Labconco PURICARE Procedure Station User Manual

1
Original instructions
Type A1 Biosafety Cabinet Models 30132 30142 30152 30162
Type A2 Biosafety Cabinet Models 30231 30241 30251 30261 30238 30248 30258 30268
Type B2 Biosafety Cabinet Models 30348 30368
Cell
Type A2 Biosafety Cabinet Models 32239 32249 32259 32269 33239 33249 33259 33269 34239 34249 34259 34269
Type B2 Biosafety Cabinet Models 32348 32368 32348 32368 32348 32368
PURICARE Procedure Station Models
31142 31162 31240 31260
Labconco Corporation 8811 Prospect Avenue Kansas City, MO 64132-2696 800-821-5525, 816-333-8811 FAX 816-363-0130 E-MAIL labconco@labconco.com HOME PAGE www.labconco.com
Logic+ Technical Manual and Specifications
2
Labconco Training Programs:
In order to assist technicians gain a better understanding of our products, Labconco Corporation offers Training Seminars at our Kansas City Facility on a regular basis. For further details about these training programs, contact Labconco's Product Service Department at 800-821-5525, or (816) 333-8811 from 7:30 a.m. to 5:30 p.m. C.S.T.
Additional Copies: Additional copies of this document can be downloaded from Labconco’s website at www.labconco.com. Electronic copies are available to members of the service community free of charge. Please request electronic copies by contacting our Product Service Department.
Labconco Purifier Logic+ Technical Manual and Specifications Printed in the U.S.A. ©2013 by Labconco Corporation, Kansas City, MO.
All Rights reserved. No part of this document may be translated or reproduced in any form without written permission from Labconco Corporation, 8811 Prospect, Kansas City, Missouri, 64132, U.S.A.
While the advice and information offered in this document are believed to be true and accurate at the date of going to press, neither the author, nor Labconco Corporation can accept any legal responsibly for any errors or omissions that may be made.
P/N 3849910
Rev. F, ECO J333
Product Service 1-800-522-7658
3
Table of Contents
Introduction 7 Contacting Labconco 7
Section One – Background Information
QuickStarts 8 What’s the password? 9 How do I calibrate blower speed, filter life and airflow sensor?10-11 How do I see the current configuration? 12 How do I change the configuration? 13-14 How do I run a diagnostic on the: Sash position switches? 15 Keypad, relays and contact? 16 Canopy Alarm? 17 Airflow Sensor? 18 How do I set up automatic operation of the blower, lights? 19
Logic+ Filter Life Gauge Operation and Resetting for Local Conditions 20 QuickCharts Logic+ Type A1 Purifiers 21-23 Logic+ Type A2 Purifiers 24-26 Logic+ / Cell Logic+ Type B2 27-29 PuriCare Procedure Stations 30-32 Cell Logic+ Type A2 Purifiers 33-35 Identifying Logic+ Models 36
Serial Number Tags 37
Model Numbering System 38 Logic+ Data Plate 39 Final Inspection and Test Report 40 Theory of Operation Airflow Patterns 41 ECM Motor 42-43 Electronics 43-44
Section Two – Installation Requirements
Prerequisites 45 Space Requirements 45 Clearance 45 Location Requirements 46 Exhaust Requirements Type A 47 Exhaust Requirements Type B 47 Electrical Requirements 48 Service Line Requirements 49
Product Service 1-800-522-7658
4
Section Three – Installation 50 Unpacking the Biosafety Cabinet 51 Preparing the Biosafety Cabinet for operation 51 Moving and Lifting the Logic 52 Installing the Purifier on an Existing Work Surface 52 Installing the Purifier on a Labconco Base Stand 52 Telescoping Base Stands 52-53 Manual or Electric Lift Base Stands 53
SoLo Electric Hydraulic Lift Base Stands 53
Connecting the Biosafety Cabinet to Utility Service Lines 54
Optional Ventus Canopy Exhaust Connections 55 Optional Vacu-Pass Cord and Cable Portal 56
Drain Valve Installation (optional) 57
Section Four – Initial Operation of the Logic System Reset Switch 58 Information Center 59 Alarm Screens 60 Operating the Sliding Sash 61 Starting the Biosafety Cabinet 61 The Logic+ Touchpad 62 Navigating the Logic+ Menu Screens 63 Navigating the MyLogic Screens Setting the Clock 64 Configuring the Logic+ 65-66 Navigating the Settings Menu Screens Display Options
Units of Measure 66
Startup Tone 67 Security Lock 67 RS-232 Output 67 UV Settings UV Lamp Hour meter 68 Reset UV Lamp Hour Meter 68 Change UV Lamp Life 68 Timer Operation Interval Timer Operation 69 Stopwatch Timer Operation 69 If An Airflow Alert Activates 69 Resetting the Airflow Alert System 69
Product Service 1-800-522-7658
5
Section Five – Certification Procedures for the Logic+
Accessing the Certifier’s Menu 70 Adjusting the Blower Speed 70 Logic+ Filter Life Gauge Operation and Resetting for Local Conditions 71 Adjusting the Optional Inflow and Downflow Values 72 Type A HEPA Filter Leak Test Information 72 If the Logic+ is contaminated 72 Type A HEPA Filter Leak Test Specifications 73 If the Logic+ is uncontaminated 74 Type A Supply HEPA Filter Leak Test 75-76 Type A Exhaust HEPA Filter Leak Test 77-78 Type B HEPA Filter Leak Test Information 79 Type B Supply HEPA Filter Leak Test 79-82
Type B Exhaust HEPA Filter Leak Test 83-84 Downflow Velocities 85-86 Inflow Velocity Calculation Primary Inflow Method 86-87 Secondary Inflow Method 88-91 Type B2 Total Exhaust Volume 92 Type B2 Exhaust (Inflow) Alarm Set point 92 Work Area Air Cleanliness Test (optional) 93 Fluorescent Light Level (optional) 94 Noise Level (optional) 94 Vibration (optional) 95 UV intensity (optional) 95 Ground Fault Circuit Interrupter 96
Section Six – Logic+ Service Operations
Recommended Tools for Service 97
External Dress Components Front Dress Panel Removal and Installation 97-98 Side Panel Removal 98 Side Panel Installation 98
Corner Post Lower Trim 99
Sash Operation/Adjustment 100 Sash Position Switches Sash Closure Position Switch 101-102
Sash Operating Position Switch 101-102
Sash Cable Retainer 103
Type A Exhaust Damper Adjustment 103 Type A Exhaust Damper Seal Installation 104
Type A HEPA Filter Replacement
Exhaust HEPA Filter Replacement 105-07
Supply HEPA Filter Replacement 108-10
Type B2 Exhaust Damper Adjustment 110
Type B2 Prefilter Replacement 111
Type B2 HEPA Filter Replacement 111-13
Motor/Blower Replacement 114-15
Work Surface Removal 116 Grille Removal 116 Towel Catch Removal 117
Diffuser Removal 118-19 Preparing the Logic for Gaseous Sterilization 120
Product Service 1-800-522-7658
6
Section Seven –Electrical System Service Operations
Fluorescent Lamp Lamp Identification 121 Changing the Fluorescent Lamp 121
Lamp Socket Replacement 122
Optional Ultraviolet Lamp Lamp Identification 122 UV Lamp Specifications 122 Changing the UV Lamp 123
Lamp Socket Replacement 123
Electronics Module Access 124 Electronic Module Component Identification 124
Circuit Breaker Resetting a circuit breaker 125 Circuit breaker specifications 125-26 Testing a circuit breaker 126 Replacing a circuit breaker 126 Power Supply Board Service Operations Fuse Testing & Replacement 127 Display Board Service Operations 128
Touchpad Connections 128
Diagnostic Operations 129 Motor Service Operations Motor Testing 129-31 Motor Output Signal Testing 132
Wiring Diagrams 133-34
Section Eight – Purifier Logic+ Accessories
Ventus Canopy Connection Kit 135-41 Air Flow Sensor Kit 142-45
Service Fixture Kit 146-47 U.V. Lamp Kit 148-50 I.V. Bar Kit 151 Prefilter Kits 152-53
RS-232 Connection Kits 155-65
Using the RS-232 Receptacle 158
Connection for Computer Interface 158
Logic+ Relay Contact Outputs 161-64
Section Nine - Miscellaneous
Troubleshooting 166-69 Purifier Logic Replacement Parts 170-71
Dimensions 172
Product Service 1-800-522-7658
7
INTRODUCTION
This text is designed for you, the Biohazard Cabinet Certifier. Based on your suggestions, comments, and ideas, Labconco has compiled this information for you to use in the certification or servicing of our Purifier Logic+ Biosafety Cabinets.
When you use this document in your office or in the field, we would appreciate your input so that we can make further improvements to future editions.
As always, we at Labconco want to assist you in having a better understanding of our products and their operation; if you have any questions, or need additional information, please contact us.
Thanks again for all your support in the past, and in the future.
Labconco
CONTACTING LABCONCO
Labconco’s Address is:
LABCONCO Corporation 8811 Prospect Kansas City, MO 64132
Our hours of operation are from 07:30 - 17:30 CST, Monday through Friday, except national holidays
We can be reached at the following numbers:
(800) 821-5525 (816) 333-8811
Our Fax numbers are:
(816) 444-5343 (816) 363-0130
Should you require Technical Assistance, Service Parts, or have general questions regarding the Purifiers, please direct them to our Product Service Department, so that your call can be properly routed and answered.
Product Service 1-800-522-7658
8
SECTION ONE –
Background Information
Quickstart
The Logic+ family of Biosafety Cabinets is a significant step forward from our Logic­platformed products. While many internal components are the same or similar, the keypad and display have changed considerably. The high resolution, color display
will offer you a more thorough explanation of the cabinet’s operation and status
than the previous models ever could. These to answer the questions asked in each case. Keystrokes are shown in
italics
, while screen selections are shown in
Quickstarts
green italics
will help you show you how
bold blue
.
Product Service 1-800-522-7658
9
Quickstart
What’s the password for the Logic+?
Like the Logic, the Logic+ models password protects the user from entering the
Calibration
the airflow sensor readings. New to the Logic+ is a
Configuration
canopy and airflow sensor options-there is more on this in the Quickstart “How do I change the BSC configuration?”
The password for all protected screens is:
1. Light
2. UV Light
3. Timer
4. Timer
5. OK/Mute
menu to prevent them from adjusting the blower speed, filter gauge or
Service
; entering this option allows you to configure the Logic+’s Type, its
menu selection entitled
Product Service 1-800-522-7658
10
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or t o choose,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics
Configuration
Calibration

Service
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Calibration
OK to proceed, MENU to return
PASSWORD:
Calibration
The ECM setting is: 80 The current RPM is: 1050 The average RPM is: 1020
Calibration
Motor Speed Adjustment
or to change mot or speed,
OK to select, ME NU to finish

How do I recalibrate the
blower speed
filter life gauge
airflow sensor reading
of the Logic+?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the will turn white).
5. Press
6. You will see a alter the BSC’s settings.
7. Press
8. When requested for the password press
Timer, Timer
9. If the password is properly entered, the first certification screen will display the blower motor’s PWM setting.
10. Press the or button to increase or decrease the blower speed as needed. When the speed is set properly, press the
OK/Mute
continue to the filter life screen.
Menu
button.
OK/Mute
OK/Mute
warning screen
OK/Mute
Services
to enter the Services menu screen.
Calibration
to start the calibration procedure.
alerting you that you are about to
to input the password.
option is highlighted (it will
option is highlighted (it
Light, UV light
then
OK/Mute
.
button to lock the new blower speed setting, and
,
Product Service 1-800-522-7658
11
Quickstart
Calibration
Filter Gauge Adjustment
or to change filte r gauge,
OK to select, ME NU to finish

Reset Filter Gauge to 100%
Leave Gauge unchanged
Set Gauge to new setting
Reduce the exhaust flow to 80% of nominal volume. Press OK when you are ready to fix the setpoint.
Calibration
Inflow Alarm Setpoint
OK to select, ME NU to finish
The Inflow displayed value is: 102 FPM
Calibration
Inflow Display
or to change disp lay value, UV Light to res et to 105 FPM, OK to select, ME NU to finish

How do I recalibrate the
blower speed filter life gauge airflow sensor reading
of the Logic+? - Continued
11. If this is an initial certification or a recertification after HEPA filter replacement, select annual recertification, select want to set the filter gauge at a preset value, select
to new setting
12. The Type A units with airflow sensor will ask you to now calibrate the average downflow to match the value you obtained when you measured it. After the downflow is calibrated, and you press
OK/Mute
with the new settings.
13. If the unit is a Type A without an airflow sensor, after the filter gauge option is selected and you press will power down, and then restart with the new settings. If the Unit is a Type B2 or a Type A with an airflow sensor, you will then be asked to calibrate the inflow sensor to match the value you obtained when you measured the inflow. After the inflow is calibrated, and you press down, and then restart with the new settings.
14. For the Type B2, the unit will now ask you to reduce the exhaust volume to 80% of the nominal value. When you have done this, press
point for the exhaust flow. If you press OK/Mute before reducing the flow to 80%, the Logic+ will assume the alarm setpoint is equal to the nominal airflow, and the unit will return an Alarm­Inflow Screen. The Logic+ will power down, and then restart
with the new settings. Be sure to reset the exhaust damper to its nominal setting.
Reset Filter Gauge to 100%
Leave Gauge unchanged
. If this is an
. If you
Set Gauge
. Then press
OK/Mute
.
, the Logic+ will power down, and then restart
OK/Mute
OK/Mute
, the Logic+ will power
, the Logic+
total
OK/Mute
. This step is critical-it sets the alarm
Product Service 1-800-522-7658
12
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics Calibration Configuration

Service
How do I see the Current Configuration of the Logic+?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the highlighted (it will turn white).
5. Press
6. If you are recertifying the unit, you may want to record the data on this screen. The firmware revision is shown in the bottom right corner as a -, or as a letter.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Current Settings
option is
to see the configuration.
Product Service 1-800-522-7658
13
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics Calibration
 Configuration

Service
Configuration
PASSWORD:
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Configuration
OK to proceed, MENU to return
How do I change the Configuration of the Logic+?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the (it will turn white).
5. Press
6. You will see a alter the BSC’s settings.
7. Press
8. When requested for the password press
Timer, Timer
Menu
OK/Mute
OK/Mute
warning screen
OK/Mute
then
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Configuration
option is highlighted
to alter the configuration.
alerting you that you are about to
to input the password.
Light, UV light
OK/Mute
.
,
Product Service 1-800-522-7658
14
Configuration
Type A Canopy Option
This cabinet has:
or to cho ose,
OK to select, M ENU to escape
a canopy
no canopy

This Logic is configured:
or to choose,
OK to select, MENU to return
to have a UV light
to NOT have a UV light

UV Settings
This cabinet is not configured for a UV light
If you want to install a UV light, contact Labconco Product Service at 800-821-5525
Attention
MENU to return
Quickstart
How do I change the Configuration of the Logic+? – continued
9. The first screen allows you to set the Type of cabinet. The only difference between the Type A1 and Type A2 configuration setting is that the airflow velocity limits for normal operation of the optional airflow sensor (because the Type A1 has a nominal inflow of 85 FPM, and the Type A2 is 105 FPM). If the air velocity goes out of range, the alarm will be displayed, but the cabinet will continue to run. Selecting Type B2 will cause an inflow alarm if the inflow velocity drops below the alarm setpoint, and will result in the cabinet blower stopping. Use the or buttons to select the cabinet Type, and then press OK/Mute.
10. The second screen allows you to configure the cabinet for a canopy or not.*
11. This screen configures the unit for a UV light or not. After your selection is chosen, and you press OK/Mute, the unit will shut off and then reset in the new configuration.
12. If the unit is configured to NOT have a UV light, and the user presses the UV Light button, they will get this message.
*Early production models of Type A Logic+ units may require a jumper wire across the canopy electrical connection located on the left side of the electronics module. Contact Labconco for assistance if this jumper is missing, and the unit in constant canopy alarm mode.
Product Service 1-800-522-7658
15
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration Configuration
Diagnostics

Service
or to choose,
OK to select, ME NU to escape
Sash sensors
Keypad -Relays Canopy Alarm Airflow Sensor

Diagnostics
OK to return
Lower the sash from full open to closed Note the sash status below: Sash Status:
The sash is open
The sash is open too high
The sash is closed
Diagnostics
How do I run a diagnostic on the sash position switches?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the Diagnostic highlighted (it will turn white).
5. Press
6. Press the button until the Diagnostic highlighted (it will turn white). Press
7. Lower the sash, and note the status line – it should properly report the sash as open too high, or open, or closed when the sash is in the corresponding position.* Press the diagnostic.
*Early production models of Type A Logic+ units may display a sash height alarm screen when the sash is raised above its operating position. This is normal.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is
to enter the Diagnostic submenu.
Sash sensors
OK/Mute
.
OK/Mute
option is
to exit
Product Service 1-800-522-7658
16
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration Configuration
Diagnostics

Service
or to choose,
OK to select, ME NU to escape
Keypad -Relays
Sash sensors
Canopy Alarm Airflow Sensor 

Diagnostics
How do I run a diagnostic on the keypad, relays and contacts?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the Diagnostic highlighted (it will turn white).
5. Press
6. Press the button until the Diagnostic highlighted (it will turn white). Press
7. Press any button on the keypad (except display.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is
to enter the Diagnostic submenu.
Keypad-Relays
OK/Mute
.
Menu
), and note the
option is
Product Service 1-800-522-7658
17
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration Configuration
Diagnostics

Service
Diagnostics
or to choose,
OK to select, MENU to escape
Canopy Alarm
Sash sensors
Keypad - Relays
Airflow Sensor

Quickstart
How do I run a diagnostic on the Canopy Alarm?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the will turn white).
5. Press
6. Press the button until the Diagnostic highlighted (it will turn white). Press
7. The display shows the status of the Canopy Inlet Valve. During normal operation, it will be open, and during a canopy alarm, it will be closed. NOTE: The canopy door function is OPPOSITE OF THE MAGNETIC SWITCH FUNCTION! – WHEN THE INLET VALVE IS OPEN, THE MAGNETIC SWITCH IS CLOSED.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Canopy Alarm
OK/Mute
.
Product Service 1-800-522-7658
option is
18
or to choose,
OK to select, MENU to escape
Keypad -Relays
Sash sensors
Canopy Alarm Airflow Sensor

Diagnostics
or to choose,
OK to select, MENU to retur n
Current Settings
 Restore Default
Diagnostics Calibration Configuration

Service
or to choose,
OK to select, MENU to retur n
Current Settings
Restore Default
Diagnostics Calibration
 Configuration

Service
or to choose,
OK to select, MENU to retur n
Current Settings
Restore Default
Diagnostics
Configuration
Calibration

Service
or to choose,
OK to select, MENU to retur n
Current Settings
Restore Default
Calibration Configuration
Diagnostics

Service
or to choose,
OK to select, MENU to escape
Canopy Alarm
Sash sensors
Keypad -Relays
Airflow Sensor

Diagnostics
or to choose,
OK to select, MENU to escape
Airflow Sensor
Sash sensors Keypad -Relays Canopy Alarm

Diagnostics
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choose,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration Configuration
Diagnostics

Service
Quickstart
How do I run a diagnostic on the Airflow Sensor?
1. Press the
2. Press the button until the turn yellow).
3. Press
4. Press the button until the will turn white).
5. Press
6. Press the button until the Diagnostic highlighted (it will turn white). Press
7. The display shows the status of the airflow sensor. Its current output, alarm setting and zero point in Millivolts, along with the corrected Inflow velocity currently being displayed.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Airflow Sensor
OK/Mute
.
Product Service 1-800-522-7658
option is
19
Quickstart
How do I set up automatic operation of the blower and lights?
1. Press the
2. Press the button until the turn blue).
3. Press
4. Press the button until the option option is highlighted (it will turn white).
5. Press the button to select either Smart-Start or manual operation of the cabinet blower. (In Smart-Start, the cabinet blower will automatically start every time the sash is opened.
6. Press the button to select either Smart-Start or manual operation of the fluorescent lights.
7. Press the button to select either Night-Smart or manual operation of the cabinet blower. (In Night-Smart, the cabinet blower will automatically operate at idle every time the sash is closed.
8. Press the button to select either Night-Smart or manual operation of the UV Light.*
9. Press the button to select the time interval the UV light will operate for until it automatically shuts off.*
* - These screens will only appear if the unit is configured for a UV light.
Menu
OK/Mute
button.
MyLogic
to enter the MyLogic menu screen.
option is highlighted it will
configure my Logic for use
Product Service 1-800-522-7658
20
Logic+ Filter Life Gauge Operation and Resetting for Local Conditions
The filter life gauge calculates the remaining filter life by measuring and comparing the current motor speed to the initial speed noted at the factory during assembly, and the calculated maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left max. speed-original speed
So
anything
Blocking the grille. Raising the air temperature. Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic dampening of the gauge will limit the change in readings to approximately 1%/minute.
Logic+ Biosafety Cabinets being installed at altitudes or operating at temperatures significantly different from those at the time of manufacture (900 +/- 500 ft above sea level, 75o +/- 5o F) conditions. Failure to do so will result in the users noticing a steady drop in Percent (%) Filter Life remaining as the unit operates. Below are the instructions on how to correct the Filter Life Gauge for local conditions.
that changes the motor’s current speed, like:
must
have their filter life gauge recalibrated for local
1. Ensure to correct all measurement equipment for local conditions (temperature, absolute pressure). Anemometers may not have this ability and might have to be done manually; whereas, a ShortRidgeTM instrument has a setting to correct for local conditions.
2. As the elevation or the ambient temperature rises, the motor power factor will have to be reduced to compensate. For an initial certification, the motor speed should be reduced until it equals the Logic’s “Initial Motor Speed” as reported on the unit’s test sheet, plus approximately 10-15 RPM per each additional 1000 feet of elevation.
3. The Logic MUST be recertified using instruments corrected for local conditions.
4. When the unit is recertified, and operating properly, the certifier MUST RESET THE FILTER LIFE GAUGE, INDICATING A NEW FILTER HAS BEEN INSTALLED.
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND RECERTIFIED FOR ITS LOCAL CONDITION, will the filter life gauge register 100% (+/- 2%) during operation. As the Filters then load, the filter life gauge will then begin to drop as appropriate.
Product Service 1-800-522-7658
21
QuickChart – Logic+ Type A1 - Imperial Units
Model
30132
30142
30152
30162
Type
A1
A1
A1
A1
Cabinet Size (in feet)
3 4 5
6
Sash Opening (inches)
12
12
12
12
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (FPM)
55+/-5
55+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
21 (3x7)
24 (3x8)
30(3x10)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
6.0
Distance between rows
5.55
5.55
5.55
5.55
Distance between columns
4.08
5.21
5.39
5.50
Inflow Data
Nominal Average Inflow (FPM)
85+/-5
85+/-5
85+/-5
85+/-5
Sash Open Area (Sq. Ft)
3.04
4.04
5.04
6.04
Nominal Avg. Exhaust Vol. (CFM)
259
344
428
514
Avg. Exhaust Vol. Range (CFM)
243-274
323-364
403-454
483-544
Secondary Inflow Data
3
Sash Opening Template1
3+
4+
5+
6+
Sensor distance (inches)2
4
3.25
3.25 4 # of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
259
344
428
281
Avg. Inflow Vel. Range (FPM)
243-274
323-364
403-454
264-297
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
243-274
323-364
403-454
483-544
Sash Open Area (Sq. Ft)
3.04
4.04
5.04
6.04
Inflow Velocity Range
(AIV / Sash open area)
85+/-5
85+/-5
85+/-5
85+/-5
HEPA Filter Leak Test Data
Air Displacement (CFM)
600
800
1000
1200
Laskin Nozzles needed
1 2 2
2
Theoretical aerosol conc. (ug/l)3
23
34
27
23
Actual aerosol conc. (ug/l)4
12
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
48x18x3.06
60x18x3.06
72x18x3.06
Performance (CFM)
335
445
555
665
Performance (Pressure in. H2O)
< .60”
<.45”
<.45”
<.42”
Labconco P/N
3838400
3838401
3838402
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
26x18x5.88
36x18x5.88
48x18x5.88
Performance (CFM)
266
353
441
529
Performance (Pressure in. H2O)
< 0.35”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838501
3838502
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832201
3832207
3832208
Motor HP
½
½ ¾ ¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721901
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889201
3889202
3889203
Canopy Slot Area (F2)
.12
.12
.12
.12
Canopy Inflow Range (CFM)
20-100
20-100
20-100
20-100
Nominal Canopy Slot Velocity (FPM)
240-260
240-260
240-260
240-260
Nominal Canopy Slot Volume (CFM)
50
50
50
50
Canopy Vacuum (In. H2O)
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
Product Service 1-800-522-7658
22
QuickChart – Logic+ Type A1 - Metric
Model
30132
30142
30152
30162
Type
A1
A1
A1
A1
Cabinet Size (in meters)
.91
1.22
1.52
1.83
Sash Opening (inches)
305
305
305
305
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (m/s)
.279 +/-.03
.279 +/-.03
.279 +/-.03
.279 +/-.03
grid # of points (rows x columns)
21 (3x7)
24 (3x8)
30(3x10)
36(3x12)
Grid distance from back & sides
152
152
152
152
Distance between rows (mm)
141
141
141
141
Distance between columns (mm)
104
132
137
140
Inflow Data
Nominal Average Inflow (m/s)
.432 +/-.03
.432 +/-.03
.432 +/-.03
.432 +/-.03
Sash Open Area (Sq. m)
.283
.375
.468
.561
Nominal Avg. Exhaust Vol. (m3/s)
.122
.162
.202
.242
Avg. Exhaust Vol. Range (m3/s)
.115-.129
.153-.172
.190-.214
.228-.257
Secondary Inflow Data
3
Sash Opening Template1
3+
4+
5+
6+
Sensor distance (mm)2
102
83
83
102
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (m/s)
1.32
1.75
2.17
1.43
Avg. Inflow Vel. Range (m/s)
1.23-1.39
1.64-1.85
2.05-2.31
1.34-1.51
Correction Factor (CF)
.0929
.0929
.0929
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.115-.129
.153-.172
.190-.214
.228-.257
Sash Open Area (Sq. m)
.283
.375
.468
.561
Inflow Velocity Range
(AIV / Sash open area)
.432 +/-.03
.432 +/-.03
.432 +/-.03
.432 +/-.03
HEPA Filter Leak Test Data
Air Displacement (m/s)
.283
.378
.472
.566
Laskin Nozzles needed
1 2 2
2
Theoretical aerosol conc. (ug/l)3
23
34
27
23
Actual aerosol conc. (ug/l)4
12
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
48x18x3.06
60x18x3.06
72x18x3.06
Performance (CFM)
335
445
555
665
Performance (Pressure in. H2O)
< .60”
<.45”
<.45”
<.42”
Labconco P/N
3838400
3838401
3838402
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
26x18x5.88
36x18x5.88
48x18x5.88
Performance (CFM)
266
353
441
529
Performance (Pressure in. H2O)
< 0.35”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838501
3838502
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832201
3832207
3832208
Motor HP
½
½ ¾ ¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721901
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889201
3889202
3889203
Canopy Slot Area (m2)
.0111
.0111
.0111
.0111
Canopy Inflow Range (m/s)
.010-.047
.010-.047
.010-.047
.010-.047
Nominal Canopy Slot Velocity (m/s)
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
Nominal Canopy Slot Volume (m3/s)
.235
.235
.235
.235
Canopy Vacuum (Pa)
25-37
25-37
25-37
25-37
Product Service 1-800-522-7658
23
QuickChart - Logic Type A1 BSCs footnotes
Logic Model Identification
The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on
the top right side of the cabinet.
The first two digits of the serial number are the year of production; the next
two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow. All tests performed as described in ANSI/NSF Standard 49:2012. UV Lamp, IV bar and all other accessories must be removed before
measuring downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2007.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. The actual aerosol concentration is what was observed during testing.
Aerosol generator should be placed in the left rear corner of the work area, pointing toward the rear grille. For uncontaminated units, the upstream concentration can be sampled from the tube located under the work surface Metric calculation of concentration is: # of Laskin nozzles @ 138K Pascals x 6.372/Volume of air in m3/sec. = Conc. In ug/l
Supply and Exhaust HEPA Filter Specifications
5. Without gasket
Motor / Blower Specifications
6. Each motor must be programmed by Labconco for the appropriate width cabinet. The speed control settings will fluctuate depending on local temperature and pressure.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
1271300.
For all 115/230 VAC models, the ballast assembly is Labconco part number
3829901.
For all 100 VAC models, the ballast assembly is Labconco part number
3830600.
Product Service 1-800-522-7658
24
QuickChart – Logic+ Type A2 – Imperial Units
Model
30231
30238
30241
30248
30248xx80
30251
30258
30261
30268
Type
A2
A2
A2
A2
A2
A2
A2
A2
A2
Cabinet Size (in feet)
3 3 4 4 4 5 5 6 6
Sash Opening (inches)
10 8 10 8 8
10 8 10 8 Starting Serial #
1303_
1303_
1303_
1303_
1303_
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (FPM)
55+/-5
55+/-5
55+/-5
55+/-5
70+/-5
55+/-5
55+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
21 (3x7)
21 (3x7)
24 (3x8)
24 (3x8)
24 (3x8)
30(3x10)
30(3x10)
36(3x12)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
Distance between rows
5.55
5.75
5.55
5.75
5.75
5.55
5.75
5.55
5.75
Distance between columns
4.08
4.08
5.21
5.21
5.21
5.39
5.39
5.50
5.50
Inflow Data
Nominal Average Inflow (FPM)
105+/-5
105+/-5
105+/-5
105+/-5
105+/-5
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.53
2.03
3.37
2.69
2.69
4.2
3.36
5.03
4.03
Nominal Avg. Exhaust Vol. (CFM)
266
213
354
283
283
441
353
529
423
Avg. Exhaust Vol. Range (CFM)
253-278
203-223
337-371
269-296
269-296
420-462
336-370
503-553
403-443
Secondary Inflow Data
3
Sash Opening Template
1
3+
3+
4+
4+
4+
5+
5+
6+
6+
Sensor distance (inches)2
4 4 3.25
3.25
3.25
3.25
3.25 4 4
# of Test points
6 6 8 8 8
10
10
12
12
Test point location
* * * * * * * * *
Nominal Avg. Inflow Vel. (FPM)
266
213
354
283
283
441
353
289
231
Avg. Inflow Vel. Range (FPM)
253-278
203-223
337-371
269-296
269-296
420-462
336-370
275-302
220-242
Correction Factor (CF)
1 1 1 1 1 1 1
1.83
1.83
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
253-278
203-223
337-371
269-296
269-296
420-462
336-370
503-553
403-443
Sash Open Area (Sq. Ft)
2.53
2.03
3.37
2.69
2.69
4.2
3.36
5.03
4.03
Inflow Velocity Range
(AIV / Sash open area)
100-110
100-110
100-110
100-110
100-110
100-110
100-110
100-110
100-110
HEPA Filter Leak Test Data
Air Displacement (CFM)
600
550
800
725
900
1000
900
1200
1100
Laskin Nozzles needed
1 1 2 2 2 2 2 2 2
Theoretical aerosol conc. (ug/l)3
23
25
34
37
30
27
30
23
25
Actual aerosol conc. (ug/l)4
12
14
18
21
17
15
17
15
17
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
36x18x3.06
48x18x3.06
48x18x3.06
48x18x3.06
60x18x3.06
60x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
335
335
445
445
445
555
555
665
665
Performance (Pressure in. H2O)
< .60”
<.60”
<.45”
<.45”
<.45”
< .45”
<.45”
<.42”
<.42”
Labconco P/N
3838400
3838400
3838401
3838401
3838401
3838402
3838402
3838403
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
18x18x5.88
26x18x5.88
26x18x5.88
26x18x5.88
36x18x5.88
36x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
266
266
353
353
353
441
441
529
529
Performance (Pressure in. H2O)
< 0.35”
< 0.35”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838500
3838501
3838501
3838501
3838502
3838502
3838503
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832200
3832201
3832201
3832201
3832207
3832207
3832208
3832208
Motor HP
½
½ ½ ½ ½ ¾ ¾ ¾
¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F25T8 TL741
F32T8 TL741
F32T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721901
9721901
9721900
9721900
9721900
9721903
9721903
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
3838100
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889200
3889201
3889201
3889201
3889202
3889202
3889203
3889203
Canopy Slot Area (F2)
.12
.12
.12
.12
.12
.12
.12
.12
.12
Canopy Inflow Range (CFM)
20-100
20-100
20-100
20-100
20-100
20-100
20-100
20-100
20-100
Nominal Canopy Slot Velocity (FPM)
240-260
240-260
240-260
240-260
240-260
240-260
240-260
240-260
240-260
Nominal Canopy Slot Volume (CFM)
50
50
50
50
50
50
50
50
50
Canopy Vacuum (In. H2O)
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
Product Service 1-800-522-7658
25
QuickChart – Logic+ Type A2 – Metric Units
Model
30231
30238
30241
30248
30248xx80
30251
30258
30261
30268
Type
A2
A2
A2
A2
A2
A2
A2
A2
A2
Cabinet Size (in m)
.91
.91
1.22
1.22
1.22
1.52
1.52
1.83
1.83
Sash Opening (mm)
254
203
254
203
203
254
203
254
203
Starting Serial #
1303_
1303_
1303_
1303_
1303_
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (m/s)
.279+/.03
.279+/.03
.279+/.03
.279+/.03
.356+/.03
.279+/.03
.279+/.03
.279+/.03
.279+/.03
grid # of points (rows x columns)
21 (3x7)
21 (3x7)
24 (3x8)
24 (3x8)
24 (3x8)
30(3x10)
30(3x10)
36(3x12)
36(3x12)
Grid distance from back & sides (mm)
152
152
152
152
152
152
152
152
152
Distance between rows (mm)
141
146
141
146
146
141
146
141
146
Distance between columns (mm)
104
104
132
132
132
137
137
140
140
Inflow Data
Nominal Average Inflow (m/s)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
Sash Open Area (Sq. m)
.235
.188
.313
.250
.250
.390
.312
.468
.374
Nominal Avg. Exhaust Vol. (m3/s)
.126
.100
.167
.134
.134
.208
.166
.249
.200
Avg. Exhaust Vol. Range (m3/s)
.120-.132
.096-.105
.159-.175
.127-.140
.127-.140
.198-.218
.159-.174
.238-.261
.190-.209
Secondary Inflow Data
3
Sash Opening Template
1
3+
3+
4+
4+
4+
5+
5+
6+
6+
Sensor distance (mm)2
102
102
83
83
83
83
83
102
102
# of Test points
6 6 8 8 8
10
10
12
12
Test point location
* * * * * * * * *
Nominal Avg. Inflow Vel. (m/s)
1.35
1.08
1.80
1.44
1.44
2.24
1.79
1.47
1.17
Avg. Inflow Vel. Range (m/s)
1.29-1.41
1.03-1.13
1.71-1.88
1.37-1.50
1.37-1.50
2.13-2.35
1.71-1.88
1.40-1.53
1.12-1.23
Correction Factor (CF)
.0929
.0929
.0929
.0929
.0929
.0929
.0929
.1700
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.120-.132
.096-.105
.159-.175
.127-.140
.127-.140
.198-.218
.159-.174
.238-.261
.190-.209
Sash Open Area (Sq. m)
.235
.188
.313
.250
.250
.390
.312
.468
.374
Inflow Velocity Range
(AIV / Sash open area)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
HEPA Filter Leak Test Data
Air Displacement (m3/s)
.283
.260
.378
.342
.425
.472
.425
.566
.519
Laskin Nozzles needed
1 1 2 2 2 2 2 2 2
Theoretical aerosol conc. (ug/l)3
23
25
34
38
30
27
30
23
25
Actual aerosol conc. (ug/l)4
12
14
18
21
17
15
17
15
17
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
36x18x3.06
48x18x3.06
48x18x3.06
48x18x3.06
60x18x3.06
60x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
335
335
445
445
445
555
555
665
665
Performance (Pressure in. H2O)
< .60”
<.60”
<.45”
<.45”
<.45”
< .45”
<.45”
<.42”
<.42”
Labconco P/N
3838400
3838400
3838401
3838401
3838401
3838402
3838402
3838403
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
18x18x5.88
26x18x5.88
26x18x5.88
26x18x5.88
36x18x5.88
36x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
266
266
353
353
353
441
441
529
529
Performance (Pressure in. H2O)
< 0.35”
< 0.35”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838500
3838501
3838501
3838501
3838502
3838502
3838503
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832200
3832201
3832201
3832201
3832207
3832207
3832208
3832208
Motor HP
½
½ ½ ½ ½ ¾ ¾ ¾
¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F25T8 TL741
F32T8 TL741
F32T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721901
9721901
9721900
9721900
9721900
9721903
9721903
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
3838100
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889200
3889201
3889201
3889201
3889202
3889202
3889203
3889203
Canopy Slot Area (m2)
.0111
.0111
.0111
.0111
.0111
.0111
.0111
.0111
.0111
Canopy Inflow Range (m/s)
.010-.047
.010-.047
.010-.047
.010-.047
.010-.047
.010-.047
.010-.047
.010-.047
.010-.047
Nominal Canopy Slot Velocity (m/s)
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
Nominal Canopy Slot Volume (m3/s)
.235
.235
.235
.235
.235
.235
.235
.235
.235
Canopy Vacuum (Pa)
25-37
25-37
25-37
25-37
25-37
25-37
25-37
25-37
25-37
Product Service 1-800-522-7658
26
QuickChart - Logic Type A2 BSCs footnotes
Logic Model Identification
The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on
the top right side of the cabinet.
The first two digits of the serial number are the year of production; the next
two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow. All tests performed as described in ANSI/NSF Standard 49:2012. UV Lamp, IV bar and all other accessories must be removed before
measuring downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2012.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. The actual aerosol concentration is what was observed during testing.
Aerosol generator should be placed in the left rear corner of the work area, pointing toward the rear grille. For uncontaminated units, the upstream concentration can be sampled from the tube located under the work surface Metric calculation of concentration is: # of Laskin nozzles @ 138K Pascals x 6.372/Volume of air in m3/sec. = Conc. In ug/l
Supply and Exhaust HEPA Filter Specifications
5. Without gasket
Motor / Blower Specifications
6. Each motor must be programmed by Labconco for the appropriate width cabinet. The speed control settings will fluctuate depending on local temperature and pressure.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
1271300.
For all 115/230 VAC models, the ballast assembly is Labconco part number
3829901.
For all 100 VAC models, the ballast assembly is Labconco part number
3830600.
Product Service 1-800-522-7658
27
QuickChart – Logic+ Type B2 Imperial Units
Model
30348
30368
Type
B2
B2
Cabinet Size (in feet)
4
6
Sash Opening (inches)
8 8 Starting Serial #
1303_
1303_
Downflow Data
Nominal Avg. Downflow (FPM)
55+/-5
55+/-5
grid # of points (rows x columns)
24 (3x8)
36(3x12)
Grid distance from back & sides
6.0
6.0
Distance between rows
5.75
5.75
Distance between columns
5.21
5.50
Inflow Data
Nominal Average Inflow (FPM)
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.69
4.03
Nominal Avg. Exhaust Vol. (CFM)
283
423
Avg. Exhaust Vol. Range (CFM)
269-296
403-443
Secondary Inflow Data
3
Sash Opening Template
1
3.7
4.95
Sensor distance (inches)2
3.25 4 # of Test points
8
12
Test point location
*
*
Nominal Avg. Inflow Vel. (FPM)
283
231
Avg. Inflow Vel. Range (FPM)
269-296
220-242
Correction Factor (CF)
1
1.83
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
269-296
403-443
Sash Open Area (Sq. Ft)
2.69
4.03
Inflow Velocity Range
(AIV / Sash open area)
100-110
100-110
Supply HEPA Leak Test Data
Air Displacement (CFM)
445
665
Laskin Nozzles needed
1 1 Theoretical aerosol conc. (ug/l)3
30
20
Actual aerosol conc. (ug/l)4
15
12
Exhaust HEPA Leak Test Data
Air Displacement (CFM)
665
998
Laskin Nozzles needed
2
2
Theoretical aerosol conc. (ug/l)3
41
27
Actual aerosol conc. (ug/l)4
25
19
Exhaust Data
DIM Exhaust Volume (CFM)5
665
998
Traverse Exhaust Volume (CFM)6
810
1218
Differential Pressure (in. H20)7
1.5
1.8
Exhaust (Inflow) Alarm Data
Alarm Setpoint (CFM Inflow)
150 +/- 5
223 +/- 5
Supply HEPA Data
Width x Depth x Height (in.)8
48x18x3.06
72x18x3.06
Performance (CFM)
445
665
Performance (Pressure in. H2O)
<.45
<.42
Labconco P/N
3838401
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 8
26x18x8.08
48x18x8.08
Performance (CFM)
720
1100
Performance (Pressure in. H2O)
.48+/-.07
.37+/-.07
Labconco P/N
3438501
3438503
Motor/Blower Data
Labconco P/N6
3832209
3832210
Motor HP
½
½
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
Product Service 1-800-522-7658
28
QuickChart – Logic+ Type B2 Metric Units
Model
30348
30368
Type
B2
B2
Cabinet Size (in m)
1.22
6
Sash Opening (mm)
203 8 Starting Serial #
1303_
1303_
Downflow Data
Nominal Avg. Downflow (m/s)
.279+/.03
55+/-5
grid # of points (rows x columns)
24 (3x8)
36(3x12)
Grid distance from back & sides
152
6.0
Distance between rows (mm)
146
5.75
Distance between columns (mm)
132
5.50
Inflow Data
Nominal Average Inflow (m/s)
.533+/-.03
105+/-5
Sash Open Area (Sq. m)
.250
.374
Nominal Avg. Exhaust Vol. (m3/s)
.134
.200
Avg. Exhaust Vol. Range (m3/s)
.127-.140
.190-.209
Secondary Inflow Data
3
Sash Opening Template
1
4+
6+
Sensor distance (mm)2
83
4
# of Test points
8
12
Test point location
*
*
Nominal Avg. Inflow Vel. (m/s)
1.44
1.17
Avg. Inflow Vel. Range (m/s)
1.37-1.50
1.12-1.23
Correction Factor (CF)
.0929
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.127-.140
.190-.209
Sash Open Area (Sq. m)
.250
.374
Inflow Velocity Range
(AIV / Sash open area)
.533+/-.03
.533+/-.03
Supply HEPA Leak Test Data
Air Displacement (m3/s)
.210
.471
Laskin Nozzles needed
1 1 Theoretical aerosol conc. (ug/l)3
30
20
Actual aerosol conc. (ug/l)4
15
12
Exhaust HEPA Leak Test Data
Air Displacement (m3/s)
.314
.471
Laskin Nozzles needed
2
2
Theoretical aerosol conc. (ug/l)3
41
27
Actual aerosol conc. (ug/l)4
25
19
Exhaust Data
DIM Exhaust Volume (m3/s)5
.314
.471
Traverse Exhaust Volume (m3/s)6
.382
.575
Differential Pressure (Pa)7
374
448
Exhaust (Inflow) Alarm Data
Alarm Setpoint (m3/s Inflow)
.071 +/- .03
.105 +/-.03
Supply HEPA Data
Width x Depth x Height (in.)8
48x18x3.06
72x18x3.06
Performance (CFM)
445
665
Performance (Pressure in. H2O)
<.45
<.42
Labconco P/N
3838401
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 8
26x18x8.08
48x18x8.08
Performance (CFM)
720
1100
Performance (Pressure in. H2O)
.48+/-.07
.37+/-.07
Labconco P/N
3438501
3438503
Motor/Blower Data
Labconco P/N6
3832209
3832210
Motor HP
½
½
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
Product Service 1-800-522-7658
29
QuickChart – Logic+/Cell Logic+ Type B2 BSCs
footnotes
Logic Model Identification
The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on the top
right side of the cabinet.
The first two digits of the serial number are the year of production; the next two are
the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow. All tests performed as described in ANSI/NSF Standard 49:2012. UV Lamp, IV bar and all other accessories must be removed before measuring
downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2012.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. The actual aerosol concentration is what was observed during testing.
Aerosol generator should be placed in the left rear corner of the work area, pointing
toward the rear grille.
For uncontaminated units, the upstream concentration can be sampled from the
tube located under the work surface.
Metric calculation of concentration is:
# of Laskin nozzles @ 138K Pascals x 6.372/Volume of air in m3/sec. = Conc. In ug/l
Exhaust Data
5. Total Exhaust Volume. Cabinet air intake sealed shut and cabinet blower off.
6. Measured as per ASHRAE methodology for measuring air volume in round ducts.
7. Measured at the exhaust transition sampling point, relative to atmosphere.
Supply and Exhaust HEPA Filter Specifications
8. Without gasket
Motor / Blower Specifications
9. Each motor must be programmed by Labconco for the appropriate width cabinet.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
For all 115/230 VAC models, the ballast assembly is Labconco part number 3829901.
For all 100 VAC models, the ballast assembly is Labconco part number 3830600. The
The speed control settings will fluctuate depending on local temperature and pressure.
1271300.
The ballast is Robertson part number PSM2GPH18MVW.
ballast is Robertson part number RSO1GPH30100.
Product Service 1-800-522-7658
30
QuickChart – Logic+ PuriCare Procedure Stations
Model
31241
31142
31261
31162
Type
A2
A1
A2
A1
Cabinet Size (in feet)
4 4 6 6 Sash Opening (inches)
10
12
10
12
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (FPM)
55+/-5
55+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
24 (3x8)
24 (3x8)
36(3x12)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
6.0
Distance between rows
5.55
5.55
5.55
5.55
Distance between columns
5.21
5.21
5.50
5.50
Inflow Data
Nominal Average Inflow (FPM)
105+/-5
85+/-5
105+/-5
85+/-5
Sash Open Area (Sq. Ft)
3.37
4.04
5.03
6.04
Nominal Avg. Exhaust Vol. (CFM)
354
344
529
514
Avg. Exhaust Vol. Range (CFM)
337-371
323-364
503-553
483-544
Secondary Inflow Data
3
Sash Opening Template
1
3.81
3.81
4.95
4.95
Sensor distance (inches)2
3.25
3.25 4 4
# of Test points
8 8 12
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
354
344
289
281
Avg. Inflow Vel. Range (FPM)
337-371
323-364
275-302
264-297
Correction Factor (CF)
1 1 1.83
1.83
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
337-371
323-364
503-553
483-544
Sash Open Area (Sq. Ft)
3.37
4.04
5.03
6.04
Inflow Velocity Range
(AIV / Sash open area)
100-110
85+/-5
100-110
85+/-5
HEPA Filter Leak Test Data
Air Displacement (CFM)
794
794
1189
1189
Laskin Nozzles needed
2 2 2
2
Theoretical aerosol conc. (ug/l)3
34
34
23
23
Actual aerosol conc. (ug/l)4
18
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
48x18x3.06
48x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
445
445
665
665
Performance (Pressure in. H2O)
<.45
<.45
<.42
<.42
Labconco P/N
3838401
3838401
3838403
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
26x18x5.88
26x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
353
353
529
529
Performance (Pressure in. H2O)
< 0.28”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838501
3838501
3838503
3838503
Motor/Blower Data
Labconco P/N6
3832201
3832201
3832208
3832208
Motor HP
½ ½ ¾
¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721900
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889201
3889201
3889203
3889203
Canopy Slot Area (F2)
.12
.12
.12
.12
Canopy Inflow Range (CFM)
20-100
20-100
20-100
20-100
Nominal Canopy Slot Velocity (FPM)
240-260
240-260
240-260
240-260
Nominal Canopy Slot Volume (CFM)
50
50
50
50
Canopy Vacuum (In. H2O)
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
Imperial Units
Product Service 1-800-522-7658
31
QuickChart – Logic+ PuriCare Procedure Stations
Model
31241
31142
31261
31162
Type
A2
A1
A2
A1
Cabinet Size (in m)
1.22
1.22
1.83
1.83
Sash Opening (mm)
254
305
254
305
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (m/s)
.279+/.03
.279 +/-.03
.279+/.03
.279 +/-.03
grid # of points (rows x columns)
24 (3x8)
24 (3x8)
36(3x12)
36(3x12)
Grid distance from back & sides (mm)
152
152
152
152
Distance between rows (mm)
141
141
141
141
Distance between columns (mm)
132
132
140
140
Inflow Data
Nominal Average Inflow (m/s)
.533+/-.03
.432 +/-.03
.533+/-.03
.432 +/-.03
Sash Open Area (Sq. m)
.313
.375
.468
.561
Nominal Avg. Exhaust Vol. (m3/s)
.167
.162
.249
.242
Avg. Exhaust Vol. Range (m3/s)
.159-.175
.153-.172
.238-.261
.228-.257
Secondary Inflow Data
3
Sash Opening Template
1
4+
4+
6+
6+
Sensor distance (mm)2
83
83
102
102
# of Test points
8 8 12
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (m/s)
1.80
1.75
1.47
1.43
Avg. Inflow Vel. Range (m/s)
1.71-1.88
1.64-1.85
1.40-1.53
1.34-1.51
Correction Factor (CF)
.0929
.0929
.1700
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.159-.175
.153-.172
.238-.261
.228-.257
Sash Open Area (Sq. m)
.313
.375
.468
.561
Inflow Velocity Range
(AIV / Sash open area)
.533+/-.03
.432 +/-
.03
.533+/-.03
.432 +/-.03
HEPA Filter Leak Test Data
Air Displacement (m3/s)
.378
.378
.566
.566
Laskin Nozzles needed
2 2 2
2
Theoretical aerosol conc. (ug/l)3
34
34
23
23
Actual aerosol conc. (ug/l)4
18
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
48x18x3.06
48x18x3.06
72x18x3.06
72x18x3.06
Performance (CFM)
445
445
665
665
Performance (Pressure in. H2O)
<.45”
<.45”
<.42”
<.42”
Labconco P/N
3838401
3838401
3838403
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
26x18x5.88
26x18x5.88
48x18x5.88
48x18x5.88
Performance (CFM)
353
353
529
529
Performance (Pressure in. H2O)
< 0.28”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838501
3838501
3838503
3838503
Motor/Blower Data
Labconco P/N6
3832201
3832201
3832208
3832208
Motor HP
½ ½ ¾
¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721900
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889201
3889201
3889203
3889203
Canopy Slot Area (m2)
.0111
.0111
.0111
.0111
Canopy Inflow Range (m/s)
.010-.047
.010-.047
.010-.047
.010-.047
Nominal Canopy Slot Velocity (m/s)
1.22-1.32
1.22-1.32
1.22-1.32
1.22-1.32
Nominal Canopy Slot Volume (m3/s)
.235
.235
.235
.235
Canopy Vacuum (Pa)
25-37
25-37
25-37
25-37
Metric Units
Product Service 1-800-522-7658
32
QuickChart-Logic+ PuriCare Procedure Stations footnotes
Logic Model Identification
The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on
the top right side of the cabinet.
The first two digits of the serial number are the year of production; the next
two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow. All tests performed as described in ANSI/NSF Standard 49:2012. UV Lamp, IV bar and all other accessories must be removed before
measuring downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2012.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. The actual aerosol concentration is what was observed during testing.
Aerosol generator should be placed in the left rear corner of the work area, pointing toward the rear grille. For uncontaminated units, the upstream concentration can be sampled from the tube located under the work surface
Metric calculation of concentration is:
# of Laskin nozzles @ 138K Pascals x 6.372/Volume of air in m3/sec. = Conc. In ug/l
Supply and Exhaust HEPA Filter Specifications
5. Without gasket
Motor / Blower Specifications
6. Each motor must be programmed by Labconco for the appropriate width cabinet. The speed control settings will fluctuate depending on local temperature and pressure.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
1271300.
For all 115/230 VAC models, the ballast assembly is Labconco part number
3829901.
For all 100 VAC models, the ballast assembly is Labconco part number
3830600.
Product Service 1-800-522-7658
33
QuickChart – Cell Logic+ Type A2 BSCs
Model
32239 33239 34239
32249 33249 34249
32259 33259 34259
32269 33269 34269
Type
A2
A2
A2
A2
Cabinet Size (in feet)
3 4 5
6
Sash Opening (inches)
9
9 9 9
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (FPM)
55+/-5
55+/-5
55+/-5
55+/-5
grid # of points (rows x columns)
21 (3x7)
24 (3x8)
30(3x10)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
6.0
Distance between rows
5.55
5.55
5.55
5.55
Distance between columns
4.08
5.21
5.39
5.50
Inflow Data
Nominal Average Inflow (FPM)
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.28
3.03
3.78
4.53
Nominal Avg. Exhaust Vol. (CFM)
240
318
397
476
Avg. Exhaust Vol. Range (CFM)
228-251
303-333
378-416
453-498
Secondary Inflow Data
3
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)2
4
3.25
3.25
4
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
240
318
397
260
Avg. Inflow Vel. Range (FPM)
228-251
303-333
378-416
248-272
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
228-251
303-333
378-416
453-498
Sash Open Area (Sq. Ft)
2.28
3.03
3.78
4.53
Inflow Velocity Range
(AIV / Sash open area)
105+/-5
105+/-5
105+/-5
105+/-5
HEPA Filter Leak Test Data
Air Displacement (CFM)
596
794
991
1189
Laskin Nozzles needed
1 2 2
2
Theoretical aerosol conc. (ug/l)3
23
34
27
23
Actual aerosol conc. (ug/l)4
12
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
48x18x3.06
60x18x3.06
72x18x3.06
Performance (CFM)
335
445
555
665
Performance (Pressure in. H2O)
< .60”
<.45”
<.45”
<.42”
Labconco P/N
3838400
3838401
3838402
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
26x18x5.88
36x18x5.88
48x18x5.88
Performance (CFM)
266
353
441
529
Performance (Pressure in. H2O)
< 0.35”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838501
3838502
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832201
3832207
3832208
Motor HP
½
½ ¾ ¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F32T8 TL741
F40T8
SP41
F40T8
SP41
Fluor. Lamp Labconco Part #
9721901
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889201
3889202
3889203
Canopy Slot Area (F2)
.12
.12
.12
.12
Canopy Inflow Range (CFM)
20-100
20-100
20-100
20-100
Nominal Canopy Slot Velocity (FPM)
240-260
240-260
240-260
240-260
Nominal Canopy Slot Volume (CFM)
50
50
50
50
Canopy Vacuum (In. H2O)
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
Imperial Units
Product Service 1-800-522-7658
34
QuickChart – Cell Logic+ Type A2 BSCs Metric
Model
32239 33239 34239
32249 33249 34249
32259 33259 34259
32269 33269 34269
Type
A2
A2
A2
A2
Cabinet Size (in m)
.91
1.22
1.52
1.83
Sash Opening (mm)
229
229
229
229
Starting Serial #
1303_
1303_
1303_
1303_
Downflow Data
Nominal Avg. Downflow (m/s)
.279+/.03
.279 +/-.03
.279+/.03
.279 +/-.03
grid # of points (rows x columns)
21 (3x7)
24 (3x8)
30(3x10)
36(3x12)
Grid distance from back & sides (mm)
152
152
152
152
Distance between rows (mm)
141
141
141
146
Distance between columns (mm)
104
132
137
140
Inflow Data
Nominal Average Inflow (m/s)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
Sash Open Area (Sq. m)
.212
.282
.351
.421
Nominal Avg. Exhaust Vol. (m3/s)
.113
.150
.187
.224
Avg. Exhaust Vol. Range
(m3/s)
.108-.118
.143-.157
.178-.196
.214-.235
Secondary Inflow Data
3
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)2
102
83
83
102
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (m/s)
1.22
1.62
2.02
1.32
Avg. Inflow Vel. Range (m/s)
1.16-1.28
1.54-1.69
1.92-2.11
1.26-1.38
Correction Factor (CF)
.0929
.0929
.0929
.1700
Average Inflow Volume Range
(AIV) (Avg. velocity x CF)
.108-.118
.143-.157
.178-.196
.214-.235
Sash Open Area (Sq. m)
.212
.282
.351
.421
Inflow Velocity Range
(AIV / Sash open area)
.533+/-.03
.533+/-.03
.533+/-.03
.533+/-.03
HEPA Filter Leak Test Data
Air Displacement (m3/s)
596
794
991
1189
Laskin Nozzles needed
1 2 2
2
Theoretical aerosol conc. (ug/l)3
23
34
27
23
Actual aerosol conc. (ug/l)4
12
18
15
15
Supply HEPA Data
Width x Depth x Height (in.)5
36x18x3.06
48x18x3.06
60x18x3.06
72x18x3.06
Performance (CFM)
335
445
555
665
Performance (Pressure in. H2O)
< .60”
<.45”
<.45”
<.42”
Labconco P/N
3838400
3838401
3838402
3838403
Exhaust HEPA Data
Width x Depth x Height (in.) 5
18x18x5.88
26x18x5.88
36x18x5.88
48x18x5.88
Performance (CFM)
266
353
441
529
Performance (Pressure in. H2O)
< 0.35”
< 0.28”
< 0.28”
< 0.28”
Labconco P/N
3838500
3838501
3838502
3838503
Motor/Blower Data
Labconco P/N6
3832200
3832201
3832207
3832208
Motor HP
½
½ ¾ ¾
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F25T8 TL741
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721901
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889200
3889201
3889202
3889203
Canopy Slot Area (m2)
.12
.12
.12
.12
Canopy Inflow Range (m/s)
20-100
20-100
20-100
20-100
Nominal Canopy Slot Velocity (m/s)
240-260
240-260
240-260
240-260
Nominal Canopy Slot Volume
(m3/s)
50
50
50
50 Canopy Vacuum (Pa)
0.1-0.15
0.1-0.15
0.1-0.15
0.1-0.15
Units
Product Service 1-800-522-7658
35
QuickChart – Cell Logic+ Type A2 BSCs footnotes
Logic Model Identification
The primary serial tag is on the lower outside edge of the right corner post. The secondary serial tag is located on the front of the electronics module on
the top right side of the cabinet.
The first two digits of the serial number are the year of production; the next
two are the month. The next 5 digits are the sequence of production, and the letter following the serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow. All tests performed as described in ANSI/NSF Standard 49:2007. UV Lamp, IV bar and all other accessories must be removed before
measuring downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2007.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. The actual aerosol concentration is what was observed during testing.
Aerosol generator should be placed in the left rear corner of the work area, pointing toward the rear grille. For uncontaminated units, the upstream concentration can be sampled from the tube located under the work surface
Metric calculation of concentration is:
# of Laskin nozzles @ 138K Pascals x 6.372/Volume of air in m3/sec. = Conc. In ug/l
Supply and Exhaust HEPA Filter Specifications
5. Without gasket
Motor / Blower Specifications
6. Each motor must be programmed by Labconco for the appropriate width cabinet. The speed control settings will fluctuate depending on local temperature and pressure.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco part number is
1271300.
For all 115/230 VAC models, the ballast assembly is Labconco part number
3829901.
For all 100 VAC models, the ballast assembly is Labconco part number
3830600.
Product Service 1-800-522-7658
36
IDENTIFYING LOGIC+ MODELS
The Logic+ platform Biosafety Cabinet can be identified readily by several external features, as shown in Figure 1-1:
Serial number beginning with 1303xxxxx Flush-mounted electrical outlets and covers. Color LED display.
Figure 1-1
Logic+ Logo
Color LED Display
Flush-mounted Electrical outlets
Product Service 1-800-522-7658
37
SERIAL NUMBER TAGS
The model/serial number tag is located on the bottom outside edge of the right corner post. A second tag is located on the front of the electronics module on the top of the unit. This tag includes the unit’s operating voltage and amperage. The model and serial numbers of each unit are also recorded on the unit test report attached beneath the front dress panel. These items are shown graphically in the figures 1-3 to 1-5 below:
Figure 1-3
Primary Serial Tag
Figure 1-4
Secondary Serial Tag
Figure 1-5
Final Inspection and Test Report Form
Obviously, you can get confirmation of the Biosafety Cabinet's model by contacting Labconco's Product Service Department, and providing us with the serial number. From this number, we can tell the date of production and its model.
Product Service 1-800-522-7658
38
LOGIC+ MODEL NUMBERING SYSTEM
Logic+ units’ model numbers define the configuration of the cabinet. The first five digits define the unit's configuration, while the last four are assigned based on the unit's options and electrical configuration. Thus, a model number of:
30248xxxx
Labconco Product Group 3=Laminar Flow Products
Indicates the Product Family 0= Logic+ 1= PuriCare 2-4= Cell Logic+
Indicates the Cabinet Type 1= Type A1 2= Type A2
3= Type B2
Indicates the Cabinet width 3= 3-foot Wide 4= 4-foot Wide 5= 5-foot Wide 6= 6-foot Wide
Indicates the sash height 1= 10” sash opening 2= 12” sash opening 8= 8” sash opening 9= 9” sash opening
Product Service 1-800-522-7658
39
Logic+ Data Plate
The Logic+ Data Plate contains much of the information required to certify the unit. Information on the plate includes nominal inflow and downflow velocity settings, a description of how to establish the downflow grid and the secondary inflow methodology are also included on the data plate, as shown below. The plate is located in the upper left corner of the dress panel.
Figure 1-6
Product Service 1-800-522-7658
40
Final Inspection and Test Report Form
A copy of the Final Inspection Test Report is attached to the blower plenum cover, beneath the front dress panel. The report contains initial setup information on inflow and downflow velocities, and the initial blower torque setting. A copy of the report is shown in Figure 1-7, below
Figure 1-7
Model/Serial Numbers
HEPA Filter Information
Test Results
Downflow Test Results
Product Service 1-800-522-7658
41
Theory of Operation
This section offers a brief overview of the theory of operation of the Logic+.
Airflow Patterns
Figure 1-8
All Logic+ Type A2 cabinets meet the airflow requirements of ANSI/NSF Standard 49:2012. Approximately 55-60% of the air in the cabinet is filtered and recirculated, while 40-45% is filtered and exhausted. ALL Logic+s feature intrinsically safe designs, jacketing contaminated positive pressure areas with negative pressure zones.
All Logic+ Type B2 cabinets meet the airflow requirements of ANSI/NSF Standard 49:2012. All of the air in the cabinet is filtered and none is recirculated. ALL Type B2 Logic+s feature intrinsically safe designs, with all contaminated areas under negative pressure.
Figure 1-9
Product Service 1-800-522-7658
42
ECM Motor
The modern Class II Biosafety Cabinet was developed in the early 1960’s as a result of the increased availability of High Efficiency Particulate Air (HEPA)
filter technology. The motor of choice at the time to drive the cabinet’s
blower was the Permanent Split Capacitor (PSC) type. At the time, the PSC motor offered manufacturers an inexpensive power source whose speed could be electronically controlled to allow for airflow adjustment as the HEPA filter(s) loaded.
The PSC motor is known as an induction type, for stationary windings (stator) surround a rotating part (rotor) composed of iron or steel. As current passes through the stator windings, it induces a magnetic field in the rotor, causing it to rotate towards the shifting field in the stator. Because a magnetic field must be induced in the rotor, the PSC motor is asynchronous, with the rotor constantly lagging behind the fields being created in the stator. As a result of this asynchronous operation, the PSC motor is inefficient, and generates high amounts of waste heat. Attempting to control the blower speed by reducing its voltage only increases the inefficiency of the PSC motor.
DC motors are more efficient than their AC counterparts. In a typical DC motor, the stator in an AC motor is replaced with permanent magnets. The rotor then has a series of windings around it. When current is applied to the motor, a magnetic field is created in some of the windings of the rotor, causing it to rotate toward the magnetic field created by the permanent magnets. Brushes in contact with a commutator allow the current, and thus the magnetic field in the rotor to progressively shift from winding to winding, forcing the rotor to keep rotating.
The greatest drawback of brushed DC motors is the brushes-they wear themselves and the commutator down, eventually causing motor failure.
With the development of greater microprocessor power in the 1970s and 80s, the stage was set for an even more efficient type of DC motor – the Electronically Commutated Motor (ECM).
Figure 1-10
In the ECM, the magnets and windings switch position – the permanent magnet is on the rotor, and the series of windings are placed around the rotor. The microprocessor precisely controls the creation of magnetic fields in the stator, so that the rotor is always synchronous with the magnetic fields being created in the stator. As a result, the ECM will always run more efficiently and cooler than a comparable PSC motor. Because of the simple, robust construction of the ECM, it offers far greater reliability and operational service life than the PSC motor.
Product Service 1-800-522-7658
43
Controlling the motor’s operation with a microprocessor adds numerous
advantages. Motor speed can be efficiently controlled across a speed range that would damage or destroy a PSC motor. Given enough microprocessor memory and power, the manufacturer can program in any number of user­selected programs controlling motor speed, power and even direction of rotation. The ultimate expression of the power of the ECM was the development of the constant volume algorithm, by General Electric, and used in the Logic+ BSC. By testing a prototype model to a variety of airflows
and filter pressures, the motor/blower can be “characterized” for that size
cabinet. This characterization allows for the creation of a model-specific motor-blower curve. By programming the curve values into the motor during assembly, the motor will deliver the correct volume of air as the HEPA filters load.
Electronics
The Logic+ utilizes two microprocessors. The first is part of the ECM motor, attached to end of the motor housing, as shown in Figure 1-11. This processor controls motor operation, and communication with the display board. The second is located on the control board, located on the right side wall, as shown in Figure 1-12. It controls the display and its interface to the touchpad.
Figure 1-11
The ECM Microprocessor board is encapsulated in epoxy to prevent moisture and dirt contamination of the microelectronics.
Figure 1-12
The control board assembly (located on the right side wall)
Product Service 1-800-522-7658
44
The Logic+ has three circuit boards. The ECM microprocessor and power supply board, located in the end of the ECM, the control board on the right side wall, shown in Figure 2-5, and the power supply board assembly, located in the electronics module, as shown in Figure 1-13.
Figure 1-13
UV Relay
Light Relay
Outlet Relay
The Logic+ also has an optional contact/RS232 board. This must be installed if the user wants to signal external building monitors or controllers, or wants the Logic+ to output operating information to a data logger. The optional board is located in the electronics module, shown in Figure 1-14.
Figure 1-14
RS-232 Board
Product Service 1-800-522-7658
45
Section Two – Installation Requirements
This section offers an overview of site requirements and how to prepare the unit for operation.
Prerequisites
Before you install the Logic+, you need to prepare the site for installation. Examine the location where you intend to install the cabinet. You must be certain that the area is level and of solid construction. In addition, a dedicated source of electrical power must be located near the installation site.
Carefully read this chapter to learn:
Location requirements.
Electrical power requirements.
Exhaust requirements.
Service utility requirements.
Space requirements.
Refer to
and environmental conditions, specifications and requirements.
Appendix C: Specifications
, for complete biosafety cabinet electrical
Space Requirements
The dimensions for the Logic+ biosafety cabinets are shown in
Miscellaneous
.
Section Nine:
Clearance
A minimum clearance of at least 6 inches (150 mm) is suggested on the top and both sides of the cabinet for service.
Product Service 1-800-522-7658
46
Location Requirements
Figure 2-1
Note: The biosafety cabinet should be located away from traffic patterns, doors, fans, ventilation registers, fume hoods and any other air-handling devices that could disrupt its airflow patterns. All windows in the room should remain closed. Figure 2-1 shows the preferred location for the biosafety cabinet.
Preferred location
Air register blocked or redirected
to prevent cabinet disruption
Alternate location
Main Disconnect Device (Power cord plug in back of the electronics module).
Do not position the unit so that it is difficult to operate the main disconnect device.
Ne placez pas l'appareil de sorte qu'il est difficile de faire fonctionner le dispositif principal de déconnexion.
Product Service 1-800-522-7658
47
Exhaust Requirements Type A
If you intend to connect the biosafety cabinet to the optional VentusTM Canopy Connection Kit, first examine the location to ensure that it
accommodates the cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port should be clear of structural elements, water and
utility lines, or other fixed obstructions. There should be enough clearance to accommodate a 10-inch diameter duct. Avoid cabinet locations that
require an elbow directly above the cabinet’s exhaust connection or an
excessive number of elbows in the exhaust system. For further information about the cabinet’s exhaust system requirements, please refer to
Installation.
Section 3:
Exhaust Requirements Type B2
NOTE: THE EXHAUST BLOWER CANNOT RUN AT ITS NOMINAL FLOW RATE WITH THE SASH COMPLETELY CLOSED. IF YOU CHOOSE TO CLOSE THE SASH COMPLETELY TO USE THE UV LIGHT FOR SURFACE DISINFECTION, THEN THE EXHAUST BLOWER MUST BE SHUT OFF, OR ITS FLOW RATE REDUCED 90% OR MORE FOR PROPER OPERATION. THE LOGIC+ HAS AN OPTIONAL EN/CONTACT CIRCUIT BOARD THAT HAS DRY CONTACTS THAT CAN BE CONFIGURED TO SIGNAL THE EXHAUST BLOWER TO TURN ON WHEN THE LOGIC+’s BLOWER IS ON. FOR FURTHER INFORMATION,
CONTACT LABCONCO’S PRODUCT SERVICE DEPARTMENT. AS AN
ALTERNATIVE, A REMOTE ELECTRICAL SWITCH FOR THE EXHAUST BLOWER CAN BE INSTALLED NEAR THE LOGIC+.
Before deciding on a location, examine it carefully to ensure that it
accommodates the cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port should be clear of structural elements, water and
utility lines, or other fixed obstructions. There should be enough clearance to allow for the passage of a 10" stainless steel duct. Avoid cabinet locations
that require either an elbow directly on top of the cabinet’s exhaust
connection or an excessive number of elbows to clear other items. For a further discussion of the cabinet’s exhaust system requirements, please go
to
Section 3: Installation.
Product Service 1-800-522-7658
48
Electrical Requirements
Model #
Requirements
All 3-& 4-foot Type A ending in -00
115 VAC, 60 Hz, 12 Amps
All 3-& 4-foot Type A ending in -10
100 VAC, 50/60 Hz, 12 Amps
All 3-& 4-foot Type A ending in -20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 6 Amps All Type B2 ending in -00
115 VAC, 60 Hz, 12 Amps
All Type B2 ending in -10
100 VAC, 50/60 Hz, 12 Amps
All Type B2 ending in -20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 6 Amps All 5-& 6-foot Type A ending in -00
115 VAC, 60 Hz, 16 Amps
All 5-& 6-foot Type A ending in -10
100 VAC, 50/60 Hz, 16 Amps
All 5-& 6-foot Type A ending in -20, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
Table 2-1
The biosafety cabinet models have the following electrical requirements:
Note: A dedicated outlet with an appropriate circuit breaker should be located as close as possible to the right rear side of the cabinet, at a height even with, or higher than, the top of the bench or stand. Consult your local electrical codes for properly rated circuit breakers. For safe operation the dedicated outlet must provide the protective earthing ground connection to the cabinet.
Note: On 100 and 115 VAC models, both electrical outlets are protected by
a ground fault interrupter circuit (GFIC). Labconco does not recommend plugging the biosafety cabinet into a GFIC outlet.
Do not use any detachable power cord that is not adequately rated
for the unit.
Ne pas utliser un fil électrique amovible qui n’est pas du tension nominale de l’appareil.
Product Service 1-800-522-7658
49
Service Line Requirements
All utility service lines should be ¼ inch O.D., brass, copper, or stainless steel, and equipped with an easily accessible shut-off valve. If the service line pressure exceeds 40 PSI, it must be equipped with a pressure regulator to reduce the line pressure.
Note: The use of flammable gases or solvents should be avoided in the biosafety cabinet. Open flame in the cabinet will disrupt the laminar airflow in the cabinet and may damage the HEPA filters. Flammable gases or solvents may reach explosive concentrations in the cabinet or ductwork. If you feel that the procedure requires the use of an open flame or flammable materials, contact the institution’s safety office.
The use of air or gases under high pressure should be avoided as they may seriously disrupt the airflow patterns in the cabinet.
Product Service 1-800-522-7658
50
Section Three – Installation
Now that the installation is properly prepared, you are ready to inspect, install, and certify the Logic+ biosafety cabinet. This chapter covers how to:
Unpack and move the biosafety cabinet.
Install the cabinet.
Connect the electrical supply source.
Connect the service lines.
Connect to an exhaust system (optional for Type As).
Tools required for installation the biosafety cabinet include two 1/2" wrenches, a flat­blade screwdriver, a #2 Phillips screwdriver, and a carpenter’s level.
Note: The biosafety cabinet models weigh between 400–700 lbs. (182-318 kg). The shipping pallet allows for lifting with a mechanical lift truck or floor jack. If you must lift the product manually, use at least six (6) persons and follow safe-lifting guidelines.
Product Service 1-800-522-7658
51
Unpacking the Biosafety Cabinet
Carefully remove the outer carton and inspect the cabinet for damage that may have occurred in transit. If the biosafety cabinet is damaged, notify the delivery carrier immediately and retain the entire shipment intact for inspection by the carrier.
Note: United States Interstate Commerce Commission rules require that claims be filed with the delivery carrier within fifteen (15) days of delivery.
Do not return goods without the prior authorization of Labconco. Unauthorized returns will not be accepted.
If the cabinet was damaged in transit, you must file a claim directly with the freight carrier. Labconco Corporation and its dealers are not responsible for shipping damages.
Do not discard the carton or packing material for the biosafety cabinet until all of the components have been checked, installed and tested.
The cabinet is secured to the pallet in two places on each side. To access the nuts and bolts, remove the side panels by removing and keeping the two Phillips screws on both panels. Swing the front of each panel away from the cabinet, and lift it straight up to remove the panel from the cabinet.
Note: The side panels must be removed to access the fasteners that secure the biosafety cabinet to the pallet. DO NOT ATTEMPT TO LIFT THE BIOSAFETY
CABINET BY THE SIDE PANELS; DAMAGE WILL OCCUR.
Preparing the Biosafety Cabinet for Operation
Installation instructions (Labconco P/N 1056801) are attached to the sash of the biosafety cabinet. If these instructions are missing or unclear, contact Product Service at 800-821-5525 or 816-333-8811. The following are located in a box either taped to the top of or underneath the work surface:
User’s Manual CD Drain Valve Assembly and fasteners Power Cord Product Registration Card Vacu-PassTM Accessories (optional)
If you did not receive one or more of the components listed for the cabinet, or if any of the components are damaged, contact Labconco Corporation immediately for further instructions.
Product Service 1-800-522-7658
52
Moving and Lifting the Cabinet
Move the cabinet, attached to its pallet, by using a floor jack, or a furniture dolly underneath the unit. DO NOT move the cabinet by tilting it onto a hand truck.
When lifting the cabinet DO NOT lift the cabinet in the middle front area of the hull. Lifting here may bend or distort the bottom of the cabinet, causing damage to the unit.
Installing the Biosafety Cabinet on an Existing Work Surface
Note: The biosafety cabinet is very top heavy. Use caution when lifting or moving it.
When installing the biosafety cabinet onto an existing work surface or benchtop, ensure that the structure can safely support the combined weight of the cabinet and any related equipment. The work surface should be at least as wide as the cabinet and 31 inches (787 mm) deep to properly support the unit.
A hole or notch may be cut in the supporting surface in the right front corner to accommodate the optional drain valve.
Installing the Cabinet on a Labconco Base Stand
Labconco offers accessory Base Stands in a variety of configurations to suit your particular needs. Stands can be ordered with adjustable telescoping legs or with a manually or electrically adjustable hydraulic lift.
Telescoping Base Stands
These stands are included with some Logic+ models, or are available separately. The base stands for each width cabinet are listed in Table 3-1 below. An optional caster wheel kit is available (part # 3730500).
Product Service 1-800-522-7658
53
Width
Base Stand w/Feet Model #
3'
3401003
4'
3401004
5'
3401005
6'
3401006
Width
Manual Lift Stand #
Electric (115V) Lift Stand
#
Electric (230V) Lift Stand
#
3'
3780200
3780100
3780103
4'
3780201
3780101
3780104
5'
3780203
3780106
3780107
6'
3780202
3780102
3780105
115V SoLo Stand
#
230V SoLo
No. America
Plug #
230V SoLo
UK Plug #
230V SoLo
Schuko Plug
#
230V SoLo
China/Australia
Plug #
3'
3780310
3780314
3780330
3780334
3780338
4'
3780311
3780315
3780331
3780335
3780339
5'
3780312
3780316
3780332
3780336
3780340
6'
3780313
3780317
3780333
3780337
3780341
Table 3-1
Table 3-2
Manual or Electric Hydraulic Lift Base Stands
These base stands offer infinitely adjustable height between 25.5 and 33.5 inches (648 to 851 mm), giving a cabinet work surface height of 28.0 to 36.0 inches. The height is adjusted either by a manual (hand crank) or electric pump that drives hydraulic rams in the legs of the stands. All of the hydraulic stands are equipped with fixed feet, but can be converted to caster wheels with the addition of Caster Kit #3784000. The base stands for each cabinet size is listed in Table 3-2 below.
Note: When installing the cabinet on the hydraulic lift base stand, ensure that the hydraulic lines and the electrical cord are clear of any obstructions before installing the cabinet on the stand or operating the lift system.
SoLoTM Electric Hydraulic Lift Base Stands
These base stands permit the Logic+ to be lowered enough to be transferred through a standard doorway as low as 78 inches. Casters provide mobility and lock in place. The SoLo Stands for each Purifier Logic+ series model is listed below.
Product Service 1-800-522-7658
54
Connecting the Biosafety Cabinet to Utility
Figure 3-1
Service Lines
Note: Some models have a solenoid valve connected to the service valve on the right side, rear position. The solenoid prevents gas from flowing to the service valve when the unit blower is off. It is the only service valve position that can be fitted with a solenoid valve. Connect the gas service to the solenoid valve.
The service lines (if any) should be connected to the tube fitting(s) on the outside of the liner wall as shown in Figure 3-1 To install the tubing, follow these steps:
1. Ensure that the tubing is ¼ inch O.D., soft metal, and that the end has been completely deburred.
2. Route the tubing from the rear of the cabinet, ensuring that it will line up with the slot in the back of the side panel. The slot is located from 8 ¾ to 11 ¼ inches (222 to 288 mm) from the bottom of the cabinet.
Note: Make sure that the tube routing will not contact any electrical wires. DO NOT loop service line tubing within the side panels of the cabinet.
3. Make sure that the nut on the tube fitting is loose, but do not remove it. Look inside the fitting to make sure the tube ferrule is there.
4. Push the tube into the fitting until it is properly seated. The tube will go approximately ¾ inch (19 mm) into the fitting.
5. Tighten the tube fitting nut hand tight and then, using a 7/16-inch wrench, tighten it at least ¾ turn more.
6. Close the service valve in the biosafety cabinet and then slowly open the shutoff valve on the service valve. Test all fittings for leakage. Tighten the tube nut slightly if needed.
Tube fitting nut
Tube fitting
Product Service 1-800-522-7658
55
Optional VentusTM Canopy Exhaust Connection
Certain applications such as working with odorous products or volatile toxic materials will require the connection of the biosafety cabinet to an exhaust system.
Note: The canopy connection, also referred to as a thimble or air gap connection, allows single or multiple biohazard cabinets to be connected to an exhaust system.
During operation, the exhaust system draws all of the cabinet’s exhaust air, plus a
volume of room air (through the vent in the canopy) into the exhaust duct. Canopy
connections function as a “shock absorber” allowing the system to function properly
during changes in room air pressure.
For information on selecting a canopy connection, go to
Note: If the research involves the use of toxic compounds or volatile materials, contact
the facility’s safety officer or Labconco to ensure that the biosafety cabinet and its exhaust system are compatible with the materials you will be working with.
Section Eight: Accessories.
Product Service 1-800-522-7658
56
Optional Vacu-PassTM Cord & Cable Portal
Figure 3-2
Use
Note: There must be enough clearance to pass the cord or cable between the Logic+’s exterior dress panel and any obstruction.
Note: Some Vacu-Pass components and the cord or cable passing through it may become contaminated during use of the cabinet. Ensure all potentially contaminated components are surface decontaminated before handling or removal from the cabinet.
1. Remove the grommet from the liner side wall. Remove the solid sealing plug from the body of the portal by either pressing it through from the outside, or by carefully inserting a spatula or similar device between the sealing plug and the body of the portal, and prying the plug out.
2. Pass the cord or cable through the body of the portal, and then through one of the plugs that has been cut for cord or cable use, then through the grommet, as shown in Figure 3-2.
Note: select a plug with a hole that is slightly smaller than the cord or cable, to create a proper seal. This will also help minimize movement of the cord or cable if it is accidentally pulled during use.
3. Position the cord or cable as it will be used in the cabinet, and then push the plug back into the body of the portal until it seats in the portal. Reinstall the grommet.
Product Service 1-800-522-7658
57
Drain Valve Installation
Figure 3-3
In order to prevent damage during shipping, the drain valve assembly has not been installed. If desired, the valve should be installed after the cabinet is in its final location.
To install the valve assembly, follow these steps:
Note: The work surface is heavy. Use caution when handling it.
4. Lift the work surface out of the biosafety cabinet by lifting on the knobs at the front of the work surface. Steady the work surface while pulling it straight out the front of the cabinet.
5. Using a putty knife, remove and discard the stainless steel cover that is sealed over the drain mounting holes. Scrape out remaining sealant that is around the holes.
6. Apply a light coating of silicone sealant (user supplied) to the mounting surface of the drain assembly. Attach the drain assembly under the bottom of the cabinet as shown in Figure 3-3. Wipe off any excess sealant from the cabinet bottom. Ensure that the center drain hole is unobstructed.
7. Make sure the drain valve is in the closed position.
8. Reinstall the work surface.
9. Allow the silicone sealant to cure for at least eight hours before exposing it to liquid.
NOTE: The drain valve assembly attaches to the underside of the cabinet bottom.
Apply a light coat of silicone sealant to this surface of the connector, aligning the three holes in the connector with the three holes in the biosafety cabinet liner.
Product Service 1-800-522-7658
58
Section Four -
Figure 4-1
Initial Operation of the Logic+
This section will take you through the steps to begin initial operation of the Logic+, with an explanation the controls, display and options, in order to prepare the unit for its initial certification.
System Reset Switch
The biosafety cabinet has a system reset switch for resetting its microprocessors. The switch is located on the front of the electronics module, on top of the cabinet, as shown in Figure 4-1. Ensure that the switch is in the “ON” (up) position before attempting to operate the cabinet.
The System Reset Switch
Product Service 1-800-522-7658
59
Information Center
Figure 4-2
Figure 4-3
The Information Center is an LCD display located on the right side wall at eye level.
When the blower is started, the words “please wait” will be displayed, as shown in
Figure 4-2. After approximately 90 seconds, the display will switch to normal operation.
The display provides a clock, the remaining filter life, the cabinet’s current status, inflow
and downflow velocities (if equipped with the optional airflow sensor), as shown in Figure 4-3. In the event of an alarm, the Information Center will immediately display a context sensitive display indicating the cause of the alarm, and possible solutions, as shown in Figure 4-4.
The display will enter sleep mode, turning itself off, one minute after the blower is turned off or the sash is closed.
Clock
Filter Life
Status Display Window
Product Service 1-800-522-7658
60
Alarm Screens
Sash is too high
The sash is open too far for safe operation.
Airflow Alert
The airflow patterns in the cabinet have changed, resulting in a sudden change in the motor speed. This is most likely due to a blockage of the grille or the exhaust filter outlet. It may also be caused by removal of the work surface while the cabinet is in operation.
Airflow Alarm
If equipped with the optional airflow sensor and the inflow or downflow velocities are excessively high or low, this alarm will be displayed.
Canopy Alarm
If equipped with the optional canopy connection, and there is insufficient exhaust system airflow, this alarm will be displayed. If this alarm is displayed, the Logic+ blower will need to be turned off, and then back on again to reset the alarm.
System Error
The motor and display circuit board are not communicating properly. DO NOT USE THE CABINET UNTIL THE PROBLEM HAS BEEN CORRECTED.
Product Service 1-800-522-7658
61
Operating the Sliding Sash
Figure 5-5
The counterbalanced, anti-racking sash mechanism requires only a few pounds of force to move the sash up or down. You can open or close the sash smoothly with one or two hands positioned on either handle.
The sash position alarm and safety interlock system senses the sash position and acts appropriately. The biosafety cabinet has been programmed to operate at either an 8-, 9­, 10- or 12-inch (203-305 mm) sash opening, depending on model. Raising the sash above its operating height will activate the audible and visual alarms. The audible alarm can be temporarily muted (for approximately five minutes) by depressing and releasing the
OK/Mute
and defeat the muting of the alarm. The safety interlock system senses when the sash is closed and allows the optional ultraviolet (UV) lamp to operate only when the sash is closed, to protect the operator from irradiation.
button. Closing the sash back to its operating position will reset the alarm
Starting the Biosafety Cabinet
1. To start the biosafety cabinet, raise the sash until its bottom edge aligns with the
sash position label on the left corner post. The decal is shown in Figure 5-5.
2. For Type A Cabinets: Press the blower button to start the unit. The unit will
display a standby screen for approximately 90 seconds to allow the cabinet to reach proper operating conditions. If the alarm sounds, recheck the sash position. If the sash is too high, the sash audible alarm and the LCD display will indicate the sash is too high.
3. For Type B2 Cabinets: Press the blower button to activate the display and
again to start the unit. If the exhaust flow is insufficient at startup, the Logic+
blower will not start, and the Status Display Window will display “airflow check”,
and continue to sample the exhaust flow. If the exhaust airflow is sufficient within 60 seconds, the cabinet blower will then start, and the Status Display
Window will display the “please wait” message for approximately 90 seconds to
allow the cabinet to reach proper operating conditions. If the exhaust flow is insufficient after 60 seconds, the audible alarm will sound, and the LCD display
will indicate an Inflow Alarm. The alarm can be reset by pressing the “Blower”
button again.
4. To turn the optional UV light on, the sash must be completely closed to prevent
the escape of any UV radiation. Push the UV light button to activate the UV light.
Note: The sash must be completely closed for the UV light to activate.
Sash position label
Product Service 1-800-522-7658
62
The Logic+ Touchpad
Figure 5-6
The touchpad of the Logic+ is shown in Figure 5-6. Take a moment to get familiar with the buttons, their locations and functions. Also familiarize yourself with the display located on the right side wall. The display will report system functions, such as filter capacity, timer displays, alarm or error messages, as well as icons that illuminate when cabinet functions such as UV light and blower are operational.
Blower Button Starts or stops the cabinet blower. When the blower is in Smart-StartTM mode, opening the sash from the closed position turns the blower on automatically. In Night-SmartTM mode, when the sash is closed, the motor slows to idle to maintain air cleanliness in the work area. When the sash is reopened, the blower resumes normal operation. Pressing this button overrides Smart-Start and Night-Smart operation.
Light Button – Turns the fluorescent lamps on or off. Closing the sash automatically turns the lights off. When the lights are in Smart-Start mode, raising the sash turns the lights on automatically.
Outlet Button – Turns the electrical outlets in the work area on or off.
UV Light Button – Turns the UV lamp on or off. When the UV lamp is in Smart-Start mode, closing the sash turns the light on. When the sash is raised, the light turns off automatically.
Timer Button – Allows you to select either a repeating interval timer, or an elapsed timer (stopwatch).
OK/Mute Button – Mutes all audible alarms for approximately 5 minutes, unless there is a system error alarm. When in the Menu mode, this button is used to select an option.
Menu Button – This button toggles the display between the display and menu modes. When in the menu mode, pressing this button returns you to the previous menu level.
Select Buttons – Allow you to choose different options in the menu mode.
Product Service 1-800-522-7658
63
Navigating the Logic+ Menu Screens
MyLogicTM allows you to use the Smart-Start or Night-Smart features that activate functions automatically when the sash is opened or closed.
If equipped, the UV lamp can be programmed to operate for a given time interval when the sash is closed, before it shuts off.
NOTE: When you are in the menu mode, if a selection is not made within 30 seconds, the display will reset back to display mode.
Keypad operations are shown as
green italics
NOTE: Pressing the appropriate touchpad button will override Smart-Start or Night-Smart selections.
To access the menu, press the menu. To select from the various menu options press the or buttons until the selected option is displayed. Press return to the previous menu level.
.
Display Mode Menu Mode
blue bold italic
Menu
button. The display panel will show the first level
OK/MUTE
. Menu screen selections are shown as
to accept that option, or press
Menu
Menu
to
Product Service 1-800-522-7658
64
Navigating the MyLogicTM Menu Screens
The MyLogic screens will allow you to set the cabinet’s clock, and to personalize its
operation. Please note all MyLogic screens have a blue background.
Setting the Clock
Using the and buttons on the touchpad, highlight the blue when selected. Press
Using the and buttons on the touchpad, highlight when selected. Press
At this screen, select whether you want the clock to display in a 12- or 24-Hour format. When you have highlighted your choice, press
OK/MUTE
Use the and buttons to select the hour, and press
Use the and buttons to select the minute, and press screen.
to go to the next screen…
OK/Mute
OK/MUTE
OK/MUTE
OK/MUTE
to return to the first MyLogic
to enter the first MyLogic screen:
OK/Mute
to enter the first clock setting screen:
set the clock
MyLogic
option-it will turn
-it will turn white
Product Service 1-800-522-7658
65
Configuring the Logic+
In the first MyLogic screen, use the and buttons on the touchpad to highlight
Logic for use
OK/MUTE
The first screen gives you the option of activating the Smart-Start option for the blower; if you want the cabinet blower to start every time you raise the sash, select
start
is selected, then the blower must be manually started from the keypad. When pressed, the next configuration screen will appear.
The next screen gives you the option of activating the Smart-Start option for the fluorescent light; if you want the lights to turn on every time you raise the sash, select If
stay off
manually turned on from the keypad. When
OK/MUTE
will appear.
If you want the cabinet blower to run slowly, maintaining reduced airflows every time you close the sash, select press
OK/Mute
blower will stop when the sash is closed. When
OK/MUTE
will appear.
If your Logic+ is configured for a UV light, then you will see the next two screens; if you want the UV lamp to turn on every time you close the sash, select
go into Night-Smart mode
OK/Mute
will not turn on when the sash is closed. When
OK/MUTE
screen will appear.
-it will turn white when selected. Press
to enter the first configuration screen:
start
, and then press
turn on
is selected, then the lights must be
is pressed, the next configuration screen
, and then press
go into Night-Smart mode
. If
stop
is selected, then the
is pressed, the next configuration screen
. If
stay off
is pressed, the final configuration
is selected, then the UV light
configure my
OK/Mute
OK/MUTE
. If
is
OK/Mute
and then
, and then press
not
.
Product Service 1-800-522-7658
66
If you choose to use Night-Smart option for the UV lamp, this screen allows you to control the time the UV lamp will remain on after the sash is closed. Use the and buttons on the touchpad to cycle through the time intervals available, and then press The screen will then return to the first MyLogic screen.
OK/MUTE
to select it.
Navigating the Settings Menu Screens
The Settings screens will allow an administrator to set some of the cabinet’s operational
parameters. Please note all Settings screens have a green background. Using the and buttons on the touchpad, highlight the green when selected. Press OK to enter the first Settings screen:
Settings
option-it will turn
OK Button
Display Options
Units of Measure
Note: The Units of Measure refers to the display of airflow velocities if the cabinet is equipped with the optional airflow sensor.
Using the and buttons on the touchpad, highlight the white when selected, and then press OK. Using the
and buttons on the touchpad, highlight either
metric
or when selected, and then press OK. The screen will then return to the first Settings screen.
Units of Measure
imperial
units of measure-it will turn white
option-it will turn
Product Service 1-800-522-7658
67
Startup tone
The Security Lock Is:
or t o choose,
OK to select, M ENU to return
turned on
button for mor e than 5
seconds to unl ock the Logic)
turned off
(Hold the

Security Lock
Using the and buttons on the touchpad, highlight the
Startup Tone
option-it will turn white when selected, and then press OK. Using the and buttons on the touchpad, highlight either
Turned on
or
Turned off
option. When turned on, an audible beep will sound during the first 90 seconds of blower operation to caution the user that the unit is not yet ready for use.
Security Lock
Note: The Security Lock feature “locks” the keypad to prevent unauthorized use of the
cabinet. The security lock is unlocked by holding the button for at least 5 seconds. The lock deactivates after cabinet is unlocked.
From the Settings menu screen, use the and buttons on the touchpad to highlight the turn white when selected. Press Security Lock screen. Using the and ▼ buttons on the touchpad, highlight either
turned on
white when selected, press return to the first Settings screen.
RS-232 Output Rate
Note: This selection will only work if the optional EN/RS-232 board is installed.
This menu option selects the rate that the RS-232 board outputs data. Data can be output at a rate of once per second, once every 10 seconds, once every 30 seconds, or once per minute.
From the Settings menu screen, use the and buttons on the touchpad to highlight the white when selected. Press 232 output screen. Using the and buttons on the touchpad, highlight either the data output rate preferred. It will turn white when selected, and then press OK. The screen will then return to the first Settings screen.
Security Lock
OK/MUTE
or
OK/Mute
RS-232 output
OK/MUTE
option-it will
to enter the
turned off
-it will turn
. The screen will then
-it will turn
to enter the RS-
Product Service 1-800-522-7658
68
UV Settings
For models equipped with the optional UV light the Logic+ has an integral UV light maintenance system. It allows you to define how many hours you want the UV lamp to operate before receiving a reminder to replace it, a way to monitor how many hours the lamp has been on, and the means to reset the UV lamp hourmeter.
UV Lamp Hourmeter
This display only shows how many hours the UV lamp has been lit, and how many hours remain until you will receive a warning to replace the lamp.
From the Settings menu screen, use the and buttons on the touchpad to highlight the option-it will turn white when selected. Press enter the UV Settings screen. Using the and buttons on the touchpad, highlight UV Hourmeter-it will turn white when selected, and then press then return to the UV Hourmeter screen.
This screen displays how many hours the UV lamp has operated, and how many hours of operation remain before replacement is recommended. When finished with this screen, press screen.
MENU
to return to the first UV Settings
OK/Mute
Reset UV Lamp Hourmeter
This option lets you reset the UV hourmeter to 0 hours whenever the lamp has been replaced.
This screen allows you to reset the UV Hourmeter to 0 hours if you press you to the first UV Settings screen without resetting the hourmeter.
OK/Mute
. Pressing
Change UV Lamp Life
In this screen, you can set the number of operating hours before receiving the replace UV lamp warning. For most UV lamps, the output of UV light decreases at a constant rate. Typically, after 6,000 hours of operation the lamp will output 80%. This option allows you to set operational life of the UV lamp, in 100 hour increments.
From the UV Settings menu screen, use the and buttons on the touchpad to highlight the it will turn white when selected. Press the Set UV life screen. Use the and buttons to increase or decrease the lamp life in 100 hour increments, until the desired value is displayed, and then press screen will then return to the UV Settings screen.
UV Settings
OK/MUTE
. The screen will
MENU
will return
Set UV Life
OK/MUTE
to enter
OK/Mute
to
option-
. The
Product Service 1-800-522-7658
69
Timer Operation
NOTE: The timer button allows activation of an interval (countdown) or stopwatch (elapsed) timer. The timers cannot be operated simultaneously.
To access the main timer menu, press the operation. The main timer menu is shown on the LCD display. Use the and buttons to highlight the highlighted timer function.
Interval
or
Stopwatch
Timer
Timer. Press the
button anytime during normal
OK/MUTE
button to select the
Interval Timer Operation
1. When selected, the Interval Timer menu is displayed on the LCD. The timer defaults to 0:00:00 (hours:minutes:seconds).
2. Press and hold the or buttons to increase or decrease the timer interval.
3. When the proper interval is entered on the display, press the to start the timer.
4. When the timer reaches 0:00:00, an audible alarm will sound, and the timer will reset itself and repeat the countdown.
5. Press the
6. Press the menu.
OK/MUTE Menu
button to pause the timer.
button to clear the interval timer and return to the main timer
OK/MUTE
button
Stopwatch Timer Operation
1. When selected, the Stopwatch Timer menu is displayed on the LCD. The timer defaults to 0:00:00.
2. Press the
3. Press the
4. Press the timer menu.
OK/MUTE OK/MUTE Menu
button to start the timer. button again to zero the timer.
button to clear the stopwatch timer and return to the main
If An Airflow Alert Activates
The most common causes of an Airflow Alert are:
Blockage of the inlet grilles or exhaust outlet.
Removal of the work surface or grille during operation.
Resetting the Airflow Alert System
The Airflow Alert automatically resets to normal operation once the motor speed has stabilized.
Product Service 1-800-522-7658
70
Section 5
Certification Procedures for the Logic+
This section will outline test procedures to validate the performance of the Logic+.
Note: These are the only Labconco-approved test procedures for validating the performance of the Logic+ Biosafety Cabinet. Other test procedures may yield different or inaccurate test results.
NOTE: In order to properly certify the Logic+, you must obtain a Logic+ Certifier Kit, Labconco P/N 3858400. Qualified certifiers can obtain this kit by contacting Labconco Customer Service Department at 800-821-5525.
Note: The ECM motor is programmed by Labconco to deliver a constant volume of air throughout the life of the HEPA filters. Any changes to the blower speed control should be small (less than 5 units).
Accessing the Certifier’s Menu
Note: You will need to access this menu to do any of the following:
Adjust the blower speed To reset the filter gauge To calibrate the optional airflow sensor
Adjusting the blower speed
1. With the Logic+ operating, press: “
2. The Display will change to Menu mode. Press the or arrows until “ is selected. Press: “OK/Mute”
3. The Display will then change to the password mode. In sequence, press:
“Light” “UV Light” “Timer” “Timer” “OK/Mute”
4. NOTE: The cabinet blower will automatically stop for approximately 60
seconds to zero the unit, and then automatically restart the blower. The display will change to the speed setting mode. The number displayed is the speed control setting, in this case a pulse width modulation (PWM) signal that indicates the percentage of the motor’s duty cycle. The number should range from 60 to 90 depending on the Logic+ model. To increase or decrease the blower speed, press the or buttons, respectively. When the speed control is set properly, press and change the display to the filter gauge mode.
OK/Mute
Menu
Service
” This will set the controller to its new value,
Product Service 1-800-522-7658
71
Logic+ Filter Life Gauge Operation and Resetting for Local Conditions
The filter life gauge calculates the remaining filter life by measuring and comparing the current motor speed to the initial speed noted at the factory during assembly, and the calculated maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left max. speed-original speed
So
anything
Blocking the grille. Raising the air temperature. Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic dampening of the gauge will limit the change in readings to approximately 1%/minute.
Logic+ Biosafety Cabinets being installed at altitudes or operating at temperatures significantly different from those at the time of manufacture (900 +/- 500 ft above sea level, 75o +/- 5o F)
must
have their filter life gauge recalibrated for local conditions. Failure to do so will result in the users noticing a steady drop in Percent (%) Filter Life remaining as the unit operates. Below are the instructions on how to correct the Filter Life Gauge for local conditions.
1. Ensure to correct all measurement equipment for local conditions (temperature, absolute
2. As the elevation or the ambient temperature rises, the motor power factor will have to be
3. The Logic+ MUST be recertified using instruments corrected for local conditions.
4. When the unit is recertified, and operating properly, the certifier MUST RESET THE
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND RECERTIFIED FOR
6. If you do not wish to reset the filter gauge, select the option “Filter not changed”, and
7. Either selection will finish the calibration mode, or lead to calibration of inflow and
that changes the motor’s current speed, like:
pressure). Anemometers may not have this ability and might have to be done manually; whereas, a ShortRidgeTM instrument has a setting to correct for local conditions.
reduced to compensate. For an initial certification, the motor speed should be reduced until it equals the Logic+’s “Initial Motor Speed” as reported on the unit’s test sheet, plus approximately 10-15 RPM per each additional 1000 feet of elevation.
FILTER LIFE GAUGE, INDICATING A NEW FILTER HAS BEEN INSTALLED.
ITS LOCAL CONDITION, will the filter life gauge register 100% (+/- 2%) during operation. As the Filters then load, the filter life gauge will then begin to drop as appropriate.
press “Mute/OK”.
downflow velocities.
Product Service 1-800-522-7658
72
Adjusting the optional inflow and downflow values
Note: This step is only available if the optional airflow sensor is installed.
1. Using the or buttons, increase or decrease the displayed inflow velocity until it matches the observed value, then press The display will now change to downflow velocity calibration screen.
2. Using the or buttons, increase or decrease the displayed downflow velocity until it matches the observed value, then press
3. Once the downflow is confirmed, the unit will then automatically turn off and then back on.
OK/Mute
OK/Mute
to confirm the value.
to confirm the value.
Type A HEPA Filter Leak Test Information
All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012.
Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding.
Figure 5-1
Note: For all Logic+ models, the aerosol generator should be placed in the left rear corner of the work area, pointing toward the rear grille, as shown in Figure 5-1.
If the Logic+ is Contaminated
(An upstream concentration cannot be established)
If the Logic+ has been used with biohazardous, toxic chemicals, or radioisotopes, the DOP access port cannot be used. The upstream concentration cannot be measured directly. Testing at Labconco has shown the actual concentration varies from the calculated value. Table 5-1 shows the actual vs. calculated concentrations for the Type A models.
Product Service 1-800-522-7658
73
Cabinet
Width (Feet)
3 3 4 4 5 5 6 6 Sash Height
(inches)
10, 12
8, 9
10, 12
8, 9
10, 12
8, 9
10, 12
8, 9
Air
Displacement
(CFM)
596
543
794
723
991
903
1189
1083
Laskin Nozzles
needed
1 1 2 2 2 2 2
2
Calculated
aerosol conc.
(ug/l)1
23
25
34
38
27
30
23
25
Actual aerosol
conc. (ug/l)2
12
14
18
21
15
17
15
17
Type A HEPA Filter Leak Test Specifications
1. The calculated concentration was established by the formula: Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
2. Based on Mineral oil
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
2. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level.
3. Establish the 100% and 0% concentration levels for the photometer.
Table 5-1
Product Service 1-800-522-7658
74
If the Logic+ is Uncontaminated
(Establishing an Upstream Concentration)
The Purifier utilizes a unique aerosol access tube for sampling the upstream concentration of aerosol. If after reading these instructions, you have further questions, please contact Labconco's Product Service Department.
Note: The access tube contains contaminated air under positive pressure. DO NOT access this line until the cabinet has been decontaminated.
1. Remove the work surface by lifting the handles on either end. Pull the work surface straight out of the Logic+.
Locate the access tube on right side of the rear plenum wall, behind through the towel
catch. As shown in Figure 5-2.
Figure 5-2
2. Pull the tube toward the front of the unit. Remove the access tube cover.
3. Using an appropriate photometer, connect the unit's upstream line to the access tube.
Note: Keep the photometer sampling tube as short as possible. It should never exceed 6 feet maximum.
4. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
5. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level.
Product Service 1-800-522-7658
75
Type A Supply HEPA Filter Test
Downflow Diffuser Removal
1. Remove the diffuser by raising the sash as high as it will go, and then removing the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-3.
Figure 5-3
Removing the diffuser acorn nuts (Dress panel and lamps removed for clarity only).
Note: The diffuser acorn nuts are secured to the studs with a removable thread locking compound to prevent them from vibrating loose during shipment of the Logic+. There may be some resistance the first time the nuts are removed; this is normal. No additional thread locking compound need be applied to these acorn nuts unless the unit is being prepared for shipment.
2. Lower the front edge of the diffuser until clears the bottom of the sash, and then pull the diffuser straight out of the cabinet, as shown in Figure 5-4.
Figure 5-4
3. The Logic+ is now ready for the HEPA Filter Leak Test. Set the photometer
sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the
sampling port of the pistol.
Product Service 1-800-522-7658
76
4. Open the following number of Laskin nozzle(s): For all 3-foot Logic+ models – 1 nozzle For all 4-, 5- and 6-foot Logic+ models – 2 nozzles
5. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
6. Scan the downstream side of the HEPA filter by passing the sampling nozzle of the gun in slightly overlapping strokes over the entire surface of both of the filters, with the sampling port not more than 1 inch from the surface of the filter media. Scan the entire periphery of the filters and the gaskets between the filter frame and the Logic+ frame. Scanning shall be done at a traverse rate of not more than 2 inches per second.
Note: Operation of the photometer may become erratic when testing the front edge of the supply filter frame, due to aspiration of room air into the front of the work area. This problem can be minimized or eliminated by placing the edge of a sheet of rigid plastic or metal at the edge of the filter gasket when scanning this area, as shown in Figure 5-5.
Figure 5-5
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassemble the unit by compressing the exhaust filter cover while installing its tabs back into the exhaust filter bracket slots. Reinstall the diffuser, ensuring that the holes in the back of the diffuser frame engage the posts on the rear wall of the work area, as shown in Figure 5-6.
Figure 5-6
Diffuser pins engaging the holes in the rear of the diffuser.
Product Service 1-800-522-7658
77
Type A Exhaust HEPA Filter Test
Opening the Exhaust HEPA Filter Cover
If there is sufficient overhead clearance (18 or more inches) –
1. Loosen the two Phillips screws on the front sides of the filter cover, as shown in Figure 5-7. Tilt the cover back access the downstream side of the filter, as shown in Figure 5-8.
Figure 5-7
Loosen these screws to tilt the cover back.
Remove these acorn nuts to remove the cover.
If there is insufficient overhead clearance –
1. Loosen the two Phillips screws on the front sides of the filter cover, and remove the four acorn nuts and washers. Carefully lift the cover off of the top of the cabinet.
Note: exercise caution when removing or installing the exhaust filter cover, to prevent damaging the Exhaust HEPA filter.
Product Service 1-800-522-7658
78
2. The Logic+ is now ready for the HEPA Filter Leak Test. Set the photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the sampling port of the pistol.
3. Open the following number of Laskin nozzle(s): For all 3-foot Logic+ models – 1 nozzle For all 4-, 5- and 6-foot Logic+ models – 2 nozzles
4. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
5. Scan the downstream side of the HEPA filter by passing the sampling nozzle of the gun in slightly overlapping strokes over the entire surface of both of the filters, with the sampling port not more than 1 inch from the surface of the filter media. Scan the entire periphery of the filters and the gaskets between the filter frame and the Logic+ frame. Scanning shall be done at a traverse rate of not more than 2 inches per second.
Note: Operation of the photometer may become erratic when testing the edges of the exhaust filter frame, due to aspiration of room air into the front of the work area. This problem can be minimized or eliminated by placing the edge of a sheet of rigid plastic or metal at the edge of the filter gasket when scanning this area, as shown in Figure 5-8.
Figure 5-8
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassemble the unit by compressing the exhaust filter cover while installing its tabs back into the exhaust filter bracket slots. Reinstall the diffuser, ensuring that the holes in the back of the diffuser frame engage the posts on the rear wall of the work area, as shown in Figure 5-6.
Product Service 1-800-522-7658
79
Type B HEPA Leak Test Information
All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012.
Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding.
Type B Supply HEPA Filter Leak Test
All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012.
Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding.
Note: For all Logic+ models, the prefilter element should be removed, and the aerosol generator should be placed nearby to inject the aerosol as shown in Figure 5-9.
Figure 5-9
Place aerosol generator on top of the electronics module
Remove the prefilter before starting the test
Measuring the Upstream Concentration
The Logic+ utilizes a unique aerosol access tube for sampling the upstream concentration of aerosol. If after reading these instructions, you have further questions, please contact Labconco's Product Service Department.
1. Remove the work surface by lifting the handles on either end. Pull the work surface straight out of the Logic+.
2. Locate the access tube on right side of the rear plenum wall, passing through the towel catch. As shown in Figure 5-10.
Product Service 1-800-522-7658
80
Figure 5-10
Model
30340
30360
Air Displacement (CFM)
445
665
Laskin Nozzles needed
1
1
Theoretical aerosol conc.
(ug/l)1
30
20
Actual aerosol conc. (ug/l)1
15
12
3. Pull the tube toward the front of the unit. Remove the access tube cover.
4. Using an appropriate photometer, connect the unit's upstream line to the access tube.
Note: Keep the photometer sampling tube as short as possible. It should never exceed 6 feet maximum.
5. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
6. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level.
Calculating the upstream concentration
If you do not want to connect the upstream line of the photometer to the sampling port located on the supply filter plenum, you must calculate the upstream concentration. Testing at Labconco has shown the actual concentration varies from the calculated value. Table 5-2 shows the actual vs. calculated concentrations for the B2 models.
Table 5-2
Type B2 Supply HEPA Filter Leak Test Specifications
1. The calculated concentration was established by the formula: Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
2. Based on Mineral oil
Product Service 1-800-522-7658
81
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
2. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level.
3. Establish the 100% and 0% concentration levels for the photometer.
4. Remove the diffuser by raising the sash as high as it will go, and then removing the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-11.
Figure 5-11
Removing the diffuser acorn nuts (Dress panel and lamps removed for clarity only).
Note: The diffuser acorn nuts are secured to the studs with a removable thread locking compound to prevent them from vibrating loose during shipment of the Logic+. There may be some resistance the first time the nuts are removed; this is normal. No additional thread locking compound need be applied to these acorn nuts unless the unit is being prepared for shipment.
5. Lower the front edge of the diffuser until it clears the bottom of the sash, and then pull the diffuser straight out of the cabinet, as shown in Figure 5-12.
Figure 5-12
6. The Logic+ is now ready for the Supply HEPA Filter Leak Test. Set the
photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum
at the sampling port of the pistol.
Product Service 1-800-522-7658
82
7. Open one Laskin nozzle.
8. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
9. Scan the downstream side of the HEPA filter by passing the sampling nozzle of the gun in slightly overlapping strokes over the entire surface of both of the filters, with the sampling port not more than 1 inch from the surface of the filter media. Scan the entire periphery of the filters and the gaskets between the filter frame and the Logic+ frame. Scanning shall be done at a traverse rate of not more than 2 inches per second.
Note: Operation of the photometer may become erratic when testing the front edge of the supply filter frame, due to aspiration of room air into the front of the work area. This problem can be minimized or eliminated by placing the edge of a sheet of rigid plastic or metal at the edge of the filter gasket when scanning this area, as shown in Figure 5-13.
Figure 5-13
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassembly
When reinstalling the supply filter diffuser, ensure that the two holes in the back edge of the diffuser engage the diffuser support posts on the rear wall of the work area, as shown in Figure 5-14. Reinstall the prefilter.
Figure 5-14
Diffuser pins engaging the holes in the rear of the diffuser.
Product Service 1-800-522-7658
83
Type B2 Exhaust HEPA Filter Leak Test
Model
30340
30360
Air Displacement (CFM)
723
1083
Laskin Nozzles needed
2
2
Theoretical aerosol conc.
(ug/l)1
38
25
Actual aerosol conc. (ug/l)1
21
17
All Logic+ models were tested to the HEPA Filter Leak Test as described in ANSI/NSF Standard 49:2012.
Note: ensure all internal surfaces of the Logic+ have been appropriately decontaminated before proceeding.
Note: If so equipped, the prefilter element on the towel catch should be removed, and the aerosol generator should be placed nearby to inject the aerosol as shown in Figure 5-15.
Figure 5-15
Testing at Labconco has shown the actual concentration varies from the calculated value. Table 6-2 shows the actual vs. calculated concentrations for the B2 models.
Table 5-3
Type B2 Exhaust HEPA Filter Leak Test Specifications
3. The calculated concentration was established by the formula: Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
4. Based on Mineral oil
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes. Leave the valve in the “CLEAR” setting.
2. Check the oil level of the generator – it must be within 1/8” of the level line when the generator is sitting level.
3. Establish the 100% and 0% concentration levels for the photometer.
Product Service 1-800-522-7658
84
4. Locate a sampling port downstream of the exhaust HEPA filter. The sampling port should ideally be at least 10 duct diameters from any elbow and 10 duct diameters downstream of the filter.
5. The Logic+ is now ready for the Exhaust HEPA Filter Leak Test. Set the
photometer sampling valve to “DOWNSTREAM”. Ensure there is a proper
vacuum at the sampling tube.
6. Open the Laskin nozzle(s).
7. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
8. Observe the average concentration of aerosol downstream.
Acceptance
Average aerosol penetration shall not exceed 0.005%.
Reassembly
Reinstall the prefilter on the towel catch, if so equipped.
Product Service 1-800-522-7658
85
Downflow Velocities
Cabinet Width (Feet)
3 3 4
4* 4 5 5 6
6
Sash Height (inches)
8, 9
10, 12
8, 9
8
10, 12
8, 9
10, 12
8, 9
10, 12
Nominal Avg. Downflow
(FPM)
55+/-5
55+/-5
55+/-5
75+/-5
55+/-5
55+/-5
55+/-5
55+/-5
55+/-5
Downflow test grid # of
points
21
21
24
24
24
30
30
36
36
Test Grid (# rows x #
columns)
3 x 7
3 x 7
3 x 8
3 x 8
3 x 8
3 x 10
3 x 10
3 x 12
3 x 12
Test Grid Data (in
inches)
Grid distance from back & sides
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
Distance between rows
5.75
5.55
5.75
5.75
5.55
5.75
5.55
5.75
5.55
Distance between columns
4.08
4.08
5.21
5.21
5.21
5.39
5.39
5.50
5.50
All Logic+ models, EXCEPT 30248xx80) are classified as having uniform downflow, and the average downflow velocity for all models is 55+/-5 FPM, tested as per ANSI/NSF Standard 49:2012.
All readings should be in a plane 4 inches above the bottom edge of the sash, and the UV Lamp, IV bar and all other accessories must be removed before performing downflow test. The test grid dimensions are outlined in Table 5-4. When taking readings in the back two rows, the anemometer probe should be pointing toward the nearest side wall, as shown in figure 5-16. When reading the front row, the probe should point outward, toward the front of the cabinet, as shown in Figure 5-17. The thermal anemometer’s time constant should be set at 10-15 seconds for greater data stability.
Table 5-4
Downflow Test Specifications
- Model #s 30248xx8x Only
Figure 5-16
Product Service 1-800-522-7658
86
Figure 5-17
Acceptance
Average downflow shall be 55 +/-5 FPM with all test points being within +/- 16 FPM.
Inflow Velocity Calculation - Primary Method
Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow value.
The average inflow velocity for Logic+ A2 and B2 models is 105 ±5 FPM, and Type A1s are 85+/-5 FPM. It should be determined by converting the inflow volume to the average inflow velocity. The inflow volume is measured directly by sealing a direct inflow measuring flow meter to the face of the unit. When corrected for local conditions, dividing the inflow volume by the opening area will yield the average inflow velocity.
Product Service 1-800-522-7658
87
Table 5-5
Width (feet)
3 4 5
6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.03
2.69
3.36
4.03
Nominal Avg. Exhaust Vol.
(CFM)
213
283
353
423
Avg. Exhaust Vol. Range
(CFM)
203-223
269-296
336-370
403-443
Width (feet)
3 4 5
6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.28
3.03
3.78
4.53
Nominal Avg. Exhaust Vol.
(CFM)
240
318
397
476
Avg. Exhaust Vol. Range
(CFM)
228-251
303-333
378-416
453-498
Width (feet)
3 4 5
6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
2.53
3.37
4.2
5.03
Nominal Avg. Exhaust Vol.
(CFM)
266
354
441
529
Avg. Exhaust Vol. Range
(CFM)
253-278
337-371
420-462
503-553
Width (feet)
3 4 5
6
Nominal Average Inflow
(FPM)
85+/-5
85+/-5
85+/-5
85+/-5
Sash Open Area (Sq. Ft)
3.04
4.04
5.04
6.04
Nominal Avg. Exhaust Vol.
(CFM)
259
344
428
514
Avg. Exhaust Vol. Range
(CFM)
243-274
323-364
403-454
483-544
Inflow Test Specifications – 8 inch Sash Opening
Inflow Test Specifications – 9 inch Sash Opening
Inflow Test Specifications – 10 inch Sash Opening
Inflow Test Specifications – 12 inch Sash Opening
Acceptance
Average inflow shall be meet the specified value.
Product Service 1-800-522-7658
88
Inflow Velocity Calculation - Secondary Method
If the primary method cannot be performed, the secondary inflow calculation method should be used. The secondary method uses a hot wire thermal anemometer. In this method, the sash is lowered, and a series of velocity readings are taken at the front of the unit.
NOTE: You must use Labconco holder P/N 3836405 to perform this test properly. Qualified certifiers can obtain this holder as part of the Logic+ Certifier Kit, Labconco P/N 3858403, by contacting Labconco Customer Service Department at 800-821-5525.
For each model Purifier, insert the proper template as indicated in Table 5-6, and shown below in Figure 5-18.
The thermal anemometer probe should be positioned such that the distance from the
bottom of the probe holder to the center of the sensor element equals “Sensor Distance”
as shown in Table 5-6. Use the marks on the 6-foot templates, or a scale as shown in Figure 5-19 & 5-20 below.
Figure 5-18
Measuring the restricted access opening height, using the appropriate template. Ensure that the bottom of the template is seated in the sash stop.
Product Service 1-800-522-7658
89
The Sensor Distance, as described in Table 5-6, using the slots cut in the 6-foot Logic template.
4.00-inch mark
3.25-inch mark
The Sensor Distance, as described in Table 5-6, using a scale.
Figure 5-19
Figure 5-20
Product Service 1-800-522-7658
90
Table 5-6
Cabinet Width (feet)
3 4 5
6
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)5
4
3.25
3.25
4
# of Test points
6 8 10
12
Test point location
*
* * *
Nominal Avg. Inflow Vel. (FPM)
213
283
353
231
Avg. Inflow Vel. Range (FPM)
203-223
269-296
336-370
220-242
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
203-223
269-296
336-370
403-443
Sash Open Area (Sq. Ft)
2.03
2.69
3.36
4.03
Inflow Velocity Range (AIV / Sash open area)
100-110
100-110
100-110
100-110
Cabinet Width (feet)
3 4 5
6
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)2
4
3.25
3.25
4
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
240
318
397
260
Avg. Inflow Vel. Range (FPM)
228-251
303-333
378-416
248-272
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
228-251
303-333
378-416
453-498
Sash Open Area (Sq. Ft)
2.28
3.03
3.78
4.53
Inflow Velocity Range
(AIV / Sash open area)
105+/-5
105+/-5
105+/-5
105+/-5
Cabinet Width (feet)
3 4 5
6
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)5
4
3.25
3.25
4
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
266
354
441
289
Avg. Inflow Vel. Range (FPM)
253-278
337-371
420-462
275-302
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
253-278
337-371
420-462
503-553
Sash Open Area (Sq. Ft)
2.53
3.37
4.2
5.03
Inflow Velocity Range (AIV / Sash open area)
100-110
100-110
100-110
100-110
Cabinet Width (feet)
3 4 5
6
Sash Opening Template
1
3+
4+
5+
6+
Sensor distance (inches)5
4
3.25
3.25
4
# of Test points
6 8 10
12
Test point location
* * *
*
Nominal Avg. Inflow Vel. (FPM)
259
344
428
281
Avg. Inflow Vel. Range (FPM)
243-274
323-364
403-454
264-297
Correction Factor (CF)
1 1 1
1.83
Average Inflow Volume Range (AIV) (Avg. velocity x CF)
243-274
323-364
403-454
483-544
Sash Open Area (Sq. Ft)
3.04
4.04
5.04
6.04
Inflow Velocity Range (AIV / Sash open area)
85+/-5
85+/-5
85+/-5
85+/-5
Secondary Inflow Test Specifications – 8 Inch Sash Opening
Secondary Inflow Test Specifications – 9 Inch Sash Opening
Secondary Inflow Test Specifications – 10 Inch Sash Opening
Secondary Inflow Test Specifications – 12 Inch Sash Opening
Product Service 1-800-522-7658
91
1. Locate the single row of holes at the front of the grille. Mark the 6
the side wall and subsequent test points every 9 holes until the number of test points marked equals the width of the cabinet in feet (for a 3-foot cabinet, for example, mark the first 3 points). Repeat for the opposite side, as shown in Figure 5-21.
2. Start the Purifier, and let it operate for at least 5 minutes. Establish the
necessary correction factor to the thermal anemometer to ensure compliance with its performance in a calibrated wind tunnel. This data should be available from the calibrator of the thermal anemometer.
3. Calculate the manufacturers recommended correction factor(s) to correct for
local conditions of temperature, humidity, barometric pressure, altitude, etc.
4. Take a series of inflow velocities by placing the probe holder so that its center
mark aligns with the marked test holes. As shown in Figure 5-22.
5. Apply the wind tunnel correction and local condition correction factors to the
thermal anemometer readings.
6. Multiply the individual readings by the correction factor shown in Table 5-6.
7. Average the corrected readings.
8. The resulting value is the inflow volume in cubic feet per minute (CFM). In order
to convert this value to the average inflow velocity of feet per minute (FPM), divide the volume by the sash open area given in Table 5-6. The resulting value will be the calculated average inflow velocity in FPM.
th
hole from
Figure 5-21
Marking the test point locations.
Mark the 6th hole from either end, then mark every 9th hole until the number of marked points equal the width of the cabinet in feet.
Repeat for the other side of the grille.
Measuring the Secondary Inflow Velocity. Note the center of the probe holder aligns with the test points marked earlier.
Acceptance
Average inflow shall meet the specification in Table 5-6.
Figure 5-22
Product Service 1-800-522-7658
92
Type B2 Total Exhaust Volume
Model
30348
30368
DIM-measured Exhaust
(CFM)
665+/-15
998+/-20
Traverse-measured
Exhaust (CFM)
810
1218
Model
30348
30368
Nominal Inflow (CFM)
283 +/-13
423+/-20
Inflow alarm setpoint volume (CFM)
150 +/- 5
223 +/- 5
The total volume of air exhausting from the cabinet can be determined as follows:
Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow value.
Note: The exhaust volume noted with a DIM on the front of the cabinet may not agree with the value obtained from a traditional Pitot tube or thermal anemometer traverse reading of the exhaust duct.
1. Shut off the cabinet blower.
2. Remove the prefilter element from the top of the cabinet.
3. Completely seal the air intake opening with tape or plastic film secured with tape.
4. Seal a DIM to the face of the Logic+.
5. Record at least 10 inflow volumes, and average the results. The total exhaust volume should approximately equal the value shown in Table 5-7.
Table 5-7
Total Exhaust Volume Specifications
Type B2 Exhaust (Inflow) Alarm Setpoint
The exhaust alarm setpoint must be entered during the calibration procedure. To do this:
1. With the cabinet operating at its nominal inflow in the calibration mode at the alarm setpoint screen, ensure that a properly operating DIM or thermal anemometer (for secondary inflow) is properly positioned at the face of the
Logic+.
2. Close the exhaust damper until the inflow equals 80% of the total exhaust volume, as shown in Table 5-8.
3. Press the ‘OK’ button when the proper inflow is obtained.
4. Return the damper to the position required for nominal inflow and lock the damper in position.
Table 5-8
Inflow Alarm Volume Specifications
Product Service 1-800-522-7658
93
Work Area Air Cleanliness Test (optional)
If the customer wants to verify air cleanliness in the work area, use the following procedure:
1. Mark test points at the geometric center of the work surface, and midway between the center test point and each side wall.
2. Place a particle counter pickup a test point, at a height of 16 inches above the work surface, pointing into the airflow, as shown in Figure 5-23. Take three samples of 1.0 ft3. Repeat for each test point.
3. Average the results.
Figure 5-23
Acceptance
The average count should be less than 100 particles 0.5um in size per ft3.
Product Service 1-800-522-7658
94
Fluorescent Light Level (optional)
The fluorescent light intensity should be measured as described in ANSI/NSF Standard 49:2012, Annex F.
NOTE: The light meter should be color- and cosign corrected for accurate readings.
1. Test points should be marked along the centerline of the work surface, starting 6 inches from the side wall, with subsequent points 12 inches apart until the center of the work surface is reached. Repeat for the other side of the work area.
2. Take background readings at the test. It should be 15 foot-candles maximum.
3. Turn on the fluorescent lights and let them warm up for at least 5 minutes.
4. Measure the light intensities at the test points.
Acceptance
The average light level should be no less than 45 foot-candles greater than the background level, where maximum background light levels average a maximum of 15 foot-candles.
Most common causes for insufficient light levels are:
a. Malfunctioning lamp(s) b. Old lamp(s) c. Dusty/dirty lamp surfaces
Noise Level (optional)
The noise level should be measured as described in ANSI/NSF Standard 49:2012.
1. Noise level should be recorded from a single point, on the centerline of the cabinet, at a position 14 inches above the work surface, and 12 inches from the front of the cabinet.
2. Take a background reading with the cabinet blower off at the test point. It should be less than 55 dbA.
3. Start the cabinet blower, and take a sound reading.
Acceptance
Sound levels should be less than 67 dbA when the cabinet is new, and less than 73 dbA when the filters are loaded.
Product Service 1-800-522-7658
95
Vibration (optional)
The vibration level should be measured as described in ANSI/NSF Standard 49:2012.
Note: The vibration meter should have a range of 20-20,000 Hz, and have an output in displacement.
1. Vibration level should be recorded from a single point, on the geometric center of the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Start the cabinet blower, and take a vibration reading.
Acceptance
Vibration should be less than 0.0002 inches displacement when the cabinet is new.
UV intensity (optional)
Note: The UV radiometer should measure light at a wavelength of 254nm.
1. UV intensity should be recorded from a single point, on the geometric center of the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Close the sash, turn on the UV light, and let it warm up for at least 5 minutes.
Acceptance
The UV intensity should be at least 200 uW-cm2.
Most common causes for insufficient UV light levels are:
d. Malfunctioning lamp(s) e. Old lamp(s) f. Dusty/dirty lamp surfaces
Product Service 1-800-522-7658
96
Ground Fault Circuit Interrupter Test
(115/100 Volt models only)
Note: The GFCI tester must be able to simulate a fault of 3mA.
1. Place the tester into any of the Logic+’s outlets. The indicator lights of the tester should indicate normal function, and the GFCI’s indicator LED should be lit.
2. Press the test button of the tester. The indicator lights should now indicate the circuit is inactive, and the GFCI indicator LED should be off.
3. Reset the GFCI by pressing the RESET button on the right outlet. The tester should again indicate normal operation, and the GFCI indicator LED will illuminate.
Figure 5-24
GFCI Reset Button
GFCI Test Button
GFCI Indicator LED
Acceptance
The GFCI trips during the simulated failure, and the indicator LED turns off. Pressing the Reset button returns the GFCI to normal function.
Product Service 1-800-522-7658
97
Section 6
Logic+ Service Operations
This section will review the tools needed, and common service operations for the Logic+.
Recommended Tools for Service
The tools needed for most common service operations are:
Logic+ Certifier Kit, Labconco Part # 3858403 #2 Phillips Screwdriver or long bit for cordless drill ½-inch Socket with extension and ratchet ½-inch nut driver 7/16-inch socket or nut driver 5/16-inch socket or nut driver
Optional tools that may be needed include:
Cordless screwdriver/drill Cordless ratchet 3/8-inch nut driver or socket and ratchet Pliers 10-24 Tap 5/16 x 18 Tap
Note: If you use a cordless drill with an adjustable torque setting, set the torque as low as possible to properly drive the screw or bolt.
External Dress Components
Front Dress Panel Removal and Installation
Figure 6-1
1. Locate and remove the two Phillips screws that secure the front panel as shown in Figure 6-1. They are located on the bottom corners of the front dress panel
2. Swing the bottom of the dress panel out to clear the
fluorescent light and then lift the front dress panel
straight up and away from the cabinet.
Product Service 1-800-522-7658
98
To reinstall the panel, reverse these steps, ensuring that the plastic pin in the top corners of the dress panel properly engage the corner posts.
Figure 6-2
Side Panel Removal
Note: The side panel(s) must be taken off to remove the Logic+ from its pallet.
1. Remove and save the two Phillips screws on the front edge of the side panel.
2. Pivot the front of the panel away from the cabinet. Lift the panel straight up and
pull the panel straight away from the cabinet to release the rear of the side panel from its hinge.
Side Panel Installation
1. Install the side panel by inserting both back panel hooks into the side panel
slots.
2. Ensure both panel slots are completely seated on the hooks.
3. Pivot the front of the panel toward the cabinet. Secure the panel by installing
and tightening the two Phillips screws.
Product Service 1-800-522-7658
99
Corner Post Lower Trim
The corner post lower trim pieces are secured to the corner post by a single machine screw and lock nut. When properly positioned, the trim piece fits tightly against corner post. See Figure 6-3.
Figure 6-3
Use a 3/8” wrench and Phillips screwdriver to adjust the corner post screw.
Note: DO NOT over tighten the screw; damage to the trim piece may occur.
If the corner post lower trim pieces do not fit flush to the bottom edge of the metal corner post, examine the front flange of the chassis. The flange should be straight. If it is bent back, it can be straightened by bending the flange forward with an adjustable
wrench, as shown in Figure 6-4.
Figure 6-4
Front side of the Logic+
Logic+ Chassis Flange
Using an adjustable wrench to straighten the flange
Product Service 1-800-522-7658
100
Sash
Operation
The Logic+ sash uses a deadweight-counterbalanced system. The system consists of two separate weights on either side of the liner. Both weights are synchronized by a locked axle-pulley system. Both pulleys are fixed to the axle so that both weights must move together, preventing the sash from racking.
Adjustment
There are no adjustments for the width of the sash track. There should be approximately 1/8-inch lateral play of the sash in its track. If there is no lateral play, examine one or both of the corner posts to ensure that they are not bent inward. If the sash becomes racked, or is closing unevenly, it can be aligned as follows:
1. Close the sash completely, until the lower edge of the sash is contacting the sash stop. If the other end of the sash is not resting on its sash stop, CAREFULLY lift the counterweight on the “high” side of the sash. This will allow the high side of the sash to lower to the sash stop, leveling the sash. See Figure 6-5.
Figure 6-5
Using pliers to lift a sash weight to level the sash.
CAUTION: Exercise caution when lifting a counterweight. There is a pinch potential between the sash cable and pulley.
Product Service 1-800-522-7658
Loading...