a timed
“Active Protection” of the user and their work.
3. A constant volume exhaust blower upstream of the Exhaust
HEPA maintains constant inflow, and allows the unit’s blowers
to continue to operate during an exhaust system failure
(Active Protection), maintaining safe inflows and downflows
while the user secures any hazardous materials in the work
area.
Product Service 1-800-522-7658
30
Figure 1-8a
Chem-ZoneTM Directly Exhausted Work Zone
Unique to the Axiom is the Chem-Zone, a directly exhausted work zone. The
central portion of the work surface is surrounded by grilles on the sides,
front and back. Air entering these grilles is drawn to the Exhaust HEPA filter,
and when the cabinet is connected to an exhaust system, out of the
laboratory. This feature prevents the recirculation of volatile chemicals as
seen in Type A cabinets, while exhausting much less air than Type B2
models. This is illustrated in Figure 1-8a.
Product Service 1-800-522-7658
31
Inlet Relief Valve
Also unique to the Axiom is the Inlet Relief Valve, The intake valve is angled
such that the incoming make-up (room) air must keep the valve open to
maintain normal operation; a loss of exhaust volume will allow gravity and
air pressure to close the inlet valve and open the magnetic switch, resulting
in an exhaust alarm.
Figure 1-8b
Intake Valve
Alarm Switch
Exhaust System
Key to the Axiom is its exhaust flexibility. When properly configured, the
HEPA-filtered exhaust can be recirculated back into the laboratory.
When configured for, and connected to an external exhaust system, the
airflow patterns are similar to the definition of a Type B1, however, the
integral exhaust blower and Inlet Relief Valve changes the operating
characteristics of the Axiom.
The CAP (Constant Airflow Profile)-programmed exhaust fan motor draws a
constant volume of air through the exhaust ductwork and exhaust HEPA
filter, and ‘presents’ the air to the exhaust system. This means the inflow
volume will remain constant as the exhaust system fluctuates, or as the
exhaust HEPA filter loads.
This arrangement lowers the vacuum required to operate the unit to a
constant 0.3 inches H2O; far lower than traditional Type B BSCs.
The inlet relief valve is pulled opened when the exhaust system draws more
air than the Axiom exhausts. If the exhaust system fails, gravity and positive
air pressure cause the Inlet Relief Valve to close, activating the sensor to
signal an exhaust alarm.
Product Service 1-800-522-7658
32
Exhaust System Alarm
The Axiom is unique in its response to an exhaust alarm. Instead of shutting
off the BSC’s blowers, the Axiom starts its “Activate Protection Protocol” – a
certifier-programmed interval of up to 5 minutes. During this interval, the
Axiom’s exhaust blower speeds up to compensate for the loss of the remote
exhaust fan to provide constant inflow. The supply blower maintains
downflow. This offers the user time to secure any hazardous material in the
BSC. At the end of the Active Protection cycle, the supply blower shuts off,
followed by the exhaust fan 10 seconds later, to ensure containment until
the unit shuts off completely.
Figure 1-8c
10” Exhaust System
Connection
Inlet Relief Valve
Exhaust Fan System
Product Service 1-800-522-7658
33
Inlet Relief Valve Open
Inlet Relief Valve Closed
Airflow Patterns of the Axiom in Recirculating and
Figure 1-8d
Exhausted Modes.
Product Service 1-800-522-7658
34
ECM Motor
The modern Class II Biosafety Cabinet was developed in the early 1960’s as
a result of the increased availability of High Efficiency Particulate Air (HEPA)
filter technology. The motor of choice at the time to drive the cabinet’s
blower was the Permanent Split Capacitor (PSC) type. At the time, the PSC
motor offered manufacturers an inexpensive power source whose speed
could be electronically controlled to allow for airflow adjustment as the HEPA
filter(s) loaded.
The PSC motor is known as an induction type, for stationary windings
(stator) surround a rotating part (rotor) composed of iron or steel. As
current passes through the stator windings, it induces a magnetic field in the
rotor, causing it to rotate towards the shifting field in the stator. Because a
magnetic field must be induced in the rotor, the PSC motor is asynchronous,
with the rotor constantly lagging behind the fields being created in the
stator. As a result of this asynchronous operation, the PSC motor is
inefficient, and generates high amounts of waste heat. Attempting to control
the blower speed by reducing its voltage only increases the inefficiency of
the PSC motor.
DC motors are more efficient than their AC counterparts. In a typical DC
motor, the stator in an AC motor is replaced with permanent magnets. The
rotor then has a series of windings around it. When current is applied to the
motor, a magnetic field is created in some of the windings of the rotor,
causing it to rotate toward the magnetic field created by the permanent
magnets. Brushes in contact with a commutator allow the current, and thus
the magnetic field in the rotor to progressively shift from winding to winding,
forcing the rotor to keep rotating.
The greatest drawback of brushed DC motors is the brushes-they wear
themselves and the commutator down, eventually causing motor failure.
With the development of greater microprocessor power in the 1970s and
80s, the stage was set for an even more efficient type of DC motor – the
Electronically Commutated Motor (ECM).
Figure 1-9
In the ECM, the magnets and windings switch position –
the permanent magnet is on the rotor, and the series of
windings are placed around the rotor. The
microprocessor precisely controls the creation of
magnetic fields in the stator, so that the rotor is always
synchronous with the magnetic fields being created in
the stator. As a result, the ECM will always run more
efficiently and cooler than a comparable PSC motor.
Because of the simple, robust construction of the ECM, it
offers far greater reliability and operational service life
than the PSC motor.
Product Service 1-800-522-7658
35
Controlling the motor’s operation with a microprocessor adds numerous
advantages. Motor speed can be efficiently controlled across a speed range
that would damage or destroy a PSC motor. Given enough microprocessor
memory and power, the manufacturer can program in any number of userselected programs controlling motor speed, power and even direction of
rotation. The ultimate expression of the power of the ECM was the
development of the constant volume algorithm, by General Electric, and
used in the Axiom BSC. By testing a prototype model to a variety of airflows
and filter pressures, the motor/blower can be “characterized” for that size
cabinet. This characterization allows for the creation of a model-specific
motor-blower curve. By programming the curve values into the motor during
assembly, the motor will deliver the correct volume of air as the HEPA filters
load.
Electronics
The Axiom utilizes two microprocessors. The first is part of the ECM motor,
attached to end of the motor housing, as shown in Figure 1-10. This
processor controls motor operation, and communication with the display
board. The second is located on the control board, located on the right side
wall, as shown in Figure 1-11. It controls the display and its interface to the
touchpad.
Figure 1-10
The ECM Microprocessor board is encapsulated in
epoxy to prevent moisture and dirt contamination of
the microelectronics.
Figure 1-11
The control board assembly
(located on the right side wall)
Product Service 1-800-522-7658
36
The Axiom has three circuit boards. The ECM microprocessor and power
supply board, located in the end of the ECM, the control board on the right
side wall, shown in Figure 1-11, and the power supply board assembly,
located in the electronics module, as shown in Figure 1-12.
Figure 1-12
UV Relay
Light Relay
Outlet Relay
RS-232 Board
Location
The Axiom also has an optional contact/RS232 board. This must be installed
if the user wants to signal external building monitors or controllers, or wants
the Axiom to output operating information to a data logger. The optional
board is located in the electronics module.
Product Service 1-800-522-7658
37
Section Two –
Installation Requirements
This section offers an overview of site requirements and how to prepare the
unit for operation.
Prerequisites
Before you install the Axiom, you need to prepare the site for installation.
Examine the location where you intend to install the cabinet. You must be
certain that the area is level and of solid construction. In addition, a
dedicated source of electrical power must be located near the installation
site.
Carefully read this chapter to learn:
Location requirements.
Electrical power requirements.
Exhaust requirements.
Service utility requirements.
Space requirements.
Refer to Section Nine: Miscellaneous, for complete biosafety cabinet
electrical and environmental conditions, specifications and requirements.
Space Requirements
The overall dimensions for the 4-foot Axiom are 64.2 inches (163 cm) high, 32
inches (81 cm) deep, and 54.2 inches (138 cm) wide. The overall dimensions
for the 6-foot Axiom are 64.2 inches (163 cm) high, 32.6 inches (83 cm) deep,
and 78.2 inches (199 cm) wide.
Complete dimensions for the Axiom biosafety cabinets are shown in
Nine: Miscellaneous
.
Section
Clearance
A minimum clearance of at least 4 inches (100 mm) is suggested on the top
and 6 inches (150mm) on both sides of the cabinet for service.
Product Service 1-800-522-7658
38
Location Requirements
Figure 2-1
Note: The biosafety cabinet should be located away from traffic patterns,
doors, fans, ventilation registers, fume hoods and any other air-handling
devices that could disrupt its airflow patterns. All windows in the room
should remain closed. Figure 2-1 shows the preferred location for the
biosafety cabinet.
Preferred location
Air register blocked or redirected
to prevent cabinet disruption
Alternate location
Main Disconnect Device
(Power cord plug in back
of the electronics module).
Do not position the unit so that it is difficult to operate the main
disconnect device.
Ne placez pas l'appareil de sorte qu'il est difficile de faire
fonctionner le dispositif principal de déconnexion.
Product Service 1-800-522-7658
39
If You Intend to Connect the Axiom to an Exhaust System:
Figure 2-1a
Figure 2-1b
NOTE: THE EXHAUST BLOWER CANNOT RUN AT ITS NOMINAL FLOW RATE
WITH THE SASH COMPLETELY CLOSED. IF YOU CHOOSE TO CLOSE THE
SASH COMPLETELY TO USE THE UV LIGHT FOR SURFACE DISINFECTION,
THEN THE EXHAUST BLOWER MUST BE SHUT OFF, OR ITS FLOW RATE
REDUCED 90% OR MORE FOR PROPER OPERATION. THE AXIOM HAS AN
OPTIONAL EN/CONTACT CIRCUIT BOARD THAT HAS DRY CONTACTS THAT
CAN BE CONFIGURED TO SIGNAL THE EXHAUST BLOWER TO TURN ON
WHEN THE AXIOM’s BLOWER IS ON. FOR FURTHER INFORMATION,
CONTACT LABCONCO’S PRODUCT SERVICE DEPARTMENT. AS AN
ALTERNATIVE, A REMOTE ELECTRICAL SWITCH FOR THE EXHAUST
BLOWER CAN BE INSTALLED NEAR THE AXIOM.
NOTE: Only connect the cabinet to a suitable exhaust system, one dedicated
to the cabinet itself, or dedicated to exhausting laboratory ventilation
equipment. DO NOT connect the unit to the
building’s HVAC system room exhaust.
Examine the location to ensure that it accommodates
the cabinet’s exhaust duct. The area directly above
the cabinet’s exhaust port should be clear of structural
elements, water and utility lines, or other fixed
obstructions. There should be enough clearance to
accommodate a 10-inch diameter duct.
Avoid cabinet locations that require an elbow directly above the cabinet’s
exhaust connection or an excessive number of elbows in the exhaust system.
There should be a straight length 10 duct
diameters long between the cabinet and any
elbow, and between subsequent elbows.
Product Service 1-800-522-7658
40
Figure 2-1c
Figure 2-1d
The Inlet Relief Valve located on the top of the cabinet is
designed to draw a maximum of 100 CFM (2.83 m3/m).
Attempting to draw additional room air through the valve
(room air exhaust), can result in unstable cabinet
operation.
If additional room exhaust is needed to be
drawn through the exhaust system, install an
additional duct and balancing damper
downstream of the cabinet’s damper. This will
allow for proper balancing of the system.
Product Service 1-800-522-7658
41
The exhaust system must be capable of moving the following volumes of
Axiom Type C1
Airflows
Airflow Volume
Concurrent
Balance Value
Recommended
Duct Vacuum1
ft3/min
m3/sec
ft3/min
m3/sec
WC
Pa
4-foot, 8" Sash
323
0.15
387
0.18
0.30
75
4-foot, 10" Sash
400
0.19
480
0.23
0.30
75
6-foot, 8" Sash
463
0.22
556
0.26
0.30
75
6-foot, 10" Sash
570
0.27
684
0.32
0.30
75
Table 2-1
exhaust air at the negative pressures listed. The Airflow Volumes are the
values recorded via a direct measurement using a flow hood at the cabinet.
The Concurrent Balance Values are measured in the exhaust duct via
traverse methodology, and will always be higher due to differences in volume
measurement methodologies.
1 – Unlike Type B cabinets, the recommended vacuum will remain constant
throughout the life of the Exhaust HEPA filter. Duct vacuums below 0.3 WC
(37 Pa), or above 0.5 WC (125 PA) may result in erratic operation.
Product Service 1-800-522-7658
42
Electrical Requirements
Model #
Requirements
30441xx0x, 30448xx0x
115 VAC, 60 Hz, 16 Amps
30441xx1x, 30448xx1x
100 VAC, 50/60 Hz, 16 Amps
30441xx-20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
30448xx-20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
30461xx0x, 30468xx0x
115 VAC, 60 Hz, 16 Amps
30461xx1x, 30468xx1x
100 VAC, 50/60 Hz, 16 Amps
30461xx-20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
30468xx-20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
Table 2-1
The biosafety cabinet models have the following electrical requirements:
Note: A dedicated outlet with an appropriate circuit breaker should
be located as close as possible to the right rear side of the cabinet,
at a height even with, or higher than, the top of the bench or stand.
Consult your local electrical codes for properly rated circuit
breakers. For safe operation the dedicated outlet must provide the
protective earthing ground connection to the cabinet.
Note: On 100 and 115 VAC models, both electrical outlets are protected by
a ground fault interrupter circuit (GFIC). Labconco does not recommend
plugging the biosafety cabinet into a GFIC outlet.
Electrical outlets in the cabinet are restricted to 5 amps maximum
current.
Prises électriques dans l'armoire sont limitées à 5 courant maximum
ampères.
The biosafety cabinet models have the following electrical requirements:
Do not use any detachable power cord that is not adequately rated
for the unit.
Ne pas utliser un fil électrique amovible qui n’est pas du tension
nominale de l’appareil.
Product Service 1-800-522-7658
43
Service Line Requirements
All utility service lines should be ¼ inch O.D., brass, copper, or stainless
steel, and equipped with an easily accessible shut-off valve. If the service
line pressure exceeds 40 PSI, it must be equipped with a pressure regulator
to reduce the line pressure.
Note: The use of flammable gases or solvents should be avoided in the
biosafety cabinet. Open flame in the cabinet will disrupt the laminar airflow
in the cabinet and may damage the HEPA filters. Flammable gases or
solvents may reach explosive concentrations in the cabinet or ductwork. If
you feel that the procedure requires the use of an open flame or flammable
materials, contact the institution’s safety office.
The use of air or gases under high pressure should be avoided as they may
seriously disrupt the airflow patterns in the cabinet.
Product Service 1-800-522-7658
44
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
45
Section Three –
Installation
Now that the installation is properly prepared, you are ready to inspect, install, and
certify the Axiom biosafety cabinet. This chapter covers how to:
Unpack and move the biosafety cabinet.
Install the cabinet.
Connect the electrical supply source.
Connect the service lines.
Connect to an exhaust system (optional for Type As).
Tools required for installation the biosafety cabinet include two 1/2" wrenches, a flatblade screwdriver, a #2 Phillips screwdriver, and a carpenter’s level.
Note: The biosafety cabinet models weigh between 400–700 lbs. (182-318 kg). The
shipping pallet allows for lifting with a mechanical lift truck or floor jack. If you must lift
the product manually, use at least six (6) persons and follow safe-lifting guidelines.
Product Service 1-800-522-7658
46
Unpacking the Biosafety Cabinet
Carefully remove the outer carton and inspect the cabinet for damage that may have
occurred in transit. If the biosafety cabinet is damaged, notify the delivery carrier
immediately and retain the entire shipment intact for inspection by the carrier.
Note: United States Interstate Commerce Commission rules require that claims be filed
with the delivery carrier within fifteen (15) days of delivery.
Do not return goods without the prior authorization of Labconco. Unauthorized returns
will not be accepted.
If the cabinet was damaged in transit, you must file a claim directly with the freight
carrier. Labconco Corporation and its dealers are not responsible for shipping damages.
Do not discard the carton or packing material for the biosafety cabinet until all of the
components have been checked, installed and tested.
The cabinet is secured to the pallet in two places on each side. To access the nuts and
bolts, remove the side panels by removing and keeping the two Phillips screws on both
panels. Swing the front of each panel away from the cabinet, and lift it straight up to
remove the panel from the cabinet.
Note: The side panels must be removed to access the fasteners that secure the
biosafety cabinet to the pallet. DO NOT ATTEMPT TO LIFT THE BIOSAFETY
CABINET BY THE SIDE PANELS; DAMAGE WILL OCCUR.
Preparing the Biosafety Cabinet for Operation
Installation instructions (Labconco P/N 1056801) are attached to the sash of the
biosafety cabinet. If these instructions are missing or unclear, contact Product Service at
800-821-5525 or 816-333-8811. The following are located in a box either taped to the
top of or underneath the work surface:
User’s Manual CD
Drain Valve Assembly and fasteners
Power Cord
Product Registration Card
Vacu-PassTM Accessories (optional)
If you did not receive one or more of the components listed for the cabinet, or if any of
the components are damaged, contact Labconco Corporation immediately for further
instructions.
Moving and Lifting the Cabinet
Move the cabinet, attached to its pallet, by using a floor jack, or a furniture dolly underneath the
unit. DO NOT move the cabinet by tilting it onto a hand truck.
Product Service 1-800-522-7658
47
When lifting the cabinet DO NOT lift the cabinet in the middle front area of the hull. Lifting here
may bend or distort the bottom of the cabinet, causing damage to the unit.
Installing the Biosafety Cabinet on an Existing Work Surface
Note: The biosafety cabinet is very top heavy. Use caution when lifting or moving it.
When installing the biosafety cabinet onto an existing work surface or benchtop, ensure
that the structure can safely support the combined weight of the cabinet and any related
equipment. The work surface should be at least as wide as the cabinet and 31 inches (787
mm) deep to properly support the unit.
A hole or notch may be cut in the supporting surface in the right front corner to
accommodate the optional drain valve.
Product Service 1-800-522-7658
48
Installing the Cabinet on a Labconco Base Stand
Width
Base Stand w/Feet Model #
4'
3401004
6'
3401006
Width
Manual Lift Stand #
Electric (115V) Lift Stand
#
Electric (230V) Lift Stand
#
4'
3780201
3780101
3780104
6'
3780202
3780102
3780105
115V SoLo Stand
#
230V SoLo
No. America
Plug #
230V SoLo
UK Plug #
230V SoLo
Schuko Plug
#
230V SoLo
China/Australia
Plug #
4'
3780311
3780315
3780331
3780335
3780339
6'
3780313
3780317
3780333
3780337
3780341
Table 3-1
Table 3-2
Table 3-3
Labconco offers accessory Base Stands in a variety of configurations to suit your
particular needs. Stands can be ordered with adjustable telescoping legs or with a
manually or electrically adjustable hydraulic lift.
Telescoping Base Stands
These stands are included with some Axiom models, or are available separately. The
base stands for each width cabinet are listed in Table 3-1 below. An optional caster
wheel kit is available (part # 3730500).
Manual or Electric Hydraulic Lift Base Stands
These base stands offer infinitely adjustable height between 25.5 and 33.5 inches (648
to 851 mm), giving a cabinet work surface height of 28.0 to 36.0 inches. The height is
adjusted either by a manual (hand crank) or electric pump that drives hydraulic rams in
the legs of the stands. All of the hydraulic stands are equipped with fixed feet, but can
be converted to caster wheels with the addition of Caster Kit #3784000. The base
stands for each cabinet size is listed in Table 3-2 below.
Note: When installing the cabinet on the hydraulic lift base stand, ensure that the
hydraulic lines and the electrical cord are clear of any obstructions before installing the
cabinet on the stand or operating the lift system.
SoLoTM Electric Hydraulic Lift Base Stands
These base stands permit the Axiom to be lowered enough to be transferred through a
standard doorway as low as 78 inches. Casters provide mobility and lock in place. The
SoLo Stands for each Purifier Axiom series model is listed below.
Product Service 1-800-522-7658
49
Optional Exhaust Connection Requirements
Certain applications such as working with odorous products or volatile toxic materials
will require the connection of the biosafety cabinet to an exhaust system.
Note: The Type C1 exhaust connection includes an integral inlet relief valve, which
functions as a one-way, or check valve. During operation, the exhaust system draws all
of the cabinet’s exhaust air, plus a volume of room air through the relief valve into the
exhaust duct. The inlet relief valve functions as a “shock absorber” allowing the cabinet
to maintain optimal inflow during changes in room air pressure.
Note: Because the Type C1 cabinet has an integral exhaust fan, the vacuum
requirements of the exhaust system will be much lower than existing Type B units.
Please see the volume and vacuum requirements in Table 2-1, in
connect the biosafety cabinet to an exhaust system:
Note: If the research involves the use of toxic compounds or volatile materials, contact
the facility’s safety officer or Labconco to ensure that the biosafety cabinet and its
exhaust system are compatible with the materials you will be working with.
in
Chapter 2: Prerequisites
If you intend to
Product Service 1-800-522-7658
50
Configuring for an Exhaust System Connection
Figure 3-1
Note: The Type C1 is configured at the factory to operate in recirculating mode (NOT
connected
inlet relief valve position. If you intend to connect the Type C1 to an exhaust
system, YOU MUST RECONFIGURE IT FOR THIS INSTALLATION.
Note: If the Type C1 is connected to an exhaust system, and you choose to disconnect
it from the exhaust system, to exhaust its HEPA-filtered air back into the laboratory,
YOU MUST RECONFIGURE IT FOR THIS INSTALLATION. These instructions
follow.
to an exhaust system). When operating in this mode, the cabinet ignores the
a) Mechanical configuration
1. Unplug the Axiom. Using an appropriate ladder or platform, remove the
exhaust cover panel on the top right side of the exhaust cover, and install it
over the hole on the left side. Hand tighten the wing nuts to secure it, as
shown in figure 3-1.
2. Connect the Axiom’s connection collar to the exhaust system, ensuring the
connection meets all appropriate codes and regulations.
Exhaust Cover Panel
Product Service 1-800-522-7658
51
b) Electronic configuration
Keypad operations are shown as
green italics
1. With the unit in operation, access the menu by pressing the
Display Mode Menu Mode
Selecting the Configuration Menu
2. Using the ▲ and ▼ buttons on the touchpad, highlight the
.
display panel will show the first level menu. Select
▲ or ▼ buttons until the
or press
it will be highlighted when selected. Press OK and you will get an Attention
screen, advising you the following screens may alter the operation of the Axiom.
Press OK to continue:
Menu
to return to the previous menu level.
blue bold italic
Service
Menu
. Menu screen selections are shown as
Menu
Service
is highlighted. Press OK to accept that option,
menu by pressing the
Configuration
button. The
option-
OK
Product Service 1-800-522-7658
52
3. The screen will now prompt you for the password;
it is:
Light
UV Light
Timer
Timer
OK
Note: Any other key sequence will return you to the
Attention screen.
4. The first screen allows you to select whether the
Axiom is connected to an exhaust system or not.
IT IS CRITICAL THAT THE
HAS AN EXHAUST CONNECTION
SELECTED. Press OK to continue.
5. The second screen allows you to set how long the
blowers in the Axiom will continue to operate in the
event of an exhaust system failure. The interval
can be programmed from 0-300 seconds.
THIS CABINET
OPTION IS
Note: Consult with your facility’s safety officer or Labconco to help establish how long
the Axiom should continue to operate after an exhaust system failure.
6. The third screen allows you to set the sash height at
either 8 or 10 inches. IT IS CRITICAL THAT THE
YOU LEAVE THE SASH HEIGHT AS IT WAS SET
AT THE FACTORY, UNLESS YOU WISH TO
RECERTIFY THE CABINET AT ITS NEW
SETTING.
Product Service 1-800-522-7658
53
7. The fourth screen allows you to select
whether the Axiom has a UV light or not. IT
IS CRITICAL THAT THE YOU LEAVE THE
UV LIGHT CONFIGURATION AS IT WAS
SET AT THE FACTORY. Press OK to return
to the first Configuration screen.
The unit is now properly configured for operation connected to an exhaust system. In
this mode, the unit will display an exhaust alarm if the inlet relief valve closes during
operation.
NOTE: If you ever want to disconnect the Axiom from the exhaust system, and use it in
a recirculating mode, you must reconfigure it as such.
Product Service 1-800-522-7658
54
Disconnecting the Axiom from an Exhaust System Connection to Operate in
Figure 3-1a
Reciculation
a) Mechanical configuration
1. Unplug the Axiom. Using an appropriate ladder or platform, remove the
exhaust cover panel on the top left side of the exhaust cover, and install it
on the studs on the right side. Hand tighten the wing nuts to secure it, as
shown in figure 3-1a.
2. Disconnect the Axiom’s connection collar from the exhaust system, and cap
the building’s exhaust connection in a way that meets all appropriate codes
and regulations. Leave the Axiom’s exhaust collar open to allow for
unrestricted airflow out of the unit.
Exhaust Cover Panel
Product Service 1-800-522-7658
55
b) Electronic configuration
Keypad operations are shown as
green italics
1. With the unit in operation, access the menu by pressing the
Menu Mode
Selecting the Configuration Menu
2. Using the ▲ and ▼ buttons on the touchpad, highlight the
.
display panel will show the first level menu. Select
▲or ▼ buttons until the
or press
Display Mode
it will be highlighted when selected. Press OK and you will get an Attention
screen, advising you the following screens may alter the operation of the Axiom.
Press OK to continue:
Menu
to return to the previous menu level.
blue bold italic
Service
is highlighted. Press OK to accept that option,
Menu
. Menu screen selections are shown as
Service
Menu
button. The
menu by pressing the
Configuration
option-
OK
Product Service 1-800-522-7658
56
3. The screen will now prompt you for the password;
it is:
Light
UV Light
Timer
Timer
OK
Note: Any other key sequence will return you to the Attention screen.
4. The first screen allows you to select whether the
Axiom is connected to an exhaust system or not. IT
IS CRITICAL THAT THE
NO EXHAUST CONNECTION
SELECTED. Press OK to continue.
.
THIS CABINET HAS
OPTION IS
5. The second screen allows you to set the sash height
at either 8 or 10 inches. IT IS CRITICAL THAT
THE YOU LEAVE THE SASH HEIGHT AS IT WAS
SET AT THE FACTORY, UNLESS YOU WISH TO
RECERTIFY THE CABINET AT ITS NEW
SETTING.
6. The third screen allows you to select whether the
Axiom has a UV light or not. IT IS CRITICAL
THAT THE YOU LEAVE THE UV LIGHT
CONFIGURATION AS IT WAS SET AT THE
FACTORY. Press OK to return to the first
Configuration screen.
The unit is now properly configured for operation recirculating its filtered exhaust air
into the room. In this mode, the unit will NOT display an exhaust alarm with the inlet
relief valve closed during operation.
NOTE: If you ever want to reconnect the Axiom to the exhaust system, you must
reconfigure it as such.
Product Service 1-800-522-7658
57
Connecting the Biosafety Cabinet to Utility Service Lines
Figure 3-2
Note: Some models have a solenoid valve connected to the service valve on the right
side, rear position. The solenoid prevents gas from flowing to the service valve when the
unit blower is off. It is the only service valve position that can be fitted with a solenoid
valve. Connect the gas service to the solenoid valve.
The service lines (if any) should be connected to the tube fitting(s) on the outside of the
liner wall as shown in Figure 3-2 To install the tubing, follow these steps:
1. Ensure that the tubing is ¼ inch O.D., soft metal, and that the end has been
completely deburred.
2. Route the tubing from the rear of the cabinet, ensuring that it will line up with the
slot in the back of the side panel. The slot is located from 8 ¾ to 11 ¼ inches (222
to 288 mm) from the bottom of the cabinet.
Note: Make sure that the tube routing will not contact any electrical wires. DO NOT
loop service line tubing within the side panels of the cabinet.
3. Make sure that the nut on the tube fitting is loose, but do not remove it. Look inside
the fitting to make sure the tube ferrule is there.
4. Push the tube into the fitting until it is properly seated. The tube will go
approximately ¾ inch (19 mm) into the fitting.
5. Tighten the tube fitting nut hand tight and then, using a 7/16-inch wrench, tighten it
at least ¾ turn more.
6. Close the service valve in the biosafety cabinet and then slowly open the shutoff
valve on the service valve. Test all fittings for leakage. Tighten the tube nut slightly
if needed.
Tube fitting
Tube fitting nut
Product Service 1-800-522-7658
58
Optional Vacu-PassTM Cord & Cable Portal Use
Figure 3-3
Note: There must be enough clearance to pass the cord or cable between the Axiom’s
exterior dress panel and any obstruction.
Note: Some Vacu-Pass components and the cord or cable passing through it may
become contaminated during use of the cabinet. Ensure all potentially contaminated
components are surface decontaminated before handling or removal from the cabinet.
1. Remove the grommet from the liner side wall. Remove the solid sealing plug from
the body of the portal by either pressing it through from the outside, or by carefully
inserting a spatula or similar device between the sealing plug and the body of the
portal, and prying the plug out.
2. Pass the cord or cable through the body of the portal, and then through one of the
plugs that has been cut for cord or cable use, then through the grommet, as shown
in Figure 3-3.
Note: select a plug with a hole that is slightly smaller than the cord or cable, to create a
proper seal. This will also help minimize movement of the cord or cable if it is
accidentally pulled during use.
3. Position the cord or cable as it will be used in the cabinet, and then push the plug
back into the body of the portal until it seats in the portal. Reinstall the grommet.
Product Service 1-800-522-7658
59
Drain Valve Installation
Figure 3-4
In order to prevent damage during shipping, the drain valve assembly has not been
installed. If desired, the valve should be installed after the cabinet is in its final location.
To install the valve assembly, follow these steps:
1. Lift the work surfaces out of the biosafety cabinet by lifting on the knobs at the front
of the work surface.
2. Using a putty knife, remove and discard the stainless steel cover that is sealed over
the drain mounting holes. Scrape out remaining sealant that is around the holes.
3. Apply a light coating of silicone sealant (user supplied) to the mounting surface of
the drain assembly. Attach the drain assembly under the bottom of the cabinet as
shown in Figure 3-4. Wipe off any excess sealant from the cabinet bottom. Ensure
that the center drain hole is unobstructed.
4. Make sure the drain valve is in the closed position.
5. Reinstall the work surfaces.
6. Allow the silicone sealant to cure for at least eight hours before exposing it to liquid.
NOTE: The drain valve assembly attaches to the underside of the cabinet bottom.
Apply a light coat of silicone sealant to this surface
of the connector, aligning the three holes in the
connector with the three holes in the biosafety
cabinet liner.
Product Service 1-800-522-7658
60
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
61
Section Four -
Figure 4-1
Initial Operation of the Axiom
This section will take you through the steps to begin initial operation of the Axiom, with
an explanation the controls, display and options, in order to prepare the unit for its
initial certification.
System Reset Switch
The biosafety cabinet has a system reset switch for resetting its microprocessors. The
switch is located on the front of the electronics module, on top of the cabinet, as shown
in Figure 4-1. Ensure that the switch is in the “ON” (up) position before attempting to
operate the cabinet.
The System Reset
Switch
Product Service 1-800-522-7658
62
Information Center
Figure 4-2a
Figure 4-2b
10:03
Figure 4-3
The Information Center is an LCD display located on the right side wall at eye level.
When the blower is started, if the Axiom is configured to be connected to an exhaust
system, Figure 4-2a will appear for 60 seconds while the unit initiates operation.
If the unit is not connected to an exhaust system, screen 4-2b will appear for the first
60 seconds of operation. After 60 seconds, the default display screen will appear. The
display provides a clock, the life remaining for both filters, the cabinet’s current status,
inflow velocities (if equipped with the optional airflow sensor), as shown in Figure 4-3.
In the event of an alarm, the Information Center will immediately display a context
sensitive display indicating the cause of the alarm, and possible solutions, as shown in
Figures 4-4a-f.
The display will enter sleep mode, turning itself off, one minute after the blower is
turned off or the sash is closed.
Clock
Filter Life
Product Service 1-800-522-7658
63
Alarm Screens
Figure 4-4b
Figure 4-4f
Figure 4-4a
Figure 4-4c
Figure 4-4d
Figure 4-4e
Sash is too high
The sash is open too far for safe operation.
Airflow Alerts
The airflow patterns in the cabinet have changed, resulting
in a sudden change in either motor speed. This is most likely
due to a blockage of the grille or the exhaust filter outlet. It
may also be caused by removal of the work surface(s) while
the cabinet is in operation.
Exhaust Fan Alarm
There has been a failure of the exhaust fan, or its
communication to the cabinet’s control board. DO NOT USE
THE CABINET UNTIL THE PROBLEM HAS BEEN
CORRECTED.
Exhaust System Alarm-Active Protection Mode
When connected to an exhaust system, and the flow drops
below acceptable limits, this screen will appear. When the
timer reaches 0, the supply blower will shut off, and the
exhaust fan will continue to operate for 10 more seconds,
protecting the operator.
Exhaust System Alarm
After the countdown reaches 0, the exhaust fan will shut off
and this screen will be displayed. If this alarm is displayed,
the Axiom blower will need to be turned off, and then back
on again to reset the alarm. Frequent Exhaust System
Alarms indicate unstable or insufficient exhaust flow, and
must be corrected.
System Error
The motors and display circuit board are not communicating
properly. DO NOT USE THE CABINET UNTIL THE PROBLEM
HAS BEEN CORRECTED.
Product Service 1-800-522-7658
64
Operating the Sliding Sash
Figure 4-5
The counterbalanced, anti-racking sash mechanism requires only a few pounds of force
to move the sash up or down. You can open or close the sash smoothly with one or two
hands positioned on either handle.
The sash position alarm and safety interlock system senses the sash position and acts
appropriately. The biosafety cabinet has been programmed to operate at either an 8- or
10-inch (203-,250- mm) sash opening, depending on model. Raising the sash above its
operating height will activate the audible and visual alarms. The audible alarm can be
temporarily muted (for approximately five minutes) by depressing and releasing the
OK/Mute
and defeat the muting of the alarm. The safety interlock system senses when the sash is
closed and allows the optional ultraviolet (UV) lamp to operate only when the sash is
closed, to protect the operator from irradiation.
button. Closing the sash back to its operating position will reset the alarm
Starting the Biosafety Cabinet
1. To start the biosafety cabinet, raise the sash until its bottom edge aligns with the
proper sash height label on the left corner post, as decal is shown in Figure 4-5.
2. Press the blower button to start the unit. The unit will display a standby screen
for approximately 60 seconds to allow the cabinet to reach proper operating
conditions. If the alarm sounds, recheck the sash position. If the sash is too
high, the sash audible alarm and the LCD display will indicate the sash is too
high.
3. To turn the UV light on, the sash must be completely closed to prevent the
escape of any UV radiation. Push the UV light button to activate the UV light.
Note: The sash must be completely closed for the UV light to activate.
Sash height labels
Product Service 1-800-522-7658
65
The Axiom Touchpad
Figure 4-6
The touchpad of the Axiom is shown in Figure 4-6. Take a moment to get familiar with
the buttons, their locations and functions. Also familiarize yourself with the display
located on the right side wall. The display will report system functions, such as filter
capacity, timer displays, alarm or error messages, as well as icons that illuminate when
cabinet functions such as UV light and blower are operational.
Blower Button – Starts or stops the cabinet blower. When the
blower is in Smart-StartTM mode, opening the sash from the closed
position turns the blower on automatically. When in recirculating
mode with Night-SmartTM, when the sash is closed, the motor slows
to idle to maintain air cleanliness in the work area. When the sash
is reopened, the blower resumes normal operation. Pressing this
button overrides Smart-Start and Night-Smart operation
Light Button – Turns the fluorescent lamps on or off. Closing the
sash automatically turns the lights off. When the lights are in
Smart-Start mode, raising the sash turns the lights on
automatically.
Outlet Button – Turns the electrical outlets in the work area on or
off.
UV Light Button – Turns the UV lamp on or off. When the UV
lamp is in Smart-Start mode, closing the sash turns the light on.
When the sash is raised, the light turns off automatically.
Timer Button – Allows you to select either a repeating interval
timer, or an elapsed timer (stopwatch).
OK/Mute Button – Mutes all audible alarms for approximately 5
minutes, unless there is a system error alarm. When in the Menu
mode, this button is used to select an option.
Menu Button – This button toggles the display between the
display and menu modes. When in the menu mode, pressing this
button returns you to the previous menu level.
Select Buttons – Allow you to choose different options in the
menu mode.
Product Service 1-800-522-7658
66
Navigating the Axiom Menu Screens
100%
100%
MyLogicTM allows you to use the Smart-Start or Night-Smart features that activate
functions automatically when the sash is opened or closed. Night-Smart will only work if
the cabinet is not connected to an exhaust system.
If equipped, the UV lamp can be programmed to operate for a given time interval when
the sash is closed, before it shuts off.
NOTE: When you are in the menu mode, if a selection is not made within 30
seconds, the display will reset back to display mode.
Keypad operations are shown as
green italics
NOTE: Pressing the appropriate touchpad button will override Smart-Start or
Night-Smart selections.
To access the menu, press the
menu. To select from the various menu options press the ▲ or ▼ buttons until the
selected option is displayed. Press
return to the previous menu level.
.
Display Mode Menu Mode
blue bold italic
Menu
button. The display panel will show the first level
OK/Mute
Menu
. Menu screen selections are shown as
to accept that option, or press
Menu
to
Product Service 1-800-522-7658
67
Navigating the MyLogicTM Menu Screens
The MyLogic screens will allow you to set the cabinet’s clock, and to personalize its
operation. Please note all MyLogic screens have a blue background.
Setting the Clock
Using the ▲ and ▼ buttons on the touchpad, highlight the
blue when selected. Press
Using the ▲ and ▼ buttons on the touchpad, highlight
when selected. Press
At this screen, select whether you want the clock
to display in a 12- or 24-Hour format.
When you have highlighted your choice, press
OK/MUTE
Use the ▲ and ▼ buttons to select the hour, and
press
Use the ▲ and ▼ buttons to select the minute,
and press
screen.
to go to the next screen…
OK/Mute
…
OK/MUTE
OK/MUTE
OK/MUTE
to return to the first MyLogic
to enter the first MyLogic screen:
OK/Mute
to enter the first clock setting screen:
set the clock
MyLogic
option-it will turn
-it will turn white
Product Service 1-800-522-7658
68
Configuring the Axiom
In the first MyLogic screen, use the ▲ and ▼
buttons on the touchpad to highlight
Logic for use
OK/MUTE
The first screen gives you the option of activating
the Smart-Start option for the blower; if you want
the cabinet blower to start every time you raise the
sash, select
start
is selected, then the blower must be manually
started from the keypad. When
pressed, the next configuration screen will appear.
The next screen gives you the option of activating
the Smart-Start option for the fluorescent light; if
you want the lights to turn on every time you raise
the sash, select
If
stay off
manually turned on from the keypad. When
OK/MUTE
will appear.
If you want the cabinet blower to run slowly,
maintaining reduced airflows every time you close
the sash, select
press
OK/Mute
blower will stop when the sash is closed. When
OK/MUTE
will appear.
If your Axiom is configured for a UV light, then you
will see the next two screens; if you want the UV
lamp to turn on every time you close the sash,
select
off
when the sash is closed. When
pressed, the final configuration screen will appear.
turn on
is selected, then the UV light will not turn on
-it will turn white when selected. Press
to enter the first configuration screen:
start
, and then press
turn on
is selected, then the lights must be
is pressed, the next configuration screen
, and then press
go into NightSmart mode
. If
stop
is selected, then the
is pressed, the next configuration screen
, and then press
OK/Mute
configure my
OK/Mute
OK/MUTE
OK/Mute
and then
. If
OK/MUTE
. If
is
stay
is
not
.
Product Service 1-800-522-7658
69
If you choose to use NightSmart option for the UV lamp,
this screen allows you to control the time the UV lamp will
remain on after the sash is closed. Use the ▲ and ▼
buttons on the touchpad to cycle through the time
intervals available, and then press
The screen will then return to the first MyLogic screen.
OK/MUTE
to select it.
Navigating the Settings Menu Screens
The Settings screens will allow an administrator to set some of the cabinet’s operational
parameters. Please note all Settings screens have a green background.
Using the ▲ and ▼ buttons on the touchpad, highlight the
green when selected. Press OK to enter the first Settings screen:
Settings
option-it will turn
OK Button
Display Options
Units of Measure
Note: The Units of Measure refers to the display of
airflow velocities if the cabinet is equipped with the
optional airflow sensor.
Using the ▲ and ▼ buttons on the touchpad,
highlight the
white when selected, and then press OK. Using the
▲ and ▼ buttons on the touchpad, highlight either
metric
when selected, and then press OK. The screen will
then return to the first Settings screen.
or
Units of Measure
imperial
units of measure-it will turn white
option-it will turn
Product Service 1-800-522-7658
70
Startup tone
The Security Lock Is:
or to choose,
OK to select, MENU to return
turned on
button for more than 5
seconds to unlock the Logic)
turned off
(Hold the
Security Lock
Using the ▲ and ▼ buttons on the touchpad, highlight the
Startup Tone
option-it will turn white when selected, and
then press OK. Using the ▲ and ▼ buttons on the
touchpad, highlight either
Turned on
or
Turned off
option.
When turned on, an audible beep will sound during the
first 60 seconds of blower operation to caution the user
that the unit is not yet ready for use.
Security Lock
Note: The Security Lock feature “locks” the keypad to prevent unauthorized use of the
cabinet. The security lock is unlocked by holding the ▼ button for 5 seconds. The lock
deactivates after cabinet is unlocked.
From the Settings menu screen, use the ▲ and ▼ buttons
on the touchpad to highlight the
turn white when selected. Press
Security Lock screen. Using the ▲ and ▼ buttons on the
touchpad, highlight either
turned on
white when selected, press
return to the first Settings screen.
RS-232 Output Rate
Note: This selection will only work if the optional EN/RS-232 board is installed.
This menu option selects the rate that the RS-232 board outputs data. Data can be
output at a rate of once per second, once every 10 seconds, once every 30 seconds, or
once per minute.
From the Settings menu screen, use the ▲ and ▼ buttons
on the touchpad to highlight the
white when selected. Press
232 output screen. Using the ▲ and ▼ buttons on the
touchpad, highlight either the data output rate preferred.
It will turn white when selected, and then press OK. The
screen will then return to the first Settings screen.
Security Lock
OK/MUTE
or
OK/Mute
RS-232 output
OK/MUTE
option-it will
to enter the
turned off
-it will turn
. The screen will then
-it will turn
to enter the RS-
Product Service 1-800-522-7658
71
UV Settings
For models equipped with the optional UV light the Axiom has an integral UV light
maintenance system. It allows you to define how many hours you want the UV lamp to
operate before receiving a reminder to replace it, a way to monitor how many hours the
lamp has been on, and the means to reset the UV lamp hourmeter.
UV Lamp Hourmeter
This display only shows how many hours the UV lamp has been lit, and how many hours
remain until you will receive a warning to replace the lamp.
From the Settings menu screen, use the ▲ and ▼
buttons on the touchpad to highlight the
option-it will turn white when selected. Press
enter the UV Settings screen. Using the ▲ and ▼ buttons
on the touchpad, highlight UV Hourmeter-it will turn white
when selected, and then press
then return to the UV Hourmeter screen.
This screen displays how many hours the UV lamp has
operated, and how many hours of operation remain before
replacement is recommended. When finished with this
screen, press
screen.
MENU
to return to the first UV Settings
OK/Mute
Reset UV Lamp Hourmeter
This option lets you reset the UV hourmeter to 0 hours
whenever the lamp has been replaced.
This screen allows you to reset the UV Hourmeter to 0
hours if you press
you to the first UV Settings screen without resetting the
hourmeter.
OK/Mute
. Pressing
Change UV Lamp Life
In this screen, you can set the number of operating hours before receiving the replace
UV lamp warning. For most UV lamps, the output of UV light decreases at a constant
rate. Typically, after 6,000 hours of operation the lamp will output 80%. This option
allows you to set operational life of the UV lamp, in 100 hour increments.
From the UV Settings menu screen, use the ▲ and ▼
buttons on the touchpad to highlight the
it will turn white when selected. Press
the Set UV life screen. Use the ▲ and ▼ buttons to increase
or decrease the lamp life in 100 hour increments, until the
desired value is displayed, and then press
screen will then return to the UV Settings screen.
UV Settings
OK/MUTE
. The screen will
MENU
will return
Set UV Life
OK/MUTE
to enter
OK/Mute
to
option-
. The
Product Service 1-800-522-7658
72
Timer Operation
NOTE: The timer button allows activation of an interval (countdown) or
stopwatch (elapsed) timer. The timers cannot be operated simultaneously.
To access the main timer menu, press the
operation. The main timer menu is shown on the LCD display. Use the ▲ and ▼ buttons
to highlight the
highlighted timer function.
Interval
or
Stopwatch
Timer
Timer. Press the
button anytime during normal
OK/MUTE
button to select the
Interval Timer Operation
1. When selected, the Interval Timer menu is displayed on the LCD. The timer
defaults to 0:00:00 (hours:minutes:seconds).
2. Press and hold the ▲ or ▼ buttons to increase or decrease the timer interval.
3. When the proper interval is entered on the display, press the
to start the timer.
4. When the timer reaches 0:00:00, an audible alarm will sound, and the timer will
reset itself and repeat the countdown.
5. Press the
6. Press the
menu.
OK/MUTE
Menu
button to pause the timer.
button to clear the interval timer and return to the main timer
OK/MUTE
button
Stopwatch Timer Operation
1. When selected, the Stopwatch Timer menu is displayed on the LCD. The timer
defaults to 0:00:00.
2. Press the
3. Press the
4. Press the
timer menu.
OK/MUTE
OK/MUTE
Menu
button to start the timer.
button again to zero the timer.
button to clear the stopwatch timer and return to the main
If An Airflow Alert Activates
The most common causes of an Airflow Alert are:
Blockage of the inlet grilles or exhaust outlet.
Removal of the work surface or grille during operation.
Resetting the Airflow Alert System
The Airflow Alert automatically resets to normal operation once the motor speed has
stabilized.
Product Service 1-800-522-7658
73
Section 5
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, MENU to escape
or to ch oose,
OK to select, MENU to return
Current Setting s
Restore Default
Diagnostics
Configur ation
Calibration
Service
A TTENTION!
The following screens are used
to alter the operatio n of the
Logic. They sh ould only be used
by a qualified certifier as part
of the certification process.
Calibration
OKtoproceed,MENUtoreturn
PASSWORD:
Calibration
Certification Procedures for the Axiom
This section will outline test procedures to validate the performance of the Axiom.
Note: These are the only Labconco-approved test procedures for validating
the performance of the Axiom Biosafety Cabinet. Other test procedures may
yield different or inaccurate test results.
NOTE: In order to properly certify the Axiom, you must obtain an Axiom
Certifier Kit, Labconco P/N 3858400. Qualified certifiers can obtain this kit by
contacting Labconco Customer Service Department at 800-821-5525.
Note: The ECM motor is programmed by Labconco to deliver a constant
volume of air throughout the life of the HEPA filters. Any changes to the
blower speed control should be small (less than 5 units).
Accessing the Certifier’s Menu
Note: You will need to access this menu to do any of the following:
Adjust the blower speed
To reset the filter gauge
To calibrate the optional airflow sensor
Adjusting the Downflow, Inflow and Filter Life Gauges
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
Menu
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
4. Press the ▼ button until the
Calibration
will turn white).
5. Press
OK/Mute
to start the calibration procedure.
6. You will see a
warning screen
alerting you that you are about to
alter the BSC’s settings.
7. Press
OK/Mute
to input the password.
8. When requested for the password press
Product Service 1-800-522-7658
option is highlighted (it
Light, UV light
,
74
The Inflow displayed
value is: 102 FPM
Calibration
Inflow Display
or to change display value,
UV Light to reset to 105 FPM,
OK to select, MENU to finish
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Supply Fan Speed
or to change motor speed,
OK to select, MENU to escape
Calibration
Supply Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Reset Filter Gauge to 100%
Leave Gauge unchanged
Set Gauge to new setting
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Exhaust Fan Speed
or to change motor speed,
OK to select, MENU to escape
Calibration
Exhaust Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Reset Filter Gauge to 100%
Leave Gauge unchanged
Set Gauge to new setting
Timer, Timer
then
OK/Mute
.
9. If the password is properly entered, the first certification screen will display the supply blower motor’s PWM setting. Press the ▲
or ▼ button to increase or decrease the blower speed as
needed. When the speed is set properly, press the
OK/Mute
button to lock the new blower speed setting, and continue to the
filter life screen.
10. If this is an initial certification or a recertification after supply
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
.
. If
Set
11. The next certification screen will display the exhaust blower motor’s PWM setting. Press the ▲ or ▼ button to increase or
decrease the blower speed as needed. When the speed is set
properly, press the
OK/Mute
button to lock the new blower
speed setting, and continue to the filter life screen.
12. If this is an initial certification or a recertification after exhaust
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
.
. If
Set
13. If the unit is has no airflow sensor, after the filter gauge option
is selected and you press
OK/Mute
, the Axiom will power
down, and then restart with the new settings. If the Unit has an
airflow sensor, you will then be asked to calibrate the inflow
sensor to match the value you obtained when you measured the
inflow. After the inflow is calibrated, and you press
OK/Mute
,
the Axiom will power down, and then restart with the new
settings.
Product Service 1-800-522-7658
.
.
75
Axiom Filter Life Gauge Operation and Resetting for Local Conditions
The filter life gauge calculates the remaining filter life by measuring and comparing the current
motor speed to the initial speed noted at the factory during assembly, and the calculated
maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left
max. speed-original speed
So
anything
Blocking the grille.
Raising the air temperature.
Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic dampening
of the gauge will limit the change in readings to approximately 1%/minute.
Axiom Biosafety Cabinets being installed at altitudes or operating at temperatures significantly
different from those at the time of manufacture (900 +/- 500 ft above sea level, 75o +/- 5o F)
must
have their filter life gauge recalibrated for local conditions. Failure to do so will result in the
users noticing a steady drop in Percent (%) Filter Life remaining as the unit operates. Below are
the instructions on how to correct the Filter Life Gauge for local conditions.
1. Ensure to correct all measurement equipment for local conditions (temperature, absolute
2. As the elevation or the ambient temperature rises, the motor power factor will have to be
3. The Axiom MUST be recertified using instruments corrected for local conditions.
4. During recertification the certifier MUST RESET THE FILTER LIFE GAUGE, INDICATING A
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND RECERTIFIED FOR
6. If you do not wish to reset the filter gauge, select the option “Filter not changed”, and
7. Either selection will finish the calibration mode, or lead to calibration of inflow and
that changes the motor’s current speed, like:
pressure). Anemometers may not have this ability and might have to be done manually;
whereas, a ShortRidgeTM instrument has a setting to correct for local conditions.
reduced to compensate. For an initial certification, the motors’ speeds should be reduced
until it equals the Axiom’s “Initial Motor Speed”as reported on the unit’s test sheet, plus
approximately 10-15 RPM per each additional 1000 feet of elevation.
NEW FILTER HAS BEEN INSTALLED.
ITS LOCAL CONDITION, will the filter life gauge register 100% (+/- 2%) during
operation. As the Filters then load, the filter life gauges will then begin to drop as
appropriate.
press “Mute/OK”.
downflow velocities.
Product Service 1-800-522-7658
76
HEPA Leak Test Information
All Axiom models were tested to the HEPA Filter Leak Test as described in ANSI/NSF
Standard 49:2012.
Note: ensure all internal surfaces of the Axiom have been appropriately
decontaminated before proceeding.
Supply HEPA Filter Leak Test
All Axiom models were tested to the HEPA Filter Leak Test as described in ANSI/NSF
Standard 49:2012.
Note: ensure all internal surfaces of the Axiom have been appropriately
decontaminated before proceeding.
Note: For all Axiom models, the work surfaces may be removed if desired, and
the aerosol generator discharge should be placed to the left of (but NOT in)
the center exhaust duct nearby to inject the aerosol as shown in Figure 5-1.
Figure 5-1
Place aerosol generator discharge into
the left recirculation duct
Center exhaust duct
Product Service 1-800-522-7658
77
If the Axiom is Contaminated
Model
3044-
3046-
Air Displacement (CFM)
520
665
Laskin Nozzles needed
1
1
Theoretical aerosol conc.
(ug/l)1
26
20
Actual aerosol conc. (ug/l)1
13
12
(An upstream concentration cannot be established)
If the Axiom has been used with biohazardous, toxic chemicals, or radioisotopes, the
DOP access line cannot be used. The upstream concentration cannot be measured
directly. Testing at Labconco has shown the actual concentration varies from the
calculated value. Table 5-1 shows the actual vs. calculated concentrations for the Axiom
models.
Table 5-1
Supply HEPA Filter Leak Test Specifications
1. The calculated concentration was established by the formula:
Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
2. Based on Mineral oil
If the Axiom is Uncontaminated
(Establishing an Upstream Concentration)
The Axiom utilizes an aerosol access tube for sampling the upstream concentration of
aerosol. If after reading these instructions, you have further questions, please contact
Labconco's Product Service Department.
1. Remove the center work surface by lifting the handles on either wing work
surface. Pull the center work surface straight out of the Axiom. Repeat for the
right wing work surface.
2. Locate the access tube on right side of the rear plenum wall, passing through the
towel catch. As shown in Figure 5-2.
Figure 5-2
Product Service 1-800-522-7658
78
3. Pull the tube toward the front of the unit. Remove the access tube cover.
4. Using an appropriate photometer, connect the unit's upstream line to the access
tube.
Note: Keep the photometer sampling tube as short as possible. It should
never exceed 6 feet maximum.
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
2. Check the oil level of the generator – it must be within 1/8” of the level line
when the generator is sitting level.
3. Establish the 100% and 0% concentration levels for the photometer.
4. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
5. Remove the diffuser by raising the sash as high as it will go, and then removing the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-3.
Figure 5-3
Removing the diffuser acorn nuts (Dress panel and
lamps removed for clarity only).
Note: The diffuser acorn nuts are secured to the studs with a removable thread locking
compound to prevent them from vibrating loose during shipment of the Axiom. There
may be some resistance the first time the nuts are removed; this is normal. No
additional thread locking compound need be applied to these acorn nuts unless the unit
is being prepared for shipment.
1. Lower the front edge of the diffuser until it clears the bottom of the sash, and
then pull the diffuser straight out of the cabinet, as shown in Figure 5-4.
Figure 5-4
Product Service 1-800-522-7658
79
2. The Axiom is now ready for the Supply HEPA Filter Leak Test. Set the
photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum
at the sampling port of the pistol.
3. Open one Laskin nozzle.
4. Ensure the pressure gauge on the generator is reading 22 +/- 1 PSIG.
5. Scan the downstream side of the HEPA filter by passing the sampling nozzle of
the gun in slightly overlapping strokes over the entire surface of both of the
filters, with the sampling port not more than 1 inch from the surface of the filter
media. Scan the entire periphery of the filters and the gaskets between the filter
frame and the Axiom frame. Scanning shall be done at a traverse rate of not
more than 2 inches per second.
Figure 5-5
Note: Operation of the photometer may become erratic
when testing the front edge of the supply filter frame,
due to aspiration of room air into the front of the work
area. This problem can be minimized or eliminated by
placing the edge of a sheet of rigid plastic or metal at
the edge of the filter gasket when scanning this area, as
shown in Figure 5-15.
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassembly
When reinstalling the supply filter diffuser, ensure that the two holes in the back edge of
the diffuser engage the diffuser support posts on the rear wall of the work area, as
shown in Figure 5-6. Reinstall the prefilter.
Figure 5-6
Diffuser pins engaging the holes in the rear of
the diffuser.
Product Service 1-800-522-7658
80
Exhaust HEPA Filter Leak Test
Model
3044-
3046-
Air Displacement (CFM)
723
1083
Laskin Nozzles needed
2
2
Theoretical aerosol conc.
(ug/l)1
38
25
Actual aerosol conc. (ug/l)1
21
17
All Axiom models were tested to the HEPA Filter Leak Test as described in ANSI/NSF
Standard 49:2012.
Note: ensure all internal surfaces of the Axiom have been appropriately
decontaminated before proceeding.
Note: For all Axiom models, the work surface may be removed if desired, and
the aerosol generator discharge should be placed in the center exhaust duct
to inject the aerosol as shown in Figure 5-7.
Figure 5-7
Testing at Labconco has shown the actual concentration varies from the calculated
value. Table 5-2 shows the actual vs. calculated concentrations for the models.
Table 5-2
Exhaust HEPA Filter Leak Test Specifications
3. The calculated concentration was established by the formula:
Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
4. Based on Mineral oil
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes.
Leave the valve in the “CLEAR” setting.
2. Check the oil level of the generator – it must be within 1/8” of the level line
when the generator is sitting level.
3. Establish the 100% and 0% concentration levels for the photometer.
Product Service 1-800-522-7658
81
4. If connected to an exhaust
system, secure the Inlet
Relief Valve in an open
position, to keep the cabinet
blowers operating, and then
remove the screws that
secure the front of the
exhaust connection to its
structure. Place the front
panel aside.
5. The Axiom is now ready for the Exhaust HEPA Filter Leak Test. Set the
photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper
vacuum at the sampling tube.
6. Open the Laskin nozzle(s).
7. Ensure the pressure gauge on the
generator is reading 22 +/- 1
PSIG.
8. Using a rigid 18” long x 3/8” o.d.
tube connected to the
photometer probe pickup, Scan
the downstream side of the filter,
resting the tube in the ridges
located on the top of the opening.
By resting the tubing in
successive ridges, and
alternatively pushing the probe in
on the first ridge, then shifting
the tube to the next ridge, and
then pulling it out, you can
quickly scan the filter surface in
overlapping strokes. By resting
your index finger under the tube
during scanning, you can
accurately control the probe
position and height.
9. Observe the average
concentration of aerosol
downstream.
Acceptance
Average aerosol penetration shall not exceed 0.01%.
Product Service 1-800-522-7658
82
Downflow Velocities
Cabinet Width (Feet)
4 4 6
6
Sash Height (inches)
8
10 8 10
Nominal Avg. Downflow
(FPM)
65+/-5
65+/-5
55+/-5
55+/-5
Downflow test grid # of
points
24
24
36
36
Test Grid (# rows x #
columns)
3 x 8
3 x 8
3 x 12
3 x 12
Test Grid Data (in
inches)
Grid distance from back & sides
6.0
6.0
6.0
6.0
Distance between rows
5.75
5.55
5.75
5.55
Distance between columns
5.21
5.21
5.50
5.50
All Axiom models, are classified as having uniform downflow, and the average downflow
velocity for all 4-foot models is 65+/-5 FPM, and all 6-foot models is 55+/-5 FPM, tested
as per ANSI/NSF Standard 49:2012.
All readings should be in a plane 4 inches above the bottom edge of the sash, and the
UV Lamp, IV bar and all other accessories must be removed before performing
downflow test. The test grid dimensions are outlined in Table 5-3. When taking readings
in the back two rows, the anemometer probe should be pointing toward the nearest side
wall, as shown in figure 5-8. When reading the front row, the probe should point
outward, toward the front of the cabinet, as shown in Figure 5-9. The thermal
anemometer’s time constant should be set at 10-15 seconds for greater readout
stability.
Table 5-3
Downflow Test Specifications
Product Service 1-800-522-7658
83
Figure 5-8
Figure 5-9
Acceptance
Average downflow shall be 65 +/-5 FPM for all 4-foot models, and 55 +/-5 FPM for all 6foot models, with all test points being within +/- 16 FPM of the overall average.
Product Service 1-800-522-7658
84
Inflow Velocity Calculation - Primary Method
Width (feet)
4
6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.69
4.03
Nominal Avg. Exhaust Vol.
(CFM)
283
423
Avg. Exhaust Vol. Range
(CFM)
269-296
403-443
Width (feet)
4
6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
3.37
5.03
Nominal Avg. Exhaust Vol.
(CFM)
354
529
Avg. Exhaust Vol. Range
(CFM)
337-371
503-553
Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow
value.
The average inflow velocity for Axiom models is 105 ±5 FPM. It should be determined
by converting the inflow volume to the average inflow velocity. The inflow volume is
measured directly by sealing a direct inflow measuring flow meter to the face of the
unit. When corrected for local conditions, dividing the inflow volume by the opening area
will yield the average inflow velocity.
Table 5-4
Inflow Test Specifications – 8 inch Sash Opening
Inflow Test Specifications – 10 inch Sash Opening
Acceptance
Average inflow shall be meet the specified value.
Product Service 1-800-522-7658
85
Inflow Velocity Calculation - Secondary Method
If the primary method cannot be performed, the secondary inflow calculation method
should be used. The secondary method uses a hot wire thermal anemometer. In this
method, the sash is lowered, and a series of velocity readings are taken at the front of
the unit.
NOTE: You must use Labconco Certifier Kit, Labconco P/N 3858403 to
perform this test properly. Qualified certifiers can obtain this kit by
contacting Labconco Customer Service Department at 800-821-5525.
For each model Purifier, the sash should be closed until the appropriate marked
template contacts the sash stop and the bottom edge of the sash, as shown below in
Figure 5-10.
The thermal anemometer probe should be positioned such that the distance from the
bottom of the probe holder to the center of the sensor element equals “Sensor Distance”
as shown in Table 5-5. Use the marks on the 6-foot templates, or a scale as shown in
Figure 5-11 & 5-12 below.
Figure 5-10
Measuring the restricted access opening
height, using the appropriate template.
Ensure that the bottom of the template is
seated in the sash stop.
Product Service 1-800-522-7658
86
Cabinet Width (feet)
4
6
Sash Opening Template
4+
6+
Sensor distance (inches)
3.25
4
# of Test points
8
12
Test point location
*
*
Nominal Avg. Inflow Vel. (FPM)
283
231
Avg. Inflow Vel. Range (FPM)
249-274
221-222
Correction Factor (CF)
1.08
2
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
269-296
403-443
Sash Open Area (Sq. Ft)
2.69
4.03
Inflow Velocity Range (AIV / Sash open area)
100-110
100-110
Cabinet Width (feet)
4
6
Sash Opening Template
4+
6+
Sensor distance (inches)
3.25
4
# of Test points
8
12
Test point location
*
*
Nominal Avg. Inflow Vel. (FPM)
354
289
Avg. Inflow Vel. Range (FPM)
312-344
251-276
Correction Factor (CF)
1.08
2
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
337-371
503-553
Sash Open Area (Sq. Ft)
3.37
5.03
Inflow Velocity Range (AIV / Sash open area)
100-110
100-110
The Sensor Distance, as described in Table 5-5,
using the slots cut in the 6-foot Logic template.
4.00-inch mark
3.25-inch mark
The Sensor Distance, as described in Table 5-5,
using a scale.
Figure 5-11
Figure 5-12
Secondary Inflow Test Specifications – 8 Inch Sash Opening
Secondary Inflow Test Specifications – 10 Inch Sash Opening
Table 5-5
Product Service 1-800-522-7658
87
1. Locate the single row of holes at the front of the grille. Mark the 6
the side wall and subsequent test points every 9 holes until the number of test
points marked equals the width of the cabinet in feet (for a 3-foot cabinet, for
example, mark the first 3 points). Repeat for the opposite side, as shown in
Figure 5-13.
2. Start the Purifier, and let it operate for at least 5 minutes. Establish the
necessary correction factor to the thermal anemometer to ensure compliance
with its performance in a calibrated wind tunnel. This data should be available
from the calibrator of the thermal anemometer.
3. Calculate the manufacturers recommended correction factor(s) to correct for
local conditions of temperature, humidity, barometric pressure, altitude, etc.
4. Take a series of inflow velocities by placing the probe holder so that its center
mark aligns with the marked test holes. As shown in Figure 5-14.
5. Apply the wind tunnel correction and local condition correction factors to the
thermal anemometer readings.
6. Multiply the individual readings by the correction factor shown in Table 5-5.
7. Average the corrected readings.
8. The resulting value is the inflow volume in cubic feet per minute (CFM). In order
to convert this value to the average inflow velocity of feet per minute (FPM),
divide the volume by the sash open area given in Table 5-5. The resulting value
will be the calculated average inflow velocity in FPM.
th
hole from
Figure 5-13
Marking the test point locations.
Mark the 6th hole from either end, then mark every
9th hole until the number of marked points equal
the width of the cabinet in feet.
Repeat for the other side of the grille.
Measuring the Secondary Inflow Velocity.
Note the center of the probe holder aligns with the
test points marked earlier.
Acceptance
Average inflow shall meet the specification in Table 5-5.
Figure 5-14
Product Service 1-800-522-7658
88
Concurrent Balance Values
Model
30448
30441
30468
30461
DIM-measured Inflow (CFM)
283
354
423
529
Nominal Inflow through Valve (CFM)
40
40
40
40
Total DIM-measured (CFM)
323
394
473
569
Traverse-measured Exhaust (CFM)
387
480
556
684
Axiom Inflow and Inlet Valve flow numbers are established by a direct measurement of
air flow. Traditional exhaust system measurements are made using either an
anemometer or Pitot traverse methodology. Because of these different methodologies,
the total volume of air flowing through the exhaust system will vary.
Table 5-6
Concurrent Balance Volume Specifications
Product Service 1-800-522-7658
89
Work Area Air Cleanliness Test (optional)
If the customer wants to verify air cleanliness in the work area, use the following
procedure:
1. Mark test points at the geometric center of the work surface, and midway
between the center test point and each side wall.
2. Place a particle counter pickup on a test point, at a height of 16 inches above the
work surface, pointing into the airflow, as shown in Figure 5-15. Take three
samples of 1.0 ft3. Repeat for each test point.
3. Average the results.
Figure 5-15
Acceptance
The average count should be less than 100 particles 0.5um in size per ft3.
Product Service 1-800-522-7658
90
Fluorescent Light Level (optional)
The fluorescent light intensity should be measured as described in ANSI/NSF Standard
49:2012, Annex F.
NOTE: The light meter should be color- and cosign corrected for accurate
readings.
1. Test points should be marked along the centerline of the work surface, starting 6
inches from the side wall, with subsequent points 12 inches apart until the center
of the work surface is reached. Repeat for the other side of the work area.
2. Take background readings at the test. It should be 15 foot-candles maximum.
3. Turn on the fluorescent lights and let them warm up for at least 5 minutes.
4. Measure the light intensities at the test points.
Acceptance
The average light level should be no less than 45 foot-candles greater than the
background level, where maximum background light levels average a maximum of
15 foot-candles.
Most common causes for insufficient light levels are:
a. Malfunctioning lamp(s)
b. Old lamp(s)
c. Dusty/dirty lamp surfaces
Noise Level (optional)
The noise level should be measured as described in ANSI/NSF Standard 49:2012.
1. Noise level should be recorded from a single point, on the centerline of the
cabinet, at a position 14 inches above the work surface, and 12 inches from the
front of the cabinet.
2. Take a background reading with the cabinet blower off at the test point. It
should be less than 55 dBA.
3. Start the cabinet blower, and take a sound reading.
Acceptance
Sound levels should be less than 67 dBA when the cabinet is new, and less than 73
dBA when the filters are loaded.
Product Service 1-800-522-7658
91
Vibration (optional)
The vibration level should be measured as described in ANSI/NSF Standard 49:2012.
Note: The vibration meter should have a range of 20-20,000 Hz, and have an
output in displacement.
1. Vibration level should be recorded from a single point, on the geometric center
of the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Start the cabinet blower, and take a displacement reading.
Acceptance
Vibration should be less than 0.0002 inches displacement when the cabinet is new.
UV intensity (optional)
Note: The UV radiometer should measure light at a wavelength of 254nm.
1. UV intensity should be recorded from a single point, on the geometric center of
the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Close the sash, turn on the UV light, and let it warm up for at least 5 minutes.
Acceptance
The UV intensity should be at least 200 uW-cm2.
Most common causes for insufficient UV light levels are:
d. Malfunctioning lamp(s)
e. Old lamp(s)
f. Dusty/dirty lamp surfaces
Product Service 1-800-522-7658
92
Ground Fault Circuit Interrupter Test
(115/100 Volt models only)
Note: The GFCI tester must be able to simulate a fault of 3mA.
1. Place the tester into any of the Axiom’s outlets. The indicator lights of the tester
should indicate normal function, and the GFCI’s indicator LED should be lit.
2. Press the test button of the tester. The indicator lights should now indicate the
circuit is inactive, and the GFCI indicator LED should be off.
3. Reset the GFCI by pressing the RESET button on the right outlet. The tester will
again indicate normal operation, and the GFCI indicator LED will illuminate.
Figure 5-16
GFCI Reset Button
GFCI Test Button
GFCI Indicator LED
Acceptance
The GFCI trips during the simulated failure, and the indicator LED turns off. Pressing
the Reset button returns the GFCI to normal function.
Product Service 1-800-522-7658
93
Section 6
Axiom Service Operations
This section will review the tools needed, and common service operations for the Axiom.
Recommended Tools for Service
The tools needed for most common service operations are:
Certifier Kit, Labconco Part # 3858403
#2 Phillips Screwdriver or long bit for cordless drill
½-inch Socket with extension and ratchet
½-inch nut driver
7/16-inch socket or nut driver
5/16-inch socket or nut driver
Optional tools that may be needed include:
Cordless screwdriver/drill
Cordless ratchet
3/8-inch nut driver or socket and ratchet
Pliers
10-24 Tap
5/16 x 18 Tap
Note: If you use a cordless drill with an adjustable torque setting, set the
torque as low as possible to properly drive the screw or bolt.
Product Service 1-800-522-7658
94
External Dress Components
Front Dress Panel Removal and Installation
1. Locate and remove the two Phillips screws that
secure the front panel as shown in Figure 6-1.
They are located on the bottom corners of the
front dress panel
2. Swing the bottom of the dress panel out to clear
the fluorescent light and then lift the front dress
panel straight up and away from the cabinet.
Figure 6-1
To reinstall the panel, reverse these steps, ensuring
that the plastic pin in the top corners of the dress
panel properly engage the corner posts.
Figure 6-2
Product Service 1-800-522-7658
95
Side Panel Removal
Note: The side panel(s) must be taken off to remove the Axiom from its
pallet.
1. Remove and save the two Phillips screws on the front edge of the side panel.
2. Pivot the front of the panel away from the cabinet. Lift the panel straight up and
pull the panel straight away from the cabinet to release the rear of the side panel
from its hinge.
Side Panel Installation
1. Install the side panel by inserting both back panel hooks into the side panel
slots.
2. Ensure both panel slots are completely seated on the hooks.
3. Pivot the front of the panel toward the cabinet. Secure the panel by installing
and tightening the two Phillips screws.
Corner Post Lower Trim
The corner post lower trim pieces are secured to the corner post by a single machine
screw and lock nut. When properly positioned, the trim piece fits tightly against corner
post. See Figure 6-3.
Figure 6-3
Use a 3/8” wrench and Phillips
screwdriver to adjust the corner post
screw.
Note: DO NOT over tighten the screw;
damage to the trim piece may occur.
Product Service 1-800-522-7658
96
If the corner post lower trim pieces do not fit flush to the bottom edge of the metal
corner post, examine the front flange of the chassis. The flange should be straight. If it
is bent back, it can be straightened by bending the flange forward with an adjustable
wrench, as shown in Figure 6-4.
Figure 6-4
Front side of the Axiom
Axiom Chassis Flange
Using an adjustable wrench to
straighten the flange
Product Service 1-800-522-7658
97
Sash
Operation
The Axiom sash uses a deadweight-counterbalanced system. The system
consists of two separate weights on either side of the liner. Both weights are
synchronized by a locked axle-pulley system, so that both weights must move
together, preventing the sash from racking.
Adjustment
There are no adjustments for the width of the sash track. There should be
approximately 1/8-inch lateral play of the sash in its track. If there is no lateral
play, examine one or both of the corner posts to ensure that they are not bent
inward. If the sash becomes racked, or is closing unevenly, it can be aligned as
follows:
1. Close the sash completely, until the lower edge of the sash is contacting
the sash stop. If the other end of the sash is not resting on its sash stop,
CAREFULLY lift the counterweight on the “high” side of the sash. This will
allow the high side of the sash to lower to the sash stop, leveling the
sash. See Figure 6-5.
Figure 6-5
Using pliers to lift a sash
weight to level the sash.
CAUTION: Exercise
caution when lifting a
counterweight. There is
a pinch potential
between the sash cable
and pulley.
Product Service 1-800-522-7658
98
Sash Position Switches
Four microswitches are used to indicate the sash position. The switches are the same,
Labconco part # 3832400. A photo of the switches is shown in Figure 6-6.
Figure 6-6
Sash Closure Position Switch
Sash Restricted Opening Switch
8” Sash Operating Position Switch
10” Sash Operating Position Switch
Sash Closure Position Switch
The sash closure position switch signals the display microprocessor that the sash
is open or closed allowing proper operation of the Blowers, fluorescent or UV
lights. It is wired in the normally open configuration. If the switch does not
actuate properly when the sash is within ¼-inch of being fully closed, ensure the
switch follower is properly actuating against the weight. See Figure 6-7.
Sash Restricted Opening Switch
The sash restricted opening switch signals the display microprocessor that the
sash is about to close. When actuated, the blowers are shut off to prevent the
exhaust blower from forming a vacuum when the sash is closed. If the switch
does not actuate properly when the sash is within 2 inches of being fully closed,
ensure the switch follower is properly actuating against the weight. See Figure 6-
7.
Product Service 1-800-522-7658
99
8”- and 10” Sash Operating Position Switches
The sash operating position switches signals the display microprocessor that the
sash is open too far for proper operation, as shown in Figure 6-8. Both switches
are wired in the normally open configuration, and the display microprocessor
only responds to the appropriate switch selected during configuration. If the
switch does not actuate properly when the sash is within ¼-inch of its operating
position, ensure the switch follower is properly actuating against the weight.
Sash Closure Position Switch properly
actuated against the sash weight
Sash Operating Position Switch
properly actuated against the sash
weight
Figure 6-7
Figure 6-8
Product Service 1-800-522-7658
100
Sash Cable Retainer
The sash cable retainers are located at the top of each sash pulley, as shown in
Figure 6-9. If the retainer needs adjustment, Use a 3/8-inch wrench to loosen
the bolt securing the retainer and adjust it until it there is approximately 1/16”
gap between the retainer and the pulley. Retighten the bolt.
Figure 6-9
HEPA Filter Replacement
CAUTION: The cabinet must be properly decontaminated before servicing the
exhaust HEPA filter. Following replacement of either HEPA filter, the cabinet
must be recertified.
CAUTION: HEPA filters can be awkward to handle and heavy. Use appropriate
lifting techniques to remove and handle it. Use two people to remove the
larger filters if possible.
1. Unplug the cabinet.
2. Remove the front dress panel as shown in Figure 6-1.
To Remove the Exhaust HEPA Filter:
3. Loosen all of the Phillips screws on the exhaust filter cover.
4. Loosen the four sealed exhaust filter clamp bolts on the top of the cabinet
hull, as shown in Figure 6-10. DO NOT remove the bolts; only loosen them
until the exhaust HEPA filter is free of the filter frame.
5. Pull the exhaust HEPA filter straight out of the cabinet.
Product Service 1-800-522-7658
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.