KYORITSU 6010A User Manual

MODEL
0A
MULTI-FUNCTIONTESTER
INSTRUCTIONMANUAL
KYORITSUELECTRICALINSTRUMENTSWORKS,LTD.
1Safe Testing................................................................................... 1
2Features.......................................................................................... 3
4Continuity (resistance) tests........................................................... 9
4.1 Instrument layout................................................................... 9
4.2 Resistance of test leads ........................................................ 9
4.3 Continuity testing .................................................................10
5Insulation Tests..............................................................................11
5.1 The nature of insulation resistance.......................................11
5.1.2 Capacitive current.................................................................11
5.1.3 Conduction current............................................................... 12
5.1.4 Surface leakage current....................................................... 12
5.1.5Total leakage current............................................................13
5.2 Damage to voltage-sensitive equipment.............................. 13
5.3 Preparation for measurement.............................................. 14
5.4 Insulation resistance measurement..................................... 14
6Loop Impedance Tests................................................................. 17
6.1Voltage measurement.......................................................... 17
6.2 What is earth fault loop impedance?....................................17
6.3 Automatic over-temperature cut-out.....................................17
6.4 The loop impedance test......................................................17
6.5 Loop impedance at 3 phase equipment............................... 19
7RCD Tests..................................................................................... 21
7.1 Purpose of RCD Test........................................................... 21
7.2 What does the RCD test really do.................................... 21
7.3 RCD testing..........................................................................21
7.4Testing RCDs used to provide supplementary protection.... 22
7.5Testing time delayed RCDs..................................................22
8General..........................................................................................23
9Battery replacement...................................................................... 24
10.Fuse replacement......................................................................... 24
11.Servicing........................................................................................25
12Case, strap and shoulder pad assembly....................................... 26
CONTENTS
―1―
1. SAFETESTING
Electricity is dangerous and can cause injury and death. Always treat it with the greatest of respect and care. If you are not quite sure how to proceed, stop and take advice from a qualified person.
The symbol on the instrument means that the user must refer to the
relevant section of this instruction manual for safe operation of the instrument.
Pay particular attention to all WARNINGS and CAUTIONS in this instruction
manual. WARNING indicates warnings to avoid electric shock and CAUTION indicates cautions to avoid damage to the instrument.
1This instrument must only be used by a competent and trained person and
operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse or non­compliance with the instructions or with the safety procedures.
2It is essential to read and to understand the safety rules contained in the
instructions. They must always be observed when using the instrument.
3This instrument is intended only for single phase operation at 230V AC ±
10% phase to earth or phase to neutral operation, and then only for loop and RCD testing. For use in the continuity testing and insulation testing modes this instrument must be used ONLY on circuits which are de-
energised.
4When conducting tests do not touch any exposed metalwork associated
with the installation. Such metalwork may become live for the duration of the test.
5Never open the instrument case (except for fuse and battery replacement
and in this case disconnect all leads first) because dangerous voltages are present. Only fully trained and competent electrical engineers should open the case. If a fault develops, return the instrument to your distributor for inspection and repair.
6If the overheat symbol appears in the display ( ) disconnect the
instrument from the mains supply and allow to cool down.
7For loop impedance tests to prevent unwanted tripping during loop testing
all residual current devices(RCD's)must be taken out of the circuit and temporarily replaced with a suitably rated MCB unit. The RCD must be replaced after the loop test is completed.
―2―
8If abnormal conditions of any sort are noted (such as a faulty display,
unexpected readings, broken case, cracked test leads, etc) do not use the tester and return it to your distributor for repair.
9For safety reasons only use accessories (test leads, probes, fuses, cases,
etc) designed to be used with this instrument and recommended by KYORITSU. The use of other accessories is prohibited as they are unlikely to have the correct safety features.
10When testing, always be sure to keep your fingers behind the safety
barriers on the test leads.
11During testing it is possible that there may be a momentary degradation of
the reading due to the presence of excessive transients or discharges on the electrical system under test. Should this be observed, the test must be repeated to obtain a correct reading. If in doubt, contact your distributor.
12The sliding shutter on the back of the instrument is a safety device. The
instrument should not be used if it is damaged or impaired in any way, but returned to your distributor for attention.
13Do not operate the function selector whilst the instrument is connected to
a circuit. If, for example, the instrument has just completed a continuity test and an insulation test is to follow, disconnect the test leads from the circuit before moving the selector switch.
14Do not rotate function dial when test button is depressed. If the function
switch is inadvertently moved to a new function when the test button is depressed or in lock-down position the test in progress will be halted. To reset, release test button and press again to restart testing on new function.
15Use a damp cloth and detergent for cleaning the instrument. Do not use
abrasives or solvents.
16Before using the instrument, please insert the batteries rightly in
accordance with the "9. BATTERY REPLACEMENT" of page 24. When not installing batteries, all the functions of the instrument don't work.
―3―
2. FEATURES
FUNCTION SWITCH
TEST BUTTON
RCD RATED TRIPPING CURRENT SWITCH
LIVE CIRCUIT LED
CONNECTOR
WIRING CHECK LED
LCD DISPLAY
Test Lead with IEC Connector
LCD DISPLAY
Test Lead for Continuity and Insulation Testing
Fig.
―4―
Model 6010A Multi-Function tester performs five functions in one instrument.
1Continuity tester 2Insulation resistance tester 3Loop impedance tester 4RCD tester 5Mains voltage warning when operating the loop impedance and RCD
mode.
The tester is designed to Safety Standard IEC 61010-1/EN 61010-1 CAT III (300V).
Dust proof construction in conformance with IP50, IEC529.
The instrument is supplied with:
-
1A KAMP10 lead for loop/RCD testing at socket outlets. 2Model 7025 lead for insulation and continuity testing.
In the insulation resistance testing mode the instrument provides a rated current of 1mA as required in
IEC 61557-2/EN 61557-2 1997.
In the continuity testing mode the instrument provides a short circuit current of 200mA as required in
IEC 61557-4/EN 61557-4 1997.
Continuity and insulation resistance functions have the following features:-
Live circuit warning A colour coded LED warns if the circuit under
test is live.
Auto discharge Electric charges stored in capacitive circuits
are discharged automatically after testing by releasing the test button.
Test current Warning Beeper Warns when the test current exceeds
200mA
(IEC 61557-4)during continuity measurement.
Loop impedance and RCD testing functions have the following features:-
Voltage level In the loop impedance mode, supply voltage
is displayed when the instrument is connected to the supply until the test button is pressed.
Wiring check Three LEDs indicate if the wiring of the circuit
under test is correct.
―5―
Over temperature protection Detects overheating of the internal resistor
(used for loop and RCD tests) and of the current control MOS FET (used for RCD tests) displaying a warning symbol ( ) and automatically halting further measurements.
Phase angle selector The test can be selected from either the
positive (0™) or from the negative (180™) half­cycle of voltage. This will prevent tripping of some polarised RCDs when loop testing and may give a more accurate reading when testing RCDs.
Auto data hold Holds the displayed reading for a time after
the test is complete.
Auto power off Automatically switches the instrument off after
a period of approximately 1 minutes.
V-NE Monitoring Circuit Automatically aborts measurement when the
N-E voltage rises to 50V or greater on RCD ranges.
Optional Accessory OMA DIEC distribution board or lighting circuit
test lead for LOOP/RCD testing.
―6―
Open Circuit Voltage(DC)
Short Circuit
Current
Range Accuracy
Greater than 4V
Greater than
200mA
20/200Ω
Auto-Ranging
Up to 2Ω
Over 2Ω
±(3%rdg+4dgt) ±(3%rdg+3dgt)
3. SPECIFICATION
Measurement Specification
Operating range(as in IEC61557) 20Ωrange0.2Ω〜19.99Ω/200ΩRange20Ω〜199.9Ω
Continuity (to IEC61557-4)
Insulation Resistance (to IEC61557-2)
Loop Impedance (to IEC61557-3)
RCD testing (to IEC61557-6)
Operating range(as in IEC61557) 20MΩ Range0.5MΩ〜19.99MΩ/200MΩ Range20MΩ〜100MΩ
Open Circuit
Voltage (DC)
500V 20%0%
Rated Current
1mA or greater
@ 500kΩ
Range
20/200MΩ
Auto-Ranging
Accuracy
±(3% rdg +3dgt)
Rated Voltage
(AC)
230V10%15%
50Hz
Nominal Test
Current at 0Ω External Loop
25A/10ms
15mA/350ms max.
Range
20Ω
2000Ω
Accuracy
±(3%rdg +8dgt) ±(3%rdg +8dgt)
Function
RCD × 1/2
RCD × 1
FAST
Rated Voltage
(AC)
230V10%15%
50Hz
Trip Current
Settings
10/30/100/300/
500mA
150mA
Trip Current
Duration
2000ms
50ms
Accuracy
Trip Current:
8% 〜−2%
Trip Current:
2% 〜+8%
Trip Time
±(1%rdg+3dgt)
Operating range(as in IEC61557) 20Ω Range:2Ω〜19.99Ω/2000Ω Range100Ω〜1999Ω
Rated Voltage
100250V 50Hz
Measuring Range
100250V 50Hz
Accuracy
3%rdg
Voltage Measurement
―7―
To prevent wrong connection of test leads and to maintain safety, the dedicated terminals used for continuity and insulation tests are automatically covered when using the terminals for loop impedance and RCD tests
Instrument dimensions 175 X 115 X 86mm Instrument weight 780g including batteries.
Reference conditions Specifications are based on the following
conditions except where otherwise stated:-
1Ambient temperature: 23± 5: 2Relative humidity: 45% to 75% 3Position: horizontal 4AC power source: 230V, 50Hz 5DC power source: 12.0 V, ripple content 1%
or less
6. Altitude: Up to 2000m
Battery type Eight R6 or LR6 batteries. Low battery warning "" symbol appears in the display if the battery
voltage drops below 8V.
Maximum numbers of Approx. 700 times for use by continuity range or measurements approx. 1000 times for use by insulation resistance
range.
Operating temperature 0 to +40:, relative humidity 80% or less, no and humidity. condensation. Storage temperature -10 to +50:, relative humidity 75% or less, no and humidity condensation.
Illuminates if there is an alternating voltage of 20V AC or more in the circuit under test before continuity or insulation resistance tests. When DC voltage is detected across the measuring terminal the LED lights up. The P-E and P-N LEDs illuminate when the wiring of the circuit under test is correct. The reverse lamp is lit when P and N are reversed.
Auto data hold In the loop impedance and RCD test functions, the
LCD reading is automatically frozen for 5 seconds after measurement.
Display The liquid crystal display has 3 1/2 digits with a
decimal point and units of measurement (Ω, MΩ, V and ms) relative to selected function. The display
LED indication of live circuit warning
LED indication of correct Polarity
―8―
is updated approximately five times per second.
Overload protection The continuity test circuit is protected by a 0.5 A
600 V fast acting(HRC)ceramic fuse mounted in the battery compartment, where a spare fuse is also stored. The insulation resistance test circuit is protected by a resistor against 600 V AC for 10 seconds.
Mains Voltage Indication On connecting test leads to the circuit under test
on Loop and RCD ranges, the LCD reads V-PE. Sign "V-PE Lo" or "V-PE Hi" is also shown when the voltage is 100V or less, or 260V or greater respectively.
Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION. Caution, risk of electric shock. Cautionrefer to accompanying instruction manual).