Refrigeration System Specications
Kool Star Refrigeration Nomenclature
MODEL NUMBER EXPLANATION (CONVENTIONAL = ACCESSIBLE HERMETIC )
BC = Built-up Remote Conventional Condensing Unit MH = Hermetic Condensing Unit BH = Built-up Remote Hermetic Condensing Unit MS = Scroll Condensing Unit BS = Built-up Remote Scroll Condensing Unit MD = Discus Condensing Unit MC = Semi-hermetic Condensing Unit
H = +25° through +70° F. Room Temperature L = 0° F. through -20° F. Room Temperature
HORSEPOWER RATING EXPLANATION (NOTE: APPLIES TO B-SERIES ONLY)
028 = 3 H.P. 050 = 5 H.P. 100 = 10 H.P. 220 = 22 H.P. 350 = 35 H.P.
030 = 3 H.P. 060 = 6 H.P. 120 = 12 H.P. 250 = 25 H.P. 400 = 40 H.P.
035 = 31/2 H.P. 075 = 71/2 H.P. 150 = 15 H.P. 270 = 27 H.P.
040 = 4 H.P. 090 = 9 H.P. 200 = 20 H.P. 300 = 30 H.P.
BTU/HR RATING EXPLANATION (NOTE: APPLIES TO M-SERIES ONLY)
Room temp H = Nominal BTUH capacity @ 30° suction, 90° ambient (1000 multiplier) Room temp L = Nominal BTUH capacity @-20° suction, 90° ambient (1000 multiplier)
EQUIPMENT VARIATION EXPLANATION
0 = Standard W = Water Cooled A = Plasma Units X = Special Applications D = Demand Cooling Y = Special Applications L = Large Condenser
VOLTAGE EXPLANATION
A = 115/60/1 F = 200-220/50/3 B = 230/60/1 or 208-230/60/1 (As Applicable) G = 380-420/50/3 C = 208-230/60/3 H = 208/60/1 D = 460/60/1 J = 380/50/1 E = 460/60/3 K = 200-220/50/1 or 220/50/1
OPTIONS EXPLANATION (NOTE: APPLIES TO B-SERIES ONLY)
C = Coated Condenser Coil D = Coated Condenser Coil, Heated And Insulated Receiver L = Large Condenser
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
Contents
Evaporator Coils For Remote Systems ...............................................................................................................2
B-Series Built-Up Condensing Units ..................................................................................................................3
B-Series Medium Temperature Specications ....................................................................................................4
B-Series Low Temperature Specications ...........................................................................................................6
B-Series Components .........................................................................................................................................8
M-Series High Ambient Remote Condensing Units ..........................................................................................9
M-Series Medium Temperature Specications .................................................................................................10
M-Series Low Temperature Specications ........................................................................................................14
M-Series Components ......................................................................................................................................16
MRS Series Modular Multi-Compressor Systems .............................................................................................17
DRS Series Dual Compressor Systems ..............................................................................................................18
Condensing Unit Base Specications ..............................................................................................................21
PRS-2 Packaged Refrigeration System Specications .......................................................................................24
As we are continuously improving and enhancing our products to benet our customers, we reserve the right to change pricing and specications without notice.
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
1
Evaporator Coils For Remote Systems
-series evaporator coils are ready to mount
E
in position and are available in either air (off cycle) or electric defrost. Each is also furnished standard with a properly sized expansion valve and
room thermostat. Electric defrost models feature defrost termination-fan delay controls and drain line heaters.
STANDARD EXPANSION VALVE
STANDARD TEMPERATURE CONTROL/ROOM THERMOSTAT
2
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
B-Series Built-Up Condensing Units
ool Star offers one of the most complete
K
condensing units in the built-up B-Series. These units are completely factory assembled on a galvanized steel base. Accessories are pre-wired and mounted, resulting in minimal eld installa­tion time. All that is required is electrical hookup,
LIQUID LINE VIBRATION ABSORBER (SEMI-HERMETIC ONLY)
ADJUSTABLE DUAL PRESSURE CONTROL
piping, connection, evacuation, leak testing and charging to become operational.
B-Series systems are available in hermetic, semi­hermetic and compliant scroll compressor models and range from 3 H.P. to 40 H.P.
SNAP-DOWN HINGED WEATHER HOOD
SUCTION LINE FILTER
HEAD PRESSURE CONTROL (FLOODING VALVE)
SUCTION LINE VIBRATION ABSORBER (SEMI-HERMETIC ONLY)
HEAVY-DUTY CHANNEL LEG BASE WITH LOCKABLE HOOD
PRE-WIRED ELECTRICAL CONTROL PANEL WITH TIMER AND CIRCUIT BREAKER OR FUSE BLOCK
CRANKCASE HEATER
LIQUID LINE FILTER/DRIER
SIGHT GLASS
LIQUID & SUCTION LINE KIT WITH SERVICE VALVE
Above components pictured are typical with the model BCLZ0300C condensing unit. Components may vary depending on horsepower and application. Consult factory for verication of standard and optional supplied com­ponents.
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
3
B-Series Medium Temperature Specications
R-22 SEMI-HERMETIC CONDENSING UNITS
BTUH @ 25°F
COND. UNIT
MODEL* H.P.
COMPRESSOR
MODEL
SUCTION TEMP.
90°F AMBIENT
BCHX0300B 3 ERF2-0310-CAB 26,000 5/8 1
BCHX0300C 3 ERF1-0310-TAC 26,000 5/8 1
BCHX0500C 5 2DC3-050E-TFC 39,576 5/8 1
1
BCHX0750C 7
/22DA3-075E-TFC 70,260 5/8 13/
BCHX1000C 10 3DB3-100E-TFC 102,088 7/8 1
BCHX1500C 15 3DS3-150E-TFC 128,702 7/8 1
BCHX2500C 25 4DH3-2500-TSK 196,176 1
BCHX3000C 30 4DJ3-3000-TSK 232,187 1
BCHX3500C 35 6DH3-3500-TSK 275,792 1
BCHX4000C 40 6DJ3-4000-TSN 336,116 1
UNIT CONNECTION SIZES
LIQUID SUCTION
1
/
8
1
/
8
3
/
8
8
3
/
8
5
/
3
/
8
3
/
8
5
/
8
5
/
8
21/
21/
21/
21/
8
8
8
8
8
BASE
RECEIVER PUMP
SIZE
DOWN CAP. @ 90%
SHIP WT.
(LB/KG) MCA
††
MOP††RLA††LRA
C 47.6 505/230 25 40 17.0 86.0
C 47.6 505/230 19 30 12.4 82.0
C 47.6 600/273 34 50 22.3 120.0
E 92.8 870/395 47 70 32.0 169.0
F 133.0 990/450 64 100 43.6 215.0
F 133.0 1010/459 84 125 59.6 275.0
P 133.0 1730/786 118 175 82.2 428.0
R 133.0 1740/791 140 225 94.0 470.0
R 180.0 1810/823 156 250 107.0 565.0
R 180.0 1940/882 200 300 142.0 594.0
††
R-22 HERMETIC CONDENSING UNITS
BTUH @ 25°F
COND. UNIT
MODEL* H.P.
COMPRESSOR
MODEL
SUCTION TEMP.
90°F AMBIENT
BHHX0300B 3 CR41KQ-PFV 26,966 1/2 7/8 C 47.6 405/184 28 45 19.4 109.6
BHHX0300C 3 CR41KQ-TF5 26,966 1/2 7/8 C 47.6 405/184 20 30 13.1 80.0
BHHX0400B 4 CRM3-0400-PFV 34,661 5/8 7/8 C 47.6 510/232 40 60 29.0 140.0
BHHX0400C 4 CRM3-0400-TF5 34,661 5/8 7/8 C 47.6 510/232 26 40 18.0 107.0
BHHX0500B 5 CRN5-0500-PFV 42,307 5/8 7/8 C 47.6 520/236 49 80 34.3 142.0
BHHX0500C 5 CRN5-0500-TF5 42,307 5/8 7/8 C 47.6 520/236 32 50 21.4 130.0
NOTES:
• Consult factory for R-134a and R-404A applications.
• Semi-hermetic medium temp units are shipped with P.O.E. oil, which is compatible with optional refrigerants (contact factory for details).
*VOLTAGE KEY: “B” sufx = 208-230 or 230 volt, 60 cycle, one phase “C” sufx = 200-230 or 208-230 volt, 60 cycle, three phase
See pp. 56-58 for unit base drawings.
††
Electrical ratings for condensing unit only. See National Electrical Code if units are combined on a single circuit.
UNIT CONNECTION SIZES
LIQUID SUCTION
BASE
RECEIVER PUMP
SIZE
DOWN CAP. @ 90%
SHIP WT.
(LB/KG) MCA
††
MOP††RLA††LRA
††
4
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
B-Series Medium Temperature Specications
MATCHING EVAPORATOR COILS FOR R-22 SEMI-HERMETIC CONDENSING UNITS
EVAPORATOR MODEL*
E1HX0300A IFA36-305A 36,600 3 76 19 19 320/145 6.0
E1HX0300B IFA36-305D 36,600 3 76 19 19 320/145 2.7
E1HX0450B IFA36-490D 58,800 3 106 20 25 415/189 9.6
E1HX1100C PAM4-1100E 132,000 4 137 30 51 830/377 11.1
E1HX1100C PAM4-1100E 132,000 4 137 30 51 830/377 11.1
E1HX1400C PAM4-1320E 158,400 4 137 30 51 885/402 11.1
E1HX2200C PAM6-2480E 297,600 6 197 30 51 1365/620 14.6
E1HX1100C (2)
E1HX1400C (2)
E1HX1610C (2)
UNIT PART NO.
††
PAM4-1100E 264,000 (total) 4 137 30 51 830/377 11.1
††
PAM4-1320E 316,800 (total) 4 137 30 51 885/402 11.1
††
PAM4-1656E 397,440 (total) 4 137 30 51 910/414 11.1
BTUH @
SUCTION TEMP.
25°F**
NO.
FANS
DIMENSIONS (INCHES)
MATCHING EVAPORATOR COILS FOR R-22 HERMETIC CONDENSING UNITS
EVAPORATOR MODEL*
E1HX0300A IFA36-305A 36,600 3 76 19 19 320/145 6.0
E1HX0300B IFA36-305D 36,600 3 76 19 19 320/145 2.7
E1HX0450A IFA36-490A 58,800 3 106 20 25 415/189 21.3
E1HX0450A IFA36-490A 58,800 3 106 20 25 415/189 21.3
E1HX0450A IFA36-490A 58,800 3 106 20 25 415/189 21.3
E1HX0450B IFA36-490D 58,800 3 106 20 25 415/189 9.6
*VOLTAGE KEY:
“A” sufx = 115 volt, 60 cycle, one phase “B” sufx = 208-230 volt, 60 cycle, one phase “C” sufx = 208-230 volt, 60 cycle, three phase
**Based on 12° T.D.
No. of fans, dimensions and weights are per evaporator.
††
Evaporator models followed by a number in parentheses indicates that multiple coils are necessary.
UNIT PART NO.
BTUH @
SUCTION TEMP.
25°F**
NO.
FANS
DIMENSIONS (INCHES)
SHIP WT. (LB/KG)
FAN
AMPS
DEFROST
AMPSL W H
NOT APPLICABLE
SHIP WT.
(LB/KG)
FAN
AMPS
DEFROST
AMPSL W H
N/A
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
5
B-Series Low Temperature Specications
R-404A SEMI-HERMETIC CONDENSING UNITS
BTUH @ -20°F
COND. UNIT
MODEL* H.P.
COMPRESSOR
MODEL
SUCTION TEMP.
90°F AMBIENT
BCLZ0280B 3 LALB-032E-CAB 15,529 5/8 1
BCLZ0280C 3 LALA-032E-TAC 15,529 5/8 1
BCLZ0300C 3 2DF3-030E-TFC 18,469 5/8 1
BCLZ0400C 4 2DL3-040E-TFC 21,531 5/8 1
BCLZ0600C 6 2DB3-060E-TFC 26,466 5/8 1
1
BCLZ0750C 7
/23DB3-075E-TFC 37,322 7/8 13/
BCLZ1000C 10 3DS3-100E-TFC 50,630 7/8 1
BCLZ1500C 15 4DL3-150E-TSK 70,782 7/8 1
BCLZ2200C 22 4DT3-220E-TSK 82,105 7/8 2
BCLZ2700C 27 6DL3-270E-TSK 108,351 1
BCLZ3000C 30 6DT3-300E-TSK 119,293 1
UNIT CONNECTION SIZES
LIQUID SUCTION
1
/
8
1
/
8
3
/
8
3
/
8
3
/
8
8
3
/
8
5
/
8
1
/
3
/
8
3
/
8
21/
21/
8
8
8
BASE
RECEIVER PUMP
SIZE
DOWN CAP. @ 90%
SHIP WT.
(LB/KG) MCA
††
MOP††RLA††LRA
C 41.5 505/230 32 40 15.0 105.0
C 41.5 505/230 32 35 12.6 112.0
C 41.5 505/230 32 45 16.8 102.0
C 41.5 530/230 44 60 26.3 161.0
C 41.5 560/255 46 70 28.2 161.0
D 53.4 730/332 55 80 31.5 161.0
E 80.8 880/400 71 100 42.0 215.0
F 116.1 990/450 90 125 52.6 278.0
F 116.1 1405/639 107 150 66.0 374.0
P 116.1 1730/786 136 200 80.8 450.0
P 116.1 1800/818 154 225 95.6 470.0
††
NOTE: model BCLZ0300C and up may be provided with optional R-22 demand cooling.
R-404A SCROLL CONDENSING UNITS
BTUH @ -20°F
COND. UNIT
MODEL* H.P.
COMPRESSOR
MODEL
SUCTION TEMP.
90°F AMBIENT
BSLZ0300B 3 ZF09K4E-PFV 10,734 1/2 7/8 C 25.6 405/184 29 40 16.4 88.0
BSLZ0300C 3 ZF09K4E-TF5 10,734 1/2 7/8 C 25.6 405/184 23 30 11.1 77.0
1
BSLZ0350B 3
BSLZ0350C 3
/2ZF11K4E-PFV 12,873 1/2 7/8 C 25.6 450/205 35 50 20.7 109.0
1
/2ZF11K4E-TF5 12,873 1/2 7/8 C 25.6 450/205 26 35 13.6 88.0
BSLZ0400B 4 ZF13K4E-PFV 15,047 1/2 7/8 C 41.5 510/232 42 60 26.8 129.0
BSLZ0400C 4 ZF13K4E-TF5 15,047 1/2 7/8 C 41.5 510/232 32 40 15.0 99.0
BSLZ0500B 5 ZF15K4E-PFV 18,124 1/2 7/8 C 41.5 520/236 54 80 31.8 169.0
BSLZ0500C 5 ZF15K4E-TF5 18,124 1/2 7/8 C 41.5 520/236 39 50 21.4 123.0
BSLZ0600C 6 ZF18K4E-TF5 21,651 1/2 7/8 C 41.5 550/250 41 60 23.9 156.0
NOTES:
• Semi-hermetic medium temp units are shipped with P.O.E. oil, which is compatible with opitional refrigerants (contact factory for details).
• Hermetic low temp units are shipped with P.O.E. oil, which is compatible with optional refrigerants (contact factory for details).
*VOLTAGE KEY:
“B” sufx = 208-230 or 230 volt, 60 cycle, one phase “C” sufx = 200-230 or 208-230 volt, 60 cycle, three phase
See pp. 56-58 for unit base drawings.
††
Electrical ratings for condensing unit only. See National Electrical Code if units are combined on a single circuit.
UNIT CONNECTION SIZES
LIQUID SUCTION
BASE
RECEIVER PUMP
SIZE
DOWN CAP. @ 90%
SHIP WT.
(LB/KG) MCA
††
MOP††RLA††LRA
††
6
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.
B-Series Low Temperature Specications
MATCHING EVAPORATOR COILS FOR R-404A SEMI-HERMETIC CONDENSING UNITS
BTUH @ EVAPORATOR MODEL*
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0240C SE66-245BE 24,500 6 118 15 16 250/114 6.0 22.6
E1LZ0260C IFE26-270E 27,000 2 76 20 25 320/145 6.4 17.0
E1LZ0390C IFE36-385E 38,500 3 106 20 25 450/205 9.6 24.5
E1LZ0520C IFE36-520E 52,000 3 106 20 25 535/243 9.6 24.5
E1LZ0722C PEL4-722E 67,500 4 137 30 33 675/307 11.1 47.8
E1LZ0810C PEL4-817E 76,400 4 137 30 33 726/330 11.1 47.8
E1LZ1020C PEL4-1100E 102,900 4 137 30 51 885/402 11.6 71.3
E1LZ1200C PEL4-1260E 117,800 4 137 30 51 895/407 11.1 71.3
UNIT PART NO.
SUCTION TEMP.
-20°F**
NO.
FANS
DIMENSIONS (INCHES)
SHIP WT.
(LB/KG)
FAN
AMPS
DEFROST
AMPSL W H
MATCHING EVAPORATOR COILS FOR R-404A SCROLL CONDENSING UNITS
BTUH @ EVAPORATOR MODEL*
E1LZ0090B SE26-92BD 9200 2 46 15 16 74/34 2.0 8.7
E1LZ0090B SE26-92BD 9200 2 46 15 16 74/34 2.0 8.7
E1LZ0120B SE36-120BD 12,000 3 64 15 16 105/48 3.0 13.0
E1LZ0120B SE36-120BD 12,000 3 64 15 16 105/48 3.0 13.0
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0160B SE46-164BD 16,000 4 82 15 16 140/64 4.0 17.4
E1LZ0240C SE66-245BE 24,500 6 118 15 16 250/114 6.0 22.6
*VOLTAGE KEY: “A” sufx = 115 volt, 60 cycle, one phase “B” sufx = 208-230 volt, 60 cycle, one phase
**Based on 10° T.D.
UNIT PART NO.
SUCTION TEMP.
-20°F**
NO.
FANS
DIMENSIONS (INCHES)
SHIP WT.
(LB/KG)
FAN
AMPS
DEFROST
AMPSL W H
888-478-8600 • FAX: 310-513-8156
Specications subject to change without notice.