Kohler M340+ Service And Parts Manual

Service and Parts
Automatic Transfer Switches
Models:
M340+
Logic:
Microprocessor
U.S.A. Plant ISO Registered
TP-5672 11/95d
SUBJECT PAGE SUBJECT PAGE
Safety Precautions and Instructions I. . . . . . . . . . .
Introduction i. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Related Manuals i. . . . . . . . . . . . . . . . . . . . . . . .
Service Assistance i. . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 1. Specifications 1-1. . . . . . . . . . . . . . . . . . .
Purpose of Switch 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Components of Switch 1-1. . . . . . . . . . . . . . . . . . . . . . .
Ratings 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interpreting a Transfer Switch Part Number 1-3. . . . .
Specifications 1-4.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard Features 1-4. . . . . . . . . . . . . . . . . . . . . . .
Shunt-Jumper-Controlled Accessories 1-5. . . . . .
Optional Features 1-5. . . . . . . . . . . . . . . . . . . . . . . .
Section 2. Operation 2-1. . . . . . . . . . . . . . . . . . . . . . .
LED Indicators 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Switches and Indicators 2-2. . . . . . . . . . . . . . .
Sequence of Operation 2-3. . . . . . . . . . . . . . . . . . . . . . .
Normal Source Failure 2-3. . . . . . . . . . . . . . . . . . . .
Normal Source Restoration 2-4. . . . . . . . . . . . . . .
Sequence of Operation Programmed Transition 2-6.
Normal Source Failure 2-6. . . . . . . . . . . . . . . . . . . .
Normal Source Restoration 2-7. . . . . . . . . . . . . . .
To Disconnect The P1 Plug 2-9. . . . . . . . . . . . . . . . . . .
Electrical Operation Test 2-9. . . . . . . . . . . . . . . . . . . . .
Section 3. Troubleshooting Guide 3-1. . . . . . . . . .
Section 4. Controller Troubleshooting 4-1. . . . . .
Power to the System 4-2. . . . . . . . . . . . . . . . . . . . . . . . .
Keypad And Status Panel 4-3. . . . . . . . . . . . . . . . . . . .
Normal Source Voltage and Frequency 4-6.. . . . . . . .
Emergency Source Voltage and Frequency 4-9.. . . .
System-Status, Not-In-Automatic Error 4-11.. . . . . . .
System-Status, System-Alert 4-12. . . . . . . . . . . . . . . .
Contactor Position Fault Error Messages 4-12. . . . . .
Transfer Hang Error Message 4-12. . . . . . . . . . . . . . . .
Power-Down Error Message 4-12. . . . . . . . . . . . . . . . .
RAM Or Memory Error Message 4-13. . . . . . . . . . . . .
Manual Transfer Message 4-13. . . . . . . . . . . . . . . . . . .
Manual-to-Off Transfer Message 4-13.. . . . . . . . . . . .
Fault #1 Or Fault #2 Message 4-14.. . . . . . . . . . . . . . .
Programming Mode Not-In-Off 4-15. . . . . . . . . . . . . . .
Engine Operates When it Should Not 4-16. . . . . . . . .
Engine Will Not Start 4-18.. . . . . . . . . . . . . . . . . . . . . . .
Area Protection 4-20. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shunt Jumper-Controlled Options 4-21. . . . . . . . . . . . .
Inphase Monitor 4-23. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Source Monitors 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Plant Exerciser 4-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delays 4-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Override 4-33. . . . . . . . . . . . . . . . . . . . . . . . . . .
Off Delays 4-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 5. Accessory Troubleshooting 5-1. . . . . .
Optional Accessories 5-2. . . . . . . . . . . . . . . . . . . . . . . .
Emergency Source Three-Phase Phase Option 5-2.
Test Switches 5-4.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delay Override Option 5-10. . . . . . . . . . . . . . . . .
Preferred Source Switch 5-14.. . . . . . . . . . . . . . . . . . .
Relay Auxiliary Dry Contacts 5-15. . . . . . . . . . . . . . . . .
Main Shaft Auxiliary Dry Contacts 5-22. . . . . . . . . . . .
Meters 5-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Charger 5-47. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Operation Switches 5-54. . . . . . . . . . . . . . . . . .
Load Shedding Contacts 5-63. . . . . . . . . . . . . . . . . . . .
Remote Communication—RS/232 Or RS/485 5-65. .
Section 6. Service Parts 6-1. . . . . . . . . . . . . . . . . . . .
Introduction 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inner Panel 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delay 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Source monitors 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Switches 6-5.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delay Override Switches 6-5.. . . . . . . . . . . . . . .
Preferred-Source Switches 6-5. . . . . . . . . . . . . . . . . . .
Auxiliary Contacts—Relay 6-5. . . . . . . . . . . . . . . . . . . .
Auxiliary Contacts—Main Shaft 6-5. . . . . . . . . . . . . . . .
Meters 6-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Plant Exercisers 6-11. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Chargers 6-11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Source Monitors—Normal and Emergency 6-12. . . .
Load-Shed Contacts 6-12.. . . . . . . . . . . . . . . . . . . . . . .
Time Delays 6-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A. Glossary of Abbreviations A-1.. . . .
Appendix B. General Controller Information B-1. Appendix C. Commonly Used Accessories C-1. .
Safety Precautions and Instructions
A transfer switch, like any other electromechanical device, can pose potential dangers to life and limb if improperly maintained or imprudently operated. The best way to prevent accidents is to be aware of the potential dangers and to always use good common sense. Below are some general precautions relating to theoperation ofa transfer switch. This manual contains several types of safety precautions which are explained below. SAVE THESE INSTRUCTIONS.
DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the danger is ignored.
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the warning is ignored.
NOTE
Note communicates installation, operation, or maintenance information that is important but not hazard related.
Safety decals are affixed to the generator set in prominent places to advise the operator or service technician of potential hazards. The decals are reproduced here to improve operator recognition. For a further explanation of decal information, refer to the safety precautions throughout this manual. Before operating or servicing the generator set, be sure you understand the messages of these decals. Replace decals if missing or damaged.
Safety decals are affixed to the transfer switch in prominent places to advise the operator or service technician of potential hazards. The decals are reproduced here to improve operator recognition. For a further explanation of decal information, refer to the safety precautions throughout this manual. Before operating or servicing the transfer switch, be sure you understand the messages of these decals. Replace decals if missing or damaged.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage if
the caution is ignored.
TP-5672 11/95
Safety Precautions and Instructions I
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set (negative lead first and reconnect it last).
Accidental starting can cause severe injury or death. Turn generator set master switch to OFF
position, disconnect power to battery charger, and remove battery cables (remove negative lead first and reconnectitlast)to disable generator setbeforeworking on any equipment connected to generator set. The generator set can be started by automatic transfer switch or remote start/stop switch unless these precautions are followed.
II Safety Precautions and Instructions TP-5672 11/95
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Use protective goggles and clothes. Battery acid can cause permanent damage to eyes, burn skin, and eat holes in clothing.
WARNING
Explosion. Can cause severe injury or death. Relays in battery charger cause arcs or sparks.
Locate in a well-ventilated area. Keep explosive fumes away.
Sulfuric acid in batteries can cause severe injury or death. Sulfuric acid in battery can cause permanent
damage to eyes, burn skin, and eat holes in clothing. Alwayswear splash-proofsafety goggleswhen working around the battery. If battery electrolyte is splashed in the eyes or on skin, immediately flush the affected area for15 minutes withlargequantities of cleanwater. Seek immediatemedicalaidin the caseofeyecontact. Never addacidtoa battery once thebatteryhasbeen placed in service. This may result in hazardous spattering of electrolyte.
Sulfuric acid in batteries can cause severe injury or death. Sulfuric acid in battery can cause permanent
damage to eyes, burn skin, and eat holes in clothing. Alwayswear splash-proofsafety goggleswhen working around the battery. If battery electrolyte is splashed in the eyes or on skin, immediately flush the affected area with large quantities of clean water. Continue flushing with water until emergency help arrives Seek immediatemedicalaidin the caseofeyecontact. Never addacidtoa battery once thebatteryhasbeen placed in service. This may result in hazardous spattering of electrolyte.
Explosioncancause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flame or spark to occur near a battery at any time, particularly when it is being charged. Avoid contacting terminals with tools, etc., to prevent burns and sparks that could cause an explosion. Remove wristwatch, rings, and any other jewelry before handling battery. Never connect negative (--) battery cable to positive (+) connection terminal of starter solenoid. Do not test batterycondition by shortingterminals together. Sparks could ignite battery gases or fuel vapors. Ventilate any compartment containing batteries to prevent accumulation of explosive gases. To avoid sparks, do not disturb battery charger connections while battery is being changed. Always turn battery charger off before disconnecting battery connections. Remove negative lead first and reconnect it last when disconnecting battery.
TP-5672 11/95
Safety Precautions and Instructions III
Hazardous Voltage/ Electrical Shock
DANGER
Hazardous voltage. Will cause severe injury or death.
Do not open enclosure until all power sources are disconnected.
(600 Volt and above)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect power sources before servicing. Barrier must be installed after adjustments, maintenance, or servicing.
(600 Volt and above)
WARNING
WARNING
Hazardous voltage. Can cause severe injury or death.
Do not open enclosure until all power sources are disconnected.
(under 600 Volt)
Hazardous voltage can cause severe injury or death. Whenever electricity is present, there is the
hazardofelectrocution. Openmaincircuitbreaker on all power sources before servicing equipment. Electrically ground the generator set and electrical circuits when in use. Never come into contact with electrical leads or appliances when standing in water oron wet ground, as the chance of electrocution is increased under such conditions.
Hazardous voltage can cause severe injury or death. Short circuits can cause bodily injury and/or
equipment damage. Do not contact electrical connections with tools or jewelry while adjustments are made. Remove wristwatch, rings, and jewelry that can cause short circuits.
Hazardous voltage can cause severe injury or death. To prevent the possibility of electrical shock,
disconnect harness plug before installing any accessories involving connection to transformer assembly primary terminals 76, 77, 78, and 79. Terminals are at line voltage!
(S340, R340, and R33 models only.)
Hazardous voltage can cause severe injury or
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Barrier must be installed after adjustments, maintenance, or servicing.
(under 600 Volt)
IV Safety Precautions and Instructions TP-5672 11/95
death. To prevent the possibility of electrical shock, disconnect harness plug before installing any accessories involving connection to transformer assembly primary terminals on microprocessor logic models. Terminals are at line voltage!
Hazardous voltage can cause severe injury or death. To prevent the possibility of electrical shock,
de-energize the normal power source to be connected to the transfer switch before makingany line or auxiliary connections.
Hazardous voltage can cause severe injury or death. De-energize bothnormal and emergencypower
sourcesbefore proceeding. Movegenerator set master switch on controller to OFF position and disconnect battery negative (--) before working on transfer switch! Turn the transfer switch selector switch to the OFF position.
Hazardous voltage can cause severe injury or death. Disconnect inner panel harness at in-line
connector. This will de-energize circuit board and logic circuitry, but allow transfer switch to continue to supply utility power to necessary lighting and equipment. Hazardousvoltage will exist ifanyaccessories mounted to inner panel are NOT wired through the inner panel harness and de-energized by in-line connector separation. Such accessories are at line voltage.
TP-5672 11/95
Safety Precautions and Instructions V
Heavy Equipment
WARNING
Unbalanced weight. Improper lift can cause severe injury or death and/or equipment damage.
Use adequate lifting capacity. Never leave transfer switch standing upright unless it is securely bolted in place or stabilized.
VI Safety Precautions and Instructions TP-5672 11/95
Notes
NOTE
Hardware Damage! Transfer switch may use both
American standard and metric hardware. Use the correct size tools to prevent rounding of bolt heads and nuts.
NOTE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. American Standard hardware uses a series of markings and metric hardware uses a numeric system to indicate hardness. Check markings on bolt head and nuts for identification.
NOTE
A manual operator handle is provided on the transfer switch for maintenance purposes only. Return the transfer switch to the normal position. Remove manual operator handle (if used) and store it on the transfer switch in the placeprovided when service is completed.
NOTE
Perform voltage checks in the order given to avoid damaging the switch.
NOTE
These battery chargers are designed strictly for use in thistransfer switch andconform with ULand CSAlisting requirements where specified. Do not use battery charger before reading instructions.
NOTE
Connect source and load phases as indicated by the markings and drawings. Improper connections may causeshortcircuitsand can causephase-sensitiveload devices to run in reverse or prevent load devices from functioning.
NOTE
Charger Damage! Connect battery charger only to a
batterywith thesame DC voltage as the battery charger output rating.
NOTE
Covertransferswitchduring installation to keepdirt,grit, metal drill chips, etc., out of components. Cover solenoid mechanism during installation. After installation, use manual operating handle to position contactor to ensure that it operates freely. Do not use a screwdriver to force contactor mechanism.
TP-5672 11/95
Safety Precautions and Instructions VII
Introduction
This manual covers the operation, troubleshooting, repair,and service parts for the M340+ microprocessor logic controller.
Read through this manual and carefully follow all procedures and safety precautions to ensure proper transferswitchoperationandtoavoidbodilyinjury.Keep this manual with the transfer switchfor futurereference.
Service requirements are minimal but are very important to the safe and reliable operation of the transfer switch; therefore, inspect associated parts often. It is recommended that an authorized service distributor perform required servicing to keep the switch in top condition.
All information found in this publication isbased on data availableat timeof printing. The manufacturerreserves the right to make changes to this literature and the products represented at any time without notice and without incurring obligation.
List of Related Manuals
The logic controller covered in this manual is part of a family of related devices. Separate service and parts manuals are available for each group within the overall family. Be sure this manual is the correct manual for the automatic transfer switch.
A power conversion unit is included in each automatic transfer switch. There are three types of power conversion units and each type is covered in a separate service and parts manual. Available power conversion units and the related manual numbers are as follows:
Service/
Power Switch Device
Mechanically held or electrically held contactors
Molded-case circuit breakers or switch
Standard contactor, programmed transition, and Bypass-Isolation
Parts Manual
TP-5667
TP-5666
TP-5668
Service Assistance
For sales and service in the U.S.A. and Canada check the yellow pages of the telephone directory under the headingGENERATORS—ELECTRICfor anauthorized service distributor/dealer or call 1-800-544-2444.
KOHLER CO., Kohler, Wisconsin 53044 U.S.A. Phone: 920-565-3381 Fax: 920-459-1646 (U.S.A. Sales)
920-459-1614 (International)
To ensure supply of correct parts or information, make note of the following identification numbers in the spaces provided:
PART NUMBER AND SERIAL NUMBER
Part and serial numbers are provided on the nameplate attached to the transfer switch.
Part No.
Serial No.
TP-5672 11/95 Introduction i
Notes
TP-5672 11/95Introduction ii
Section 1. Specifications
Purpose of Switch
An automatic transfer switch (ATS)is a device used for transferring critical electrical loads from a normal (preferred) source of electrical power to an emergency (standby) source. This transfer occurs automatically when the normal source voltage fails, or is substantially reduced, and the emergency source’s voltage has reached an acceptable level.
Upon normal source failure, the automatic transfer switchcontrollersignalsthe generator set(s)tostartand
Components of Switch
A typical automatic transfer switch includes the actual power switching device and the logic controller to perform power monitoring and transfer sequencing tasks. See Figure 1-1. An interface board is also included to match the controller inputs/outputs to the levels required by a specific switching device.
The three functional units that make up the automatic transfer switch are mounted in an enclosure with a hinged front door. The controller mounts on the back of thefront doorso its controls and indicatorsare available to an operator. A signal cable with in-line connectors to facilitate component replacement and door removal connects the controller to the interface board and the switching devices.
transfer to the emergency source. The automatic transfer switch controller continuously senses for an acceptable normal source and will retransfer the load to the normal source after it has been restored to an acceptable level. After retransfer of the load, the generator set start signal is removed and the generator set(s) is allowed to shut down.
1
2
TP-5672 11/95
3
1. Power Conversion Unit
2. Interface Panel
3. Logic Controller
Figure 1-1. Transfer Switch Components
Specifications 1-1
567111
Normal (Utility)
Power
Emergency (Generator) Power
Generator
Start Generator
Power Switching Device
To Load
Figure 1-2. Basic Transfer Switch Block Diagram
Ratings
Anameplate is attachedtotheautomatic transfer switch enclosure. See Figure 1-3. The nameplate label includes a factory part number coded to provide characteristic and rating information that affects installationandoperation. Copy the partnumberinto the blank spaces provided in the introduction and then use the charts in Figure 1-4 to interpret the part number.
NOTE
Also copy the part number and serial number from the nameplate into the spaces provided in the Service Assistance Section of the Introduction for use when requesting service or parts.
Interface
Logic
Controller
Automatic Transfer Switch
AUTOMATICTRANSFER SWITCH
PARTNO. ZCS-160341-0800
SERIAL NO. VOLTS PHASE HERTZ
KOHLER CO. KOHLER WISCONSIN 53044
567112
KOHLER
AMPS WIRES POLES
295232
Figure 1-3. Transfer Switch Nameplate
1-2 Specifications TP-5672 11/95
Interpreting a Transfer Switch Part Number
Record the transfer switch part number in the boxes below. The transfer switch part number defines characteristics and ratings as explained in the accompanying chart.
Type of Switch Type of Logic Voltage & Frequency
Number of
Poles
Number of
Wires
Type of
Enclosure Amperage Rating Code
Kohler Part Number Key
This chart explains the Kohler transfer switch part numbering code system. The sample part number shown is for a standard molded-case switch with M340+ logic rated at 480 volts, 60 hertz, 3-phase, 3-pole, and 4 wires in a NEMA 1 enclosure with an amperage rating of 80 amperes.
Classification of Power Switch
M: Switch or Circuit Breaker T: Electrically & Mechanically Held Z: Contactor Style
Type of Power Switch
C: Contactor E: Electrically Held Contactor L: Mechanically Held Contactor M: Molded-Case Circuit Breaker N: Molded-Case Switch (no protection)
Type of Switch
S: Standard B: Bypass
Type of Logic
5: M340+ 6: M340+ with programmed transition
Voltage Code
60:600 Volt, 60 Hz 66: 480 Volt, 60 Hz 62:120 Volt, 60 Hz 68: 208 Volt, 60 Hz 63:220 Volt, 50 Hz 71: 380 Volt, 50/60 Hz 64:240 Volt, 60 Hz
SAMPLE PART NUMBER
MNS-566341-0080
Number of Poles
2: 2 pole, 1 phase (MM_, MN_, TE_, TL_, devices
will be supplied with 3 poles) 3: 3 pole, 3 phase 6: 4 pole, fully rated switched poles
(no overlapping neutral)
Number of Wires
2: 2 wire 3: 3 wire 4: 4 wire
Enclosure
1: NEMA type 1
Amperes
Available sizes vary with the type of switch.
Figure 1-4. Transfer Switch Model Description
TP-5672 11/95
Specifications 1-3
Specifications
The specifications listed below are for the M340+ logic controller. See the respective power switching device manual for its specifications.
Standard Features
D Normal source voltage sensing adjustable from
75% to 130% of normal for pickup and from 70% to 135% for dropout; provides monitoring line-to-line for all phases of 3-phase switches.
D TDNE (Time Delay Normal-to-Emergency)
adjustable 0 to 5 minutes.
D TDES (Time Delay Engine Start) adjustable from
0 to 6 seconds.
D TDEN (Time Delay Emergency-to-Normal)
adjustable 0 to 30 minutes.
D Program Transition (Center off)—time delay
during transfer with neither source connected to the load. Adjustable 0 to 2 minutes.
D LCD digital voltmeter. D LCD digital running time meter.
D LCD digital transfer counter. D LCD digital frequency meter. D Status panel with keypad data entry. D Area protection with override. D TDEC (Time Delay Engine Cooldown) adjustable
from 0 to 30 minutes.
D Generator engine start contacts. D Indicators for switch position—normal and
emergency.
D Indicators for source available—normal and
emergency.
D Lamp test switch, momentary. D Underfrequency sensing—one phase emergency
source only.
1-4 Specifications TP-5672 11/95
Shunt-Jumper-Controlled Accessories
Enable or disable shunt-jumper-controlled accessories by altering socket JP1 on the main logic board. See Figure 1-5. All shunt-jumper features are disabled from thefactoryunlessthe function was ordered atthetimeof purchase. But features can be enabled after factory delivery by adding jumpers to the JP1 socket.
Main Logic Board
JP1
MANUAL
TIME
PLANT
VOLT/
PHASE
OFF
Figure 1-5. Logic Board Accessory Programming
Shunts
D Manual Override. Enabling manual override
allows automatic transfer to an available source when the connected source fails. Transfer time delays will be bypassed. Disabling manual override causes the logic board to wait for manual operation. The logic board will not automatically seek the available source.
D Inphase Monitor. Abnormal inrush currents from
switching between two live power sources can damage motors and related equipment. The purpose of the inphase monitor is to minimize abnormal inrush currents to equipment when the ATS transfers from one source to a new power source. The inphase monitor samples a single phase of one source and compares it to a single phase of the other source. When the two voltages are within the desired phase angle and approaching a zero phase angle difference, the inphase monitor signals the transfer switch to
OVRIDE DELAY EXER FREQ SEQUENCER MONITORIN-PHASE DELAYS
567215
operate. The transfer may be from utility to generator,from generator to generator,or utility to utility.
NOTE
This option is available only on contactor type, nonprogrammed transition switches. If the contactor is not of this type, then the controller will not allow this option to be enabled. Enable this accessory by installing the INPHASE MONITOR jumper on the controller’s main logic board.
D Phase Rotation and Anti-Single Phasing. This
function provides source monitoring for both the normal and emergency sources. The feature includesphaserotation(A B C only)andanti-single phase protection. This option must be used in conjunction with accessory DD-05-K in order to provide source monitoring on the emergency side. Enable this accessory by installing the PHASE SEQUENCER jumper on the controller’s main logic board.
D Normal and Emergency Source Sensing. This
function provides overvoltage sensing on all phasesof the normalsource,over/underfrequency sensing on one phase of the normal source, overvoltage sensing on one phase of the emergency source, and overfrequency sensing on one phase of the emergency source. Enable this accessory by installing theVOLT/FREQjumper on the controller’s main logic board.
D Plant Exerciser. This function enables a no-load
plantexerciser.Userhasachoice of 7-day,14-day, or calendar-based exercise modes. Enable this accessory by installing the PLANT EXER jumper on the controller’s main logic board.
D Extended Time Delay. This function extends the
time delay to 99 minutes for TDNE, TDES, TDEN, TDOE, TDON, and TDEC. Enable this accessory by installing the TIME DELAY jumper on the controller’s main logic board.
D Off Position Time Delay. This function enables
the time delay during transfer when neither source is connected to the load. Enable this accessory by installing the OFF DELAYS jumper on the controller’s main logic board.
Optional Accessories
See Appendix C for details of optional accessories. The nameplate includes a list of the accessories selected. See Figure 1-3.
TP-5672 11/95
Specifications 1-5
Section 2. Operation
Control Switches and Indicators
Various optional control switches and indicator lamps may be present on the transfer switch door depending
AUTO
TRANSFER
MANUAL
TRANSFER TO
EMERGENCY
MANUAL
TRANSFER TO
OFF
MANUAL
TRANSFER TO
NORMAL
MANUAL
TRANSFER
TEST SWITCH
NORMAL TEST
BYPASS
EMERGENCY TO
NORMAL TIME DELAY
BYPASS NORMAL
TO EMERGENCY
TIME DELAY
AUTO INHIBIT
Contactor Position Time Delays
Normal On EndEmergency
·
Source Available
Normal Emergency
· ·
System Status
Not In Automatic
· ·
Programming Mode Not in Off
·
Flashing, Local Steady,Remote
· ·
Plant Exerciser Load Shed Inphase Monitor Area Protection
· · · ·
Off
·
·
System Alert
Accessory Active
on the options chosen. See Figure 2-1 for LED, Switch, and Key locations.
Engine Start
·
·
Normal To Emergency
·
·
Emergency To Normal
·
·
Engine Cooldown
·
·
Off Position
·
·
Figure 2-1. Front Panel
LED Indicators
Contactor Position. LEDs indicate transfer switch
position—NORMAL (green), EMERGENCY (red), or OFF (yellow).
Source Available. LEDs indicate source with acceptable voltage and frequency—Normal (green) and/or Emergency (red).
System Status
Not in Automatic (red). LED flashes to indicate that
Test switch is actuated, or Auto/Manual switch is in the Manual position.
System Alert (red). LED flashes to indicate possible problem with contactor or logic operation. System alert will also flash if any fault signals are received from the generator set.
Programming Mode Not in Off (yellow). LED flashes to indicate that programming switch is in the LOCAL position. A steady, nonflashing light indicates that the programming switch is in the REMOTE position.
Operation 2-1TP-5672 11/95
Time Delays
Engine Start (If emergency source is a generator set).
ON LED indicates that engine-start time delay is timing. ENDLED indicates thattheengine has been signaledto start.
Normal to Emergency. ON LED indicates that the normal-to-emergency time delay is timing. END LED indicates that the time delay has completed timing.
Emergency to Normal. ON LED indicates that the emergency to normal time delay is timing. END LED indicates that the time delay has completed timing.
transfer from emergency to normal and normal to emergency when sources are near synchronization.
NOTE
When a programmed transition switch is ordered, the inphase monitor option is disabled by the microprocessor.
Area Protection. Area protection LED indicates that the controller is in the area protection mode. The generator will be signaled to START and the contactor will transfer to the emergency positionand remain there while in area protection.
Engine Cooldown. ON LED indicates that the generator set engine cooldown timer is timing. END LED illuminates until the engine has shut down.
Off Position. ON LED indicates that the time delay off positionistiming. ENDLEDindicatesthatthetimedelay has completed timing.
Accessory Active
Plant Exerciser. Plant excerciser LED indicates that
the system is in the exerciser mode. LoadShed. LoadshedLEDindicates that programmed
load shedding is active. Inphase Monitor (availableon ZCtype powerswitches
only). Inphase monitor LED indicates that the sources are being monitored for phase relationship to allow inphase transfer. The inphase monitor will permit
Control Switches
Test Switch (Standard). Move the test switch to the
TEST position to simulate a normal source outage. Not-in-Automatic system status light will flash.
Bypass N-E Time Delay Pushbutton Switch (Option). If the bypass normal-to-emergency time
delay pushbutton is pressed when normal-to-emergency time delay is on, time delay will end.
Bypass E-N Time Delay Pushbutton Switch (Option). If the bypass normal-to-emergency time
delay pushbutton is pressed, when emergency-to-normal time delay is on, time delay will end.
Manual Transfer to Emergency Switch (Option).
When the transfer switch control is in the manual mode of operation and manual to emergency is required, press the manual transfer-to-emergency pushbutton to
Programming Mode Switch
NOTE
Theprogramming modeswitch keysshould bekept ina safe place to prevent unwanted tampering with the transfer switch control. Do not leave the programming switch in the LOCAL position with the transfer switch unattended.
Remote. Allows both status monitoring and setting of the transfer switch controls by a connected personal computer.
Off. Transfer switch status settings and power source may be monitored from the local LCD display or connected computers.
Local. Allows both status monitoring and setting of transfer switch control from the microprocessor’s LCD display and keypad.
cause the transfer switch to transfer to the emergency position.
Manual Transfer to Off Switch (Option). When the transfer switch control is in the manual mode of operation and manual to off is required, press the manual transfer-to-emergency pushbutton to cause the transfer switch to transfer to the off position.
Manual Transfer to Normal Switch (Option). When the transfer switch control is in the manual mode of operation and manual to normal is required, press the manual transfer-to-emergency pushbutton to cause the transfer switch to transfer to the normal position.
Auto/Inhibit Switch (Option). If the auto/inhibit switch is in the AUTO position, the transfer switch will operate normally. If the switch is in the Inhibit position, the transfer switch will not transfer under any conditions.
2-2 Operation TP-5672 11/95
Sequence of Operation
This section describes the correct operation of a microprocessor-controlled transfer switch.
Sequence of Operation Standard Switch
When the Normal Source Fails
1. The source-available normal LED turns off.
2. The time-delay-engine-start ON LED illuminates to indicate the engine-start-time-delay is timing.
3. The time-delay-engine-start END LED illuminates to indicate the engine has been signaled to start.
4. The source-available emergency LED illuminates.
5. The time-delay normal-to-emergency ON LED illuminates to indicate the normal-to-emergency time delay is timing.
6. The time-delay normal-to-emergency END LED illuminates to indicate the time delay has completed timing.
7. The load-shed LED illuminates at the same time all loads to be shed are disconnected from the switch (if equipped with load-shed option).
8. The inphase monitor LED illuminates (if equipped with inphase monitor option on ZC type power switches only). The controller monitors the two voltagesto makesure theyare ata desiredphase angle and approaching zero phase angle difference.
9. The contactortransfers tothe emergency position after the load-shed time-before-transfer timer has completed timing. The contactor-position normal LED turns off and the contactor-position emergency LED illuminates. The inphase monitor LED turns off.
10. After the load-shed time-after-transfer timer has completed timing, the selected loads for the emergencysource are nowreturnedto the switch. The load-shed LED turns off (if equipped with load-shed option).
Operation 2-3TP-5672 11/95
When the Normal Source Returns
1. The source-available, normal LED illuminates.
completed timing. The contactor-position emergency LED turns off and the contactor-position normal LED illuminates.
2. The time-delay emergency-to-normal ON LED illuminates to indicate the emergency-to-normal time delay is timing.
3. The time-delay emergency-to-normal END LED illuminates to indicate the time delay has completed timing.
4. The load-shed LED illuminates at the same time all loads to be shed are disconnected from the switch (if equipped with load-shed option).
5. The inphase monitor LED illuminates (if equipped with load-shed option).
6. The contactor transfers to the normal position after the load-shed time-before-transfer timer has
7. After the load-shed time-after-transfer timer has completed timing, the selected loads for the normal source are returned to the switch. The load-shed LED turns off (if equipped with load-shed options).
8. The time-delay engine-cooldown ON LED illuminates to indicate the generator set engine cooldown timer is timing.
9. The time-delay engine-cooldown END LED stays illuminated until the generator has shut down.
10. The source-available, emergency LED turns off.
2-4 Operation TP-5672 11/95
Microprocessor-Controlled Transfer Logic
Standard Switch
Normal Source Failure
Time Delay Engine Start
Time Delay Normal-to-Emergency
Load Shed (all)—if equipped
Inphase Monitor—if equipped
Contactor Transfer to Emergency Position
Load Return (programmed sequence)—if equipped
Normal Source Return
Time Delay Emergency-to-Normal
Load Shed (all)—if equipped
Inphase Monitor—if equipped
Contactor Transfer to Normal Position
Load Return (programmed sequence)—if equipped
Time Delay Engine Cooldown
Operation 2-5TP-5672 11/95
Sequence of Operation Programmed Transition Switch
When the Normal Source Fails
NOTE
When a programmed transition switch is ordered, the inphase monitor option is disabled by the microprocessor.
1. The source-available, normal LED turns off.
2. The time-delay-engine-start ON LED illuminates to indicate the engine-start-time-delay is timing.
3. The time-delay-engine-start END LED illuminates to indicate the engine has been signaled to start.
4. The source-available emergency LED illuminates after the generator is at rated voltage and frequency.
5. The time-delay normal-to-emergency ON LED illuminates to indicate the normal-to-emergency time delay is timing.
6. The time-delay normal-to-emergency END LED illuminates to indicate the time delay has completed timing.
7. The load-shed LED illuminates at the same time all loads to be shed are disconnected from the switch (if equipped with load-shed option).
8. After the load-shed time-before-transfer timerhas completed timing, the contactor transfers to the Off position. The contactor-position normal LED turns off and the contactor-position Off LED illuminates.
9. The time-delay-off-position ON LED illuminates to indicate the Off position time delay is timing.
10. The time-delay-off-position END LED illuminates to indicate the time delay has completed timing.
11. The contactor transfers to the emergency position. The contactor-position Off LED turns off and the contactor-position emergency LED illuminates.
12. After the load-shed time-after-transfer timer completes timing, the selected loads for the emergencysource arereturned to the switch. The load-shed LED turns off (if equipped with load-shed option).
2-6 Operation TP-5672 11/95
When the Normal Source Returns
1. The source-available, normal LED illuminates.
2. The time-delay emergency-to-normal ON LED illuminates to indicate the emergency-to-normal time delay is timing.
3. The time-delay emergency-to-normal END LED illuminates to indicate the time delay has completed timing.
4. The load-shed LED illuminates at the same time all loads to be shed are disconnected from the switch (if equipped with load-shed option).
5. After the load-shed time-before-transfer timerhas completed timing, the contactor transfers to the Off position. The contactor-position emergency LED turns off and the contactor-position Off LED illuminates.
6. The time-delay off-position ON LED illuminates to indicate the off-position-time-delay is timing.
7. The time-delay off-position END LED illuminates to indicate the time delay has completed timing.
8. The contactor transfers to the normal position. The contactor-position OFF LED turns off and the contactor-position normal LED illuminates.
9. After the load-shed time-after-transfer timer has completed timing, the selected loads for the normal source are returned to the switch. The load-shed LED turns off (if equipped with load-shed option).
10. The time-delay-engine-cooldown ON LED illuminates to indicate the generator set engine cooldown timer is timing.
11. The time-delay-engine-cooldown END LED stays illuminated until the generator has shut down.
12. The source-available emergency LED turns off.
Operation 2-7TP-5672 11/95
Microprocessor-Controlled Transfer Logic
Programmed Transition Switch
Normal Source Failure
Time Delay Engine Start
Time Delay Normal-to-Emergency
Load Shed (all)—if equipped
Contactor Transfer to Off Position
Time Delay Off-to-Emergency
Contactor Transfer to Emergency Position
Load Return (programmed sequence)—if equipped
Normal Source Return
Time Delay Emergency-to-Normal
Load Shed (all)—if equipped
Contactor Transfer to Off Position
Time Delay Off-to-Normal
Contactor Transfer to Normal Position
Load Return (programmed sequence)—if equipped
Time-Delay-Engine-Cooldown
2-8 Operation TP-5672 11/95
To Disconnect The P1 Plug
1. If the transfer switch isin the normal position, open the emergency-source circuit breaker.
it is available, after a time delay. For immediate retransfer, open and then reclose the emergency-source circuit breaker. Place the generator set start switch in the AUTO position.
2. If the transfer switch is in the emergency position, open the normal-source circuit breaker.
3. Separate the in-line disconnect plug by grasping and squeezing the plug. Do NOT pull on the wires.
560423
Electrical Operation Test
Place the transfer switch in the NORMAL position. Use thefollowing procedureto check theelectrical operation of the automatic transfer switch:
1. Press andhold the testpushbutton for 15seconds. See Figure 2-1.
2. The generator set should start and run after the time delay engine start (TDES) completed timing.
3. The transfer switch will transfer to the emergency position. The transfer occurs after the normal-to-emergency time delay (TDNE) has completed timing.
4. Release the test pushbutton. The transfer switch retransfers to normal after the emergency-to-normal time delay.
5. Time delay engine cooldown (TDEC) allows the engineto continue running foranunloaded running time. The transfer switch TDEC will complete timing before any TDEC function in the generator set controller begins timing.
6. Close load circuit breaker(s) when loads may be safely energized.
Figure 2-2. In-Line Disconnect Plug
To Reconnect The P1 Plug
1 Engage the in-line disconnect plugby grasping the
connectors and pressing them together. See Figure 2-2.
2 If thetransfer switch isin the normalposition, place
thegenerator set startswitchin the AUTOposition. Then close the emergency-source circuit breaker.
3. If the transfer switch is in the emergency position, close the normal-source circuit breaker. The load willautomatically retransferto the normalsource, if
NOTE
Connecting the transfer switch in-line disconnect plugs(P1)togetherwhen the generator controller’s master switch is in the AUTO position causes the generator set to IMMEDIATELY start and run until the generator set controller’s cooldown timer completes timing.
This completes functional tests of the transfer switch. Leave the AUTO/MANUAL switch in the AUTO TRANSFER position.
Operation 2-9TP-5672 11/95
Section 3. Troubleshooting Guide
For location of pushbuttons, switches, LEDs, and keys referred to in this section, see Figure 2-1. Refer to Figure 3-1 as a guide to troubleshooting problems with
Problem Refer to Section 4—Controller Troubleshooting
None of the LEDs are on and the LCD is blank Power to the system Pressing a key on the keypad does not supply the appropriate
response Every LED does not turn on and every character block on the LCD
does not blacken The normal source should be available but the Source-Available,
Normal LED is not on The emergency source should be available but the
Source-Available, Emergency LED is not on The Automatic/Test pushbutton is pressed, the Automatic/Inhibit
switch (option DD-09) is set to Inhibit, or the Automatic-Transfer key switch (option DD-29) is set to manual, but the System-Status, Not-In-Automatic LED is not flashing
The System-Status, System-Alert LED is flashing; check the LCD for a message
The LCD displays Auxiliary-Switch Fault or Double Auxiliary--Switch fault message
The LCD displays Transfer Hang error message Transfer hang error message The LCD displays Power-Down error message Power-down error message The LCD displays RAM or Memory error message RAM or memory error message The Programming-Mode-Not-In-Off LED is flashing Programming-mode-not-in-off The engine operates when it should not be operating Engine operates when it should not The engine should start Engine will not start One of the control options is not working (the control options
include the inphase monitor, source-phase-sequence, normal/emergency voltage/frequency sensing, plant exerciser, extended time delay,and manual override)
the microprocessor logic controller. Refer to Figure 3-2 as guide to troubleshooting problems with the microprocessor accessories.
Keypad and status panel
Keypad and status panel
Source-available, normal error
Source-available, emergency error
System-status, not-in-automatic error
System-status, system-Alert error
Auxiliary-switch fault or double auxiliary-switch fault error message
Shunt-jumpered controlled options
TP-5672 11/95
Figure 3-1. Microprocessor logic controller troubleshooting chart
TroubleshootingGuide
3-1
Problem Refer to Section 5—Accessory Troubleshooting
Controller will not sense three-phase emergency voltage Phase sequencer,accessory DD-05 The generator set does not start when the test switch is in the
Test switch, accessory DD-06 and DD-07
engine start position The generator set does not start when the test switch is in the test
Test switch, accessory DD-06 and DD-07
position The normal-to-emergency time delay pushbutton does not work Time delay override, accessory DD-08 The emergency-to-normal time delay pushbutton does not work Time delay override, accessory DD-08 The auxiliary dry contacts relay boards do not operate Relay auxiliary dry contacts, accessory DD-14 The analog meters are not working Meters, accessory DD-18 The battery charger is not working Battery charger, accessory DD-24 The manual transfer to emergency source does not work Manual operation switches, accessory DD-29 The manual transfer to normal source does not work Manual operation switches, accessory DD-29 The manual transfer to off does not work Manual operation switches, accessory DD-29 The auto/manual switch does not work in the manual position Manual operation switches, accessory DD-29 The auto/manual switch does not work in the auto position Manual operation switches, accessory DD-29 The load shed contacts do not work Load-shed contacts, accessory DD-35 Problems with remote communication exist Remote communication—RS/232 or RS/485, accessory
DD-51
Figure 3-2. Accessory troubleshooting chart
3-2 TroubleshootingGuide
TP-5672 11/95
Section 4. Controller Troubleshooting
The following section will assist in solving common problems with the M340+ controller. Note any optional accessoriesthatmayhavebeenfurnishedonthisswitch
Is the LCD screen blank and no LEDs illuminated?
Is there 19 vac between terminals TB-AC1-NAS and TB-AC1-NCS of the power supply board?
No
Yes
Replace the power supply board.
Is a battery connected to terminals TB-DC1-29 and TB-DC1-34 of the power supply board?
Yes
Is there rated battery voltage between terminals TB-DC1-29 and TB-DC1-34 of the power supply board?
No
Check battery and wiring from battery to assembly for open of shorted leads.
Is an optional remote communications board installed?
Yes No
Is there 10 vdc between pin P2-13 of plug 2 and terminals TB-DC1-34 of the power supply board?
Is there normal source voltage between terminals TB-AC1-NA and TB-AC1-NC of the power supply board?
Is there 10 vdc between terminals TB-DC1-30 and TB-DC1-34 of the power supply board?
No
Replace the load-shed board.
No
and review their operation in section 5—Accessory Troubleshooting.
No
Yes
Is there from 12 to 30 vdc
No
Yes
Yes Yes
Yes
between terminals TB-DC1-23 and TD-DC1-34 of the power supply board?
Replace the logic board.
Yes
Troubleshooting complete.
Check the normal source and contactor-to-power supply board wiring harness for open or shorted leads.
Yes
Is there an optional load-shed board installed?
No
Disconnect the load-shed board.
Yes
Recheck the voltage at terminals TB-DC1-23 and TB-DC1-30 of the power supply board, and pin P2-13 of plug 2. Are the voltages correct?
No
No
Yes
Disconnect the communications board.
Recheck the voltage at terminals TB-DC1-23 and TB-DC1-30 of the power supply board, and pin P2-13 of plug 2. Are the voltages correct?
No
Replace the logic board.
TP-5672 11/95
No
Recheck the voltage at terminals TB-DC1-23 and TB-DC1-30 of the power supply board, and pin P2-13 of plug 2. Are the voltages correct?
Yes
Yes
Replace the remote communication board.
Yes
Replace the power supply board.
Figure 4-1. Troubleshooting—Power to the system
Yes
No
Recheck the voltage at terminals TB-DC1-23 and TB-DC1-30 of the power supply board, and pin P2-13 of plug 2. Are the voltages correct?
Disconnect the status panel board.
Disconnect the logic board.
No
Controller Troubleshooting
No
Yes
Replace the logic board.
4-1
Power to the System
Ifthereisaproblemwiththelogicboard,thefirststepisto check the status panel. If no LEDs on the status panel are illuminated and the liquid crystal display (LCD) is blank, check the power to the system by performingthe following steps. See Figure 4-1 for the Power to the System troubleshooting flowchart. See Appendix B Figure B-4 for location of power supply board components referred to in this section. See Appendix B FigureB-6forlocationanddescriptionofP2ribboncable pins. See Appendix B Figure B-9 for location of main logic board components referred to in this section.
1. Using a voltmeter, connect one test lead to TB-AC1-NA. Connect the other test lead to TB-AC1-NC. If the voltmeter does not read the expected normal source voltage,check the normal sourceandthecontactor-to-assemblyharness,P1.
2. If thenormalsourcevoltageispresent,connectone test leadto TB-AC1-NAS and the other test leadto TB-AC1-NCS. If the voltmeter does not read approximately 19 volts AC, the secondary normal source voltage, check that the transformer is wired correctly. If the transformer is wired correctly and the voltmeter still does not read 19 volts AC, disconnect transformer secondary wires andretest transformer secondary voltage to determine if the transformer or the logic board assembly is at fault.
3. If boththenormalsourcevoltageandthesecondary normal source voltage are present, connect one test lead to TB-AC1-EA and the other test lead to TB-AC1-EC. If the voltmeter does not read the expected emergency source voltage, check the emergency source and the contactor-to-assembly harness, P1.
4. If theemergencysourcevoltageispresent,connect one test lead to TB-AC1-EAS and the other test leadtoTB-AC1-ECS.If thevoltmeterdoesnot read approximately19voltsAC,theexpectedsecondary emergency source voltage, check that the transformer is wired correctly. If the transformer is wiredcorrectly andthe voltmeter still doesnot read 19 volts AC, disconnect transformer secondary wires and retest transformer secondary voltage to determine if the transformer or the logic board assembly is at fault.
5. If the emergency source, normal source, and transformers are all working properly, and the batteryback-upoptionisused,connectthe positive testleadtoTB-DC1-29andthe negativetestleadto TB-DC1-34.If thevoltmeterdoesnot read between 12and30voltsDC,expectedbatteryvoltage,check the battery-to-assembly wires and the battery.
6. Connect the positive test lead to TB-DC1-23, and the negative test lead to TB-DC1-34. If the voltmeter does not read betweenapproximately12 and30voltsDC,checkifanaccessoryisconnected toTB-DC1-23.Ifthereisanaccessoryconnectedto TB-DC1-23,disconnectit. If the voltmeter stilldoes notread between12and30 voltsDC, performstep
9.
NOTE
When taking a voltage or resistance measurement at a ribbon cable pin, do not disconnect the ribbon cable from the board. Use a needle point probe to take the readings from the holes on the top side of the ribbon cable connector.
7. Connect the positive test lead to P2-13, and the negative test lead to TB-DC1-34. If the voltmeter does not read approximately 10 volts DC, perform step 9. See Appendix B Figure 6 for location of P2 ribbon cable pins.
8. Connect the positive test lead to TB-DC1-30 and the negative test lead to TB-DC1-34. If the voltmeterdoesnotreadapproximately10voltsDC, perform step 9.
9. If eachofthemeasurementstakeninsteps6,7,and 8 was correct, this step may be skipped.
a. Disconnect the main logic board ribbon cable
from P2, and recheck the voltages in steps 6, 7, and8. If thevoltagereadings in steps 6,7, and8 are now correct, the main logic board is defective. Replace the logic board assembly.
b. If the logic board is equipped with a load shed
board, disconnect the load shed ribbon cable from P10 on the main logic board, and recheck the voltages in steps 6, 7, and 8. If the voltage readings in steps 6, 7, and 8 are now correct, replace the Load Shed board.
c. If the logic board is equipped with a remote
communications board, disconnect the remote communications ribbon cable from P12 on the main logic board, and recheck the voltages in steps6, 7, and 8. If thevoltagereadings in steps 6, 7, and 8 are now correct, replace the remote communications board.
d. Disconnect the status panel ribbon cable from
P4,andrecheckthevoltagesinsteps6,7, and8. If the voltage readings in steps 6, 7, and 8 are now correct, the status panel is defective. Replace the logic board assembly.
e. If the voltages measured in steps 6, 7, and 8
were never correct, replace the power supply board.
4-2 Controller Troubleshooting
TP-5672 11/95
Keypad And Status Panel
For location of pushbuttons, switches, LEDs, and keys referred to in this section, see Figure 2-1.
1. Testthe keypadby pressinga keyandcheckingthe response.If theresponseiscorrect,repeatthisstep until satisfied that there is not a problem with the keypad. If the response is ever incorrect, the keypad is defective. Replace the logic board assembly.
2. Press the LAMP TEST key on the keypad.
3. If afterpressingtheLAMPTEST keysomeLEDson thedisplaypanelareon, butat leastoneLED isnot on, the status panel is defective. Replace the logic board assembly.
4. If after pressing the LAMP TEST key some of the character blocks on the LCD appear black, but at least one character block is not black, the status panel is defective. Replace the logic board assembly.
5. If after pressing the LAMP TEST key no LEDs are on, and the character blocks in the LCD are black, verify that there is power to the system by performing the steps outlinedin Section 4—Power To The System. Check the P2 and P4 ribboncable connections by performingthefollowingsteps. See Appendix B FigureB-9 for locationof ribboncables andotherpowersupplyboardcomponentsreferred to in this section.
a. Disconnect all power sources. b. Wait 30 seconds.
c. Being careful not to bend or break any of the
pins, remove both P2 and P4 ribbon cable connectors.
d. Inspect the pins on the P2 and P4 ribbon cable
connectors.
e. If pinsarebent,carefullybendthemback. Ifpins
are broken, replace the ribbon cable connector.
f. Carefully reconnect P2 and P4 ribbon cable
connector.
g. If the problem still exists,replacethe logic board
assembly.
560442
Figure 4-2. The M340+ LCD display during a lamp
test
TP-5672 11/95
Controller Troubleshooting
4-3
Loading...
+ 124 hidden pages