Kohler MPac1500 User Manual

Operation
Automatic Transfer Switches
Controls:
Decision-Makerr MPAC 1500
Transfer Switch Models:
KCS/KCP/KCC
KBS/KBP/KBC
KAS/KAP
KGS/KGP
TP-6883 4/21d
Table of Contents
Safety Precautions and Instructions 7........................................................
Introduction 9..............................................................................
List of Related Materials 9.....................................................
Service Assistance 10........................................................................
Section 1 Operation 11.......................................................................
1.1 Introduction 11..........................................................
1.2 Source Names 11........................................................
1.3 User Interface Panel 11...................................................
1.3.1 Display 12......................................................
1.3.2 Display Contrast 12..............................................
1.3.3 Pushbuttons 12..................................................
1.3.4 LED Indicators 13................................................
1.3.5 Lamp Test 13....................................................
1.3.6 Examples 13....................................................
1.4 Main Menu 15...........................................................
1.5 Passwords 16...........................................................
1.5.1 Changing Passwords 16..........................................
1.5.2 Test Password Reset and Disable 16...............................
1.6 Normal Operation Menus 17..............................................
1.7 System Test 18..........................................................
1.7.1 Unloaded System Test 19.........................................
1.7.2 Loaded System Test 19...........................................
1.7.3 Closed-Transition Loaded Test 19..................................
1.7.4 Auto-Loaded System Test 20......................................
1.7.5 Sync Check (closed-transition) 20..................................
1.8 Automatic Operation Test 20..............................................
1.9 Exercise 23.............................................................
1.9.1 Unloaded Exercise 23............................................
1.9.2 Load Bank Control 23............................................
1.9.3 Loaded Exercise 23..............................................
1.10 Warnings and Faults 24...................................................
1.10.1 Fault Reset 25...................................................
1.1 1 Accessory Module Faults 25..............................................
1.11.1 Module Status Change 25.........................................
1.11.2 Module Status Conflict 26.........................................
1.12 Reset Data 27...........................................................
1.12.1 Reset Maintenance Records 27....................................
1.12.2 Reset Event History 27...........................................
1.12.3 Reset Default Parameters 28......................................
1.12.4 Reset and Disable Test Password 28...............................
Section 2 Sequence of Operation 29..........................................................
2.1 Controller Power-up/Reset 29.............................................
2.2 Sequence of Operation, Standard Transition Models 30.......................
2.2.1 Preferred Source Loss and Return, Standard Transition 30............
2.2.2 Exerciser Operation, Standard Transition 30.........................
2.2.3 Test Sequence, Standard Transition 31.............................
2.3 Sequence of Operation, Programmed-Transition 32..........................
2.3.1 Preferred Source Loss and Return, Programmed Transition 32.........
2.3.2 Exerciser Operation, Programmed Transition 32
2.3.3 Test Sequence, Programmed Transition 33..........................
.....................
TP-6883 4/21 Table of Contents 3
Table of Contents, continued
2.4 Sequence of Operation, Closed-Transition Models 34.........................
2.4.1 Preferred Source Loss and Return, Closed Transition 34..............
2.4.2 Failure to Synchronize (Programmed-Transition Override) 34..........
2.4.3 Exerciser Operation, Closed Transition 35...........................
2.4.4 Test Sequence, Closed Transition 35...............................
2.4.5 Extended Transfer Time Relay 36..................................
2.5 Sequence of Operation, Service Entrance Models 37.........................
2.5.1 Preferred Source Loss and Return, Service Entrance Models 37.......
2.5.2 Exerciser Operation,
Service Entrance Models 37.......................................
2.5.3 Test Sequence,
Service Entrance Models 38.......................................
Section 3 View Screens 39...................................................................
3.1 Introduction 39..........................................................
3.2 Main Screen 39..........................................................
3.3 View Screens 39.........................................................
3.4 View Event History 40....................................................
3.5 View Maintenance Records 40.............................................
3.6 View Exerciser Setup 41..................................................
3.7 View Prime Power Setup 41...............................................
3.8 View System Setup 41...................................................
3.9 View Source Setup 42....................................................
3.10 View Time Delays, Source 1 44............................................
3.1 1 View Time Delays, Source 2 46............................................
3.12 View Inputs/Outputs 48...................................................
3.13 View Common Alarms 48.................................................
3.14 View Communications Setup 49...........................................
3.15 View Control Parameters 49...............................................
Section 4 Setup 51...........................................................................
4.1 Introduction 51..........................................................
4.2 Setup Menus 51.........................................................
4.3 Time/Date 52............................................................
4.4 Exerciser 53............................................................
4.4.1 Setting the Exerciser 53..........................................
4.4.2 Source/Source Mode 53..........................................
4.5 Prime Power Run 55.....................................................
4.5.1 Prime Power Mode Setup 55......................................
4.5.2 Prime Power Mode Operation 55...................................
4.6 Time Delays 56..........................................................
4.6.1 Time Delays 56..................................................
4.6.2 Load Control Time Delays 56......................................
4.6.3 Set S1 Time Delays 57...........................................
4.6.4 Set S2 Time Delays 59...........................................
4.7 Load Control 61.........................................................
4.7.1 Time-Based Load Control 61......................................
4.7.2 Current-Based Load Control 63....................................
4.8 Set Sources 65..........................................................
4.8.1 Phase Rotation 65...............................................
4.8.2 In-Phase Monitor 65..............................................
4.8.3 Preferred Source Selection 65.....................................
4.8.4 System Voltage and Frequency 67
4.8.5 Voltage and Frequency Pickup and Dropout Settings 67...............
4.8.6 Set Sources 68..................................................
.................................
TP-6883 4/21Table of Contents4
Table of Contents, continued
4.9 Inputs and Outputs 71....................................................
4.9.1 Controller Inputs and Outputs 71...................................
4.9.2 Input/Output Modules 71..........................................
4.9.3 Input Functions 72...............................................
4.9.4 Output Functions 73..............................................
4.9.5 User-Defined I/O Descriptions 74..................................
4.10 Common Alarms 75......................................................
4.10.1 Common Alarm Output 75........................................
4.10.2 Audible Alarm 75................................................
4.10.3 Chicago Alarm 75................................................
4.11 Set System 76..........................................................
4.11.1 Default Settings 76...............................................
4.11.2 Source Type/Source Type 76......................................
4.11.3 Transition Type 76...............................................
4.11.4 Service Entrance 78..............................................
4.11.5 Rated Current 78................................................
4.11.6 Three Source Engine Start Mode 78................................
4.11.7 Transfer Commit 78..............................................
4.11.8 Remote Test Loading 78..........................................
4.11.9 Peak Shave TD Bypass 78........................................
4.12 Three-Source Systems 79................................................
4.12.1 Three Source Engine Start Mode 79................................
4.12.2 Preferred Source Toggle 79.......................................
4.12.3 Three Source System Te st and Exercise 79.........................
4.12.4 Three-Source System Setup 81....................................
4.12.5 ATS1 and ATS2 System Setup 81..................................
4.13 Communications 83......................................................
4.14 Set Passwords 83.......................................................
4.15 Calibration 84...........................................................
4.16 Setting the Current to Zero 84.............................................
4.17 Reset Data 84...........................................................
Section 5 Communications 85................................................................
5.1 Introduction 85..........................................................
5.2 Connections 85..........................................................
5.2.1 USB Port SiteTech Connection 85..................................
5.2.2 Modbus Connection 86...........................................
5.2.3 Ethernet Connection 86...........................................
5.3 Communications Setup 87................................................
5.3.1 Modbus Serial Communication Setup 87............................
5.3.2 Network Communication Setup 87.................................
5.3.3 Setup Using the Controller Keypad 87..............................
5.3.4 Setup Using SiteTech 87..........................................
5.4 Parameter Files 91.......................................................
5.5 Controller Firmware Updates 91...........................................
Section 6 Scheduled Maintenance 93..........................................................
6.1 Introduction 93..........................................................
6.2 Testing 94..............................................................
6.2.1 Weekly Generator Set Exercise 94.................................
6.2.2 Monthly Automatic Control System Test 94..........................
TP-6883 4/21 Table of Contents 5
Table of Contents, continued
6.3 Inspection and Service 94.................................................
6.3.1 External Inspection 94............................................
6.3.2 Internal Inspection 95.............................................
6.3.3 SPD Inspection 95...............................................
6.3.4 Other Inspections and Service 95..................................
6.3.5 Model KGS/KGP Bypass/Isolation Switches 95......................
6.4 Service Schedule 96.....................................................
Section 7 Accessories 97....................................................................
7.1 Introduction 97..........................................................
7.2 Accessory Modules 97...................................................
7.2.1 Input/Output (I/O) Modules 98.....................................
7.2.2 External Battery Supply Module (EBSM/BOB) 99.....................
7.2.3 Alarm Module 100................................................
7.3 Controller Disconnect Switch 102...........................................
7.4 Current Sensing 103......................................................
7.5 Digital Meter 105..........................................................
7.6 Heater 105...............................................................
7.7 Line-to-Neutral Voltage Monitoring 106.......................................
7.8 Load Shed (Forced Transfer to OFF) 106....................................
7.8.1 Description 106...................................................
7.8.2 Customer Connection 107..........................................
7.9 Supervised Transfer Control Switch 108......................................
7.9.1 Manual Transfer 108..............................................
7.9.2 Automatic Transfer Switches 108....................................
7.9.3 Non-Automatic Transfer Switches 109...............................
7.10 Surge Protection (SPD) 110................................................
7.10.1 SPD Status Indicators 112.........................................
7.10.2 SPD Remote Status Indicator 112...................................
7.10.3 SPD Replacement 112............................................
7.11 User Interface Cover 113..................................................
Appendix A Abbreviations 115................................................................
Appendix B Screen Summaries 117...........................................................
TP-6883 4/21Table of Contents6
Safety Precautions and Instructions
IMPORT ANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (- ) lead first when disconnecting the battery. Reconnect the negative (- ) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (- ) lead first. Reconnect the negative (- ) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
DANGER
Hazardous voltage. Will cause severe injury or death.
Only authorized personnel should open the enclosure.
Grounding electrical equipment. Hazardous voltage will cause severe injury or death. Electrocution is
possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current will cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
TP-6883 4/21 7Safety Precautions and Instructions
Servicing the transfer switch. Hazardous voltage will cause severe injury or death. Deenergize all power
sources before servicing. Turn off the main circuit breakers of all transfer switch power sources and disable all generator sets as follows: (1) Move all generator set master controller switches to the OFF position. (2) Disconnect power to all battery chargers. (3) Disconnect all battery cables, negative (- ) leads first. Reconnect negative (- ) leads last when reconnecting the battery cables after servicing. Follow these precautions to prevent the starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer. Before servicing any components inside the enclosure: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Test circuits with a voltmeter to verify that they are deenergized.
Making line or auxiliary connections. Hazardous voltage will cause severe injury or death. To
prevent electrical shock deenergize the normal power source before making any line or auxiliary connections.
deenergized by inline connector separation. Test circuits with a voltmeter to verify that they are deenergized before servicing.
Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry,approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Heavy Equipment
WARNING
Notice
NOTICE
Improper operator handle usage.
Use the manual operator handle on the transfer switch for maintenance purposes only . Return the transfer switch to the normal position. Remove the manual operator handle, if used, and store it in the place provided on the transfer switch when service is completed.
NOTICE
Electrostatic discharge damage.
Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short,to ground.
Servicing the transfer switch controls and accessories within the enclosure. Hazardous voltage will cause severe injury or death.
Disconnect the transfer switch controls at the inline connector to deenergize the circuit boards and logic circuitry but allow the transfer switch to continue to supply power to the load. Disconnect all power sources to accessories that are mounted within the enclosure but are not wired through the controls and
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Use adequate lifting capacity. Never leave the transfer switch standing upright unless it is securely bolted in place or stabilized.
TP-6883 4/218 Safety Precautions and Instructions
Introduction
This manual provides operation instructions for the Kohlerr Decision-Makerr MPAC 1500 automatic transfer switch controller and related accessories.
The Decision-Makerr MPAC 1500 controller is available for the transfer switch models shown below.
Model Description
KCS Standard-Transition Any Breaker ATS *
KCP Programmed-Transition Any Breaker ATS *
KCC
KBS
KBP
KBC
KAS Standard-Transition Electrically Operated
KAP Programmed-Transition Electrically Operated
KGS
KGP
KEP
* Available with automatic or non-automatic controller [ Available with automatic controller only
Closed-Transition Any Breaker ATS [
Standard-Transition Bypass/Isolation ATS [
Programmed-Transition Bypass/Isolation ATS [
Closed-Transition Bypass/Isolation ATS [
Bypass/Isolation ATS [
Bypass/Isolation ATS [
Standard-Transition Bypass/Isolation ATS [
Programmed-Transition Bypass/Isolation ATS [
Service Entrance ATS [
For Bypass/Isolation models, refer to the Installation Manual for instructions to bypass and isolate the transfer switch. See List of Related Materials for document part numbers.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this literature and the products represented
without n otice and without any obligation or liability whatsoever.
The equipment service requirements are very important to safe and efficient operation. Inspect parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
List of Related Materials
A separate transfer switch installation manual provided with the unit contains instructions for transfer switch installation instructions, manual operation procedures, and bypass/isolation instructions, if applicable.
Literature Item Part Number
Specification Sheet, MPAC 1500 Controller G11-128
Installation Manual, Model KCS/KCP/KCC TP-6833
Installation Manual, Model KBS/KBP/KBC TP-6835
Installation Manual, Model KGS/KGP TP-6836
Installation Manual, Model KEP TP-6946
Installation Manual, Model KAS/KAP TP-7190
Operation Manual, Modbus Protocol TP-6113
TP-6883 4/21 9Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please c ontact your nearest Kohler distributor or dealer.
D Visit the Kohler Co. website at KOHLERPower.com.
D Look at the labels and decals on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler EMEA Headquarters Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific
Kohler Asia Pacific Headquarters Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
TP-6883 4/2110 Service Assistance
Section 1 Operation
1.1 Introduction
This section contains operation instructions, including:
D User interface panel, with display, pushbuttons, and
LED indicators
D Main menu D System status, warnings, and faults D Passwords D Te s ts D Warnings and Faults D Reset Data
1.2 Source Names
Throughout this manual, the sources are referred to as follows. Source 1 (S1) is connected to the Normal side of the transfer switch and is also referred to as Source N. Source 2 (S2) is connected to the Emergency side of the transfer switch and is also called Source E. The engine start contacts are associated with Source 2.
1
2
ThePreferredSourceisthesourcethatwillbeusedif both sources are available. Typically, this is the normal utility source 1. If the transfer switch is equipped with the optional alarm module, the Set Preferred Source menu allows the operator to select either source as the preferred source. Source 2 (connected to the emergency side of the contactor) can be set as the preferred source using this menu. See Section 4.8.3 for more information about preferred source selection.
Other applications may use different configurations, such as the gen-gen configuration which uses two generator set sources and no utility.
1.3 User Interface Panel
The user interface panel is located on the transfer switch door. Figure 1-1 shows the user interface pushbuttons and LED indicators.
3 4
5
9
1. Source N Available LED
2. Source N Position LED
3. Source E Position LED
4. Source E Available LED
5. USB port for SiteTecht
connection
Figure 1-1 User Interface Panel
8
6. System Alert LED
7.NotinAutoLED
6
7
GM85884
8. Pushbuttons (4)
9. Display
TP-6883 4/21 11Section 1 Operation
1.3.1 Display
The four-line display indicates transfer switch status and setup, including the following:
D System status D Faults and warnings D Active time delays D Source voltages D Source frequency (Hz) D Current (amps) D Source setup information D Time and date D Time and date of next scheduled exercise
The display also identifies the pushbutton functions, which can change from menu-to-menu.
B
Down arrow (closed). Step down to the next menu or scroll through a list.
Y
Up arrow (closed). Step back to the previous menu.
"
Right arrow (closed). Move to the next submenu.
Up arrow (open). Increases the selected numerical value.
Down arrow (open). Decreases the selected numerical value.
Right arrow (open). Steps to the next digit in a selected numerical value.
Back Steps back to the previous menu or submenu.
1.3.2 Display Contrast
To adjust the display contrast, press and hold the second button until two rows of asterisks (*) appear. Then press the up arrow button to increase the contrast or the down arrow button to decrease the contrast. The display will return to the main menu after a few seconds if no buttons are pressed.
1.3.3 Pushbuttons
The user interface panel has four pushbuttons below the display. Pushbutton functions are shown above each button in the last line of the display and can change from menu-to-menu. The pushbutton functions are defined in Figure 1-2.
Note: The current can be set to zero (0) by pressing the
first and last pushbuttons together. See section
4.16 for instructions.
End
Delay
End
OK Enters the displayed numerical value
Reset Reset the fault condition shown on the display,
Save Saves settings shown on the display.
Start From the Test menu, starts the test sequence.
Test From the main menu, moves to the test
Ends the current time delay.
Ends an active test sequence. See
Tes t
Section 2.2.3.
(password or setting).
Main Returns to the main menu.
Next Steps to the next parameter in an item with
multiple settings (for example, in Exerciser Setup).
or reset an accessory module after connection.
Set From the main menu, moves to the first
setup menu.
sequence menus. See Section 1.7.
View From the main menu, moves to the first
view menu.
Figure 1-2 Pushbutton Functions
TP-6883 4/2112 Section 1 Operation
1.3.4 LED Indicators
1.3.5 Lamp Test
LEDs on the user interface indicate contactor position, source availability, faults, and other conditions. The table in Figure 1-3 describes the functions of the LED indicators.
See Section 1.10 for more information about warnings and faults.
Some programmable inputs will trigger the LEDs to light or flash. See Section 4.9.
LED Indicator Condition
Source N Available, Green
Source E Available, Red Source E is available.
Position A, Green Contactor is in Normal position.
Position B, Red Contactor is in Emergency position.
System Alert, Red Fault. Identify and correct the cause
Not in Auto, Red ATS is not set for automatic
Source N is available.
of the fault condition, then reset faults at the controller. See Section 1.10.
Input active: Low Battery Voltage or Remote Common Alarm. See Section 4.9.
operation or a load shed (forced transfer to OFF) sequence is active.
Flashes for manual transfer waiting.
Input active: Inhibit Transfer, Forced Transfer to OFF. See Section 4.9.
Figure 1-3 User Interface LED Indicators
To test the LEDs on the controller’s user interface, go to the Main menu. Press the down arrow button once, then press the Lamp Test button and verify that the LCD menu and all 6 LEDs on the user interface illuminate. SeeFigure1-4.
System Ready
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
Press the down arrow button.
B View Set Test
Norm AB BC AC ##Hz ###V ###V ###V
Lamp
Press and hold the Lamp Test button.
BYTe s t Ma in
Figure 1-4 Lamp Test
1.3.6 Examples
Figure 1-5 illustrates navigation through the menus.
Figure 1-6 illustrates how to use the pushbuttons to step through menus and change settings. This example shows setting the time.
Set Common Alarms
BY"Main
Press the right arrow button to enter the Set Common Alarms menu.
Set Common Alarms
Alarm Group 1
BY "Back
Press the up and down arrow buttons to step between alarm groups 1 and 2.
Press the right arrow to modify settings in the displayed group.
Figure 1-5 Example: Set Common Alarms
Modify Alarm
BY "Back
Press the up and down arrow buttons to select Modify Alarm or Remove All Alarms
Remove All Alarms
BY "Back
Alarm Description
Common Audible
BY "Back
Press the up and down arrow buttons to step through the alarm descriptions. Then press the right arrow to change the common and audible assignments for that function.
Remove All Alarms
Yes/N o
Back Save
Press the up arrow button to toggle yes or no. If Yes is displayed, pressing Save will remove all alarms from the selected group (1 or 2). Pressing Back exits without executing the Remove command.
Alarm Description
Common Y Audible N
Back Save
Press the up arrow button to step through all combinations of yes and no for common and audible.
Press Save to save the common and audible alarm settings.
TP-6883 4/21 13Section 1 Operation
1
System OK
LD Exer ##/## @ ##:##
Norm ###V Emer ###V
B View Set Test
6
Set Time
BY "Back
Press the SET button.
2
Enter Password
Time to Enter #:##
???
?
OK
Press the open UP arrow button to increase the first digit of the password from 0 through 9.
Note: The default password is 0000.
3
Press the open RIGHT arrow button to move to the next digit. Repeat Steps 2 and 3 until the correct password is displayed.
4
Enter Password
Time to Enter #:##
Time to Enter #:##
??
0?
Enter Password
0
000
OK
OK
Press the right arrow button to enter the Set Time submenu.
7
Set Time #
Back Save
Press the open up arrow button to increase the first digit. (Use 00:00 to 23:59 for time.)
8
Set Time 1#:##
Back Save
Press the open right arrow button to step to the next digit. Repeat steps 7 and 8 until the correct time is displayed.
9
Set Time 14:37
#:##
Press OK to enter the password.
5
Set Time/Date
BY "Main
Press the right arrow button to enter the Set Time/Date submenu.
Figure 1-6 Example: Setting the Time
Back Save
Press Save.
TP-6883 4/2114 Section 1 Operation
1.4 Main Menu
The main menu appears at system startup and displays the following information(seeFigure1-7):
D System Status (see F igure 1-8)
Press the Test button to enter the Test mode. A password is required. See Section 1.7.
The display returns to the main menu after 10 minutes of no activity (no buttons pressed).
D Date and time of the next scheduled exercise run (if
programmed)
D Measured source voltages
D Pushbutton functions
Pressing the down arrow button steps to the normal operation menus shown in Section 1.6. Step through these menus to check the measured frequency, line voltages, current (if the current sensing accessory is installed), and other system information.
Some parameters will appear only under certain conditions. For example:
D If no exercise runs are scheduled, the second line of
themainmenuisblank.
D The Daylight Saving Time settings are displayed only
if DST is enabled.
D Phase rotation and in-phase monitoring are
displayed only for three-phase systems.
D Some parameters and time delays appear only for
programmed-transition models.
D The menus displayed during a test or exercise
sequence will vary depending on the time delay settings.
Pressing the View button steps to the view menus shown in Section 3.3.
Passwords are required to enter the setup and test modes. See Section 1.5 for more information about passwords.
System Ready
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
B View Set Test
1. System status message
2. Next scheduled exercise, if programmed
3. Source voltages detected
Figure 1-7 Main Menu
System Status Messages
Aux Switch Fault
Aux Switch Open
Exerciser Active
External Battery Low
Fail to Acquire Pref
Fail to Acquire Stby
Fail to Transfer
In Phase Waiting
Inhibit Transfer
Low Battery Voltage
Maint DIP Switch
Module Lost Comm
New Module
Peak Shave Active
Phase Rotation Error
Remote Common Alarm
System Ready
Test Mode Active
Figure 1-8 System Status Messages
1
2
3
6446
Press the Set button to enter the setup mode. A password is required. See Section 4.2 for system setup menus.
TP-6883 4/21 15Section 1 Operation
1.5 Passwords
Passwords are required to enter the Test and Setup menus. Passwords are 4-digit numbers. See Figure 1-9 for instructions to enter the password using the pushbuttons on the controller’s user interface.
There a re two passwords:
Setup Password. The setup password controls access to the system setup menus, which allow changes to system settings, time delays, etc.
For closed-transition models, the setup password is required to initiate a transfer when the programmed transition override function is set to manual. See Section 1.7.3.
Note: The factory default password is 0000.
Enter Password
Time to Enter #:##
???<
>?
OK
Press the open up arrow button to increase the first digit of the password from 0 to 9.
Enter Password
Time to Enter #:##
>0???<
OK
Test Password. The test password controls access to the test sequence menus. The test password is required to initiate a loaded, unloaded, or auto-loaded test, and also to initiate a sync check test on closed-transition models.
If the correct password is not entered within 30 seconds, the display returns to the main menu.
The factory default password is 0000. Change the password to allow only authorized personnel to start and end tests or change settings.
1.5.1 Changing Passwords
Use the Passwords Setup Menu to change passwords. See Section 4.14.
1.5.2 Test Password Reset and Disable
The test password can be reset to the default value or disabled. Use the Setup Menu- Reset Data menu. See Figure 1 -26.
Note: Disable the test password only during service
unless the transfer switch is located in a secure location.
Press the open right arrow button to step to the next digit. Repeat for all four digits.
Enter Password
Time to Enter #:##
>0000
Press the OK button to enter the password.
Incorrect Password
If the wrong password is entered, the Incorrect Password message appears. Check the password and try again.
<
OK
Figure 1-9 EnteringaPassword
Disabling the test password allows any user to initiate a test sequence from the controller’s user interface without entering a password. Initiating a t est starts the generator set and, if a loaded test is selected, transfers the load.
TP-6883 4/2116 Section 1 Operation
1.6 Normal Operation Menus
During normal transfer switch operation, the screens shown in Figure 1-10 or Figure 1-11 are displayed. Use the up a nd down arrow buttons to view the sy stem status information as shown. Press Main to return to the main menu from any screen.
The Sequence of Operation descriptions in Sections 2.2 through 2.4 describe the transfer switch normal operation for standard, programmed, and closed transition models.
System Ready
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
B View Set Test
System Ready
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
B View Set Test
Norm AB BC AC ##Hz ###V ###V ###V
Lamp
BYTe st M ai n
Norm AN BN CN ##Hz ###V ###V ###V
BY Main
Emer AB BC AC ##Hz ###V ###V ###V
Norm L1 L2 ##Hz ###V ###V
Lamp
BYTe s t Ma i n
Emer L1 L2 ##Hz ###V ###V
BY Main
Amps L1 L2
#### ####
BY Main
Time/Date
09:10 DST 01/13/06
BY Main
Daylight Saving Time
Clock Ahead 1 Hour
Sun 03/12/06
BY Main
Daylight Saving Time
ClockBack1Hour
Sun 11/05/06
BY Main
Normal Preferred
Util-Gen Operation
No Commit Transfer
BY Main
Standard Transition
BY Main
Emer AN BN CN ##Hz ###V ###V ###V
BY Main
Amps LA LB LC
#### #### ####
BY Main
Time/Date
09:10 DST 01/13/06
BY Main
Daylight Saving Time
Clock Ahead 1 Hour
Sun 03/12/06
BY Main
Daylight Saving Time
Clock Back 1 Hour
Sun 11/05/06
BY Main
Normal Preferred
Util-Gen Operation
No Commit Transfer
BY Main
Standard Transition
Phase Rotation ABC
In Phase Enabled
BY Main
Figure 1-11 Three-Phase Operation
BY Main
Figure 1-10 Single-Phase Operation
TP-6883 4/21 17Section 1 Operation
1.7 System Test
Use the system test feature to:
D Start and run the generator set.
D Simulate a preferred source failure, resulting in a
transfer to the standby source.
D Check source synchronization (closed-transition
models only).
time delays. See Figure 1-16 for Sync Check menus for closed-transition models.
Press the End Test designated pushbutton to end the test. Time delays will execute as programmed when the test is ended. Press the End Delay button to end the currently displayed time delay, if desired.
To check the source voltage and frequency while a test is running, press the Main button. Press the Test button to return to the test sequence menus.
See Figure 1-12 for the test sequence menus. From the main menu, press the Test button and then enter the password. The password ensures that only authorized personnel can start a test.
Press the down arrow button to navigate to the desired test sequence. Press the Start button to start the test.
Figure 1-13 shows the menus displayed during the test run. Menus are dependent on the system settings and
System Ready
LD Exer ##/## @ ##:##
Norm ###V Emer ###V
B View Set Test
Enter Password
Time to Enter #:##
>?
???<
OK
Press the Test button to enter the Test mode. A password is required.
If the emergency source is lost during a system test, the fail to acquire standby signal is indicated immediately, and the test is terminated. If the contactor is in the standby position, it transfers immediately to the preferred position.
See Section 4.9.3 for additional information about the remote test input.
Type of Test
Auto Load
Time :## min
B Main " Start
Type of Test
Loaded
B Main Start
Type of Test
Unloaded
B Main Start
Auto Load Test
Enter Time
Time ?? min
Back OK
Figure 1-12 Test Selection Menus
Type of Test Sync Check
B Main Start
TP-6883 4/2118 Section 1 Operation
Engine Start in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
LD# Disc in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
Xfr to Off in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
XfrtoEmerin##:##
Norm ###V Emer ###V
End End
Main Delay Test
Add LD# in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
System on Test
Norm ###V Emer ###V
End End
Main Delay Test
LD# Disc in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
Xfr to Off in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
XfrtoNormin##:##
Norm ###V Emer ###V
End End
Main Delay Test
Add LD# in ##:##
Norm ###V Emer ###V
End End
Main Delay Test
Appears if load control time delays are set
Programmed-transition models only
Appears if load control time delays are set
Appears if load control time delays are set
Programmed-transition models only
Appears if load control time delays are set
1.7.1 Unloaded System Test
When an unloaded test is initiated, the controller immediately signals the generator to start, without waiting for the engine start time delay to expire. The contactor does not change position during an unloaded test, but if the normal source should fail, the contactor will transfer to the emergency source.
The unloaded test feature is available only with the Util-Genset and Genset-Genset modes of operation.
The load bank control output is active during an unloaded exercise or unloaded system test. If the contactor transfers to the standby position during the test, the load bank control is deactivated. (The standby source supplies power to the load.)
1.7.2 Loaded System Test
A loaded test simulates a preferred source failure, except that the engine start time delay is bypassed. The generator set is signaled to start immediately upon test activation. Load control signals are issued prior to transfer with their associated time delays. Since the loaded test transfer will be between two live sources, the in-phase monitor or closed transition feature will be activated if it is enabled. If the preferred source is lost during a loaded test with the contactor in the standby position, the test will continue to be active, even on restoration of preferred. If the standby source is lost and the preferred source is available, the test will be terminated, and the transfer switch will immediately transfer to the preferred source position, bypassing all time delays except the off-position requirements in a programmed-transition system.
When a loaded test is terminated normally, the retransfer sequence operates as though the preferred source has been restored after a failure. All time delays are executed and an in-phase transfer will occur if enabled. The loaded test feature is available with the Util-Genset, Util-Util and Genset-Genset modes of operation.
1.7.3 Closed-Transition Loaded Test
Eng Cooldown ##:##
Norm ###V Emer ###V
End End
Main Delay Test
When a loaded test is initiated on a closed-transition model, the generator set is signaled to start and the controller monitors the sources for synchronization. The load is transferred when the sources are synchronized.
Note: See Figure 1-16 for Sync Check menus.
Figure 1-13 Test Sequence Menus
TP-6883 4/21 19Section 1 Operation
If the sources do not sync before the Fail to Sync time delay expires, the programmed-transition override function operates.
D If the override function is set to Automatic, a
programmed-transition transfer will occur when the Fail to Sync time delay expires. The contactor stops in the OFF position for the length of the off-to standby time delay before proceeding to transfer to the standby source.
D If the override function is set to manual, the user can
either initiate a programmed-transition type transfer (setup password required) or cancel the test sequence. See Figure 1-14. If neither action is taken, the controller will continue to check for synchronization and transfer if the sources synchronize.
See Section 4.11.3 for instructions to set the programmed-transition override function.
Manual Transfer
Password:
Cancel OK
2
1. Use arrow buttons to enter the setup password and click OK to initiate a manual programmed-transition transfer. OR
2. Press the Cancel button to cancel the test.
1
Figure 1-14 Manual Transfer Menu for
Programmed-Transition Override
1.7.5 Sync Check (closed-transition)
The Sync Check allows a test of the synchronization of two available sources without initiating a transfer. Navigate to the Type of Test, Sync Check menu and press the Start button to begin the test. The controller displays Syncing during the test, and the phase angle difference is shown between two arrows. For example, > 10 < indicates that the sources are 10 degrees out of phase. The arrows move closer together as the sources approach synchronization. When the sources synchronize, the controller indicates Synced and continues to monitor the source synchronization. The load is not transferred. See Figure 1-16. Press the End Te st button to end the test.
Type of Test Sync Check
B Main Start
System on Test
Norm ###V Emer ###V
Syncing
End
Main > 102 < Test
System on Test
Norm ###V Emer ###V
Synced
End
Main >< Test
Figure 1-16 Sync Check Menus
1.7.4 Auto-Loaded System Test
The auto-loaded test feature is a timed, loaded test. The auto-loaded time delay determines how long after the transfer to standby to terminate the test and transfer back to the preferred source. The time is defaulted to 30 minutes and can be adjusted from 1 minute to 60 minutes. See Figure 1-15.
Type of Test Auto Loaded Time :## min
B Main " Start
1
1. Press right arrow button to go to the Enter Time menu.
2. Use the open arrow buttons to enter the duration time for the test. Then press OK.
3. Press Start to start the test.
3 2
Figure 1-15 Auto Loaded Test Menus
Auto Loaded Test
Enter Time
Time: ?? min
Back OK
1.8 Automatic Operation Test
Note: Close and lock the enclosure door before starting
the test procedure.
Preferred Source Selection. The test procedure assumes that Source N is the preferred source. If the ATS is equipped with the alarm board accessory, check the preferred source selection before proceeding with the automatic operation test. To check the preferred source selection, use the down arrow button to step down from the main s creen until Normal Preferred or Emergency Preferred is displayed. See Figure 1-10 or Figure 1-11.
Supervised Transfer Switch. If the transfer switch is equipped with a supervised transfer switch, verify that it is set to the Auto position.
Follow the procedure below to start a loaded test. Verify that the ATS starts the generator set and transfers the load to the emergency source, executing all time delays that are set up to operate during a loss of the normal source. End the test and verify that the transfer switch transfers the load back to the normal source and removes the engine start signal, executing all
TP-6883 4/2120 Section 1 Operation
appropriate programmed time delays. Refer to Section
2.2.3 for a more detailed description of the test sequence of operation.
Load control time delay settings may affect the operation sequences.
Note: If the standby source fails during a loaded test,
theATSwillimmediatelyattempttotransfertothe preferred source.
Automatic Operation Test Procedure
1. Check the controller LED indicators to verify that the Position N and Source N Available indicators are lit.
If the sources do not synchronize before the fail to sync time delay expires, operation depends on the programmed transition override setting. If automatic override is enabled, the ATS will transfertheloadusingaprogrammed­transition transfer. If automatic override is not enabled, the ATS will continue to monitor the source synchronization and transfer when/if the sources synchronize. The operator can initiate a programmed-transition transfer (password required) or cancel the transfer.
8. Press the End Test button.
9. Verify that the switch transfers the load back to Source N.
2. Verify that the generator set m aster switch is in the AUTO position.
3. Refer to Figure 1-17. From the main screen, press the Test button. Enter the test password when prompted and press OK.
4. Press the down arrow button to display Type of Test Loaded.
5. Press the Start button.
6. Verify that the generator set starts and the Source E Available LED lights.
7. Verifythat the switch transfers the load to Source E. Observe the controller LEDs and display as the time delays execute and the load is transferred.
a. Standard-Transition Models: After the
preferred-to-standby transfer time delay, verify that the Position N LED turns off and the Position E LED lights, indicating that the switch has transferred the load to Source E.
b. Programmed-Transition Models: After the
preferred-to-off time delay, verify that the Position N LED turns off. After the off-to-standby time delay, check that the Position E LED lights, indicating that the switch has transferred the load to Source E.
c. Closed-Transition Models: See Section 1.7.3.
After the preferred-to-standby time delay, the controller monitors the sources for synchronization. When the sources are in sync,theATStransferstheloadtoSourceE and the Position E LED lights. Both sources will be connected for less than 100 milliseconds before Source N is disconnected and the Position N LED turns off.
a. Standard-Transition Models: After the
standby-to-preferred time delay, verify that the Position E LED goes out and the Position N LED lights, indicating that the switch has transferred the load to Source N.
b. Programmed-Transition Models: After the
standby-to-off time delay, verify that the Position E LED goes out. After the off-to­preferred time delay, check that the Position N LED lights, indicating that the switch has transferred the load to Source N.
c. Closed-Transition Models: See Section 1.7.3.
After the standby-to-preferred time delay, the controller monitors the sources for synchronization. When the sources are in sync, the ATS transfers the load to Source N and the Position N LED lights. Both sources will be connected for less than 100 milliseconds before Source E is disconnected and the Position E LED turns off.
If the sources do not synchronize before the fail to sync time delay expires, operation depends on the programmed transition override setting. If automatic override is enabled, the ATS will transfertheloadusingaprogrammed­transition transfer. If automatic override is not enabled, the ATS will continue to monitor the source synchronization and transfer when/if the sources synchronize. The operator can initiate a programmed-transition transfer (password required).
10. After the engine cooldown time delay expires, the engine start s ignal is removed. Verify that the generator set stops.
Note: The generator set may have an engine
cooldown time delay that causes the generator set engine to run after the transfer switch engine start signal is removed.
TP-6883 4/21 21Section 1 Operation
System OK
LD Exer ##/## @ ##:##
Norm ###V Emer ###V
B View Set Test
On the main screen, press the Test button.
Enter Password
Time to Enter #:##
???<
>?
Typ e of Test
Auto Load
Time :## min
B Main " Start
Typ e of Test
Loaded
B Main Start
Engine Start in ##:##
Norm ###V Emer ###V
End End Delay Test
Use the open arrow buttons to enter the Test password. See Section 1.5 for instructions. Then press t he OK button.
OK
Press the down arrow button to step to the loaded test screen.
Press the Start button to initiate the test sequence.
Additional test sequence screens may appear, depending on the system settings.
System on Test
Norm ###V Emer ###V
End
Main Test
PresstheMainbuttontoreturntothemainscreen during the test, if desired. From the main screen, press Test to return to the test screen.
PresstheEndTestbuttontoendthetest.
Figure 1-17 Starting and Stopping the Automatic Operation Test
TP-6883 4/2122 Section 1 Operation
1.9 Exercise
Schedule exercise runs through the Set Exercise menus. See Section 4.4. To run the generator set at a time other than a scheduled exercise sequence, use the Test function. See Section 1.7 for instructions.
When a scheduled exercise is running, the menus shown in Figure 1-18 appear. Press Main to return to the main menu, if desired. Press the End button to end the exercise sequence before the scheduled stop time, if necessary.
If a system test or peak shave is active when the exercise is scheduled to occur, the exercise is skipped. A preferred-source failure during an exerciser period causes the exercise to be terminated and normal ATS operation to resume.
An exercise event can be temporarily disabled to prevent its execution and then re-enabled later using the enable/disable setting in the Set Exercise menus. See Section 4.4.
1.9.1 Unloaded Exercise
An unloaded exercise starts and runs the generator set without transferring the load.
contactor transfers to the standby position, the load bank control will be deactivated. (The standby source supplies power to the load.)
1.9.3 Loaded Exercise
A loaded exercise starts the generator set and transfers the load from the normal source to the standby source.
On closed-transition models, transfer will occur when the sources are synchronized. If the sources do not sync, press Cancel to end the exercise.
Exerciser Active
Fail to Acquire 00:59
Norm ###V Emer ###V
Main End
Exerciser Active
Time Remaining 00:29
Norm ###V Emer ###V
Main End
Figure 1-18 Exercise Sequence Menus
Display during generator set engine start or if engine does not start immediately.
Display during exercise run.
1.9.2 Load Bank Control
The load bank control output is active during an unloaded exercise or unloaded system test. If the
TP-6883 4/21 23Section 1 Operation
1.10 Warnings and Faults
When a fault exists, the System Alert indicator flashes, a designated output and the common fault output are turned on, and an appropriate message is displayed to indicate the fault. See Figure 1-19 for the location of the System Alert indicator.
ATS warnings and faults are shown in Figure 1-20. There are three types of warning/fault conditions:
Warning. Warnings automatically reset with a source availability change or a transfer request.
Fault Requiring Manual Reset. Under these conditions, normal ATS operation is halted. Active modes are turned off. If the contactor is in the preferred source position, the engine cooldown time delay executes and the engine start contacts open, allowing the generator set to shut down. See Section 1.10.1 for instructions to reset faults.
1
Self Resetting Faults. Under these conditions, active modes are turned off. If the contactor is in the preferred source position, the engine cooldown time delay executes and the engine start contacts open, allowing the generator set to shut down. When the fault condition is corrected, the fault is automatically cleared from the controller and normal ATS operation continues.
1. System Alert LED
GM85888
Figure 1-19 Fault Indication
Condition Ty p e Description
Failure to Acquire Standby Source Warning The source voltage did not reach the acceptable range within a set
Failure to Acquire Preferred Source Warning
IPM Synching (In-Phase Monitor Synching)
External Battery Low Warning The voltage of the battery connected to the external battery supply
Failure to Transfer Warning The signal to transfer is sent to the contactor and the main shaft
Src N (or Src E) Rotation Err Self-Resetting Fault The detected phase rotation of one or both sources does not match
I/O Module Lost Comm Self-Resetting Fault An I/O device has stopped communicating or does not have a
Auxiliary Switch Fault Manual Reset Fault The main shaft auxiliary switches indicate that the ATS is in more
Auxiliary Switch Open Manual Reset Fault The main shaft auxiliary switches indicate that the ATS is in neither
Source1/Source2 Breaker Trip (service entrance models only)
Module Status Change Manual Reset Fault An accessory module has been disconnected OR a new module is
Module Status Conflict Manual Reset Fault An accessory module has been replaced with a different type of
External Fault Self-Resetting Fault The external input dedicated to this condition is closed.
Warning (status) ThetwosourcesdidnotcomeintophasewithintheFailto
Manual Reset Fault The Source1 or Source2 circuit breaker in the service entrance
time (see Time Delays). For example, the standby source generator set did not start.
Synchronize time delay. Note: If the sources do come into phase after the time delay expires, the warning is automatically cleared and normal ATS operation continues.
module (EBSM) is low.
auxiliary switch fails to indicate a complete ATS position change. The controller will attempt to transfer the unit three times before the fault is indicated.
the preselected setting.
correct address specified. Fault resets if communication is reestablished.
than one position, or the position changed when no signal was sent to initiate the change.
position (all inputs are open).
transfer switch has tripped due to an overcurrent condition. Identify and correct the cause of the fault before resetting the controller.
detected. See Section 1.11.1 to reset.
module with the same address. See Section 1.11.2 to reset.
Figure 1-20 Warnings and Faults
TP-6883 4/2124 Section 1 Operation
1.10.1 Fault Reset
To clear a fault or warning condition and reset the System Alert LED, go to the Main menu and press the down arrow button to open the Reset menu. See Figure 1 -19 and Figure 1-21. Then press the button labeled Reset. A fault reset does not change the controller settings.
Module Status Change
Norm ###V Emer ###V
Reset View Set Test
Reset
New Module
Press Reset.
Press Reset.
See Section 1.11, Accessory Module Faults, for instructions to correct and reset faults related to the I/O modules and other accessory modules.
When a fault message is displayed, press the down arrow on the Main menu to step to the Reset Fault menu.
Then press the Reset button.
(B) button
Fault Message
LD Exer ##/## @ ##:##
Norm ###V Emer ###V
B View Set Test
Reset
Fault Description
BYReset Main
Figure 1-21 Fault Reset
1.11 Accessory Module Faults
Accessory modules are optional equipment.
1.11.1 Module Status Change
Connecting or disconnecting one or more accessory modules can cause the Module Status Change message to be displayed.
Module Connection (new or reconnected module)
Installing or reconnecting one or more accessory modules triggers the Module Status Change message. See Figure 1-22. Press the Reset button to display Reset New Module. Press the Reset button from that menu. The controller recognizes the module type(s). See Figure 1-23.
BYReset Main
Figure 1-22 Menus after Module Connection
Module
Type
AOB
SOB
POB
Description
Switch/Alarm Module (alarm option board)
Standard I/O Module (standard option board)
High-Power I/O Module (power option board)
Figure 1-23 Module Types
Disconnected Module
If one or more accessory modules are disconnected from the controller, the message Module Status Change appears. See Figure 1-24. Pressing the Reset button displays the m essage Check Module Setup to Clear Fault. Use the following Module Uninstall Procedure to uninstall modules after disconnection.
Module Status Change
Norm ###V Emer ###V
Reset View Set Test
Check Module Setup
to Clear Fault
BYReset Main
Press Reset.
Press Main and follow Module Uninstall Procedure.
Figure 1-24 Menus after Module Disconnection
Navigate to the Set Input/Outputs>Set Aux I/O menu to check that the controller has recognized the connected modules.
See Section 4.9 for instructions to assign programmable inputs and outputs to I/O modules. Go to Section 4.10 for instructions to assign functions to the audible alarm for an Alarm Module.
TP-6883 4/21 25Section 1 Operation
Module Uninstall Procedure
1.11.2 Module Status Conflict
1. Press Main t o return to the main menu.
2. Press Set to enter setup mode.
3. Enter the setup password.
4. Press the down arrow to step to the Set Inputs/ Outputs menu.
5. Navigate to the Set Auxiliary I/O menu. See Figure 1-25. Press the right arrow button to see the status of module 1. Press the down arrow to step to the next module, if necessary, until the menu shows Status: Lost.
6. Press the right arrow button to move to the Uninstall Module menu. Verify that the menu says Uninstall Module Yes. (Press the open arrow button to toggle no/yes, if necessary.)
7. When Yes is displayed, press Save to uninstall the module.
8. Repeat the uninstall procedure for additional modules, if necessary.
Other Module Status Change Conditions
A Module Status Change message that cannot be cleared as described in this section may indicate a failure of the controller’s real-time clock. Carefully follow the Module Connection or Module Uninstall procedures to attempt to reset the fault. If the fault cannot be reset, the controller’s logic board may need to be replaced. Contact an authorized distributor/dealer for service.
The message Module Status Conflict appears if one type of module is replaced with another type of module that has the same address. Follow the procedure below to resolve the conflict.
Procedure to Clear a Module Status Conflict
1. Disconnect power to the transfer switch.
2. Disconnect the module.
3. Close the enclosure door and reconnect power to the ATS. The display will show Module Status
Change.
4. Press the button labeled Reset. The display will show Check Module Setup to Clear Fault.
5. Follow the procedure in Section 1.11.1 to uninstall the module through the ATS controller keypad.
6. Disconnect power to the ATS.
7. Connect the new module.
8. Close the enclosure door and reconnect power to the ATS. The display will show Module Status Change. SeeFigure1-22.
9. Press the button labeled Reset to display Reset New Module. Press the reset button from that menu. The controller will now recognize the new module type.
10. Navigate to the Set Auxiliary I/O menu to check the status and settings for the new module. See Figure 1-25. Press the right arrow button to see the status of module 1. Press the down arrow t o step to the next module, if necessary,
Set Inputs/Outputs
BY"Main
Main Board I/O
BY"Back
Auxiliary I/O
BY"Back
Figure 1-25 Uninstall Module
Set
Set
Module 1
Type POB Addr 1
Status: Lost
BY"Back
Pressthedownarrowbuttontosteptothe next module, if necessary.
Module 1
Uninstall Module
Yes
Save Back
TP-6883 4/2126 Section 1 Operation
1.12 Reset Data
1.12.1 Reset Maintenance Records
Be sure to read and understand the information in this section before resetting records or parameters.
Note: Resetting to the d efault parameters will reset all
parameters to a factory default setting.
Use the Reset Data menus to set records or parameters back to factory default settings. See Figure 1-26.
1. Use the black arrow buttons to step to the desired menu.
2. Press the open up arrow button to toggle Yes or No until Yes is displayed.
3. Press Save to reset the records or parameters to the factory defaults. Pressing Back exits the menu without resetting.
Reset Data
BY "Main
B Save Back
B Save Back
Reset
Maintenance Records
Yes /No
Reset
Event History
Yes /No
Reset the maintenance records after transfer switch service to update the last maintenance date and totals since reset that are displayed in the maintenance records menu.
1.12.2 Reset Event History
Resetting the event history clears the events from the event history log. The history lists the 100 most recent transfer switch events, including transfers and DIP switch setting changes as well as faults and alarms.
Figure 1-26 Reset Data
Reset
Default Parameters
Yes /No
B Save Back
Reset
Exerciser Setup
Yes /No
B Save Back
Reset
Test Password
Yes /No
B Save Back
Disable
Test Password
Yes /No
B Save Back
Note: Resetting to the default parameters will reset all
parameters, including the system voltage and frequency, to a factory default setting. The transfer switch will not operate correctly if the system voltage and frequency do not matc h the sources.
Note: Disable the test password only during service
unless the transfer switch is installed in a secure location.
TP-6883 4/21 27Section 1 Operation
1.12.3 Reset Default Parameters
1.12.4 Reset and Disable Test Password
Resetting to the default parameters will reset all parameters, including the system voltage and frequency, to a factory default setting. The default system voltage and frequency settings may not match the settings for your application.
The transfer switch will not operate correctly if the system voltage and frequency do not match the sources. Use the Set Sources menu to set the system voltage and frequency after resetting to the default parameters. See Section 6 for instructions.
Check the system operation to verify the settings after resetting.
Reset the Test password to r eturn the test password to the default, 0000.
Note: Disable the test password only during service
unless the transfer switch is installed in a secure location.
Disabling the test password allows any user to initiate a test sequence from the controller’s user interface without entering a password. Initiating a test starts the generator set and, if a loaded test is selected, transfers the load.
TP-6883 4/2128 Section 1 Operation
Section 2 Sequence of Operation
This section explains the transfer switch sequence of operation during the following events:
D Controller power-up or reset
D Preferred source loss and return
D Te s t
D Exercise
D Emergency source loss and return
The Sequence of Operation descriptions in Sections 2.2 through 2.4 describe the transfer switch normal operation for standard, programmed, and closed transition models. Operation can be affected by faults such as the normal or emergency contacts failing to open or close when signaled to do so.
2.1 Controller Power-up/Reset
Following is an explanation of the sequence of operation for the Decision-Makerr MPAC 1500 ATS Controller when power is initially applied to the controller or a controller reset occurs.
1. Controller self test is executed.
2. System parameters are downloaded from nonvolatile memory.
3. Contactor position and source availability are determined.
4. If neither source is acceptable, the contactor does not change p osition.
5. If both sources are available, the controller immediately transfers the contactor to the preferred source.
6. If only one source is available, the controller immediately transfers the contactor to that source, executing only the off-position and load control time delays.
If the available source is the preferred source, and the contactor is in the standby position, the contactor transfers to preferred, the engine cooldown time delay runs, and then the engine start contacts open.
If the available source is the preferred source and the contactor is already in the preferred position, the engine start contacts open immediately, bypassing the engine cooldown time delay.
TP-6883 4/21 29Section 2 Sequence of Operation
2.2 Sequence of Operation, Standard Transition Models
2.2.2 Exerciser Operation, Standard Transition
Operation can be affected by faults such as the normal or emergency contacts failing to open or close when signaled to do so.
2.2.1 Preferred Source Loss and Return, Standard Transition
Following is an explanation of the transfer switch sequence of operation when Preferred Source failure is detected.
Preferred Source Fails
1. Load control contacts open.
2. Engine start time delay expires.
3. The generator is signaled to start.
4. The generator starts and the standby source becomes available.
5. Preferred-to-standby time delay expires.
6. Contactor transfers to standby.
7. Post-transfer load control sequences run.
Unloaded Exercise Sequence Starts
1. Exerciser timer begins.
2. The generator is signaled to start.
3. The generator starts and the standby source becomes available.
4. The load bank control is activated.
Unloaded Exercise Sequence Ends
1. The load bank control is deactivated.
2. Engine cooldown time delay expires.
3. The engine start contacts open, signaling the generator to stop.
Loaded Exercise Sequence Starts
1. Exerciser timer begins.
2. The generator is signaled to start.
3. The generator starts and the standby source becomes available.
8. Load control contacts close.
Preferred Source Returns
1. Standby-to-preferred and pre-transfer load control time delays expire.
2. Load control contacts open.
3. Contactor transfers to preferred source.
4. Post-transfer load control sequences and engine cooldown time delay expire.
5. Load control contacts close.
6. The engine start contacts open, signaling the generator to stop.
4. Preferred-to-standby time delay and pre-transfer load control sequences run.
5. Load control contacts open.
6. Contactor transfers to standby.
7. Post-transfer load control sequences run.
8. Load control contacts close.
Emergency Source Fails (Normal Source is available)
1. Exerciser is deactivated.
2. Load control contacts open.
3. Contactor immediately transfers to preferred.
4. Immediate failure to acquire standby alarm.
5. Post-transfer load control sequences and engine cooldown time delay expire.
6. Load control contacts close.
7. Engine start contacts open.
TP-6883 4/2130 Section 2 Sequence of Operation
Loading...
+ 94 hidden pages