KYORITSU KEW2200R Instruction Manual

INSTRUCTION MANUAL
WARNING
DANGER
WARNING
CAUTION
DIGITAL CLAMP METER
KEW2200R
Barrier
Data Hold Key
Mode Key
COM Terminal
Snap Band
Barrier of Test Leads
Cap
Current Sensor
Trigger
Function Switch
LCD
V/Ω Terminal
1. Safety Warnings
This instrument has been designed, manufactured and tested according to IEC 61010: Safety requirements for Electronic Measuring apparatus, and delivered in the best condition after passed the inspection. This instruction manual contains warnings and safety rules which must be observed by the user to ensure safe operation of the instrument and retain it in safe condition. Therefore, read through these operating instructions before using the instrument.
● Read through and understand the instructions
contained in this manual before using the instrument.
● Keep the manual at hand to enable quick reference
whenever necessary.
● The instrument is to be used only in its intended
applications.
● Understand and follow all the safety instructions
contained in the manual.
● It is essential that the above instructions are adhered to.
● Failure to follow the above instructions may impair the
protection provided by the instrument and test leads, and may cause injury, instrument damage and/or damage to equipment under test.
The symbol indicated on the instrument means that
the user must refer to the related parts in the manual for safe operation of the instrument. It is essential to read the instructions wherever the symbol appears in the manual.
DANGER is reserved for conditions and actions that
are likely to cause serious or fatal injury.
WARNING is reserved for conditions and actions that
can cause serious or fatal injury.
CAUTION is reserved for conditions and actions that
can cause injury or instrument damage.
● Marks listed below are used on this instrument.
User must refer to the manual. Instrument with double or reinforced insulation
Indicates that this instrument can clamp on
bare conductors when measuring a voltage corresponding to the applicable measurement category, which is marked next to this symbol.
AC DC Ground (Earth)
This instrument is subject to WEEE Directive
(2002/96/EC). Please contact our dealer near you at disposal.
Measurement Category
O Circuits which are not directly connected to the mains
power supply.
CAT II Primary electrical circuits of equipment connected
to an AC electrical outlet by a power cord.
CAT III Primary electrical circuits of the equipment
connected directly to the distribution panel, and feeders from the distribution panel to outlets.
CAT IV The circuit from the service drop to the service
entrance, and to the power meter and primary over current protection device(distribution panel).
Current measurement section of this instrument is designed for CAT IV 300V / CAT III 600V and Voltage measurement section is for CAT III 300V / CAT II 600V
respectively. Test leads 7107A with the Cap is designed for CAT IV 600V / CAT III 1000V and without the Cap is for CAT II 1000V.
● Never make measurements under the circumstances
exceed the designed measurement category and the rated voltage of the instrument and the test leads.
● Do not attempt to make measurement in the presence of
flammable gasses. Otherwise, the use of the instrument may cause sparking, which can lead to an explosion.
● Never attempt to use the instrument if its surface or your
hand is wet.
● Do not exceed the maximum allowable input of any
measuring range.
● Never open the Battery cover during a measurement.
● To avoid electrical shock by touching the equipment
under test or its surroundings, be sure to wear insulated protective gear.
● Never measure current while the test leads are inserted
into the input terminals.
● Test leads to be used for voltage measurements shall be
rated as appropriate for Measurement Category III or IV according to IEC 61010-031 and shall have a voltage rating of 600V or higher.
● Barriers on the instrument body and the test leads
provide protection to keep your fingers and hands from touching an object under test. Keep your fingers and hands behind the barriers during measurement.
● Never attempt to make measurement if any abnormal
conditions, such as broken case and exposed metal parts are found on the instrument or test leads.
● Verify proper operation on a known source before use or
taking action as a result of the indication of the instrument.
Firmly attach the Caps to the test leads when
performing measurements at CAT III or higher test environment.
When KEW2200R and the test leads are combined and used together, whichever is lower category & voltage to earth either of them belong to is applied.
● Do not rotate the Function Switch while the test leads are
being connected.
● Do not install substitute parts or make any modification to
the instrument. For repair or re-calibration, return the instrument to your local distributor from where it was purchased.
● Use of this instrument is limited to domestic, commercial
and light industry applications. If equipments generating strong electromagnetic interference or strong magnetic fields due to large currents exist nearly, malfunctions of the instrument may be caused.
● Set the Function Switch to an appropriate position before
starting measurement.
● Firmly insert the test leads.
● The LCD shows some readings at the ACV and the DCV
ranges even while the test leads are open. And, it may show some digits instead of 0 when short-circuiting the test leads. However, these phenomena don’t affect measurement results.
● This instrument isn’t dust & water proofed. Keep away
from dust and water.
● Be sure to power off the instrument after use. When the
instrument will not be in use for a long period, place it in storage after removing the batteries.
● Do not expose the instrument to the direct sun, high
temperature and humidity or dewfall.
● Use a cloth dipped in water or neutral detergent for
cleaning the instrument. Do not use abrasives or solvents.
2. Specification
Accuracy guaranteed
100% or less of each range (AC0.1A/0.01V or more) Temperature: 23 ± 5°C, Humidity: 45 - 75%
ACA (Auto Range)
Range Display Range Accuracy
40A 0.00, 0.06-41.99A
400A 32.0-419.9A
1000A 320-1049A
Input protective current : AC1200A
CF<2.5 (less than 1500A Peak) For non-sinusoidal waveforms, add ± 1.5 %rdg ± 5dgt(45-65Hz), ±3.0 %rdg±5dgt(40-1kHz) ,
ACV (Auto Range)
Range Display Range Accuracy 4V 0.000, 0.006-4.199V 40V 3.20-41.99V 400V 32.0-419.9V 600V 320-629V
CF<2.5. For non-sinusoidal waveforms, add ±1.5 %rdg ±5dgt(45-65Hz), ±3.0 %rdg±5dgt(40-500Hz)
DCV (Auto Range)
Range Display Range Accuracy
400mV ±0.0-±419.9mV Accuracy is not guaranteed 4V ±0.320-±4.199V 40V ±3.20-±41.99V 400V ±32.0-±419.9V 600V ±320-±629V
ACV/DCV input impedance :
>100MΩ (400mV Range), 11MΩ (4V Range), 10MΩ (40/400/600V Range)
Resistance / Continuity (Auto Range)
Range Display Range Accuracy
400Ω 0.0-419.9Ω 4kΩ 0.320-4.199 kΩ 40kΩ 3.20-41.99 kΩ 400kΩ 32.0-419.9 kΩ 4MΩ 0.320-4.199 MΩ ±4.0%rdg±4dgt 40MΩ 3.20-41.99 MΩ ±8.0%rdg±4dgt Cont. 0.0-419.9Ω Bz threshold value 50±30Ω
Open-loop voltage :
<3.4V (400Ω / Cont Range), 0.7V typ (4kΩ Range)
±1.5 %rdg±5dgt
(45-65Hz)
±2.0 %rdg±5dgt
(40-1kHz)
±1.8 %rdg±7dgt
(45-65Hz)
±2.3 %rdg±8dgt
(65-500Hz)
±1.0%rdg±3dgt
±2.0%rdg±4dgt
0.47V typ (40k - 40MΩ Range)
WARNING
CAUTION
Test lead
Test lead
Resistance
Continuity
C
Input protective voltage : AC/DC600V 10 sec
Measuring method : Dual integration
Over-range indication : OL
Measurement cycle : 2.5 times per second
Applicable Standards :
IEC/EN 61010-1/ 61010-2-032/ 61010-2-033
Pollution degree 2, Indoor use, Altitude up to 2000m Current measurement section
CAT III 600V / CAT IV 300V
Voltage measurement section
CAT II 600V / CAT III 300V
IEC/EN 61010-031(Test leads Model 7107A)
w/ caps CAT IV 600V / CAT III 1000V w/o caps CAT II 1000V
EN61326 (EMC)
In the radio-frequency electromagnetic field of 3V/m, accuracy is within five times the rated accuracy.
EN50581 (RoHS)
Withstand voltage :
AC5160Vrms 5sec between Current sensor and enclosure AC3470Vrms 5sec between circuit and enclosure
Insulation resistance :
>100MΩ /1000V between enclosure and electrical circuit
Operating Temperature and humidity range :
0 to 40°C 85%RH or less (no condensation)
Storage Temperature and humidity range :
-20 to 60°C 85%RH or less (no condensation)
Power source : DC3V R03/LR03 (AAA) ×2
Current consumption : < 5mA
Battery life (ACA, continuous, no load, with R03) :
Approx. 120 hours
Dimension, Weight : 190(L)×68(W)×20(D)mm,
approx. 120gincluding batteries
Accessories : Test leads Model 7107A 1set Battery R03(AAA) 2pcs Instruction manual 1pce Carrying case Model 9160 1pce
[ Effective Value (RMS) ]
Most alternating currents and voltages are expressed in effective values, which are also referred to as RMS (Root-Mean-Square) values.
The effective value is the square root of the average of square of alternating current or voltage values. Many clamp meters using a conventional rectifying circuit have "RMS" scales for AC measurement. The scales are, however, actually calibrated in terms of the effective value of a sine wave though the clamp meter is responding to the average value. The calibration is done with a conversion factor of 1.111 for sine wave, which is found by dividing the effective value by the average value. These instruments are therefore in error if the input voltage or current has some other shape than sine wave.
[ CF (Crest Factor) ]
CF (Crest Factor) is found by dividing the peak value by the effective value. Examples: Sine wave: CF=1.414
Square wave with a 1: 9 duty ratio: CF=3
3. Other Function
Data Hold
Press the Data Hold Key to freeze the reading. Press the Data Hold Key again to release the freezing display.
Low battery indication indicated “ ” on LCD at 2.3±0.15V or less
Sleep Function Automatically powered off in about 10min after. To disable the sleep function, power the instrument on with the Data Hold Key pressed. (indicated " " for about 2 seconds on LCD)
indicated “ ” on LCD
4. ACA Measurement
DANGER
Never measure current while the test leads are inserted
into the V/Ω and/or COM Terminals.
Press the trigger to open the Current Sensor and clamp the one conductor (Dia. 33mm max.) under test.
Correct Incorrect
NOTE
Measurement accuracy is guaranteed when the measured object is placed at the center (zone A) of the Current Sensor. In zone B, 4% of tolerance should be added to the specified accuracy. In zone C, measured values should be considered as reference values (Accuracy is not guaranteed).
Center (zone A)
C
B
B
5. ACV/DCV Measurement
DANGER
Never make measurement on a circuit in which voltage over 600V exists.
Black test lead Red test lead
ACV
Black(-) Red(+)
DCV
NOTE
If the connection is reversed, the LCD indicates the “ “ mark (DCV measurement).
6.Resistance(Continuity)Measurement
WARNING
Never use the instrument on an energized circuit.
Display “ “ to LCD when push this button.
NOTE Beep less than 50±30Ω.
LCD indicates ”OL” when the test leads are open.
7. Battery Replacement
● Replace the batteries when a Low Battery Voltage
warning " " mark(< 2.3±0.15V) is indicated on the LCD. Otherwise, precise measurement cannot be made. Note that when the battery is completely exhausted, the LCD goes blank without showing " " mark.
● Do not try to replace the batteries if the surface of the
instrument is wet.
● Disconnect the test leads from the object under test and
power off the instrument before opening the Battery Compartment Cover for Battery replacement.
● Do not mix old and new batteries.
● Install batteries in correct polarity as indicated in
the Battery Compartment.
(1) Set the Function Switch to "OFF" position. (2) Unscrew and remove the Battery
Compartment Cover on the bottom of the instrument.
(3) Replace the batteries
observing correct polarity.
Use new two R03/LR03 (AAA)
1.5V batteries.
(4) Install the Battery
Compartment Cover and tighten the screws.
DISTRIBUTOR
Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations.
7-14 92-2180A