KYORITSU 3123A User Manual

INSTRUCTION MANUAL
KEW3121A, 3122A KEW3123A
HIGH VOLTAGE INSULATION TESTER
KEW 3121A, 3122A, 3123A
CONTENTS
Page
1Features …………………………………………………………1
2Specifications ……………………………………………2 3
3Instrument Layout ………………………………………………4
4Operating Instructions …………………………………………5
4-1Mechanical Zero Adjustment ……………………………5
4-2Battery Check ……………………………………………5
4-3Insulation Resistance Measurement ……………………6
4-4Continuous Measurement ………………………………6
4-5Use of Guard Terminal  …………………………………7
6.Accessories and options ………………………………………8
6-1.Metal part for Line Probe, and replacement ……………8
6-2.How to use the adaptor for recorder …………………8
7Cleaning Meter Cover  …………………………………………9
1
1. Features
●  Battery powered, t he instruments test insulation up to 100000MΩ at 2500V for KEW 3121A, 200000MΩ at 5000V for KEW 3122A and 200GΩ at 5000V and 400GΩ at 10000V for KEW 3123A.
●  Suited for heavy duty electrical maintenance and servicing of industrial installations, cables, transformers, generators and switchgear where high voltage insulation tests are required.
●  Dual scale s for l o w an automatically. Colour coded scales for easy reading plus LED's that illuminate in matching colour.
●  Drip proof construction. The case is sealed with rubber gaskets to protect internal circuit against rain.
●  Hard carrying case furnished as standard accessory. Houses
both instrument and test leads in compact form. Made of plastic, it is highly water resistant.
●  Designe current consumption is 90mA eight pieces of 1.5V SUM-3or equivalent ) permit about 6 hours of continuous operation even when the instrument is used on maximum load or twice longer on minimum load.
●  Rated output voltage is maintained down to 100MΩ for KEW 3121A, 200MΩ for KEW 3122A and 0.2GΩ/0.4GΩ for KEW 3123A. This permits accurate measurements of resistance.
d for low power consumption. Since the maximum
d high r a n g e s wh i c h ch a n g e
low insulation
2
2. Specifications
DC Test Voltage 2500V 5000 V 5000V 10000V
Measuring Ranges
Accuracy
Operating Temperature & Humidity
Storage Temperature & Humidity
Insulation Resistance 1000MΩ max./ 1000V between electrical circuit
Withstand Voltage 5000V AC for one minute between electrical circuit & housing case Dimensions 200L×140W×80Dmm Weight Approx. 1kgincluding batteries
Power Source 8 pcs of R6P (AA) battery or equivalent
Accessories
Insulation Resistance
Output Voltage
KEW 3121A KEW 3122A KEW 3123A
02000MΩ/
1000100000MΩ
automatic change
±5% of reading
10050000MΩ)
±10% of reading
or 0.5% of scale length
ranges other than
listed above
23 ±5
at
±10% of reading
10050000
±20% of reading
or 1.0% of scale length
ranges other than
listed above
at 10℃〜+40
2500V ±5%
10050000MΩ)
Hard Carrying Case:M-9158 Test Leads (Line Probe:M-7165A, Cord:M-7224A, Guard Cord:M-7225A)
MΩ)
05000 MΩ/
2000 200000MΩ
(automatic change)
±5% of reading (200〜 100000MΩ) ±10% of reading
or 0.5% of scale length
( ranges other than
listed above
at 23 ±5 ±10% of reading
(200〜 100000MΩ) ±20% of reading
or 1.0% of scale length
( ranges other than
listed above
at 10 40
5000V ±5% (200〜 100000MΩ)
10 40 at 85% max. relative humidity
20 60 at 90% max. relative humidity
Earth
3
05GΩ/2200GΩ
(automatic change)
±5% of reading
0.2100GΩ)
±10% of reading
or 0.5% of scale length
ranges other than
listed above
at 23 ±5
±10% of reading
0.2100GΩ)
±20% of reading
or 1.0% of scale length
ranges other than
listed above
at 10℃〜+40
5000V ±5%
0.2~100GΩ)
& housing case
Hard Carrying Case:M-9158 Batteries, Test Leads (Line Probe:M-7165 A, Earth Cord:M-7224A, Guard Cord:M­7225A) Pickel type prod:M-8019
Optional adaptor model 8324 is available for connection to recorder
010GΩ/4400GΩ
(automatic change)
±5% of reading
0.4200GΩ)
±10% of reading
or 0.5% of scale length
ranges other than
listed above
at 23 ±5
±10% of reading
0.4200GΩ)
±20% of reading
or 1.0% of
scale length
ranges other than
listed above
at 10℃〜+40
10000V ±5%
0.4~200GΩ)
4
3. Instrument Layout
Line Terminal Guard Terminal Earth Terminal LE D's fo r H igh & Lo w
Range Indication
Press to Test Button Function Switch Me ter Move men t Zero
Adjust
Bat tery Compa r t ment
Cover
Line Probe (Red) Earth Cord (Black) Guard Cord (Green)
Fig.1
5
4. Operating Instructions
CAUTION: BE CAREFUL ABOUT HIGH VOLTAGE PRESENT ACROSS LINE AND EARTH TERMINALS OF INSTRUMENT WHEN PRESS TO TEST BUTTON IS OPERATED. MAKE SURE TO EARTH CIRCUIT UNDER TEST. ALWAYS CONNECT EARTH TERMINAL OF INSTRUMENT TO EARTH. THE BUZZER WILL KEEP SOUNDING DURING INSULATION RESISTANCE MEASUREMENT.
4-1. Mechanical Zero Adjustment
With the function switch set at OFF position, adjust the meter pointer to zero adjust screw located at the center of the front panel.
4-2. Battery Check
With the function switch set at BATT. CHECK position, operate the press to test button. The batteries are good when the pointer stays in BATT. GOOD area or to the right of this area. If not, replace them.
Note:  Refrain from holding down or locking the press to
∞ mark on the scale. Use a screwdriver to turn the
test butt co nsum ption l arg er than in sul atio n resi stance measurement while the batteries are still new.
on during this test as it will result in current
6
4-3. Insulation Resistance Measurement
With the function switch set at OFF position, always connect the circuit under test to earth. Attach the test lead to the earth terminal of the instrument and connect to the earthed side of the circuit under test. With the function switch set at 2500V and 5000V for KEW 3121A and 3122A or 5000V or 10000V for KEW 3123A, place the line probe in contact with the c
ircuit under test and operate the press to test button. When the green LED illuminates, read insulation resistance on the outer scale (for high range). Use the inner scale where the red LED illuminates. For insulation testing at 5000V and 10000V, read the black and red scales respectively (for KEW 3123A). After a test, release the press to test button and wait for several seconds without disconnec
ting the line probe from the circuit tested. This is intended to discharge the charge stored in the circuit tested.
4-4. Continuous Measurement
Make sure that the circuit under test is earthed and that the test lead attached to the earth terminal of the instrument is connected to the earthed side of the circuit under test. Push the press to test button and turn clockwise to lock for continuous measu
rement. When making this measurement, good care must be taken against the high voltage continuously present across the line and earth terminals of the instrument.
Note:  Make certain that the circuit under test does not
include components which will be damaged by the high voltage applied.
7
4-5. Use of Guard Terminal
When measuring the insulation resistance of a cable, Ieakage current flowing on the surface of cable jacket and the current flowing inside the insulator are mixed and may cause error in insulation resistance value. In order to prevent such error, wind a conductive wire around the point where leakage current flows. Then connect it to the Guard terminal as shown in below Fig
.2. This is to move out the surface leakage resistance of the cable insulation to measure only the volume resistance of insulator. Make sure to use the Guard cord supplied with this instrument to connect the instrument to Guard terminal.
Fig.2
8
5. Batttery Replacement
Remove the battery compartment cover by loosening the screw located on the back of the housing case. Replace the whole battery pack. Alkaline batteries are recommended where the instrument is used at a temperature below the freezing point. The ordinary manganese batteries will deteriorate below the freezing point.
6. Accessories and options
6-1. Metal part for Line Probe, and replacement
1Tip metal parts
MODEL8252: Standard Prod (straight type, with molded parts) MODEL8254: Straight Type Prod MODEL8019: Pickel Type Prod (accessory) To be used to hook the instrument.
  Note:Option KEW3121A, KEW3122A
2How to replace it
Turn the Line probe counterclockwise to remove the attached tip
tip metal you want to use to the hexagon socket and turn it to clockwise together with the tip of probe, and tight up screws.
metal. Put the
6-2. How to use the adaptor for recorder
MODEL8324 is the adaptor for recorder for output current measurement. Connect
it as shown in the below Fig.3.
Output is DC10mV when current of 1μA is flowing
9
To recorder
To shield or Earth
Fig.3
7. Cleaning Meter Cover
This earth tester is managed by our company's quality standard and is delivered in the best condition after passed the inspection. But in the dry time of winter static electricity sometimes builds up on the meter cover due to the characteristic of plastic. When the pointer deflects by touching the surface of this tester or zero adjustment can not be made, do not try to make m When static electricity builds up on the meter cover and affects the meter reading, use a cloth dampened with off-the-shelf anti-statics agent or detergent to wipe the meter cover surface.
easurement.
DISTRIBUTOR
Kyoritsu reserves the rights to change specific ations o r design s described in this manual without notice and without obligations.
2-11 92-1919B
Loading...