Kohler Industrial Generator Set Operation Manual

Operation
Industrial Generator Sets
Models:
10-1000 kW
Controller:
APM402/Decision-Makerr 3000
TP-6694 7/18j
to chemicals, including carbon monoxide and benzene, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov
Product Identification Information
W ARNING: Breathing diesel engine
exhaust exposes you to chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
S Always start and operate the engine in
a well-ventilated area.
S If in an enclosed area, vent the exhaust
to the outside.
S Do not modify or tamper with the
exhaust system.
S Do not idle the engine except as
necessary.
For more information go to www.P65warnings.ca.gov/diesel
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice. Record the Controller Serial Number from the controller nameplate.
Controller DescriptionAPM402/Decision-Maker
Controller Serial Number
r 3000
Firmware/Software Version Numbers
Record the version and reference numbers as shipped from the manufacturer. Determine the Application Program Version Number as shown in Menu 20. Determine the Personality Profile Reference Number from the disk supplied with the literature packet.
Application Program Version Number
Personality Profile Reference Number
User Parameter File Reference Number
Version Number Upgrades/Updates
Record the version number upgrade/updates when installed.
Version No./Date Installed
Software Options
Record the software options.
Number and Description
Table of Contents
Product Identification Information 2...........................................................
Safety Precautions and Instructions 7.........................................................
Introduction 13...............................................................................
Abbreviations 13...............................................................
SiteTech Software 13...........................................................
List of Related Materials 13......................................................
Service Assistance 14.........................................................................
Section 1 Specifications and Features 15......................................................
1.1 Introduction 15...........................................................
1.2 Controller Features 15....................................................
1.2.1 Switches and Controls 16..........................................
1.2.2 Annunciator Lamps 16............................................
1.2.3 Digital Display 18.................................................
1.2.4 Controller Fault Diagnostics 23.....................................
1.2.5 Digital Display Circuit Board and Connections 25.....................
1.2.6 Main Logic Circuit Board 25........................................
1.2.7 Terminal Jumper 26...............................................
1.2.8 Communication Ports 26..........................................
1.2.9 Fuses 26........................................................
1.3 Controller Logic Specifications 27...........................................
1.3.1 Status Event and Fault Specifications 27............................
1.3.2 Voltage Regulator and Calibration Specifications 33...................
1.3.3 Voltage Regulator Adjustments 33..................................
Section 2 Operation 35........................................................................
2.1 Prestart Checklist 35......................................................
2.2 Exercising Generator Set 35...............................................
2.3 Operation in Cold Weather Climates 36.....................................
2.4 Controller Operation 36...................................................
2.4.1 Starting 36.......................................................
2.4.2 Stopping (User Stopping and Fault Shutdown) 37.....................
2.4.3 Emergency Stop Switch Resetting 37...............................
2.4.4 System Status Lamps 38..........................................
2.4.5 System Fault Warning Lamp with Digital Displays 38..................
2.4.6 System Fault Shutdown Lamp With Digital Displays 40................
2.4.7 Status and Notice Digital Displays 43...............................
2.4.8 Controller Resetting (Following System Shutdown or Warning) 45.......
2.4.9 Powering Up the Engine Control Module (ECM) 45...................
2.5 Menu Displays 46........................................................
2.6 Monitoring and Programming Setup 49......................................
2.6.1 PC Communications 49...........................................
2.6.2 Modbus Communications 49.......................................
2.7 Reviewing Menu Displays 50...............................................
2.7.1 Error Messages 51...............................................
2.7.2 Overview 52.....................................................
2.7.3 Engine Metering 52...............................................
2.7.4 Generator Metering (and Calibration) 53
2.7.5 GenSet Information 54............................................
2.7.6 GenSet Run Time 54.............................................
2.7.7 GenSet System 54...............................................
2.7.8 GenSet Calibration 56.............................................
.............................
TP-6694 7/18 Table of Contents 3
Table of Contents, continued
2.7.9 Voltage Regulator 57..............................................
2.7.10 Digital Inputs 58..................................................
2.7.11 Digital Outputs 59................................................
2.7.12 Analog Inputs 60.................................................
2.7.13 Battery Charger 1 and 2 61........................................
2.7.14 Event Log 62....................................................
2.7.15 Volt Select 62....................................................
Section 3 Scheduled Maintenance 63..........................................................
3.1 Alternator Service 63......................................................
3.2 Engine Service 63........................................................
3.3 Service Schedule 64......................................................
3.4 Alternator Bearing Service 66..............................................
3.4.1 20--300 kW Models 66............................................
3.4.2 300--1000 kW Models with 4M/5M/7M Single-Bearing Alternator 66.....
3.5 Diesel Fuel Systems 66...................................................
3.5.1 Bleeding Air from Fuel System 66..................................
3.6 Gaseous Fuel Systems 67.................................................
3.6.1 Gaseous Fuel System Concept (Single Fuel) 67......................
3.6.2 LPG Liquid Withdrawal Fuel System Concept 67.....................
3.6.3 Natural Gas and LPG Conversion 67................................
3.6.4 Fuel System Changeover Kits (Dual Fuel) 68.........................
3.7 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1 68.....................
3.8 Air Cleaner Restrictor Indicator (if equipped) 70..............................
3.9 Cooling System 70.......................................................
3.9.1 Coolant Level Check 70...........................................
3.9.2 Cooling System Component Inspection 70...........................
3.9.3 Procedure to Drain Cooling System 71..............................
3.9.4 Procedure to Flush and Clean Cooling System 71....................
3.9.5 Procedure to Refill Cooling System 71..............................
3.10 Battery 72...............................................................
3.10.1 Clean Battery 73.................................................
3.10.2 Electrolyte Level Inspection 73.....................................
3.10.3 Specific Gravity Check 73.........................................
3.10.4 Charge Battery 74................................................
3.11 Storage Procedure 74.....................................................
3.11.1 Lubricating System 75............................................
3.1 1.2 Cooling System 75...............................................
3.11.3 Fuel System 75..................................................
3.1 1.4 Internal Engine Components (Gaseous-Fueled Engines) 75............
3.11.5 Exterior 75.......................................................
3.11.6 Battery 76.......................................................
Section 4 General Troubleshooting 77.........................................................
4.1 General Troubleshooting Chart 78..........................................
4.2 Controller Display and Voltage Regulation Troubleshooting Chart 81............
Section 5 Voltage Reconnection 83............................................................
5.1 Introduction 83...........................................................
5.2 Voltage Reconnection Procedure 83........................................
5.3 Voltage Reconnection Procedure 84........................................
TP-6694 7/18Table of Contents4
Table of Contents, continued
Section 6 Accessories 89.....................................................................
6.1 Accessories and Connections 89...........................................
6.1.1 Battery Charger Kit with Alarm Option 89............................
6.1.2 Common Fault/Failure (32A) Relay Kit 90............................
6.1.3 Fifteen-Relay Dry Contact Kit 91....................................
6.1.4 Gas Fuel Valve Kit 94.............................................
6.1.5 Input/Output (I/O) Module Board 95.................................
6.1.6 Key Switch 96....................................................
6.1.7 Low Fuel (Level/Pressure) Switch 96................................
6.1.8 Manual Speed Adjust (Engine RPM Menu) 97........................
6.1.9 Prime Power Switch Kit 97.........................................
6.1.10 Remote Emergency Stop Kit 98....................................
6.1.11 Remote Reset Feature 98.........................................
6.1.12 Remote Serial Annunciator 99......................................
6.1.13 Run Relay Kit 101.................................................
6.1.14 Shunt-Trip Line Circuit Breaker 101..................................
6.2 Accessory Connections 102.................................................
Appendix A Abbreviations 107................................................................
Appendix B Programmer-Defined Settings 109.................................................
Appendix C Voltage Regulator Definitions and Adjustments 115.................................
Appendix D Alternator Protection 119..........................................................
Appendix E Controller Displays from the Engine ECM 121.......................................
TP-6694 7/18 Table of Contents 5
Notes
TP-6694 7/186
Safety Precautions and Instructions
IMPORTANTSAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
7Safety Precautions and InstructionsTP-6694 7/18
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from thebattery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Battery gases. Explosion can cause severe injury or death. Incorrect use
of the equalize charge state may leadto hazardous situations. Equalization is ONLY applicable for flooded lead acid (FLA) type batteries and will damage gel, absorbed glass mat (AGM), or nickel-cadmium (NiCad) type batteries. In the controller menu or SiteTecht settings, verify that the battery topology is set correctly for the battery typeused. Do not smoke or permit flames, sparks, or other sources of ignition to occur near a battery at any time.
Engine Backfire/Flash Fire
WARNING
Risk of fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building unless the exhaust gas is piped safely outside. Never operate the generator set where exhaust gas could accumulate and seep back inside a potentially occupied building.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
8 Safety Precautions and Instructions TP-6694 7/18
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operatethe generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Explosive fuel vapors can cause severe injury or death. Take
additional precautions when using the following fuels:
Propane (LPG)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
Fuel tanks. Explosive fuel vapors can cause severe injury or death.
Gasoline and other volatile fuels stored in day tanks or subbase fuel tanks can cause an explosion. Store only diesel fuel in tanks.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
LPG liquid withdrawal fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage
can cause an explosion. Check the LPG liquid withdrawal fuel system for leakage by using a soap and water solution with the fuel system test pressurized to at least 90 psi (621 kPa). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
DANGER
Hazardous voltage. Moving parts. Will cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Grounding electrical equipment. Hazardous voltage will cause severe injury or death. Electrocution is
possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
9Safety Precautions and InstructionsTP-6694 7/18
High voltage test. Hazardous voltage will cause severe injury or death. Follow the instructions of the
test equipment manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
Installing the battery charger. Hazardous voltage will cause severe injury or death. An ungrounded
battery charger may cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead on the battery charger . Install the battery charger as prescribed in the equipment manual. Install the battery charger in compliance with local codes and ordinances.
Connecting the battery and the battery charger. Hazardous voltage will cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current will cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Engine block heater. Hazardous voltage will cause severe injury or death. The engine block heater can
cause electrical shock. Remove the engine block heater plug from the electrical outlet before working on the block heater electrical connections.
Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Servicing the generator set when it is operating. Exposed moving parts will cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the alternator. Hot parts can cause severe injury or death.
Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
10 Safety Precautions and Instructions TP-6694 7/18
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
246242
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Canadian installations only.For
standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
11Safety Precautions and InstructionsTP-6694 7/18
Notes
12 Safety Precautions and Instructions TP-6694 7/18
Introduction
This manual provides operation instructions for 10 kW and larger generator sets equipped with the following controllers:
D APM402 generator set controller
D Decision-Makerr 3000 generator set controller
Note: In 2018, Kohler adopted a global controller
naming convention. To support this, the name of the Decision-Makerr 3000 controller has transitioned to APM402. The APM402 has the same form, fit and function as the Decision-Makerr 3000 and supports the same accessories.
Wiring diagram manuals are availableseparately. Refer to the engine operation manual for generator set engine scheduled maintenance information.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
SiteTecht Software
Several instances in this manual refer to SiteTecht software, which can be used for programming the APM402 or Decision-Makerr 3000 controller. SiteTecht software is required for updating the controller application code (firmware), loading personality profiles, and saving or loading controller configuration files. Contact your local distributor/dealer for assistance.
Note: The APM402 controller uses different firmware
than the Decision-Makerr 3000 controller. Do not attempt to load Decision-Makerr 3000 firmware on an APM402 controller, or vice-versa.
To determine the generator set controller software version, go to the Overview menu.
List of Related Materials
Separate literature contains communication and software information not provided in this manual. Figure 1 lists the available literature part numbers.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation andto avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipmentservice requirements are very important to safe and efficient operation. Inspect the parts often and perform required service atthe prescribedintervals. Maintenance work must be performed by appropriately skilled and suitably trained maintenance personnel familiar with generator set operation and service.
Abbreviations
This publication makes use of numerous abbreviations. Typically, the word(s) are spelled out along with the abbreviation in parentheses when shown for the first time in a section. Appendix A, Abbreviations, also includes many abbreviation definitions.
Literature Description Literature Part No.
APM402 Controller Spec Sheet
Decision-Makerr 3000 Controller Spec Sheet
Generator Set/Controller Wiring Diagram Manual
Modbusr Communications Protocol Operation Manual
SiteTecht Software Operation Manual
Remote Serial Annunciator (RSA III) TT-1625
Remote Serial Annunciator (RSA II) TT-1485
Converters, Connections, and Controller Setup for Network Communication
G6-161
G6-100
Multiple Part Numbers
Contact your
Distributor/Dealer
TP-6113
TP-6701
TT-1405
Figure 1 Related Literature
Several engine manufacturers provide engines with electronic controls. These electronic controls indicate engine fault codes in addition to the generator set controller. The engine operation and service literature provide information for identifying engine fault codes. For the latest literature part numbers,see therespective Parts Catalog.
Modbusr is a registered trademark of Schneider Electric.
13IntroductionTP-6694 7/18
Service Assistance
For professional advice on generator set power requirements and conscientiousservice, please contact your nearest Kohler distributor or dealer.
D Visit the Kohler Co. website at KOHLERPower.com.
D Look at the labels and decals on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada,call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler EMEA Headquarters Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific
Kohler Asia Pacific Headquarters Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
14 Service Assistance TP-6694 7/18
Section 1 Specifications and Features
1.1 Introduction
The spec sheets for each generator set provide model­specific generator and engine information. The controller spec sheet provides specifications for this controller. Refer to the respective spec sheet for data not supplied in this manual. Refer to the generator set service manual, installation manual, engine operation manual, and engine service manual for additional specifications.
1.2 Controller Features
The controller features include the annunciator lamp, digital display and pushbutton/rotary selector dial, switches and controls, and fuses and terminal strip. The following paragraphs detail the features by general topics.
See Figure 1-1 for an illustration of the controller front panel.
12 45
3
The controller features,accessories, and menudisplays depend upon the engine electronic control module (ECM) setup and features. Controller features apply to generator set models with ECM and non-ECM engines unless otherwise noted.
Note: Press the pushbutton/rotary selector dial to turn
on the controller lights and display. The lights and display turn off 60 minutes after the last entry when in the AUTO mode.
Note: After about 5 minutes of no user input
(pushbutton/rotary selector dial or buttons), the menu is reset to the top of the main menus and auto-paging activates for the Overview submenus.
Note: Measurements display in metric or English units.
Use the Generator Set System menu to change the measurement display.
OFF/RESET AUTO RUN ALARM SILENCE/
1. Emergency stop switch
2. Generator set master control switches, OFF/RESET-- AUTO--RUN buttons with lamps
3. Digital display
4. Alarm horn (behind panel)
5. Pushbutton/rotary selector dial
6. Annunciator fault lamp
7. Controller terminal strips (on circuit board)
8. Alarm silence/lamp test button with lamp
9. Mini USB connection
Figure 1-1 Controller with Digital Display and Pushbutton/Rotary Selector Dial
FAU LT
LAMP TEST
6
7
8
9
GM65741-
TP-6694 7/18 15Section 1 Specifications and Features
1.2.1 Switches and Controls
Note: US/Metric Display is selectable in Section
1.2.3—Digital Display—Generator Set System Menu.
Alarm Horn. The alarm horn alerts theoperator or other attendants that a shutdown or warning condition exists.
Alarm (Horn) Silence. The alarm silence/lamp test switch silences the alarm horn at the operator’s discretion. Press the master control switch AUTO button before pressing the alarm silence/lamp test button. The alarm horn cannot be silenced unless the master control switch AUTO button is pressed.
Note: Additional alarm silencing options are shown in
Section 1.2.3—Digital Display—Generator Set System Menu.
Restore alarm horn switches at all locations including those on remote annunciator kits after correcting the fault shutdown to avoidreactivating the alarm horn. See Section 2—Operation, 2.4.8 Controller Resetting for resetting the controller.
Emergency Stop. The operator-activated pushbutton immediately shuts down the generator set inemergency situations. Reset the emergency stop switch after shutdown by pulling the emergency stop switch outward. Usethe emergency stopswitch for emergency shutdowns only. Use the master control switch OFF/RESET button for normal shutdowns.
The pushbutton/rotary selector dial hasseveral features and functions:
D Momentarily press the dial to activate the digital
display if dark.
D Rotate the dial to navigate through the main
menus—turn clockwise to go forward (down) and counterclockwise to go back (up). The menus do not wrap to the beginning.
D Press the dial at a given main menu to access the
submenus within the selected main menu.
D When in the submenu, rotate the dial to navigate
through the submenu—clockwise to go forward (down) and counterclockwise to go back (up). The menus do not wrap to the beginning.
D Momentarily press the dial when in the submenu to
make a user selection choice (if available) or to go back to the respective main menu.
D Press the dial forat least3 seconds to return tothe top
of the main menus (Overview) regardless if you are in the main menus or submenus.
D After about 5 minutes of no user input (pushbutton/
rotary selector dial or buttons), the menu resets to the top of the main menus and auto-paging activates for the Overview submenus.
1.2.2 Annunciator Lamps
The controller has a single annunciator fault lamp providing visual generator set status. In addition, each button has a corresponding lamp. See Figure 1-2.
Generator Set Master Control Switches (OFF/RESET--AUTO--RUN). These switches reset the
controller fault lamps and start/stops the generator set. Additional information in shown in Section 2— Operation.
Lamp Test. Press and hold the Alarm Silence/Lamp Test button for two seconds to test the controller indicator lamps, alarm horn, and digital display.
Manual Speed Adjust (Engine RPM). The control allows varying the engine speed for applications using closed transition ATS. The user can set the nominal running frequency slightly above or below the utility frequency to ensure that synchronization occurs. Additional information is shown in 2.7.7 GenSet System. Available as a factory-installed option o r requires a new factory personality profile.
Pushbutton/Rotary Selector Dial. This control provides access to the menus for monitoring. Press the selector dial to activate the digital display and to select choices shown on the display. Rotate the dial to navigate through the menus.
Lamp/Button Lamp Color
Alarm (Fault) Lamp Yellow (Warning) or Red (Shutdown)
Off/Reset Button Red
Auto Button Green (System Ready)
Run Button Yellow
Alarm Silence/Lamp
Test Button
Yellow
Figure 1-2 Annunciator Lamps
System Status Lamps (Master Control Switches)
The green lamp illuminates on the master controlswitch AUTO (automatic start) button indicating the system senses no faults and the unit is ready to start by remote command.
The red lamp illuminates on the master control switch OFF/RESET button indicating the generator set is stopped.
The yellow lamp illuminates onthe master control switch RUN button indicating the generator set is cranking or running from a local command.
Only one of the three master control switch lamps will illuminate at any given time.
TP-6694 7/1816 Section 1 Specifications and Features
Alarm Silence Lamp. Yellow lamp illuminates indicating the alarm horn was silenced.
(System) Fault Lamp. Yellow lamp illuminates indicating a warning condition or red lamp illuminates indicating a shutdown condition. See System Warning Fault Lamp and System Shutdown Fault Lamp following for system fault conditions.
System Warning Fault Lamp. Yellow lamp identifies an existing fault condition that does not shut down the generator set. A continuing system warning fault condition may cause a system shutdown. Correct all system warnings as soon as practical.
See Section 2.4.5, System Fault Warning Lamp with Digital Displays, for definitions of the items listed. The following conditions cause a system warning:
D AC sensing loss D Auxiliary input (analog or digital) D Battery charger communication loss D Battery charger fault *
Note: Optional input sensors not required with charger
GM87448.
D Battery charger identity conflict D Battery charger parameter mismatch D Battery fault D Common warning D Critical high fuel level (diesel-powered models only) * D Default parameters loaded D ECM diagnostics (multiple engine inputs) D Fuel tank leak (diesel-powered models only) * D Ground fault * D High battery voltage D High coolant temperature D High fuel level (diesel-powered models only) * D Input/output communication loss D Low battery voltage D Low coolant temperature D Low cranking voltage D Low engine oil level * D Low fuel (level for diesel-powered models) * D Low fuel (pressure for gas-powered models) * D Low oil pressure D Not-in-auto (master control switch) D Speed sensor fault
* Requires optional input sensors with all battery chargers except
battery charger GM87448.
System Shutdown Fault Lamp. Red lamp indicates that the generator set has shut down because of a fault condition. The unit will not start without resetting the controller, see Section 2.4.8, Controller Resetting procedure.
See Section 2.4.6, System Fault Shutdown Lamp with Digital Displays, for definitions of the items listed. The following conditions cause a system shutdown:
D AC sensing loss D Alternator protection D Auxiliary input (analog or digital) D Common fault D ECM address conflict D ECM communications loss D ECM diagnostics (multiple engine inputs) D ECM model mismatch D Emergency stop D Enclosure temperature: high shutdown (available on
select Telecom units only)
D Engine over speed D Engine under speed D File system error (controller firmware fault) D Fuel tank leak (diesel-powered models only) * D High coolant temperature D Internal failure D kW overload D Locked rotor (failed to crank) D Loss of fuel D Low coolant level * D Low engine oil level * D Low fuel level (diesel-powered models only) * D Low oil pressure D Megajector communications loss
(GM/PSI and Doosan gas-powered models only)
D Metering communication loss D No coolant temperature signal D No oil pressure signal D Overcrank D Overfrequency D Overvoltage (each phase) D Run relay overload D Underfrequency D Undervoltage (each phase) D (Voltage) regulator communication loss
* Requires optional input sensors.
TP-6694 7/18 17Section 1 Specifications and Features
1.2.3 Digital Display
Overview Menu
Press the pushbutton/rotary selector dial to turn on the controller lamps and display. The lamps and display turn off 60 minutes after the last entry.
Note: The APM402 controller takes about 5--10
seconds to power on.
The generator set must be running for some displays to indicate values. If the generator set is not running some values will display zero or N/A (not available).
Some displays are engine dependent, refer to the Appendix, Controller Displays from the Engine ECM.
The 12-character, 2-line backlit heated display provides generator set and engine data, system status, and fault information. See Figure 1-1. The digital display shows abbreviations in some instances, refer to 1.3.1 Status Event and Fault Specifications for theabbreviations and their full descriptions.
Note: US/Metric Unit Display is selectable in
Generator Set System.
Note: Display Contrast is selectable in Generator Set
System. The contrast display adjustment allows user selected resolution values to improve digital display clarity.
Note: After about 5 minutes of no user input
(pushbutton/rotary selector dial or buttons), the menu resets to the top of the main menus and auto-paging activates for the Overview submenus.
The main menus are listed below. Within each main menu are multiple submenus with descriptions following.
D Overview D Engine Metering D Generator Metering D GenSet Information D GenSet Run Time D GenSet System D GenSet Calibration (Decision-Makerr 3000
controllers before Version 3.0.25)
D Voltage Regulation D Digital Inputs D Digital Outputs D Analog Inputs D Event Log D Volt Select
When a new shutdown or warning fault occurs, the auto-paging display feature activates.
Active Shutdowns display if any are present. This alerts the user to single or multiple shutdown fault conditions. See 1.2.2—Annunciator Lamps—System Shutdown Fault Lamp for a list of possible shutdown faults.
Active Warnings display if any are present. This alerts the user to single or multiple warning fault conditions. See 1.2.2—Annunciator Lamps—System Warning Fault Lamp for a list of possible warning faults.
Generator Set State displays the generator set status:
D Off D Standby D Running D Cooldown D Stopping
Average Volts Line-to-Line value displays. For three-phase configurations the average line-to-line voltage of L1, L2, and L3 is displayed. Single-phase configurations show the L1-L2 voltage.
Frequency (Hz) value displays for the output AC voltage.
Current value displays as the average for three-phase configurations or the current value for L1-L2 with single-phase configurations.
Average kW displays. For three-phase configurations the average line-to-line kilowatts of L1, L2, and L3 is displayed. Single-phase configurations show the L1-L2 kilowatts.
Coolant Temperature diplays for the engine coolant temperature.
Oil Pressure displays the engine oil pressure.
Fuel Level % displays the fuel tank level for diesel-
powered models when so equipped.
Fuel Pressure displays fuel pressurefor someengines. Refer to the Appendix, Controller Displays from the Engine ECM.
Battery displays the DC voltage of the engine starting battery(ies).
CHG1 and CHG2 display battery charger voltage and current (amps) if one or two CAN-enabled 10 Amp battery chargers (GM87448 only) have been connected. Shows N/A if charger GM87448 was
TP-6694 7/1818 Section 1 Specifications and Features
connected and then removed. (DEC3000 version 4.11 or higher, and APM402)
Engine Run Time displays the total run time hours.
The calibration values are r eviewable at all times and provide the calibration of the voltage and current sensing logic. Changing the systemvoltage or replacing the circuit board requires a calibration adjustment.
Software Version displays in the Overview menu. Use the version number to determine if an upgrade is needed and/or when troubleshooting the controller.
Engine Metering Menu
Note: The Engine Metering Menu may vary depending
upon if the selector dial is rotated clockwise or counterclockwise.
Engine Speed (Tachometer) displays the engine speed in RPM.
Oil Pressure displays the engine oil pressure. This value also shows in the Overview Menu.
Coolant Temperature displays the engine coolant temperature. This value also shows in the Overview Menu.
Fuel Level % displays the fuel tank level for diesel­powered models if so equipped. This value also shows in the Overview Menu.
Battery displays the DC voltage of the engine starting battery(ies). This value also shows in the Overview Menu.
Fuel Pressure displays fuel pressurefor someengines. Refer to the Appendix, Controller Displays from the Engine ECM. This value also shows in the Overview Menu.
Generator Metering Menu
Total Power kVA and kW displays alternator output as
actual output values.
To enable calibration
, start the generator set and select the Volts L1-L2 display. Then push and hold the pushbutton/rotary selector dial until the Calibration Enabled popup appears. Calibration of each display is now available. The display will show the following values for three-phase generator sets. Single-phase generator sets will only display items marked (*).
D Volts L1-L2 * D Volts L2-L3 D Volts L3-L1 D Volts L1-N * D Volts L2-N * D Volts L3-N D Current L1 * D Current L2 * D Current L3
The user can change individual values or can select Reset Calib?--Yes to reset all values. The Reset Calib? display will only show if calibration is enabled. Refer to the requirements shown with Generator Set Calibration in 2.4.7 Status and Notice Digital Displays.
To disable calibration
, Rotate the pushbutton/rotary selector dial until the <-- Return popup appears. Momentarily press the pushbutton/rotary selector dial. Stop the generator set if not already done.
Generator Set Information Menu
GenSet M/N displays the generator set model number.
GenSet S/N displays the generator set serial number.
Controller S/N displays the controller serial number.
Rated Power displays alternator output as a
percentage of the entered data value.
Volt s displays the alternator output AC voltages. The display shows all line-to-line and line-to-neutral voltage combinations for three-phase or single-phase configurations.
Current displays the alternator output AC amps. The display shows each line (L1-L2-L3) of three-phase models or L1-L2 current for single-phase models.
Frequency (Hz) value displays for the output AC voltage. This value also shows in the Overview Menu.
Reset Calibration providing the means to reset the configuration values is available in this menu.
TP-6694 7/18 19Section 1 Specifications and Features
Generator Set Run Time Menu
Engine Run Time displays the total run time hours.
This value also shows in the Overview Menu.
Engine Loaded displays the total loaded hours.
Engine Starts displays the total number of generator
set startup events.
Total Ene rgy displays the total kW hours.
Generator Set System Menu
Generator Set (Reset) Calibration Menu
The values in this menus are user-entered for the generator set configuration and are NOT measured values of the generator set.
Changes to the Generator Set System menu require the use of SiteTecht software except for Measure System and Contrast selections.
System Frequency displays the programmer-entered L1-L2-L3 output voltage frequency for three-phase or the L1-L2 output voltage frequency for single-phase.
System Phase displays the programmer-entered configuration as Single Phase, Single Phase Dog Leg, Three Phase Wye, or Three Phase Delta.
System Voltage displays the programmer-entered L1-L2-L3 output voltage for three-phase or the L1-L2 output voltage for single-phase.
Power Rating displays the programmer entered kW value for the generator set.
Amp Rating displays the programmer entered current value for the generator set.
Power Type displays the programmer entered generator set application configuration as Standby or Prime.
Battery Voltage displays the engine electrical system 12 or 24 volts.
Measurement System displays the user selected unit of measure as Metric or English.
Contrast displays user selected resolution values to improve digital display clarity.
Alarm (Horn) Silence displays the programmer selected alarm silence method as Always or Auto Only using SiteTecht software. TheAlways selectionallows the alarm to be silenced in any of the OFF/RESET--AUTO--RUN modes. The Auto Only selection allows silencing of the alarm only while in the Auto mode.
This menu is only available in Decision-Makerr 3000 controller firmware versions before 3.0.25. On Decision-Makerr 3000 controllers with later firmware versions, or on APM402 controllers, go to Generator Metering Menu—Reset Calibration.
The calibration values are r eviewable at all times and provide the calibration of the voltage and current sensing logic. Changing the systemvoltage or replacing the circuit board requires a calibration adjustment. In order to review the values when the generator set is NOT running, enter Yes when the Enter Calib? is displayed. The user can review the values but attempting to change the values will cause a Cannot calibrate error message.
If the unit is NOT running and No is entered when the Enter Calib? is shown, the display returns to the Generator Set Calibration main menu and entry to the Generator Set Calibration menu is denied.
If the unit is running and Yes is entered when the Enter Calib? is shown, the display will show the following values for three-phase generator sets. Single-phase generator sets will only display items marked (*).
D Volts L1-L2 * D Volts L2-L3 D Volts L3-L1 D Volts L1-N * D Volts L2-N * D Volts L3-N D Current L1 * D Current L2 * D Current L3
The user can change individual values or can enter Yes when Reset all Calib? is displayed. At the end of the Generator Set Calibration menu, Exit calibration is shown. Press the pushbutton/rotary selector dial to exit this menu. Refer to the requirements shown with Generator Set Calibration in 2.4.7 Status and Notice Digital Displays.
Note: Press the Alarm Silence/Lamp Test button to
silence the alarm horn.
Manual Speed Adjust (Engine RPM) is available as a user selectable adjustment. The user can set the nominal running frequency slightly above or below the utility frequency to ensure that synchronization occurs. Refer to 2.7.7 GenSet System for more information. Available as a factory-installed option or requires a new factory personality profile.
TP-6694 7/1820 Section 1 Specifications and Features
Voltage Regulator Menu
Digital Inputs Menu
Decision-Makerr 3000 Controller firmware before
3.0.25:
The voltage regulator value is reviewable at all times. In order to review the value when the generator set is NOT running, enter Yes when the Enter volt reg? is displayed. The user can review the value but attempting to change the value will cause a Cannot edit when stopped error message.
If the unit is NOT running and No is entered when the Enter volt reg? is shown, the display returns to the Voltage Regulator main menu and entry to the Voltage Regulator menu is denied.
If the unit is running and Yes is entered when the Enter volt reg? is shown, the display will show the value.
The usercan change the value at this time. At the endof the Voltage Regulator menu, Exit voltage reg is shown----press the pushbutton/rotary selector dial to exit this menu.
Decision-Makerr 3000 Controller firmware 3.0.25 and higher, or APM402 Controller:
The voltage regulator value is reviewable at all times and provides the ability to fine adjust voltage. Changing the system voltage or replacing the circuit board typically requires a voltage adjustment.
To enable calibration
, start the generator set and select the VR Volt Adj display. Then push and hold the pushbutton/rotary selector dial until the Editing Enabled popup appears. Editing of thevoltage adjustment isnow available.
This menu allows the user to review the settings. There are up to three digital inputs that are programmer selectable if not reserved by factory options.
The displays for digital inputs appear as shown below with Values true or false. Items shown in the digital displayasTrueareactive.
D DIn A1 (digital input A1) standard D DIn A2 (digital input A2) standard D DIn A3 (digital input A3) standard (see note below) D DIn B1 (digital input B1) with I/O module board D DIn B2 (digital input B2) with I/O module board
Changes to the Digital Inputs menu requires the use of SiteTecht software. The digitalinput caneither openor close the circuit to activate.
Note: DIn A3 digital input is factory reserved for
Enclosure Temperature: High Shutdown on select Telecom units.
Digital Outputs Menu
This menu allows the user to review the settings. There is one digital output standard with the controller that is programmer selectable. The one SPDT switch has 2 amp. contacts at 32 VDC or 0.5 amp. contacts at 120 VAC max.
There is an optional 2 input/5 output (I/O) module board available that can provide five digital outputs. The standard digital output on the controller is used to drive the optional I/O Module board and becomes factory reserved and no longer available as programmer selectable.
The user can change the individual value or can select
Reset VR?--Yes to reset to the default value. The Reset VR Settings display will only show if editing is enabled.
To disable calibration
, Rotate the pushbutton/rotary selector dial until the <-- Return popup appears. Momentarily press the pushbutton/rotary selector dial. Stop the generator set if not already done.
The displays for digital outputs appear as shown in the following list with Values as True or False. Items shown in the digital display as True are active.
D DOut A1 (digital output A1) standard D DOut B1 (digital output B1) with I/O module board D DOut B2 (digital output B2) with I/O module board D DOut B3 (digital output B3) with I/O module board D DOut B4 (digital output B4) with I/O module board D DOut B5 (digital output B5) with I/O module board
Changes to the Digital Outputs menu requires the use of SiteTecht software. The digital output can either open or close the circuit to activate.
TP-6694 7/18 21Section 1 Specifications and Features
Analog Inputs Menu
Volt Select Menu
This menu allows the user to review the settings. There is one analog input that is programmer selectable if not reserved by factory options.
There is an optional 2 input/5 output (I/O) module board available that can provide two additional analog inputs.
The displays for analog inputs appear as shown below with Values of 0--5 volts.
D AIn A1 (analog input A1) standard
(reserved and not user programmable)
D AIn A2 (analog input A2) standard D AIn B1 (analog input B1) with I/O module board D AIn B2 (analog input B2) with I/O module board
Changes to the Analog Inputs menu requires the use of SiteTecht software.
Event Log Menu
This menu allows the user to reviewup to1000 entries of system events including shutdown faults, warning faults, and status events. See 1.2.4 Controller Fault Diagnostics for a list of the items that appear on the Event Log.
Note: The generator set must be stopped before
changing the voltage selection.
This menu allows the user to readily change controller voltage settings. Thevolt select feature is typically used in towable or temporary applications.
Note: The volt select menu requires initial activation by
SiteTecht software. In SiteTecht software, select True to activate the volt select menu.
Note: The generator set output leads require voltage
reconnection if the generator set does not have a voltage selector switch installed.
With the generator set stopped, go to the Volt Select menu. Then push and hold the pushbutton/rotary selector dial until the voltage selection starts to flash. Volt selection is now available. Scroll to the desired voltage and momentarily press the pushbutton/rotary selector dial to confirm the voltage selection.
The displays for Volt Select appear as shown in the following list.
D 120/240 V 1 Ph D 120/208 V 3 Ph D 139/240 V 3 Ph D 277/480 V 3 Ph D 120/240 V 3 Ph
TP-6694 7/1822 Section 1 Specifications and Features
1.2.4 Controller Fault Diagnostics
This table provides descriptions of the system events and their types—warning, shutdown, status, and notice.
Warnings show yellow fault lamp and signal an impending problem. Shutdowns show red fault lamp and stopthe generator set. Status isan event that is not an alert but is part of the event history. Notice is an alert
System Events Display Message List
that is NOT part of the event history. System events are available as a Relay Output as shown.
Throughout this manual there are examples of the display text. In some cases, the message words and phrases are abbreviated or shortened to accommodate the number of characters in the 12 x 2 digital display. See the following table fora full description of thesystem event display messages.
Warning
Description Display Message
Engine Functions
Critically high fuel level (diesel-powered models only) * Fuel Level Critically High X X
ECM communications loss ECM Comm Err Shutdwn X X
ECM diagnostics (multiple inputs) [
ECM diagnostics (multiple inputs) [
ECM faults (address conflict) ECM Addr Err Shutdwn X X
ECM faults (model mismatch) ECM Mismatch Shutdwn X X
Engine over speed Eng Speed High Shutdwn X] X
Engine start aid active Starting Aid Notice N X
Engine under speed Eng Speed Low Shutdwn X X
Fuel tank leak * Fuel Leak Warning X X
Fuel tank leak * Fuel Leak Shutdwn X X
High battery voltage Battery High Warning X X
High coolant (engine) temperature Coolnt Temp High Warning X X
High coolant (engine) temperature Coolnt Temp High Shutdwn X] X
High fuel level (diesel-powered models only) * Fuel Level High Warning X X
Loss of fuel Loss of fuel X X
Low battery voltage Battery Low Warning X X
Low coolant level * Coolant Lvl Low Shutdwn X X
Low coolant temperature Coolant Temp Low Warning X X
Low cranking voltage Lo Crank Vlt Warning X X
Low engine oil level * Oil Level Low Warning X X
Low engine oil level * Oil Level Low Shutdwn X X
Low fuel level (diesel models) * Fuel Level Low Warning X X
Low fuel level (diesel models) * Fuel Level Low Shutdwn X X
Low fuel pressure (gas models) * Fuel Press Low Warning X X
Low oil pressure Oil Press Low Warning X X
Low oil pressure Oil Press Low Shutdwn X] X
No coolant temperature signal Temp Sig Loss Shutdwn X X
No oil pressure signal Press Sig Loss Shutdwn X X
Overcrank Over Crank Shutdwn X] X
Speed sensor fault Spd Sens Flt Warning X X
ECM xxxxxx Warning X X
ECM xxxxxx Shutdwn X X
Function
Shutdown
Function
Status/
Notice
Relay
Output
TP-6694 7/18 23Section 1 Specifications and Features
Warning
Description
General Functions
Alarm horn silenced (Alarm Silence LED only) X
Alarm silence, auto only (NFPA 110) or always AlrmSilence: Auto Only or
Aux. inputs 0--5 VDC, 1 analog (2 additional inputs available with I/O module option)
Aux. inputs 0--5 VDC, 1 analog (2 additional inputs available with I/O module option)
Auxiliary inputs, up to 3 digital (2 additional inputs available with I/O module option)
Auxiliary inputs, up to 3 digital (2 additional inputs available with I/O module option)
Backup parameters loaded Backup Pars Status S No
Battery charger 1 communication loss Bat1CommLoss X
Battery charger 2 communication loss Bat2CommLoss X
Battery charger fault * (* does not apply to charger GM87448)
Battery charger identity conflict BatIdErr X
Battery charger parameter mismatch Param Mismatch X
Battery Fault Battery Flt X
Chicago code active Auto Locked Notice N X
Common fault (includes ])
Common warning fault Common Warng X N X
Default parameters loaded Default Pars Warning X X
Emergency stop Emerg Stop Shutdwn X] X
Enclosure temperature: high shutdown Enclsr Temp: High Shutdwn X X
Engine cooldown (delay) active Eng Cooldown Notice N X
Engine start delay active Start Delay Notice N X
Engine started Engine Start Status S X
Engine stopped Engine Stop Status S X
EPS supplying load Emerg Pwr On Notice N X
File system error (controller fault) File Error Shutdwn X X
Generator running Gen Running Notice N X
Input/output (module option board) communication loss OB1 Com Loss X X
Internal failure Intern Error Shutdwn X X
Metering communication loss MeterCommLos Shutdwn X X
NFPA 110 alarm active NFPA Alarm Notice N X
Not in auto (master switch) Not In Auto Warning X X
Remote start Remote Start Status S X
System ready System Ready Status S X
System timer failed TimerErrorNotice N X
Generator Functions
AC sensing loss AC Sens Loss Warning X X
AC sensing loss AC Sens Loss Shutdwn X X
Alternator protection Alt Protect Shutdwn X X
Ground fault input * Ground Fault Warning X X
kW overload Total Power High Shutdwn X X
Locked rotor (failed to crank) Locked Rotor Shutdwn X X
Overfrequency Freq High Shutdwn X X
Overvoltage (each phase) Volts xx--xx High Shutdwn X X
Underfrequency Frequency Low Shutdwn X X
Undervoltage (each phase) Volts xx--xx Low Shutdwn X X
(Voltage) regulator communication loss RegCommLoss Shutdwn X X
* Function requires optional input sensors or kits or is engine ECM dependent on some generator set models.
[ ECM inputs are engine manufacturer dependent. ] The Common Fault Shutdown includes the items marked X] in the Shutdown Function column.
Display Message
AlrmSilence: Always
Aux Input Warning X X
Aux Input Shutdwn X X
Aux Input Warning X X
Aux Input Shutdwn X X
Batt Chg Flt X
Common Fault Shutdwn X N X
Function
Shutdown
Function
Status/
Notice
S No
Relay
Output
X
TP-6694 7/1824 Section 1 Specifications and Features
1.2.5 Digital Display Circuit Board and
Connections
The digital display circuit board provides:
D The backlit LCD (liquid crystal display) for monitoring
the generator set functions and output values
D Master control switches with status lights D Fault lamp D Pushbutton/rotary selector dial to navigate the
generator set displays
D Alarm horn and alarm silence/lamp test switch/light D Mini USB connector for PC setup using SiteTecht
software
See Figure 1-3 for the circuit board connections.
Circuit Board Connections
P9 Connector the 24-pin connector attaches directly to
the main logic circuit board.
P10 Connector mini USB for PC upgrades located on the front panel using SiteTecht software.
1.2.6 Main Logic Circuit Board
The main logic circuit board provides the terminal strips and connection sockets to connect the controller to the engine/generator, input/output connections, optional I/O module kit, and circuit protection fuses. See Figure 1-4 and Figure 1-5 for the circuit board connections. See Section 6, Accessories for more information.
1
2
P11 Connector is a 20-pin connector (not used).
1
2
3
GM65741-
1. P9 24-pin connector (opposite side) connects to main board
2. P10 5-pin mini USB connector
3. P11 20-pin connector (not used)
Figure 1-3 Digital Display Circuit Board Connectors
1. Main logic circuit board
2. Remote emergency stop switch
GM65741-
Figure 1-4 Main Circuit Board and Emergency Stop
Switch
Circuit Board Connections
P1 (24-Pin) Connector for engine/generator wiring
harness.
P2 (6-Pin) Connector for AC current.
(4) Push-on Connectors for V7/V8/V9/V0 for
generator set output voltage connection.
TP-6694 7/18 25Section 1 Specifications and Features
1.2.8 Communication Ports
10
9
8
7
1. (4) push-on terminal connectors
2. TB2 4-position terminal block
3. TB3 6-position terminal block
4. P2 6-pin connector
5. P1 24-pin connector
6. TB1 6-position terminal block
7. P22 3-pin connector
8. P30 jumper (Wound Field or Fast Response)
9. P23 8-pin connector (RJ45)
10. P21 6-pin connector (for RS-485 communication)
6
5
Figure 1-5 Main Circuit Board Connectors
4
GM64345-1-A
1
The main logic circuit board contains a single mini USB communication port forPC connections, seeFigure 1-6. For Modbusr communication using RS-485, see Figure 1-5 (P21). Refer to the List of Related Materials
2
in the Introduction for corresponding SiteTecht software and/orcommunication installationinformation.
3
GM65741-
1. Mini USB connection
1
Figure 1-6 Communication Port
1.2.9 Fuses
P21 (6-Pin) Connector for (RS-485) connection of
optional RSA or Modbusr communication.
P22 (3-Pin) Connector for engine ECM. Alternate CAN connection.
P23 (8-Pin) Connector (RJ45) for optional input/output (I/O) module circuit board.
Refer to Section 6.2, Accessory Connections for specific connections of the following terminal block connections.
TB1 (6-Position) Terminal Block for analog and digital inputs.
TB2 (4-Position) Terminal Block for K1 relay outputs.
TB3 (6-Position) Terminal Block for E-stop, remote
start contacts, and aux. input connections.
1.2.7 Terminal Jumper
A circuit board P30 jumper is set based on alternator type—Wound Field (300 kW and larger) or Fast Response (less than 350 kW). The jumper is factory set and needs no further adjustment. See Figure 1-5 for location of the P30 jumper.
AC Circuit Fuses (TB5). Fuses are located inside the generator set control box. See Figure 1-7
D 1.5-Amp (V7) fuse protects L1 sensing input to
interconnection circuit board.
D 1.5-Amp (V8) fuse protects L2 sensing input to
interconnection circuit board.
D 1.5-Amp (V9) fuse protects L3 sensing input to
interconnection circuit board.
DC Circuit Fuses are located on the controller circuit board. See Figure 1-8.
D 1-Amp (F1) auto-resettable, fuse protects the
controller circuits.
D 1-Amp (F2) auto-resettable fuse protects the
controller circuits.
D 12-Amp (F3) non-replaceable fuse protects the
engine/starting circuitry and accessories.
Modbusr is a registered trademark of Schneider Electric.
TP-6694 7/1826 Section 1 Specifications and Features
1
1. V7/V8/V9 fuses, 1.5 Amp. (qty. 3)
Figure 1-7 AC Circuit Fuses in Control Box
GM69407
1.3 Controller Logic Specifications
The controller logic specifications sectionis an overview of the various features and functions of the controller. Certain features function only when optional accessories are connected. See Section 2, Operation, for details.
The default selection time delays and digital outputs are factory set and adjustable. Data entries require using a PC and SiteTecht software. See the SiteTecht software operation manual for details.
Inhibit Time Delay. The inhibit time delay is the time period following crank disconnect during which the generator set stabilizes and the controller does not detect a fault or status event. Select the desired inhibit time delay from 0 to 60 seconds.
TIme Delay (Shutdown or Warning). The time delay follows the inhibit time delay. The time delay is the time period between whenthe controller first detects a fault or status event and the controller warning or shutdown lamp illuminates. The delay prevents nuisance alarms. Select the desired time delay from 0 to 60 seconds.
1
1. F1 1 Amp. auto-resettable
2. F2 1 Amp. auto-resettable
3. F3 12 Amp. non-replaceable
Figure 1-8 Controller DC Fuses
GM64345-C
1.3.1 Status Event and Fault
2
The Factory-Defined Settings List contains all status
3
events and faults with ranges and time delays including items that do not have user adjustments.
Note: The engine ECM may limit the crank cycle even if
Specifications
the controller is set to a longer time period.
TP-6694 7/18 27Section 1 Specifications and Features
Factory-Defined Settings List
Description
Controller Display
Message
Alarm
Horn
Fault
Lamp
Warning
hutdown
S
Write
Access
Display
Si
Engine Functions
Critically high fuel level (diesel-powered models only) *
ECM communications loss ECMCommErr
ECM diagnostics (multiple inputs) [
ECM diagnostics (multiple inputs) [
ECM faults (address conflict) ECM Addr Err
ECM faults (model mismatch) ECM Mismatch
Engine over speed Eng Speed High
Fuel Level Critically
High
Shutdwn
On W 0--100% 95% 0--10 5
On S Fixed 10
ECM xxxxxx Warning On W
ECM xxxxxx Shutdwn On S
Shutdwn
Shutdwn
Shutdwn
On S
On S 0--255 0
On S S A 105-- 120% 115%
Engine start aid active Starting Aid Notice
Engine under speed Eng Speed Low
Shutdwn
On S S A 75--95% 85%
Fuel tank leak * Fuel Leak Warning On W
Fuel tank leak * Fuel Leak Shutdwn On S
High battery voltage Battery High Warning On W S A 110--135% 125% Fixed 10
High coolant temperature
High coolant temperature
High fuel level (diesel-powered models only) *
Coolnt Temp High
Warning
Coolnt Temp High
Shutdwn
Fuel Level High
Warning
On W
On S
On W 0--100% 90% 0--10 5
Loss of fuel Loss of Fuel On S
Low battery voltage Battery Low Warning On W S A 80--105% 100% Fixed 90
Low coolant level * Coolant Lvl Low
Shutdwn
Low coolant temperature
Coolant Temp Low
Warning
On S Fixed 5
On W Fixed
Low cranking voltage Lo Crank Vlt Warning On W Fixed 60% Fixed 6
Low engine oil level * Oil Level Low Warning On W
Low engine oil level * Oil Level Low Shutdwn On S
Low fuel level (diesel models) * Fuel Level Low
Warning
Low fuel level (diesel models) * Fuel Level Low
Shutdwn
Low fuel pressure (gas models) *
Fuel Press Low
Warning
On W 0--100% 35% 0--10 10
On S 0--100% 5% 0--10 0
On W
Low oil pressure
Oil Press Low Warning On W
Low oil pressure
Oil Press Low
Shutdwn
On S
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent. ] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
teTech
GenSet
Mode
Always
unning
R S
topped
Range
Setting
Default
Selection
16_C
(60_F)
Time
Delay
Range
(sec.)
0--10
(0--30
inhibit)
0--10
(0--30
inhibit)
0--10
(0--30
inhibit)
Fixed (Fixed inhibit)
Fixed (Fixed inhibit)
Default
Delay (sec.)
(5 FAA)
inhibit)
inhibit)
inhibit)
inhibit)
inhibit)
Time
0
(0
0 (0
5 (0
0
(30
5
(30
ST-- Short Term, LT--Long Term
TP-6694 7/1828 Section 1 Specifications and Features
GenSet
Time
Default
Time Delay (sec.)
inhibit)
Controller Display
Description
Message
No coolant temperature signal Temp Sig Loss
Shutdwn
No oil pressure signal Press Sig Loss
Shutdwn
Overcrank
Over Crank Shutdwn On S Fixed
Write
Access
Display
teTech
Si
Mode
Always
unning
R
topped
S
Range
Setting
Default
Selection
Delay
Range
(sec.)
Alarm
Horn
Fault
Lamp
Warning
hutdown
S
On S
On S Fixed 5
Speed sensor fault Spd Sens Flt Warning On W
General Functions
Alarm silence, 0--Auto only (NFPA 110), 1--Always
AlarmSilenceMode S A 0--1 1
Aux. inputs 0--5 VDC, 1 analog Aux Input Warning On W 0--100% 100% 0--10 0
Aux. inputs 0--5 VDC, 1 analog Aux Input Shutdwn On S 0--100% 100% 0--10 0
Auxiliary inputs, up to 3 digital (2 additional digital inputs available with I/O module option)
Auxiliary inputs, up to 3 digital (2 additional digital inputs available with I/O module option)
Aux Input Warning On W
Aux Input Shutdwn On S
0--10
(0--30
inhibit)
0--10
(0--30
inhibit)
0(0
inhibit)
0(0
inhibit)
Backup parameters loaded Backup Pars Status
Battery charger 1 communication loss
Battery charger 2 communication loss
Bat1CommLoss On W
Bat2CommLoss On W
Battery charger fault * (does not apply to charger
Batt Chg Flt On W
GM87448)
Battery charger identity conflict BatIdErr On W
Battery charger parameter mismatch
ParMisatch On W
Battery fault Battery Flt On W
Chicago code active * Auto Locked Notice
Common fault Common Fault
Shutdwn
On S
Common warning Common Warng On W
Default parameters loaded Default Pars Warning On W
Emergency stop Emerg Stop Shutdwn On S
Enclosure temperature: high shutdown
Enclsr Temp: High
Shutdwn
On S Fixed Active Fixed
5(20
inhibit)
Engine cooldown (delay) active Eng Cooldown Notice
Engine start delay active Start Delay Notice
Engine started Engine Start Status
Engine stopped Engine Stop Status
EPS supplying load Emerg Pwr On Notice
File system error (controller fault)
File Error Shutdwn On S
Generator running Gen Running Notice
Input/output (optional module board) communication loss
OB1 Com Loss On W
Internal failure Intern Error Shutdwn On S * Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent. ] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
(30
ST-- Short Term, LT--Long Term
TP-6694 7/18 29Section 1 Specifications and Features
GenSet
Time
Default
Time Delay (sec.)
Controller Display
Description
Measurement Units, 0--English, 1--Metric
Message
Measurement Display DS A 0--1 1
Metering communication loss MeterCommLos
Shutdwn
Alarm
Horn
On S
Fault
Lamp
Warning
hutdown
S
Write
Access
Display
teTech
Si
Mode
Always
unning
R
topped
S
Range
Setting
Default
Selection
Delay
Range
(sec.)
NFPA 110 alarm active NFPA Alarm Notice
Not in auto (master control buttons)
Prime power application, 0-- Standby, 1--Prime
Not In Auto Warning On W
Power Type DS A 0--1 0
Remote start Remote Start Status
System ready System Ready Status
System timer failed TimerErrorNotice
Generator Functions
AC sensing loss AC Sens Loss
Warning
AC sensing loss AC Sens Loss
Shutdwn
On W
On S Fixed 3
Alternator protection Alt Protect Shutdwn On S
Ground fault input * Ground Fault Warning On W
kW overload
Total Power High
Shutdwn
On S Fixed
102%
standby,
112%
Fixed 60
prime
Locked rotor (failed to crank) Locked Rotor Shutdwn On S S A 1--5 5
Overfrequency Freq High Shutdwn On S 102--140% 110% Fixed 10
Overvoltage (each phase) Volts (L1--L2, L2--L3,
or L3-- L1) High
On S S A 105-- 135% 120% 2--10 2
Shutdwn
Power rating Pwr Rating DS S 10--5000 275
System frequency System Freq DS S 50--60 60
System voltage System Volt DS S 110--600 208
Underfrequency Frequency Low
Shutdwn
On S 80--95% 90% Fixed
10 ST 60 LT
Undervoltage (each phase) Volts (L1--L2, L2--L3,
or L3-- L1) Low
On S S A 70--95% 80% 5--30 10
Shutdwn
Voltage/phase configuration, 0--Single phase, 1--Single phase dogleg, 2--three phase
SystemPhase DS S 0--3 2
wye, 3--three phase delta
Voltage regulator average voltage adjustment
(Voltage) regulator communication loss
VR Volt Adj DS R 108--600 208
RegCommLoss
Shutdwn
On S
SiteTech Read/Write Display Only
Charger Absorption Current Termination Target (A)
S A 1–5 2
Charger Automatic Equalize Enable
Note: Equalize is only available with FLA/VRLA
S A
Active
Inactive
Inactive
topology selected. * Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent. ] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST-- Short Term, LT--Long Term
TP-6694 7/1830 Section 1 Specifications and Features
Loading...
+ 94 hidden pages