KYORITSU 4118A, 4116A, 4120A Instruction Manual

MODEL 4118A
DIGITAL PSC-LOOP TESTER
INSTRUCTION MANUAL
KYORITSU ELECTRICAL INSTRUMENTS
WORKS,LTD.
1. SAFE TESTING .................................................................................. 1
2. PROCEDURE OF REMOVING COVER ........................................... 4
3. FEATURES .......................................................................................... 5
 3.1 Instrument Layout ........................................................................ 5
 3.2 Test Lead ...................................................................................... 6
 3.3 Features ........................................................................................ 7
4. SPECIFICATIONS .............................................................................. 9
5. OPERATING INSTRUCTIONS ......................................................... 10
 5.1 Initial Checks ................................................................................ 10
 5.2 Measurement of the Loop Impedance ...................................... 11
 5.3 Measurement of Prospective Short Circuit Current .............. 12
6. DETAILED EXPLANATION ............................................................ 13
 6.1 Measurement of Fault Loop Impedance and
Prospective Fault Current ........................................................ 13
 6.2 Measurement of OLD-TT System .............................................. 18
 6.3 Measurement of Line Impedance and
Prospective Short Circuit Current .......................................... 19
7. SERVICING ................................................................................... 20
8. CASE AND STRAP BELT ASSEMBLY .......................................... 20
1
1. SAFE TESTING
#
Electricity is dangerous and can cause injury and death. Always treat it with the greatest of respect and care. If you are not quite sure how to proceed, stop and take advice from a qualified person. This instruction manual contains warnings and safety rules which must be observed by the user to ensure safe operation of the instrument and retain it in safe condition. Therefore, read through these operating instructions before using the instrument.
IMPORTANT:
1. This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse or non-compliance with the instructions or with the safety procedures.
2. It is essential to read and to understand the safety ru
les contained
in the instructions or with the safety procedures.
3. The symbol
#
indicated on the instrument means that the user
must refer to the related sections in the manual for safe operation of the instrument. Be sure to carefully read instructions following each
symbol # in this manual.
#
DANGER
is reserved for conditions and actions that are likely to
cause serious or fatal injury.
#
WARNING
is reserved for conditions and actions that can cause
serious or fatal injury.
#
CAUTION
is reserved for conditions and actions that can cause a
minor injury or instrument damage.
2
  #
DANGER
●  The instrument is to be used only in its intended applications or conditions. Otherwise, safety functions equipped with the instrument will not work, and instrument damage or serious personal injury may occur. Verify proper operation on a known source before use or taking action as a result of the indication of the instrument.
●   This instrument is intended only for use in single phase operation at 230V +10% -15% AC phase to earth or for use in OLD-TT system phase to neutral.
●  When conducting tests do not touch any exposed metalwork associated with the installation. Such metalwork may become live for the duration of the test.
●  When testing, always be sure to keep your fingers behind the safety barriers on the test leads.
●  Be sure to remove the test lead from the mains power supply promptly after measurement. Do not leave the instrument connected to the mains power supply for a long time.
  #
WARNING
●  The instrument is to be used only in its intended applications. Understand and follow all the safety instructions contained in the manual. Failure to follow the instructions may cause injury,
instrument damage and/or damage to equipment under test. Kyoritsu is by no means liable for any damage resulting from the instrument in contradiction to this cautionary note.
●  
Never open the instrument case
- there are dangerous voltages present. If a fault develops, return the instrument to your distributor for inspection and repair.
●   If the overheat symbol appears in the display (
) disconnect the
instrument from the mains supply and allow to cool down.
●   If abnormal conditions of any sort are noted (such as a faulty display, unexpected readings, broken case, cracked test leads, etc) do not use the tester and return it to your distributor for repair.
●   Never attempt to use the instrument if the instrument or your
hand
is wet.
3
  #
CAUTION
●   For those testers without the D-LOK circuitry (models 4118A) all
RCD's (RCCB, ELCB) in the circuit must be by-passed for the duration of the test (except on loop-2000Ω range).
  Do not operate the RCD Test Button with the RCD by-passed.
●   During testing it is possible that there may be a momentary
degradation of the reading due to the presence of excessive transients or discharges on the electrical system under test. Should this be observed, the test must be repeated to obtain a correct reading. If in doubt, contact your distributor.
●   Use a damp cloth and detergent for cleaning the instrument. Do
not use abrasives or solvents.
Measurement categories(Over-voltage categories)
To ensure safe operation of measuring instruments, IEC 61010 establishes safety standards for various electrical environments, categorized as O to CAT IV, and called measurement categories. Higher-numbered categories correspond to electrical environments with greater momentary energy, so a measuring instrument designed for CAT III environments can endure greater momentary energy than one designed for CAT.II. O : Circuits which are not directly connected to the mains power supply. CAT II : Electrical circuits of equipment connected to an AC electrical outlet
by a power cord.
CAT III : Primary electrical circuits of the equipment connected directly to the
distribution panel, and feeders from the distribution panel to outlets.
CAT IV : The circuit from the service drop to the service entrance, and to the
power meter and primary overcurrent protection device (distribution panel).
O: Device which is not directly connected to the mains power supply
4
2. PROCEDURE OF REMOVING COVER
Model 4118A have a dedicated cover to protect against an impact from the outside and prevent the operation part, the LCD and the connector socket from becoming dirty. The cover can be detached and put on the back side of the main body during measurement.
Fig. 2
2.1 Method of removing the cover
2.2 Method of housing the cover
Fig. 1
5
3. FEATURES
3.1 Instrument Layout
1............ LCD display
2............ Wiring check LEDs
3............ Test button
4............ Range switch
5............ Connector
LCD
Connector
Fig. 3
  #
DANGER
●   Use original test lead only.
●   Max. allowed voltage between mains test terminals and ground is 300V.
●   This instrument is intended only for use in single phase operation at 230V +10% -15% AC phase to earth or for use in OLD-TT system phase to neutral.
Wiring correct
(Green LED's)
Reversed L/N terminals
(Red LED)
6
3.2 Test Lead
The instrument is supplied with Model 7125 lead at socket outlets and Model 7121B distribution board lead.
(1) Model 7125
Mains lead mentioned in this instruction manual is Model 7125(EU) European SCHUKO plug, however, there are some other types for the areas, and the shipping is made along with the suitable plug-shaped cable according to the areas of the globe as follows; Model 7123 (AU) for Australian plug Model 7124 (UK) for British plug (13A) Model 7126 (SA) for South African plug
(2) Model 7121B
Black-Neutral
Red-Phase
Green-Earth
Fig.4
The loop impedance of this instrument is adjusted to show the true value by using the attached mains lead (either of Models 7123 through 7126) prior to the shipment. However, when the attached test lead for distribution board Model 7121B is used, the total internal resistance shows approx. 0.1Ω bigger than those of other mains lead due to the internal fuse resistance. Therefore, when measurement is taken by using the Model 7121B, the measured value between PHASE-EARTH shows approx. 0.1Ω bigger than the true value. PHASE make sure that 0.1Ω subtracted from the measured value leaves the true value in case of using the test lead of this distribution board. As for the PSC range, use the following equation and divide supply voltage by loop impedance, therefore, the measured value shows smaller than the true value contrary to the case of the case of loop impedance range.
● PSC(A) = Supply Voltage(V) / Loop Impedance(Ω)