Labconco Protector Demonstration Hoods User Manual

User’s Manual
Protector®Demonstration Hoods
Models 3944300, 3944301 3945000, 3945001 3945020, 3945021
complete your product registration card
online at register.labconco.com
Labconco Corporation 8811 Prospect Avenue Kansas City, MO 64132-2696 800-821-5525, 816-333-8811 FAX 816-363-0130 E-MAIL labconco@labconco.com HOME PAGE www.labconco.com
Please read the User’s Manual before operating the equipment.
Copyright © 2004, 2007, 2010 Labconco Corporation. All rights reserved.
g
The information contained in this manual and the accompanying products are copyrighted and all rights reserved by Labconco Corporation. Labconco Corporation reserves the right to make periodic design changes without obligation to notify any person or entity of such change.
Warranty
Labconco provides a warranty on all parts and factory workmanship. The warranty includes areas of defective material and workmanship, provided such defect results from normal and proper use of the equipment.
The warranty for all Labconco products will expire one year from date of installation or two years from date of shipment from Labconco, whichever is sooner, except the following;
Purifier® Logic® Biological Safety Cabinets and PuriCare® Lab Animal Research Stations
carry a three-year warranty from date of installation or four years from date of shipment from Labconco, whichever is sooner.
SteamScrubber® & FlaskScrubber® Glassware Washers carry a two-year warranty from date
of installation or three years from date of shipment from Labconco, whichever is sooner.
Blood Drawing Chairs carry a ten year warranty.
Carts carry a lifetime warranty.
Glassware is not warranted from breakage when dropped or mishandled.
This limited warranty covers parts and labor, but not transportation and insurance charges. In the event of a warranty claim, contact Labconco Corporation or the dealer who sold you the product. If the cause is determined to be a manufacturing fault, the dealer or Labconco Corporation will repair or replace all defective parts to restore the unit to operation. Under no circumstances shall Labconco Corporation be liable for indirect, consequential, or special damages of any kind. This statement may be altered by a specific published amendment. No individual has authorization to alter the provisions of this warranty policy or its amendments. Lamps and filters are not covered by this warranty. Damage due to corrosion or accidental breaka
e is not covered.
Returned or Damaged Goods
Do not return goods without the prior authorization from Labconco. Unauthorized returns will not be accepted. If your shipment was damaged in transit, you must file a claim directly with the freight carrier. Labconco Corporation and its dealers are not responsible for shipping damages.
The United States Interstate Commerce Commission rules require that claims be filed with the delivery carrier within fifteen (15) days of delivery.
Limitation of Liability
The disposal and/or emission of substances used in connection with this equipment may be governed by various federal, state, or local regulations. All users of this equipment are required to become familiar with any regulations that apply in the user’s area concerning the dumping of waste materials in or upon water, land, or air and to comply with such regulations. Labconco Corporation is held harmless with respect to user’s compliance with such regulations.
Contacting Labconco Corporation
If you have questions that are not addressed in this manual, or if you need technical assistance, contact Labconco’s Customer Service Department or Labconco’s Product Service Department at 1-800-821-5525 or 1-816-333-8811, between the hours of 7:00 a.m. and 6:00 p.m., Central Standard Time.
Part #3943400, Rev. B
ECO F773
T
AABBLLEE
T
CHAPTER 1: INTRODUCTION 1
CHAPTER 2: PREREQUISITES 3
Support Requirements 4 Location and Air Current Requirements 4 Exhaust and Blower Requirements 4 Electrical Requirements 5 Space Requirements 5
CHAPTER 3: GETTING STARTED 6 Unpacking the Hood 7
Installing the Hood on a Supporting Structure & Work Surface 7 Connecting to the Exhaust System 9 Connecting the Electrical Supply 14 Sealing to the Work Surface 14 Validating the Hood 14
CHAPTER 4: HIGH PERFORMANCE FEATURES AND
High Performance Features 15 Safety Precautions 20
CHAPTER 5: USING YOUR PROTECTOR
CHAPTER 6: MAINTAINING YOUR PROTECTOR
Routine Maintenance Schedule 23
Guardian 500 Airflow Monitor Kit No. 3944700 or 3944701 24 Guardian 500 Component Identification 24 Guardian 500 Installation Procedure 25 Guardian 500 Calibration Procedure 27 Guardian 500 Alarm Activation 27
O
O
SAFETY PRECAUTIONS 15
DEMONSTRATION HOOD 21
DEMONSTRATION HOOD 23
FF
C
C
OONNTTEENNTTSS
Guardian Digital 1000 Kit No. 3908800 or 3908801 29
Guardian Digital 1000 Operation 29 Guardian Digital 1000 Installation Procedure 32 Guardian Digital 1000 Calibration 35 Digital 1000 Alternate Calibration Procedure – Constant Volume Conditions 33
CHAPTER 7: ACCESSORIZING YOUR PROTECTOR DEMONSTRATION HOOD 36
Work Surfaces 38 Guardian Digital 1000 and Guardian 500 Airflow Monitors 38 Fluorescent Light 38 Exhaust Transition Adapters 38 Remote Blowers 39 Exhaust Dampers 39 FilterMate Portable Exhausters and Filters 40 Storage Cabinets 41 Mobile Cart 8026000 42 Hose, Hose Clamps and Hose Kits 42
CHAPTER 8: TROUBLESHOOTING 43
APPENDIX A: REPLACEMENT PARTS 45
APPENDIX B: DIMENSIONS 49
APPENDIX C: SPECIFICATIONS 50
APPENDIX D: REFERENCES 53
DECLARATION OF CONFORMITY 56
CChhaapptteerr 11:: IInnttrroodduuccttiioonn
Congratulations on your purchase of a Protector® Demonstration Hood. Your high performance enclosure is designed to protect you by providing superior containment while conserving energy at OSHA approved “low flow” velocities as low as 60 feet per minute. It is the result of Labconco’s more than 50 years experience in manufacturing fume hoods.
The Protector Demonstration Hood has been engineered to provide maximum containment. It will effectively contain toxic, noxious, or other harmful materials when properly installed. The Protector Demonstration Hood offers many unique features to enhance safety, performance, and energy savings. To take full advantage of them, please acquaint yourself with this manual and keep it handy for future reference. If you are unfamiliar with how the Protector Demonstration Hood operates, please review Chapter 4: High Performance Features and Safety Precautions before you begin working in the hood. Even if you are an experienced user, please review Chapter 5: Using Your Demonstration Hood, which describes the features so that you can use the hood efficiently.
Product Service 1-800-522-7658
1
Chapter 1: Introduction
Protector Demonstration Hood System 3945001
2
Product Service 1-800-522-7658
CChhaapptteerr 22:: PPrreerreeqquuiissiitteess
Before you install the Protector Demonstration Hood, you need to prepare your site for installation. Carefully examine the location where you intend to install the hood. You must be certain that the area is level and of solid construction. In addition, a dedicated source of electrical power should be located near the installation site to power the accessory FilterMate Portable Exhauster or other apparatus.
Carefully read this chapter to learn the requirements for your installation site:
The support requirements.
The location and air current requirements.
The exhaust and blower requirements.
The electrical power requirements.
The space requirements.
Refer to Appendix B: Dimensions for complete Protector Demonstration Hood dimensions.
Refer to Appendix C: Specifications for complete electrical and environmental conditions, specifications and requirements.
Product Service 1-800-522-7658
3
Chapter 2: Prerequisites
Support Requirements
At a minimum, the supporting structure usually consists of a base cabinet, or a base stand and chemically-resistant work surface. When setting up a chemical station, a mobile stand or cart is allowable. Labconco manufactures a mobile cart with work surface specifically designed to support the Protector Demonstration Hood and FilterMate Portable Exhauster. The cart is supplied with the Mobile Protector Demonstration Hood or can be ordered separately as an accessory. See Chapter 7 for accessories.
Location and Air Current Requirements
The Protector Demonstration Hood has been designed to contain hazards by negating typical cross drafts and movements within the opening. As a precautionary measure it is recommended that the enclosure be placed in such an area away from:
High traffic areas where walking might cause an air disturbance.
Overhead or wall HVAC diffusers, fans, radiators or other lab equipment
producing air currents.
Next to doorways or windows that may be opened.
Exhaust and Blower Requirements
The exhaust connection has been designed to accept a 2" x 10" (5.1cm x
25.4cm) nominal exhaust collar. The Protector Demonstration Hood has two possible exhaust connections with either the top exhaust open and the bottom exhaust closed or vice versa. The bottom exhaust connection is primarily used in installations where the hose or ductwork will be concealed. The bottom exhaust is used on the Mobile Protector Demonstration Hood to conceal the exhaust and facilitate connection to the FilterMate Portable Exhauster. Labconco offers accessory Transition Adapters for the top or bottom exhaust connection to either a 5" hose or 6" duct. (See Chapter 7 for ordering any of these accessories). Only one exhaust connection is required. The mobile Protector Demonstration Hood includes the lower 5" hose exhaust transition, FilterMate Portable Exhauster, 5" hose, mobile cart and work surface. Data for the exhaust volume and enclosure static pressure loss are listed for each model at face velocities of 60, 80 and 100 fpm.
Demo
Hood
Width
3' 22.75" Demonstration
3' 32" Demonstration
Demo
Hood
Height Model Description
Hood w/ 8" sash
opening
Hood w/ 10" sash
opening
Face
Velocity
(fpm)
60 80
100
60 80
100
Exhaust
Volume
(CFM)
110 145 185 140 185 230
Static
Pressure Loss
(in w.g..)
.04" .06" .10" .06" .10" .15"
4
Product Service 1-800-522-7658
Chapter 2: Prerequisites
Proper blower selection can be determined from these exhaust requirements and the total system static pressure loss. The enclosure must be connected to either a dedicated blower, a house exhaust system or a dedicated filtered exhauster, such as a Labconco FilterMate Portable Exhauster.
Labconco offers three accessory remote blowers listed in Chapter 7.
Electrical Requirements
Standard duplex electrical receptacles should be nearby for connecting the Demonstration Hood, FilterMate Portable Exhauster, an airflow monitor, accessory Fluorescent Light or other equipment. For your convenience both the accessory FilterMate and accessory fluorescent light kit have auxiliary outlet receptacles. It is required that the airflow monitor be connected directly to the auxiliary switched outlet on the rear of the FilterMate so the airflow monitor is ON when the blower is ON. The FilterMate auxiliary switched outlet is rated for 8 amps.
For other blower exhaust systems, it is recommended that the airflow monitor be switched by the same circuit as the exhaust blower. If this is not possible, then the airflow monitor may be connected to the switched auxiliary outlet on the accessory fluorescent light kit. The fluorescent light kit auxiliary outlet can be used for any accessory under 8 amps.
Space Requirements
The dimensions for the different models are shown in Appendix B: Dimensions.
Product Service 1-800-522-7658
5
CChhaapptteerr 33::
Geettttiinngg SSttaarrtteedd
G
Now that the site for your Protector Demonstration Hood is properly prepared, you are ready to unpack, inspect, install, and validate your hood system. Read this chapter to learn how to:
Unpack and move the hood.
Set up the hood with the proper supporting structure and work
surface.
Connect to an exhaust system.
Connect the electrical supply.
Seal the hood to the work surface.
Arrange validation for the enclosure.
Depending upon which model you are installing, you may need common plumbing and electrical installation tools in addition to wrenches, ratchets, sockets, a nut driver set, a flat-blade screwdriver, a Phillips screwdriver, and a carpenter level to complete the instructions in the chapter.
The hoods weigh either 100 or 120 lbs. each (45 to 54 kg). The shipping container allows for lifting with a mechanical lift truck or floor jack. If
you must lift the hood manually, follow safe-lifting guidelines.
Do not
lift by the front air foil.
6
Product Service 1-800-522-7658
The United States Interstate Commerce Commission rules require that claims be filed with the delivery carrier within fifteen (15) days of delivery.
Chapter 3: Getting Started
Unpacking the Hood
Carefully remove the shrink-wrap or carton on the hood and inspect it for damage that may have occurred in transit. If damaged, notify the delivery carrier immediately and retain the entire shipment intact for inspection by the carrier.
DO NOT RETURN GOODS WITHOUT THE PRIOR AUTHORIZATION OF LABCONCO. UNAUTHORIZED RETURNS WILL NOT BE ACCEPTED.
IF ENCLOSURE WAS DAMAGED IN TRANSIT, YOU MUST FILE A CLAIM DIRECTLY WITH THE FREIGHT CARRIER. LABCONCO CORPORATION AND ITS DEALERS ARE NOT RESPONSIBLE FOR SHIPPING DAMAGES.
Do not discard the packing material until you have checked all of the components and tested the unit.
We recommend that you do not remove the hood from its shipping container until it is ready to be placed into its final location. Move the unit by placing a flat, low dolly under the shipping skid, or by using a floor jack.
Do not move the hood by tilting it onto a hand truck.
Installing the Hood on a Supporting Structure and Work Surface
When installing the hood onto a chemically resistant work surface or benchtop, ensure that the structure can safely support the combined weight of the hood and any related equipment. The work surface should be at least as wide as the hood to properly support it. The front of the hood should be aligned within 1/8" of the front of the work surface. Mounting holes are provided in Labconco accessory work surfaces to secure the hood. The mobile Demonstration Hood features a work surface attached to the cart.
Product Service 1-800-522-7658
7
Chapter 3: Getting Started
Work Surface Specifications
The work surface should be smooth, rigid, and durable, such as a chemically resistant epoxy resin. The surface should be non-porous and resistant to the acids, solvents and chemicals used in conjunction with the Protector Demonstration Hood. The work surface should also contain a dished recessed area for containing primary spills.
Work Surface and Hood Installation
1. Level the base cabinets and the work surface. Work surface should be
placed flush with the front of the base cabinet as shown in Figure 3-1.
2. Position the work surface in its intended location and with the front of
the work surface (wide flange) towards you.
3. Secure the work surface to the base cabinet with a structural adhesive
or silicone sealant.
4. Insert the supplied mounting screws in the four holes. Allow a
minimum of 1/8" clearance under the head of the screw for
positioning the enclosure.
5. Place the hood on the work surface and slide the rear flange and front
air foil flanges under the mounting screw heads.
6. Tighten the four screws to complete the installation.
Figure 3-1
Side View of Typical Installation
Airflow monitor moved forward per Chapter 6.
8
Product Service 1-800-522-7658
Chapter 3: Getting Started
Connecting to the Exhaust System
WARNING: The weight of the exhaust ductwork system must be supported independently of the superstructure or damage may occur.
The exhaust system should be installed by a qualified HVAC contractor.
The exhaust connection on the Demonstration Hood has been designed to accept a 2" x 10" (5.1cm x 25.4cm) nominal transition adapter. See Chapter 7 for ordering accessory transition adapters. Labconco manufactures transition adapters for either top or bottom exhaust and for both 5" dia. hose or 6" dia. duct. Review Chapter 2 for remote blower and FilterMate Portable Exhauster exhaust prerequisites and review Chapter 7 for ordering blower exhaust equipment. For your convenience several exhaust options are shown in Figures 3-2, 3-3, 3-4, 3-5 and 3-6. Consult Labconco Customer Service should you require help sizing your blower for the exhaust volume and system static pressure loss.
Top Connection to Outside Exhaust
Figure 3-2
Airflow monitor moved forward per Chapter 6.
Product Service 1-800-522-7658
9
Chapter 3: Getting Started
Airflow monitor moved forward per Chapter 6.
10
Side View of Bottom Connection
Figure 3-3
to Outside
Product Service 1-800-522-7658
Chapter 3: Getting Started
(Moved forward per Chapter 6)
Top Connection to FilterMate Portable
Product Service 1-800-522-7658
Figure 3-4
Exhauster
11
Chapter 3: Getting Started
Airflow monitor moved forward per Chapter 6.
12
Figure 3-5
Bottom Connection to FilterMate
With Outside Thimble Exhaust Connection
Product Service 1-800-522-7658
Chapter 3: Getting Started
(Moved forward per Chapter 6)
Airflow monitor moved forward per Chapter 6.
Connection to FilterMate on Mobile Cart
Figure 3-6
Product Service 1-800-522-7658
13
Chapter 3: Getting Started
Connecting the Electrical Supply
A standard duplex receptacle should be nearby for connecting the FilterMate Portable Exhauster, airflow monitor and accessories. Please review Chapter 2 for electrical prerequisites.
All wiring for the building duplex outlets SHOULD be performed by a licensed electrician and conform to all local codes.
Sealing to the Work Surface
When the hood has been set in place, ducted and wired, it may be sealed at the work surface to prevent spilled materials from collecting under the walls. A bead of silicone sealant is recommended to seal the hood to the work surface.
Validating the Hood
The exhaust damper, exhaust blower or FilterMate gives you the flexibility to change the airflow at the sash opening of your enclosure. Determine the actual face velocity at the sash opening by taking airflow velocity readings. These should be taken across the sash opening of the enclosure in accordance with the Industrial Ventilation Manual. (See Appendix D) The “average face velocity” is achieved by taking readings in two rows across the enclosure with the readings 6" from the ends and evenly spaced every 12"; the first row is 3" down from the upper sash foil and the second row is 3" up from the work surface. Labconco recommends an average face velocity at the sash opening of 60 to 100 feet per minute for Protector Demonstration Hoods. Refer to Chapter 2 for proper airflow volumes for your particular model.
Your Protector Demonstration Hood has been tested at the factory per ASHRAE 110-1995. All enclosures achieve an “as manufactured rating” of less than 0.05 part per million (ppm) at 4 liters per minute (lpm); AM <0.05 (Consult Labconco for individual ratings). For “field use” ASHRAE testing contact Labconco for a certified on-site contractor.
NOTE: Face velocity profiles and smoke testing should be performed frequently per your organization’s quality system to ensure safe performance.
14
Product Service 1-800-522-7658
CChhaapptteerr 44:: HHiigghh PPeerrffoorrm aanndd SSaaffeettyy PPrre
High Performance Features:
The patented (U.S. Patent No. 6,461,233) Protector Demonstration Hood is designed to meet the needs of a variety of laboratory applications, and provide superior containment while conserving energy at OSHA approved “low flow” velocities as low as 60 feet per minute. The Protector Demonstration Hood has been designed to effectively contain toxic, noxious, or other harmful materials when properly installed and operated. What makes the Protector Demonstration Hood so unique is the revolutionary way it directs air into and through the contaminated air chamber. Labconco engineered the hood to minimize the effects of turbulence. The containment enhancing and aerodynamic designs of the upper sash foil, side air foils, lower air foil, upper dilution air supply, and rear baffle all work in concert to produce airflow patterns that significantly reduce both powder and chemical concentrations through the work area. The Protector Demonstration Hood incorporates unique 360° visibility, which is useful in laboratory demonstrations and visibility across classrooms.
maannccee FFeeaattuurreess
eccaauuttiioonnss
Product Service 1-800-522-7658
15
Chapter 4: High Performance Features and Safety Precautions
14
Airflow monitor moved forward per Chapter 6.
3
12
6
13
9
2
5
1
Figure 4-1
8
4
10
7
16
16
Product Service 1-800-522-7658
Chapter 4: High Performance Features and Safety Precautions
1. Aerodynamic Clean-Sweep™ Air Foil has a unique low profile
shape that allows air to sweep the work surface for maximum containment. The Clean-Sweep™ openings create a constant protective barrier from contaminants. In addition, should the operator inadvertently block the airflow entering the air foil, air continues to pass under the air foil and through the Clean-Sweep openings. See Figure 4-2.
Figure 4-2
2. Containment-Enhancing Upper Sash Foil includes a perforated air
passage directly atop the sash foil to bleed air into the hood chamber and direct chemical and powder concentrations away from the sash opening. The radiused sash foil sweeps airflow into the hood with minimal turbulence. See Figure 4-3.
Figure 4-3
Product Service 1-800-522-7658
17
Chapter 4: High Performance Features and Safety Precautions
3. Upper Dilution Air Supply provides bypass air from above the work
area. This feature constantly bathes the sash interior with clean air and
reduces powders and chemical fumes along the sash plane, near the
critical breathing zone. Five to seven percent of the required air
volume is introduced through the upper dilution air supply to ensure
maximum containment. Additionally, the upper dilution air supply
reduces stagnant pockets of air in the upper interior. See Figure 4-4.
Figure 4-4
4. Visible Clear Rear Baffle directs air streams to the baffle in a single
pass. The baffle and rear panel are manufactured from framed glass
panels to provide maximum visibility on all sides. This smooth flow
minimizes the potential for air to roll forward preventing
contamination from moving toward the sash opening. The
concentrations of materials are largely removed on the first pass
through the contaminated chamber.
5. Side Entry Air Foils allow turbulence-free air to enter the hood from
the sides and allow clean air to sweep the interior walls.
6. Ergonomic Slope provides maximum visibility, and comfort reduces
glare, thereby minimizing operator fatigue.
7. Internal Depth of 23" provides necessary space to support
equipment without extending outside the hood or resting on the lower
air foil.
8. Two Heights available as standard enclosures in 22.75" or 32".
Taller height Demonstration Hoods are typically used for pipet
operations, titration or taller auxiliary equipment.
9. Unique Flush Sash with Spring-Loaded Latch has a wiping seal to
contain contaminants and features a spring-loaded latch for loading
auxiliary equipment. The sash pivots down for normal operation.
18
Product Service 1-800-522-7658
Chapter 4: High Performance Features and Safety Precautions
10. Electrical Pass through Iris allows electrical cords and data cords to
pass through the back of hood without leaving a large hole for contaminants to escape. The hood ships with solid plugs and the iris plugs are included with the instruction manual for your convenience.
11. Shipped fully assembled to eliminate the need for costly onsite
assembly. Accessories such as the exhaust transition connections, work surfaces, airflow monitors and fluorescent light kits are easily installed.
12. Accessory Exhaust Connections. The Protector Demonstration
Hoods feature two exhaust locations: One is located on the top of the rear plenum and the other is located on the bottom of the rear plenum. The bottom exhaust incorporates a tissue screen to prevent debris from clogging the exhaust blower. Exhaust transition connectors are available for either a 6" OD outside exhaust or a 5" ID hose. All exhaust transition connectors are illustrated in Chapters 2 and 3 and accessories listed in Chapter 7. The lower 5" ID hose exhaust connection is used with the mobile cart for connection to the FilterMate Portable Exhauster which rests on the lower shelf.
13. Accessory Guardian™ Digital 1000 Airflow Monitor or Guardian
500 Monitor continuously monitors airflow. An audio/visual alarm alerts the user to low airflow conditions. The Guardian™ 1000 Digital Airflow Monitor also displays a face velocity value, provides an RS232 output, a night setback mode and several auxiliary relay ports. See Chapter 7 for ordering information. See Chapter 6 for details, installation and calibration.
14. Accessory Fluorescent Light Kits provide excellent illumination
with an auxiliary outlet plug for supplying power to auxiliary equipment such as a balance or printer. See Chapter 7 for ordering information.
15. Accessory Roof-Mounted Blower sized to provide adequate airflow
to Protector Demonstration Hoods when used with an exhaust damper. See Chapters 2, 3 and 7.
16. Accessory FilterMate Portable Exhauster provides up to 280 cfm
for HEPA or Carbon filtration or up to 220 cfm for combination HEPA/Carbon filtration when connected to the hood. See Chapters 2, 3 and 7.
17. Mobile Demonstration Hood includes FilterMate Portable
Exhauster, Demonstration Hood, work surface and mobile cart to allow easy transport throughout the facility. See Figure 3-6. Mobile cart can be ordered separately as shown in Chapter 7.
Product Service 1-800-522-7658
19
Chapter 4: High Performance Features and Safety Precautions
Safety Precautions
Although the hood has been engineered to maintain optimum operator safety, caution should always be used while working. Prior to using the hood, check to make sure that the exhaust blower is operating and that air is entering the hood at its specified face velocity. The use of an airflow monitor is recommended to alert the user if there is a problem with airflow.
Use good housekeeping in the hood at all times. Clean up spills immediately. Periodically clean enclosure interior.
Do not overload the work surface with apparatus or work material. The safe operation of the hood is based upon having proper airflow through the structure. Do not place large, bulky objects such as block heaters, directly on the work surface. Instead, elevate the object 3/4" on blocks to allow a flow of air under the object and into the rear baffle exhaust slots. Ensure blocks are level and secured in place.
Blocking large portions of the rear baffle will change the airflow pattern in the hood causing turbulence. (Do not store containers or supplies against the rear baffle, as this will affect airflow).
Always work with your hands as far back in the hood as possible. It is best to keep all powders, chemicals and apparatus inside the lower air foil of the hood.
Do not work with chemicals in this hood without the exhaust system running. Perchloric acid use in this hood is prohibited.
High-level radioisotope materials are prohibited in this hood.
Avoid cross drafts and limit traffic in front of the hood. Air disturbances created may draw contaminants out of the hood.
The hood should be tested by a qualified certification technician before it is initially used. The hood should be validated whenever it is relocated, serviced or at least annually thereafter.
The use of safety goggles, protective clothing, gloves and any other personal protective equipment recommended by your safety officer should be used.
The sash should remain in the down position while using the hood.
Proper operation of the hood depends largely upon its location and the operator’s work habits. Consult the references in Appendix D.
20
Product Service 1-800-522-7658
CChhaapptteerr 55:: UUssiinngg YYoouurr PPrrootteeccttoorr DDeem
Planning
Start-up
Loading Materials and Equipment
moonnssttrraattiioonn HHoooodd
Thoroughly understand procedures and equipment required before
beginning work.
Arrange for minimal disruptions, such as room traffic or entry into the
room while the hood is in use.
Turn on exhaust system and accessory light if so equipped.
Only raise the sash for loading.
Check the baffle air slots for obstructions.
Allow the enclosure to operate unobstructed for 1 minute.
Wear a long sleeved lab coat and rubber gloves. Use protective
eyewear. Wear a protective mask if appropriate. Consult your Safety Officer for additional personal protective equipment recommendations.
Only load the materials required for the procedure. Do not overload
the hood.
Do not obstruct the air foil, or rear baffle slots.
Large objects should not be placed close together and should be
elevated above the work surface to permit airflow to sweep under the equipment.
Product Service 1-800-522-7658
21
Chapter 5: Using Your Protector Demonstration Hood
Work Techniques
Keep all materials inside the lower air foil, and perform all
contaminated operations as far to the rear of the work area as possible.
Segregate all clean and contaminated materials in the work area.
Avoid using techniques or procedures that disrupt the airflow patterns
of the hood.
Final Purging
Upon completion of work, the hood should be allowed to operate for
two to three minutes undisturbed, to purge airborne contaminants
from the work area before shutting down the blower.
Unloading Materials and Equipment
Objects in contact with contaminated material should be surface
decontaminated before removal from the hood.
All open trays, weigh vessels or chemical containers should be
covered before being removed from the hood.
Shutdown
Turn off the exhaust system and accessory light if provided.
22
Product Service 1-800-522-7658
CChhaapptteerr 66::
Maaiinnttaaiinniinngg YYoouurr PPrrootteeccttoorr
M DDeem
Now that you have an understanding of how to work in the hood, we will review the suggested maintenance schedule and the common service operations necessary to maintain your hood for peak performance.
Only trained and experienced certification technicians should perform some of the service operations after the hood has been properly decontaminated. DO NOT attempt to perform these operations if you are not properly trained. The wrench icon precedes the service operations that require qualified technicians.
moonnssttrraattiioo
n HHoooodd
n
Routine Maintenance Schedule
Weekly
Clean the hood interior appropriate for the application.
Operate the exhaust system, noting the airflow velocity through the
enclosure using a source of visible smoke. Airflow alarms are recommended for constant monitoring.
Monthly (or more often as required)
Determine the actual face velocity through the sash opening of the
hood where the average reading should be at the specified velocity. (Use calibrated thermal anemometer or other approved apparatus). Airflow alarms are recommended for constant monitoring.
Using a cloth and glass cleaner, clean the exterior surfaces of the
hood, particularly the front of the hood, to remove any accumulated dust.
The hood rear baffle should be checked for any blockage to ensure
that the enclosure is maintaining proper airflow.
All weekly activities.
Product Service 1-800-522-7658
23
Chapter 6: Maintaining Your Protector Demonstration Hood
Annually
Have the hood validated by a qualified certification technician. See
Validating the Hood in Chapter 3.
All monthly activities.
Guardian™ 500 Airflow Monitor Kit No. 3944700 or 3944701
The Guardian 500 Airflow Monitor is designed to continuously monitor airflow through enclosures and fume hoods. This permanently installed device provides both visual and audible alarms to alert the user of abnormal airflow conditions. A green light on the front of the monitor indicates normal flow conditions. When flow conditions lower than the set point are encountered, a flashing red light is activated along with an audible alarm. To temporarily mute the audible alarm, press and release the test/reset button. The Guardian 500 Airflow Monitor has a built-in sensor, 3 relay inputs and 1 relay output. The relay inputs can be configured for night setback, external alarm, and sash high alarm. The night setback features disables the alarm. The relay output is configured for Low Air Alarm.
Guardian 500 Component Identification
See Figure 6-1 on the following page.
1. Air Inlet A portion of the air coming into the enclosure passes
through the air inlet and across the flow sensors.
2. Normal Flow Indicator This green light indicates normal flow conditions.
3. Alarm Indicator This red light is activated approximately 10-30
seconds after the low flow set point is reached. Low flow set points are 10-20 fpm below normal flow.
4. Mute Button If no alarm is present, this button will cause the red
lamp to light and the audible alarm to sound. If an alarm is present, the button will silence the audible alarm.
5. Adjustment for Alarm
Set Point
This potentiometer is used to set the low flow indicators for the alarm. It is adjusted with a small screwdriver.
24
Product Service 1-800-522-7658
Chapter 6: Maintaining Your Protector Demonstration Hood
3
2
4
Figure 6-1
Component Identification
Guardian 500 Installation Procedure
1
5
1. The enclosure comes prepared to except the Guardian™ 500 Airflow
Monitor.
2. First remove the large 1.19" dia. gray hole plug. See Figure 2. See
Figure 3 only to reference internal assembly of the airflow monitor. Locate the elbow, locknut, and washer and install it in the 1.19" dia. hole per Figure 6-2 and Figure 6-3. The enclosure baffle pivots down to install the elbow, washer and locknut.
3. Cut the 1" hose supplied with the kit to 15.5" approximate length and
install it between the airflow sensor and the elbow.
4. Secure the Guardian 500 Airflow Monitor to the enclosure with double
stick tape as shown in Figure 6-4. The airway passage between the alarm module and the enclosure is now complete.
5. Locate the metal hose cover and install with double stick tape per
Figure 6-4.
6. Locate the power supply transformer. One end should already be
connected to the two-pin connector labeled 15 VDC on the back of the alarm module and through the strain relief bushing. If disconnected, then reconnect to power the airflow monitor. Plug the 115V power supply into a standard 115V duplex receptacle, the back of the accessory FilterMate portable exhauster or the back of the accessory light. For 230V, plug into a standard receptacle with your specific outlet plug. (It is recommended that the airflow monitor be
connected directly to the FilterMate switched auxiliary outlet so the airflow monitor is powered at the same time.)
7. Installation is now complete.
Product Service 1-800-522-7658
25
Chapter 6: Maintaining Your Protector Demonstration Hood
Remove Large 1.19"
Dia. Hole Plug
Hole Plug and Mounting Screws Location
Figure 6-2
Install Elbow,
Locknut and
Washer
Display
Guardian 500
Monitor
26
Figure 6-3
Guardian 500 Details
Product Service 1-800-522-7658
Chapter 6: Maintaining Your Protector Demonstration Hood
Guardian 500 Calibration Procedure
Each alarm module and enclosure/fume hood is unique and needs to be individually calibrated in the field. The procedure for the adjustment is as follows:
1. Double check the installation to make sure that monitor and power supply are
properly installed.
2. Allow 10 minutes for the monitor to warm up once power has been connected.
3. Determine the low flow set point for your monitor. This is the value where
the monitor will first indicate a low flow condition. The red light will be on for this value. Refer to your industrial hygiene officer for the proper low flow set point or consult the table below.
4. Adjust your enclosure/fume hood airflow to the low flow set point as
previously determined. The exhaust flow can be lowered by adjusting the speed control on the FilterMate or by using an adjustable damper on the exhaust blower. Typical alarm conditions are set at face velocities of 10 to 20 feet per minute below the normal operating conditions due to supply air and exhaust air fluctuations, as well as room air cross drafts. See note 8 if the low airflow volume or sash opening cannot be adjusted.
5. Using a properly calibrated thermoanemometer, determine the velocity
through the face of the enclosure by taking a detailed velocity traverse. Divide the face area into equal increments. One reading per square foot of face area is normally recommended for an accurate traverse. Compute the average velocity for this area.
6. If the red light alarm is on, slowly turn the adjustment screw counterclockwise
until the green light is activated. If the green light is on, slowly turn the adjustment screw clockwise until the red light comes on. Slowly turn the adjustment screw back until the red light is activated. It is important that these adjustments be done in small increments, at intervals about 30 seconds apart to allow for delayed reaction of the alarm itself. The alarm low flow set point should now be set and the red light activated.
7. Readjust the enclosure airflow to its normal operating levels. The green light
should now be activated. Calibration is now complete.
Enclosure Operating In Flow Speed Alarm Condition Set Point Speed
100 fpm 80 - 90 fpm
80 fpm 60 - 70 fpm 60 fpm 40 - 50 fpm
8. Note: If the low airflow volume or sash opening cannot be adjusted, then a 1/4 to
1/3 of a turn counterclockwise can be adjusted to set the airflow alarm condition at 10-25% below normal operating levels.
Guardian 500 Alarm Activation
The audio and visual alarm will activate approximately 10-30 seconds after an alarm condition is detected. To temporarily mute the audible alarm, press and release the test/reset button.
NOTE: After an alarm condition has been detected, the red light will stay on. The audible alarm will remain muted until airflow returns to normal levels.
Product Service 1-800-522-7658
27
Chapter 6: Maintaining Your Protector Demonstration Hood
Enclosure
Accessory Light
Hose Cover
Monitor
28
Figure 6-4
Guardian 500 Installation
Product Service 1-800-522-7658
Chapter 6: Maintaining Your Protector Demonstration Hood
Guardian™ Digital 1000 Kit No. 3908800 or 3908801
Guardian Digital 1000 Operation
The Guardian Digital Airflow Monitor consists of the airflow sensor, the Alarm Unit and the 15 VDC power supply. For 115V operation the alarm unit is powered by plugging the power supply into the factory-prepared digital airflow monitor socket. For 230V operation, the Alarm Unit is powered by plugging the power supply into a building outlet. The alarm has “Enter”, “+”, and “-” buttons to program the monitor. There is also a green LED “SAFE”, yellow LED “CAUTION”, and red LED “LOW” with audible alarm for airflow conditions. The audible alarm can be permanently muted if desired. The Guardian Digital 1000 Airflow Monitor displays a face velocity value, provides an RS232 communications port to a PC or building computer system, can be configured for external input connections such as night setback or external alarm and provides up to three output relays that can be configured. For complete detailed information, please refer to the separate Labconco 1000 Alarm User’s Manual provided with the enclosure.
Guardian Digital 1000 Installation Procedure
1. The enclosure comes prepared to accept the Guardian Digital airflow
monitor system.
2. First remove the large 1.19" dia. gray hole plug. See Figure 6-5. See
Figure 6-6 only to reference internal assembly of the airflow monitor. Locate the elbow, locknut, and washer and install it in the 1.19" dia. hole per Figure 6-5 and Figure 6-6. The enclosure baffle pivots down to install the elbow, washer and locknut.
3. Cut the 1" hose supplied with the kit to 10.5" approximate length and
install it between the airflow sensor and the elbow.
4. Secure the Guardian Digital alarm to the enclosure with double stick
tape as shown in Figure 6-7. The airway passage between the alarm module and the enclosure is now complete.
5. Locate the metal hose cover and install with double stick tape per
Figure 6-3.
6. Locate the power supply transformer. One end should already be
connected to the two-pin connector labeled 15 VDC on the back of the alarm module and through the strain relief bushing. If disconnected, then reconnect to power the airflow monitor. Plug the 115V power supply into a standard 115V duplex receptacle, the back of the accessory FilterMate portable exhauster or the back of the accessory light. For 230V, plug into a standard receptacle with your specific outlet plug. (It is recommended that the airflow monitor
be connected directly to the FilterMate switched auxiliary outlet so the airflow monitor is powered at the same time.)
7. Installation is now complete.
Product Service 1-800-522-7658
29
Chapter 6: Maintaining Your Protector Demonstration Hood
Remove Large 1.19"
Dia. Hole Plug
Hole Plug and Mounting Screws Location
Figure 6-5
Airflow
Sensor
Install Elbow,
Locknut and
Washer
Display Digital
1000 Monitor
30
Figure 6-6
Digital 1000 Airflow Monitor Details
Product Service 1-800-522-7658
Enclosure
Chapter 6: Maintaining Your Protector Demonstration Hood
Accessory Light
Hose Cover
Monitor
Digital 1000 Airflow Monitor Installation
Product Service 1-800-522-7658
Figure 6-7
31
Chapter 6: Maintaining Your Protector Demonstration Hood
Guardian Digital 1000 Calibration
1. Calibrate the airflow monitor according to the instruction manual that
comes with the kit. To successfully calibrate, it will be necessary to
change the face velocity by adjusting the airflow exhaust volume. The
exhaust volume can be adjusted with the speed control on the FilterMate
or by using an adjustable damper on the exhaust blower. Typical
calibration conditions are set at face velocity air sample differences of at
least 20 feet per minute. The airflow monitor is factory set to be
calibrated with a difference of at least 50 fpm and can be changed by
changing the “lower/higher air sample difference”. The following
suggested in flow face velocity speeds are recommended to successfully
calibrate. Typical low air alarms are set 10-20 fpm below operational
speeds. Follow Step 2 below and review the Labconco 1000 Alarm
User’s Manual that comes with the airflow monitor.
Low Air
Alarm
Set Point
40 - 50 fpm 60 fpm 40 - 60 fpm 100 – 120 fpm 60 - 70 fpm 80 fpm 50 - 90 fpm 100 – 150 fpm
80 – 90 fpm 100 fpm 50 – 110 fpm 100 – 170 fpm
2. Go to setup and then CAL CONFIG MENU and change the
“lower/higher air sample difference” to 20 fpm. This will allow you
to successfully calibrate with values of a minimum of 20 fpm
difference.
Enclosure
Operating In
flow Speed
Low
Calibration
Set Point
High
Calibration
Set Point
3. While in CAL CONFIG MENU, change the “sensor difference” from
10% to 3%.
4. While in CAL CONFIG MENU, adjust the red low air alarm to the
desired setting such as 55 fpm. Then adjust the yellow “CAUTION
or WARNING” to 59 fpm. Then adjust the “CAUTION or
WARNING” air reset to 3 fpm. This sets the alarm condition.
5. To complete the CAL CONFIGURATION, be sure to enter “DONE”.
6. To start the calibration mode, use the Labconco 1000 Manual and
enter “CALIBRATION” mode on the display from the SETUP menu.
7. Follow the instructions on the display and alter the low exhaust
volume with the speed control on the FilterMate or exhaust damper.
Measure the average face velocity and enter the low value on the
display. Be careful not to block the opening. The low exhaust
volume calibration will take about 5 seconds.
8. Now alter the high exhaust volume with the speed control on the
FilterMate or exhaust damper. Measure the average face velocity and
enter the high value on the display. The high value must be at least
20 fpm greater than the low value. The high exhaust volume
calibration will take about 5 seconds.
32
Product Service 1-800-522-7658
Chapter 6: Maintaining Your Protector Demonstration Hood
9. Be sure to enter “DONE” after successfully completing the low and
high calibration set points.
10. Once calibration is completed, go to “RUN” and hit “ENTER”. The
value should read close to the high calibration set point.
11. To lower the face velocity to the operating point, simply alter the
exhaust volume with the speed control on the FilterMate or exhaust damper. Then recheck the face velocity with an anemometer to confirm the display on the digital airflow monitor.
Digital 1000 Alternate Calibration Procedure ­Constant Volume Conditions
1. To successfully calibrate, it will be necessary to change the face
velocity by opening and closing the enclosure’s sash. The airflow monitor is factory set to be calibrated with a difference of at least 50 fpm and can be changed by adjusting the “lower/higher air sample difference”. The in flow face velocity speeds provided in the chart below are suggested to successfully calibrate the Digital 1000.
2. Before proceeding with calibration, it will first be necessary to
configure the airflow monitor. Go to the setup and then CAL CONFIG MENU and adjust the “lower/higher air sample difference” to 10 fpm. This will allow you to successfully calibrate with minimum difference values of 10 fpm.
3. While in CAL CONFIG MENU, change the “sensor difference” from
10% to 3%.
4. While in CAL CONFIG MENU, adjust the red low alarm to the
desired setting (See the chart below for range and suggested settings). Then adjust the yellow “CAUTION or WARNING” to the desired setting (See the chart below for range and suggested settings). Then adjust the “CAUTION or WARNING” air reset to 3 fpm. This sets the alarm condition.
CAUTION WARNING
“YELLOW LED” Setting
Range
user defined
(fpm)
43 – 53 51 40 – 50 48 27 23 60 fpm 63 – 73 67 60 – 70 64 37 30 80 fpm
83 - 93 83 80 - 90 80 47 37 100 fpm
Suggested
Set Point
(fpm)
LOW ALARM
“RED LED”
Setting
Range
user defined
(fpm)
* Suggested
Set Point
(fpm)
Low Calibration
Set Point
Sash Open
(fpm)
8" Sash
Height
10" Sash
Height
High Calibration
Set Point
or Enclosure
Operating
Inflow Speed
Sash Closed
* Because of airflow fluctuations in a typical laboratory environment Labconco
suggests setting the “RED LED” low alarm set point to 20% below the enclosure’s operating speed.
Product Service 1-800-522-7658
33
Chapter 6: Maintaining Your Protector Demonstration Hood
5. To complete the CAL CONFIGURATION, be sure to enter “DONE”.
If needed, refer to the Configuration procedure provided on the
following page for additional details.
6. To start the calibration mode, enter “CALIBRATION” mode on the
display from the SETUP menu.
7. Follow the instructions on the display and simulate the low exhaust
volume by fully opening the sash. You may measure the average face
velocity for the low calibration set point or utilize the calculated value
provided in the chart above. The average face velocity for the low set
point is accurately measured by dividing the opening of the enclosure
into equal area grids consisting of at least 9 data collection points and
measuring the velocity at the center of each grid with a calibrated
thermo anemometer. Enter the low value on the display. Be careful
not to block the opening. The low exhaust volume calibration will
take about 5 seconds.
8. Now simulate the high exhaust volume by fully closing the sash to its
normal operating position. Measure the average face velocity for the
high calibration set point to confirm that the source of constant air
volume is providing the desired face velocity for the enclosure. The
average face velocity for the high set point is accurately measured by
dividing the opening of the enclosure into equal area grids consisting
of at least 3 data collection points and measuring the velocity at the
center of each grid with a calibrated thermo anemometer. Enter the
high value set point on the display. The high value must be at least 10
fpm greater than the low value. The high exhaust volume calibration
will take about 5 seconds.
9. Be sure to enter “DONE” after successfully completing the low and
high calibration set points.
10. Once calibration is completed, go to “RUN” and hit “ENTER”. The
value should read close to the high calibration set point.
11. With the sash fully open, the Digital 1000 monitor should go into
“RED LED” low air alarm if successfully calibrated.
34
Product Service 1-800-522-7658
Chapter 6: Maintaining Your Protector Demonstration Hood
Note: Enter Button stores information and +/- Buttons allow for scrolling.
1. Push the “ENTER” Button on the face of the alarm until the “SET
UP” Menu is displayed.
2. Scroll to “SET UP” and hit “ENTER”.
3. The PASSWORD MENU displays (The Password is 0000). Press
the ENTER button repeatedly until the CAL CONFIG MENU is displayed.
4. In the CAL CONFIG MENU set the following:
CALIBRATION - CONFIGURATION MENU SETTINGS
DISPLAY UNITS FPM
LOW AIR ALARM “RED LED”
LOW AIR CUTOFF OFF
WARNING AIR ALARM “YELLOW LED”
WARNING AIR RESET 3 FPM HIGH AIR ALARM OFF LOWER AIR SAMPLE FLUCTUATIONS OFF HIGHER AIR FLUCTUATIONS 3% LOWER / HIGHER AIR SAMPLE DIFFERENCE 3% WARN TO ALARM AIR TIME 10 SECONDS ALARM TO WARN AIR TIME 3 SECONDS SHOW AIR FLOW ON SHOW TIME LINE OFF = DISPLAYS BAR GRAPH AUDIBLE ALARM ENABLED SENSOR DIFFERENCE 2% SENSITIVITY 80%
* 48 FPM (60 fpm Operating inflow) * 64 FPM (80 fpm Operating inflow) * 80 FPM (100 fpm Operating inflow)
* 51 FPM (60 fpm Operating inflow) * 67 FPM (80 fpm Operating inflow) * 83 FPM (100 fpm Operating inflow)
OFF
* (Suggested Air Alarm Settings) Refer to the chart on the previous pages for a range of air velocity settings that may be used.
5. To complete the CAL CONFIG, be sure to enter “DONE”. You
are returned to the Main Menu.
Product Service 1-800-522-7658
35
CChhaapptteerr 77:: AAcccceessssoorriizziinngg YYoouurr PPrrootteeccttoorr DDeem
There are several ways to accessorize the hood for your individual requirements. These include the addition of accessory work surfaces, airflow monitors, fluorescent lights, exhaust transition adapters, hoses, remote blowers, exhaust dampers, FilterMate Portable Exhausters, filters, storage cabinets and mobile carts.
moonnssttrraatt
ioonn HHoooodd
i
36
Product Service 1-800-522-7658
Chapter 7: Accessorizing Your Protector Demonstration Hood
Optional Equipment for the Demonstration Hood
Airflow monitor moved forward per Chapter 6.
Product Service 1-800-522-7658
Figure 7-1
37
Chapter 7: Accessorizing Your Protector Demonstration Hood
1. Work Surfaces
An optional dished work surface is available to attach to the hood.
Dished work surfaces are contoured to fit the dimensions of the hood to contain spills. Epoxy is chemical-resistant.
Catalog # Description Dimensions (W x D x H)
3908402 Black, 4-foot wide 48" x 26.66" x 1" 3908405 Gray, 4-foot wide 48" x 26.66" x 1"
2. Guardian™ Digital 1000 and Guardian™ 500 Airflow Monitors
The Guardian Digital 1000 Airflow Monitor or Guardian 500 Airflow Monitor allows you to continuously monitor airflow through the hood. The rear exhaust plenum is factory prepared to mount either monitor.
Catalog # Description
3944700 Guardian 500 Airflow Monitor, 115V, 60 Hz 3944701 Guardian 500 Airflow Monitor, 230V, 50 Hz 3908800 Guardian Digital 1000 Airflow Monitor 115V, 60 Hz 3908801 Guardian Digital 1000 Airflow Monitor 230V, 50 Hz
3. Fluorescent Lights
A fluorescent light, which rests on the top of the hood, is available.
Catalog # Description
3909200 18.25" W x 10.12"D x 3.00" H Light, 115V, 60 Hz 3909201 18.25" W x 10.12"D x 3.00" H Light, 230V, 50 Hz
4. Exhaust Transition Adapters
Adapter connects to the hood from either the top or the bottom of the rear plenum so the duct can be routed either up or down, respectively. The transition is available for either 5.00" ID hose or 6" OD duct. The 5.00" ID hose lower connection is included with the FilterMate supplied with the mobile cart.
Catalog # Description Material
3912400 Upper connection, 5" Hose Epoxy-Coated Steel 3912401 Upper connection, 6" Duct Epoxy-Coated Steel 3912402 Lower connection, 5" Hose Epoxy-Coated Steel 3912403 Lower connection, 6" Duct Epoxy-Coated Steel
38
Product Service 1-800-522-7658
Chapter 7: Accessorizing Your Protector Demonstration Hood
5. Remote Blowers
Has a 1/4 hp direct drive motor and corrosion-resistant phenolic coated­steel housing and wheel with blower inlet of 6.00" ID. Outlet dimensions are 4.25" x 7.38" OD.
CFM @ Static Pressure-Inches of H2O
S.P. 0.0" 0.125" 0.25" 0.50" 0.75" 0.87" CFM 595 560 515 420 300 167
Catalog # Description
4863500 Remote Blower, 115 V, 60 Hz. 4.4 amps 35/16 4863501 Remote Blower, 115/230 V, 50 Hz, 5.6/2.8 amps 35/16
7053501
Explosion-Proof Remote Blower, 115 V, 60 Hz,
4.4 amps
Shipping Wt.
(lbs./kg.)
40/18
6. Exhaust Dampers
Exhaust dampers allow an adjustment required to maintain proper airflow for roof-mounted blowers or house exhaust systems.
Catalog # Description
3924000 6" Epoxy-Coated Steel In-Line Adjustable Damper 4724200 6" PVC In-Line Adjustable Damper
Product Service 1-800-522-7658
39
Chapter 7: Accessorizing Your Protector Demonstration Hood
7. FilterMate Portable Exhausters and Filters
For filtered exhaust, Labconco offers FilterMate Portable Exhausters capable of exhausting up to 280 cfm of HEPA filtered air or up to 220 cfm of combination Dual Carbon or HEPA/Carbon filtered air when connected to the enclosure.
Catalog # Voltage Filter
3970000 115 Volt/60 Hz HEPA None 280 3970001 115 Volt/60 Hz Carbon None 280 3970002 115 Volt/60 Hz HEPA Thimble to outside 280 3970003 115 Volt/60 Hz HEPA/Carbon None 220 3970004 115 Volt/60 Hz Carbon/Carbon None 220* 3970020 230 Volt/50 Hz HEPA None 280 3970021 230 Volt/50 Hz Carbon None 280 3970022 230 Volt/50 Hz HEPA Thimble to outside 280 3970023 230 Volt/50 Hz HEPA/Carbon None 220 3970024 230 Volt/50 Hz Carbon/Carbon None 220*
Exhaust
Connection
Exhaust
Airflow
(cfm)
*Indicates model supplied with mobile cart with lower 5" exhaust
transition included.
HEPA Filter - 3707900
99.99% efficient on particles 0.3 micron.
HEPA Filter Bag-In/Bag-Out Bag - 3776002
Helps contain hazardous particulate matter during filter changing operations.
Carbon Filter
Provides granular activated carbon or impregnated carbon.
Filter Classification Catalog # x Pounds
Organic 3923400 12.0 lbs activated carbon Formaldehyde 3923401 14.0 lbs impregnated carbon Ammonia 3923402 16.0 lbs impregnated carbon
40
Product Service 1-800-522-7658
Chapter 7: Accessorizing Your Protector Demonstration Hood
8. Storage Cabinets
Size/Description Dual Doors Right Hinge Left Hinge Dual Doors Right Hinge Left Hinge
48" 9902000 - - 9901000 - ­36" 9902100 - - 9901100 - ­30" 9902200 - - 9901200 - ­24" - 9902300 9902400 - 9901300 9901500 18" - - - - 9901400 9901600 12" - - - - - ­48" w/Self Closing Doors 9903000 - - - - ­36" w/Self Closing Doors 9903100 - - - - ­30" w/Self Closing Doors 9903200 - - - - ­24" w/Self Closing Doors - 9903300 9903400 - - ­24" ADA - 9906000 9906100 - 9905000 9905200 24" ADA w/Self Closing Doors 18" ADA - - - - 9905100 9905300 12" ADA - - - - - -
- 9906200 9906300 - - -
SOLVENT ACID
Size/Description Dual Doors Right Hinge Left Hinge Dual Doors Right Hinge Left Hinge 48" 9900000 - - - - ­36" 9900100 - - - - ­30" 9900200 - - - - ­24" - 9900300 9900600 - - ­18" - 9900400 9900700 - 9907000 9907100 12" - 9900500 9900800 - - ­48" w/Self Closing Doors - - - - - ­36" w/Self Closing Doors - - - - - ­30" w/Self Closing Doors - - - - - ­24" w/Self Closing Doors - - - - - ­24" ADA - 9904000 9904300 - - ­24" ADA w/Self Closing Doors 18" ADA - 9904100 9904400 - - ­12" ADA - 9904200 9904500 - - -
STANDARD BASE VACUUM PUMP
- - - - - -
Product Service 1-800-522-7658
41
Chapter 7: Accessorizing Your Protector Demonstration Hood
9. Mobile Cart 8026000
Provides a mobile cart and dished solid epoxy work surface for supporting the Protector Demonstration Hood.
10. Hoses, Hose Clamps, and Hose Kits
Provides alternatives for ducting.
Catalog # Description
4868600 8 Feet of 5" ID gray flexible polypropylene hose (included with
FilterMate). General purpose chemical-resistant hose suitable in
pharmaceutical applications. 1921000 5" T-Bolt Hose Clamp (two included with FilterMate) 3927500 8 Feet of 5" ID clear smooth bore static dissipation hose with two hose
clamps. Suitable in clean rooms or pharmaceutical applications. 3927600 8 Feet of 6" ID black thermoplastic hose with two 6.09" ID cuffs.
Include two 6" hose clamps. Suitable for connection to house exhaust
in pharmaceutical applications. 1921500 6" T-Bolt Hose Clamp
42
Product Service 1-800-522-7658
C
HHAAPPTTEERR
C
T
RROOUUBBLLEESSHHOOOOTTIINNGG
T
Refer to the following table if your Protector Demonstration Hood fails to operate properly. If the suggested corrective actions do not solve your problem, contact Labconco for additional assistance.
PROBLEM CAUSE CORRECTIVE ACTION
Contaminants outside of enclosure
Restriction of the
External factors are
8
8
Improper user techniques for the enclosure.
baffle air slots or blockage of the exhaust outlet.
disrupting the hood airflow patterns or acting as a source of contamination.
Hood has improper face velocity.
See “Certifying the Hood” Chapter 3 and “Safety Precautions” Chapter 4 sections in the manual. (Ref. Appendix D)
Remove obstruction to ensure that all air slots and the exhaust outlet are unobstructed.
See “Location Requirements” Chapter 2, “Certifying the Hood” Chapter 3, and “Safety Precautions” Chapter 4 sections of this manual. (Ref. Appendix D)
Have hood certified and check exhaust system. Check FilterMate filters for loading. Adjust FilterMate speed control. Hood should have average face velocity of 60-100 fpm.
Product Service 1-800-522-7658
43
Chapter 8: Troubleshooting
PROBLEM CAUSE CORRECTIVE ACTION
Airflow monitor malfunction.
No power. No lights. No display.
Power supply is not plugged into proper voltage; plug in power supply. Verify that airflow monitor interface cables are connected. Check fuses on FilterMate or accessory light.
No audible alarm. Alarm has been temporarily silenced
using “test/reset” or “enter” buttons.
Wrong alarm set
point.
Airflow monitor was not properly adjusted. Repeat calibration steps outlined in the airflow monitor manual.
Constant audible
alarm.
Check airflow and calibration of airflow monitor.
Continuous alarm. Check the face velocity of the
enclosure as the airflow may have changed. If face velocity is correct, calibrate the airflow monitor as outlined in the User’s Manual.
Monitor alarms; air
way to airflow monitor sensor is
Lightly clean the airway with clean air. Be careful not to touch sensitive
electrical components. blocked by insects, dust or debris.
Audible disable
will not stay ON
An alarm condition must be
continuously present before the
audible alarm can be silenced. If
flow conditions fluctuate near the
alarm set point, the airflow monitor
will automatically reset itself.
Action should be taken to bring the
hood airflow into proper operating
parameters or adjust the alarm set
point lower.
44
Product Service 1-800-522-7658
A
PPPPEENNDDIIXX
A
R
EEPPLLAACCEEMMEENNT
R
The following illustrations indicate the replacement parts.
A
A
P
T
P
AARRTTSS
Product Service 1-800-522-7658
45
Appendix A: Replacement Parts
Item Qty. Part Number Description
1A 1 3906500 Glass, Side Short 1B 1 3926500 Glass, Side Tall 2 1 3906801 Glass, Top 3' 3A 1 3906101 Glass, Sash 3' Short 3B 1 3926101 Glass, Sash 3' Tall 4 1 3907601 Foil, Sash 3' 5 2.3 Ft. 6913700 Wiper, Sash 6A 1 3907500 Stop, Right Sash 6B 1 3907501 Stop, Left Sash 7A 1 1927403 Spring, Compression Sash Latch 7B 1 3906700 Latch Bracket 7C 1 6916500 Latch Sash 7D 2 1893206 Screw, #8-32 x .38 Phil, SS, Type F 7E 1 6916501 Latch Sash Tall 7F 1 3925300 Latch Bracket Tall 8A 1 3905201 Sash Assembly 3', Short 8B 1 3925201 Sash Assembly 3' Tall 9A 1 3907400 Bracket, Air Foil Right 9B 1 3907401 Bracket, Air Foil Left 9C 2 1932401 Washer, Shoulder Plastic 9D 2 1912108 Washer, .194 ID x .38 OD x .03 thick plastic 9E 2 1909217 Cap Nut #10-24 SS 10 1 3905601 Air Foil 3' 11 1 3905301 Header 3' 12 1 3913100 Cover Plate, Exhaust (Top or Bottom) 13A 1 3912400 Upper Exhaust Transition 5" Hose 13B 1 3912401 Upper Exhaust Transition 6" Duct 13C 1 3912402 Lower Exhaust Transition 5" Hose 13D 1 3912403 Lower Exhaust Transition 6" Duct 14A 1 1934601 Bushing, Heyco with Flex Shutter 1.50 dia.
14B 1 1936800 Bushing, Heyco Closed 1.50 dia. 15A 2 7868402 Spacer Bushing
15B 2 1912108 Washer, .194 ID x .38 OD x .03 T. Plastic 15C 2 1889316 Screw, #10-24 x 1.00 PH. (SS)
16A 2 3915400 Side Air Foil, Short 16B 2 3915401 Side Air Foil, Tall
16C 4 1889912 Screw, 6-32 x .75 PH. Type F, Oval Head 17 1 1595619 Hole Plug, .500 dia. Gray
18 1 1595621 Hole Plug, 1.187 dia. Gray 19 1 3941900 Label, Protector Demonstration Hood
46
Product Service 1-800-522-7658
Appendix A: Replacement Parts
Item Qty. Part Number Description
20A 1 3942500 Baffle Assy, Short 20B 1 3941700 Baffle Assy, Tall 20C 2 1914200 Captive Screw, Baffle 20D 2 1923900 Receptacle, Clip-on 21 1 3943000 Shelf, Demo Cart 22 4 8009501 Caster 4" w/ Brake Demo Cart
Airflow monitor moved forward per Chapter 6.
Figure A-1A
Product Service 1-800-522-7658
47
Appendix A: Replacement Parts
Airflow monitor moved forward per Chapter 6.
48
Figure A-1B
Product Service 1-800-522-7658
A
PPPPEENNDDIIX
A
D
IIMMEENNSSIIOONNS
D
X
S
B
B
Product Service 1-800-522-7658
49
A
PPPPEENNDDIIXX
A
S
PPEECCIIFFIICCAATTIIOONNSS
S
Electrical Specifications
115V, 60 Hz Mobile Demonstration Hood, 10 Amps Max. 230V, 50/60 Hz Mobile Demonstration Hood, 5 Amps Max.
Environmental Conditions
Indoor use only.
Maximum altitude: 6562 feet (2000 meters).
Ambient temperature range: 41° to 104°F (5° to 40°C).
Maximum relative humidity: 80% for temperatures up to 88°F (31°C),
decreasing linearly to 50% relative humidity at 104°F (40°C).
Main supply voltage fluctuations not to exceed ±10% of the nominal
voltage.
Transient over-voltages according to Installation Categories II (Over-
voltage Categories per IEC 1010). Temporary voltage spikes on the AC input line that may be as high as 1500V for 115V models and 2500V for 230V models are allowed.
Used in an environment of Pollution degrees 2 (i.e., where normally
only non-conductive atmospheres are present). Occasionally, however, a temporary conductivity caused by condensation must be expected, in accordance with IEC 664.
C
C
50
Product Service 1-800-522-7658
Appendix C: Specifications
Product Service 1-800-522-7658
51
Appendix C: Specifications
52
Product Service 1-800-522-7658
A
PPPPEENNDDIIXX
A
R
EEFFEERREENNCCEES
R
Many excellent reference texts and booklets are currently available. The following is a brief listing:
Laboratory Ventilation Standards
Federal Register 29 CFR Part 1910
Non-mandatory recommendations from “Prudent Practices”.
Fume hoods should have a continuous monitoring device
Face velocities should be between 60-100 linear feet per minute (lfpm)
Average 2.5 linear feet of hood space per person
Occupational Health and Safety U.S. Department of Labor 200 Constitution Avenue N.W. Washington, DC 20210 (202) 523-1452 www.osha.gov
Industrial Ventilation-ACGIH
Fume hood face velocities between 60-100 lfpm
Maximum of 125 lfpm for radioisotope hoods
Duct velocities of 1000-2000 fpm for vapors, gasses and smoke
Stack discharge height 1.3-2.0 x building height
Well designed fume hood containment loss, <0.10 ppm
Industrial Ventilation, A Manual of Recommended Practice.
th
24
Edition, 2001 American Conference of Governmental Industrial Hygienists 1330 Kemper Meadow drive Cincinnati, OH 45240-1634 (513) 742-2020 www.acgih.org
D
D
S
Product Service 1-800-522-7658
53
Appendix D: References
ASHRAE 110-1995 Method of Testing Performance of Fume Hoods
Evaluates fume hood’s containment characteristics
Three part test: Smoke generation, Face velocity profile, Tracer gas release @ 4
liters per minute
Rated As Manufactured (AM), As Installed (AI) and As Used (AU)
American Society of Heating, Refrigerating, and Air Conditioning Engineers 1791 Tullie Circle N.E. Atlanta, GA 30329 (404) 636-8400 www.ashrae.org
ANSI Z9.5-1993 Laboratory Standard
Covers entire laboratory ventilation system.
Vertical stack discharge @ 2000-3000 fpm
New and remodeled hoods shall have a monitoring device
Ductless hoods should only be used with non-hazardous materials
Fume hood face velocities between 80 – 120 fpm
American Industrial Hygiene Association 2700 Prosperity Avenue, Suite 250 Fairfax, VA 22031 (703) 849-8888 www.aiha.org
SEFA 1-2002
Fume hood face velocities based on toxicity levels of chemicals
Class A – 125 to 150 fpm Class B – 80 to100 fpm Class C – 75-to 80 fpm
Test method – face velocity profile and smoke generation
Scientific Equipment & Furniture Association 1028 Duchess Drive McLean, VA 22102 (703) 538-6007 www.sefalabs.com
NFPA 45 – 2002 Fire Protection for Laboratories Using Chemicals
Laboratory hoods should not be relied on for explosion protection
Exhaust air from fume hoods should not be recirculated
Services should be external to the hood
Canopy hoods only for non-hazardous applications
Materials of construction should have flame spread of 25 or less
80 to 120 fpm to prevent escape
NFPA 30 – 2000 Flammable and Combustible Liquids Code
Approved cabinets may be metal or wood
Vent location on cabinets are required
Venting of cabinets not a requirement
54
Product Service 1-800-522-7658
Appendix D: References
National Fire Protection Association 1 Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9101 (800) 344-3555 www.nfpa.org
General References
American Conference of Governmental Industrial Hygienists. Industrial Ventilation, A Manual of Recommended Practice, Cincinnati, OH
ASHRAE Standard Committee. ASHRAE Standard Atlanta: ASHRAE Publications Sales Department, 1995
British Standards Institution, Laboratory Fume Cupboards. Parts 1, 2 and 3, London: 1990
Department of Labor, Occupational Safety and Health Administration, 29 CFR Part 1910, Occupational Exposures to Hazardous Chemicals in Laboratories, Final Rule. Vol. 55, No. 21. Washington D.C.:1990
DiBerardinis. L. et al. Guides for Laboratory Design, Health and Safety Considerations. Wiley & Sons, 1987
McDermott, Henry, Handbook of Ventilation for Contaminant Control, 2 Butterworth Publishers, 1985.
Miller, Brinton M. et al. Laboratory Safety: Principles and Practices. American Society for Microbiology, Washington, D.C.: 1986
NIH Guidelines for the Laboratory Use of Chemical Carcinogens. NIH Publication No. 81-2385.
Rayburn, Stephen R. The Foundation of Laboratory Safety, A Guide for the Biomedical Laboratory. Springer-Verlag, New York: 1990
Sax, N. Irving and Lewis, JR., Richard J. Rapid Guide to Hazardous Chemicals in the Workplace. Van Nostrand Reinhold, 1987.
Schilt, Alfred A. Perchloric Acid and Perchlorates. The G. Frederick Smith Chemical Company, Columbus, OH: 1979.
Steere, Norman. CRC Handbook of Laboratory Safety, 2
nd
Edition. CRC Press,
1971.
nd
Edition.
Product Service 1-800-522-7658
55
DECLARATION OF CONFORMITY
Application Council Directive(s): 73/23/EEC, 89/336/EEC, 2002/95/EC (ROHS), 2002/96/EC (WEEE)
Standard(s) to which conformity is declared: EN61010-1, EN61326-1
Manufacturer’s Name: Labconco Corporation
Manufacturer’s Address: 8811 Prospect Avenue Kansas City, MO 64132 USA
Importer’s Name: See Shipping/Customs Documents
Importer’s Address: See Shipping/Customs Documents for your equipment
Type of Equipment: Laboratory Equipment Protector Demonstration Hoods
3944300 Series 3' Demonstration Hoods 3945000 Series 3' Mobile Demonstration Hoods
Serial No.: Various – See Individual Declaration
Year of Manufacture: 2004 and subsequent
I, the undersigned, hereby declare that the equipment specified above conforms to the above Directive(s) and Standard(s).
See individual Declaration of Conformity which will be signed by the importer for your country.
Place: _______________________________________ (Signature)
Date: _______________________________________ (Full Name)
_______________________________________
(Position)
Labconco P/N 36960-55, Rev. A, ECO E305
56
Product Service 1-800-522-7658
Loading...