Kool Star Indoor Ice Merchandiser Installation Manual

ICE MERCHANDISER
Installation, Operation and
Maintenance Instructions
1 1/08 N138647
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested in the manufacturing facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
INSTALLATION
GENERAL
After the unit crate and crate base have been removed, locate the casters or legs found inside the cabinet. Attach the casters or legs to the unit base (if not already installed) by screwing them into the same threaded fittings that were used to secure the crate base to the cabinet. Insure that the legs or casters are screwed completely into the base. The cabinet should also be levelled when it is placed in its permanent location.
If the doors are out of alignment on the cabinet, the doors can be adjusted. This can be accomplished by opening the door(s) and loosening the screws that hold both the top and bottom hinges to the cabinet. After adjusting the door so that it is aligned correctly, tighten the screws to securely hold the hinges in place.
Ice Merchandisers are designed to operate at 20°F in a controlled environment. The operating ambient temperature should not exceed 75°F (24°C) with relative humidity (RH) of 55% or less. At temperatures higher than 75°F with the RH greater than 55% could adversely affect the cabinet’s performance and diminish capacity.
The Ice Merchandiser should not be placed in a position where it is directly exposed to the rays of the sun or near a source of radiant heat or heated air flow.
ELECTRICAL
Check the proposed outlet to be used to insure that the voltage, phase and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.
NEVER use an extension cord to wire any unit. Refer to the serial tag for all
GENERAL OPERATION
The Ice Merchandiser employs a unit cooler evaporator located inside the cabinet as the heat removing source. Through the refrigeration process, heat is captured in the evaporator, transferred to the condensing unit at the bottom of the cabinet, and expelled to the surrounding outside air. It is extremely important to allow a four (4) inch clearance on the top, rear, and sides of the unit for the refrigeration process to function properly.
2 1/08 N138647
The Ice Merchandiser utilizes a programmable controller to control the temperature and defrost settings. The controller, which is located on the facade of the unit, is factory set. Please see the default settings sheet and separate instructions that are included on the operation of this controller.
After shutting the door on freezer models, a short amount of time must be allowed before the door can be reopened. This is due to the tight seal maintained between the door and the cabinet. Waiting a few moments for the pressure to equalize permits the door to be opened easily.
A positive defrost is required to remove frost from the coil in freezer models. This is accomplished by energizing heaters during the defrost cycle that are positioned on the coil surface. The programmable controller is factory set to allow four defrosts per day.
As the preset defrost time is reached, the controller automatically terminates the refrigeration process by turning off the condensing unit and unit cooler fan motors, and energizes the defrost heaters. As the coil temperature increases, the frost begins to melt producing water which runs down the coil to the unit cooler drain pan and exits through the drain tube to the vaporizer. After all the frost has been removed and the coil temperature reaches approximately 50°F [10ºC], the defrost is terminated through the action of the defrost termination control located on the unit cooler, and the refrigeration process resumes.
GENERAL MAINTENANCE
PERIODIC CLEANING WARNING! To avoid electrical shock, disconnect all electrical power to the merchandiser prior to cleaning
The exterior of the Ice Merchandiser should be wiped with a damp cloth daily. A commercial grade glass cleaner may be used. Do not use a brush, scouring pad or any
other abrasive material on the painted surfaces.
The interior (and exterior if desired) may be cleaned with a soft cloth and a mild germicidal detergent. Do not use any ammonia-based products as this may damage electrical components within the unit. Do not use a brush, scouring pad or any other abrasive material on the painted surfaces. Care should be taken not to wet any electrical components, connections or controls.
Monthly cleaning of the condenser will aid the heat transfer characteristics of the refrigeration system and increase its efficiency. To accomplish this, remove the bottom facade from the cabinet by removing 2 screws located at the bottom of the facade on each side. Slide facade any dirt particles that are attached to the fins. Use a vacuum cleaner to remove the loosened particles and other debris. If dirt is noticeable on the fan blades, simply wipe the blades with a damp cloth. Failure to keep the condenser coil clean and clear of obstructions could result in temperature loss and damage to the compressor.
All moving parts have been permanently lubricated and will generally require no maintenance.
down off key slots and pull out to remove. Use a bristle brush to loosen
3 1/08 N138647
MAINTENANCE SERVICE AND ANALYSIS GUIDE
MALFUNCTION POSSIBLE CAUSE SOLUTION
Compressor will not start - 1. Service cord unplugged 1. Plug in service cord no hum 2. Fuse blown or removed 2. Replace fus e
3. Overload tripped 3. Determine reasons and correct
4. Control stuck open 4. Repair or replace
5. Wiring incorrect 5. Check wiring against the diagram Compressor will not start - 1. Improperly wired 1. Check wiring against the diagram
hums but trips on overload 2. Low voltage to unit 2. Determine reason and correct protector 3. Starting capacitor defective 3. Determine reason and replace
4. Relay failing to close 4. Determine reason, correct or replace Compressor starts and runs, 1. Low voltage to unit 1. Determine reason and correct
but short cycles on overload 2. Overload defective 2. Check current, replace overload protector protector 3. Excessive head pressure 3. Check ventilation or restriction in refrigeration system
4. Compressor hot-return gas hot 4. Check refrigerant charge, fix leak if necessary Compressor operates long 1. Short of refrigerant 1. Fix leak, add charge
or continuously 2. Control contact stuck 2. Repair or replace
3. Evaporator coil iced 3. Determine cause, defrost manually
4. Restriction in refrigeration system 4. Determine location and remove restriction
5. Dirty condenser 5. Clean condenser
6. Location too warm 6. Ventilate area or change location. Compressor runs fine, but 1. Overload protector 1. Check wiring diagram
short cycles 2. Cold control 2. Differential too close - widen
3. Overcharge 3. Reduce charge
4. Air in system 4. Purge and recharge
5. Undercharge 5. Fix leak, add refrigerant Starting capacitor open, 1. Relay contacts stuck 1. Clean contacts or replace relay
shorted or blown 2. Low voltage to unit 2. Determine reason and correct
3. Improper relay 3. Replace Relay defective or burned out 1. Incorrect relay 1. Check and replace
2. Voltage too high or too low 2. Determine reason and correct Refrigerated space too warm 1. Control setting too high 1. Reset control
2. Refrigerant overcharge 2. Purge refrigerant
3. Dirty condenser 3. Clean condenser
4. Evaporator coil iced 4. Determine reason and defrost
5. Not operating 5. Determine reason, replace if necessary
Objectionable noise 1. Fan blade hitting fan shroud 1. Reform or cut away small section of shroud
2. Tubing rattle 2. Locate and reform
3. Vibrating fan blade 3. Replace fan blade
4. Condenser fan motor rattles 4. Check motor bracket mounting, tighten
5. General vibration 5. Compressor suspension bolts not loosened on applicable models - loosen them
6. Worn fan motor bearings 6. Replace fan motor
4 1/08 N138647
Loading...