Kohler GM32337-KP1, GM100956-KP1 Installation Instructions Manual

Original Issue Date: 5/04
Model: 4--32 kW
Market: Marine
Subject: Three-Inch (J1939) Remote Digital Gauge Kits
GM32337-KP1 and GM100956-KP1
TT-1379 5/16d
INSTALLATION INSTRUCTIONS
Introduction
Model Controller Kit Number
EGD, EFGD, and EGZD
EOD and EFOD
EOZD and EFOZD
EKD and EFKD ADC II
EKOD and EFKOD
EKOZD and EFKOZD
EKOZD and EFKOZD
Figure 1 Kit Number for Model with Controller Type
ADC 2100
ADC IId
Decision-
Makerr 3500
GM32337-KP1
GM100956-KP1
1
Note: For generator sets with an ADC 2100
controller and with serial numbers below 2051416: These units used an earlier version of
the ADC 2100controller that was equipped witha removeable power mode jumper at P7. Operation of the remote digital gauge’s start/stop function requires that the jumper is enabled on the Advanced Digital Control (ADC) (generator sets shipped from the factory already have the jumper enabled). Refer to the wiring diagram in the generator set operation manual if the jumper was disconnected from terminals 1 and 2 on the P7 connector (continuous power mode).
Note: For generator sets with an ADC 2100
controller: ADC application program version
3.32 or higher is required for complete digital gauge operation. If your application program version is lower than 3.32, use your SecurID to access Kohler Power Resource Center, click on the TechTools button, and follow the instructions to download the files.
Note: For generator sets with a Decision-Makerr
3500 controller: Firmware version 1.14.3 or
higher is required for complete digital gauge operation. If your firmware version is lower than
1.14.3, visit the Kohler Power Resource Center website using the TechTools button.
1. SELECT button
2. UP arrow button
3. DOWN arrow button
Figure 2 Remote Digital Gauge
Parts List
Remote Digital Gauge Kits
23
Kit: GM32337-KP1
Qty. Description Part Number
1 Gauge GM100649 1 Harness, gauge GM32325 1 Decal, warning 249494
Kit: GM100956-KP1
Qty. Description Part Number
1 Gauge GM100649 1 Harness, gauge GM100955 1 Decal, warning 249494
Safety Precautions
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Operating thegenerator set. Carbon monoxidecan cause severe nausea, fainting, or death. Be especially careful if
operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings.
WARNING
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Explosion. Gasoline vapors can cause explosion and severe injury or death.
Before starting the generator set, operate the blower 4 minutes and check the engine compartment for gasoline vapors.
Ignition-protected equipment. Explosive fuel vapors can cause severe injury or death. Gasoline vapors can cause an
explosion. USCG Regulation 33CFR183 requires that all electrical devices (ship-to-shore transfer switch, remote start panel, etc.) must be ignition protected when used in a gasoline and gaseous-fueled environment.
2 TT-1379 5/16
Installation Procedure
1. Remove the generator set from service.
1.1 For generator sets with an ADC 2100 controller: Place the generator set master
switch in the OFF position.
For generator sets with an ADC II or ADC IId controller: Press the start/stop button to stop
the generator set. Then, press the power button to turn off the controller.
For generator sets with a Decision-Makerr 3500 controller: Press the OFF/RESET button
to shut down the generator set.
1.2 Disconnect the generator set engine starting battery, negative (--) lead first.
2. Install the remote digital gauge.
2.1 Select a dry location to mount the remote digital gauge. Consider the length of the wiring harness and the gauge’s mounting depth and size when selecting a location. See Figure 5 for the mounting dimensions.
2.2 For unitswith an ADCcontroller, ordera remote extension harness kit. See Figure 3 for kit selection. Do not use more than 3 remote harness kits and do not exceed 23 m (75 ft.) in harness length.
Remote Extension
Harness Kit Number
GM32333-KP1 4.6 (15)
GM32333-KP2 7.6 (25)
Figure 3 Remote Extension Harness Kits (For Units
with an ADC Controller)
For units with a Decision-Makerr 3500 controller, order a remote extension harness kit. See Figure 4 for kit selection. DO NOT
exceed 91.4 m (300 ft.) CAN network length.
Length
m (ft.)AsShown In
Figure 8
NOTE: Dimensions in brackets are inch equivalents.
GM30565-B
Figure 5 Mounting Dimensions
2.3 Connect the 6-pin inline connector of the gauge harness (GM32325 or GM100955) to the 6-pin inline connector on the digital gauge. See Figure 6 and Figure 7 or Figure 10.
2.4 For Kit GM32337-KP1: Connect the 12-pin connector end of the gauge harness or a remote extension harness to the generator set’s customer-interface 12-pin connector. See Figure 7, Figure 8, and Figure 9.
2.5 For Kit GM100956-KP1: Connect the 6-pin connector end of the gauge harness to a remote extension harness. See Figure 10, Figure 11, Figure 12, Figure 13, Figure 14, and Figure 15.
Connect the lead ends of the extension harness to the TB12 terminal strip. The TB12 terminal strip is located inside the junction box. See Figure 15 for TB12 connections.
Remote Extension
Harness Kit Number*
GM91774-KP1 7.6 (25)
GM91774-KP2 15.2 (50)
GM91774-KP3 30.5 (100)
GM92053-KP1 7.6 (25)
GM92053-KP3 30.5 (100)
* Y Harness shown in Figure 13
Figure 4 Remote Extension Harness Kits (For Units
with a Decision-Makerr 3500 Controller)
TT-1379 5/16 3
Length
m (ft.)AsShown In
Figure 11
Figure 12GM92053-KP2 15.2 (50)
Connects to the
remote harness.
Connects to
additional serial
gauges, if equipped.
NOTE: Dimensions in brackets are inch equivalents.
Figure 6 Remote Digital Gauge Connections
(Back View)
Connects to the remote digital gauge connector.
Connects to the
generator set
customer-interface
connector or
a remote harness
connector.
Figure 7 Remote Gauge Harness GM32325
(Included with Kit GM32337-KP1)
15 ft. Extension Harness Kit GM32333-KP1 25 ft. Extension Harness Kit GM32333-KP2
GM30565A-B
GM32325-F
Figure 8 Remote Extension Harness Kits
(For Use With Kit GM32337-KP1)
4 TT-1379 5/16
GM30248-
GM33846A-D
Figure 9 Harness Connection Diagram
For Kit GM32337-KP1
25 ft. Extension Harness Kit GM92053-KP1 50 ft. Extension Harness Kit GM92053-KP2
100 ft. Extension Harness Kit GM92053-KP3
Connects to the remote digital gauge connector.
Connects to the
remote extension
harness connector.
Figure 10 Remote Gauge Harness GM100955
(Included with Kit GM100956-KP1)
25 ft. Extension Harness Kit GM91774-KP1 50 ft. Extension Harness Kit GM91774-KP2
100 ft. Extension Harness Kit GM91774-KP3
Figure 11 Remote Extension Harness Kits
(For Use With Kit GM100956-KP1)
GM100955-
GM100990-
GM100997
Figure 12 Remote Extension Harness Kits
(For Use With Kit GM100956-KP1)
Y Harness Kit GM92054-KP1
GM100996-
Figure 13 Y Harness Kit
(For Use With Kit GM100956-KP1)
Figure 14 Remote System Diagram For Kit GM100956-KP1
TT-1379 5/16 5
GM92060-A
Sheet 1 of 2
Sheet 2 of 2
Figure 15 Interconnection Diagram For Kit GM100956-KP1
6 TT-1379 5/16
GM88254-B
2.6 Use rubber grommets and cable ties as necessary to protect and secure the wiring from sharp objects, exhaust system, water, and any moving parts.
2.7 For gasoline-powered marine generator sets, select a location as near as practical to the generator remote digital gauge for mounting the warning decal. The decal should be visible when starting the generator set from the remote digital gauge. Before applying the decal, ensure that the surface is clean and dry.
3. Restore the generator set to service.
3.1 Check that the generator set is off and stopped.
3.2 Reconnect the generator set engine starting battery, negative (--) lead last.
4. Set the controller parameter for J1939 communications.
4.1 For generator sets with an ADC 2100 controller: Set the ADC 2100 controller’s
communication parameter to Cn01 or Cn06. Consult TT-1364 for instructions to change the controller’s parameter settings.
For generator sets with a Decision-Makerr
3500 controller: Using SiteTecht, under the Genset System Configuration menu, select
J1939 for the Public CAN Protocol parameter. See Figure 16.
Note: For more information on SiteTecht,see
TP-6701t SiteTech Software Operation Manual.
Note: ADC 2100 controllers: When the
master switch is in the AUTO position, the controller may automatically power down and go into Sleep Mode to conserve battery power. This will occur, after one hour of inactivity, only when the CAN parameter is set to Cn06. If the CAN parameter is set to Cn01, the controller will remain powered and will draw battery power. See TT-1364 for more information.
ADC 2100 Controller
CAN
Setting
Cn01 Never/None J1939 gauge with
Cn06 1 Hour J1939 gauge with
Power
Down Time
Application
Notes
no sleep mode
one hour sleep mode
For generator sets with an ADC II controller: Set the CAN A parameter to J1939. Consult the generator set installation manual for full instructions to set the CAN A parameter.
Figure 16 Genset System Configuration (in SiteT echt)
For generator sets with an ADC IId controller: Set the CAN A parameter, under the Gen Set System menu, to J1939. Consult the generator set operation manual for full instructions to set the CAN A parameter.
TT-1379 5/16 7
Gauge Operation
To Select the Units of Measure:
Note: Data can be displayed in either US or
international units.
1. With no power to the gauge, press and hold the SELECT button. See Figure 17.
2. Apply power to the gauge.
3. The gauge displays: Adc 2100
Note: The gauge will display Adc 2100 even if
the generator set is equipped with an ADC II or ADC IId controller.
4. The gauge displays: UnIT SEt
5. Press and hold both the UP and DOWN buttons until the gauge beeps and the display changes.
6. Use the UP or DOWN buttons to selecteither Int or USA units.
7. Press and hold both the UP and DOWN buttons until the gauge beeps and the display changes.
8. Press the DOWN button.
21
!
GM30565-B
10
1. Fault indicator
2. Arrow (if blinking, indicates that the generator set is running)
3. Select button
4. Voltage (volts)
5. Oil pressure (psi or kPa)
6. Engine speed (rpm)
7. Frequency (Hz)
8. Coolant temperature (_For_C)
9. Battery voltage (VDC)
10. Runtime hours
Figure 17 Remote Digital Gauge
3
4 5 6
7 8
9
9. The gauge displays: ESC 08 ?
10. Press and hold both the UP and DOWN buttons until the gauge switches to the monitor mode.
8 TT-1379 5/16
Digital Gauge Modes:
Start/Stop Command Mode
Note: The digital gauge has three normal operating
modes: monitor, start/stop, and backlight adjust. Use the SELECT button at the top of the gauge to step through the modes.
Monitor Mode
Press the SELECT button until the display shows generator set data and indicator arrows. Use the UP or DOWN arrow to scroll through the data. The corresponding illuminated arrow indicates which data is being displayed. See Figure 17. Any faults are displayed in blinking text. The following generator set operation data is displayed in this mode:
D Voltage (AC volts)
D Oil pressure (psi or kPa). May require the
installation of an optional oil pressure sender on the engine. See Figure 18.
D Engine speed (rpm)
D Frequency (Hz)
D Coolant temperature (_For_C)
D Runtime hours
D Battery voltage (VDC)
Note: The maximum battery voltage that the
ADC will display on the remote digital gauge is 31.5 volts. If the voltage is higher than 31.5, it will display 31.5 volts.
Model Oil Pressure Sender
EKD and EFKD
EOD and EFOD
EOZD and EFOZD
EGD, EFGD, and EGZD
EKOZD and EFKOZD
Figure 18 Models with Optional or Standard
Oil Pressure Sender
Optional
StandardEKOD and EFKOD
Press the SELECT button until the display shows SEND RUN or SEND STOP. Use the UP or DOWN arrow to send a remote start/stop command.
Note: The ADC 2100 must be powered (display active)
and the master switch must be in the AUTO position for remote start/stop. If the ADC 2100 master switch is in the RUN position, a remote stop command will not stop the generator set. The arrow at the top left side of the display blinks to indicate that the generator set is running (see Figure 17, item 2).
Note: The ADC II and ADC IId must be powered
(display active) for remote start/stop.
Note: The Decision-Maker 3500 must be powered
(display active) and in the AUTO position for remote start/stop. If in the RUN position, a remote stop command will not stop the generator set. The arrow at the top left side of the display blinks to indicate that the generator set is running (see Figure 17, item 2).
Refer to the generator set operation manual and follow the safety precautions when operating the generator set.
Backlighting Mode
Press the SELECT button until the display shows LEVL. Use the UP or DOWN arrow to select a lighting level:
D 0 = no backlight
D 3 = brightest backlight.
Note: While in this mode, faults appear on the display,
however no audible alarm is heard.
Once set, the backlight level defaults to the last selection.
The maximumpower draw of the remote gauge is50 mA at 12 VDC (or 25 mA at 24 VDC) with the brightest backlight.
TT-1379 5/16 9
To Silence an Audible Alarm:
Faults are indicated by blinking or solid text and an audible alarm. To silence an audible alarm, press and hold the UP and DOWN arrow buttons simultaneously until the gauge emits a long beep and then release.
Note: For a fault warning, the background lamp is solid.
For a fault shutdown, the background lamp will flash. Consult your operation manual for more details on warnings and shutdowns.
Note: Always identify and correct the cause of a fault
shutdown before resetting the controller. Consult the operation manual for guidance and items to check.
Digital Gauge Fault Codes
Fault codes are displayed on the gauge when a fault condition is detected.
See Figure 19 for faults displayed on the gauge for units equipped with an ADC 2100 controller.
See Figure 20 for faults displayed on the gauge for units equipped with an ADC II or ADC IId controller.
See Figure 21 for faults displayed on the gauge for units equipped with a Decision-Makerr 3500 controller.
Units with ADC 2100 Controller
Digital Gauge
Display
LOP Low Oil Pressure
OC Over Crank
OS Over Speed
LCL Low Coolant Level
LOC Loss of Coolant
AF Auxiliary Input Fault
HE High Engine Temperature
OU Over Voltage
UU Under Voltage
OF Over Frequency
UF Under Frequency
LB Low Battery Voltage
HB High Battery Voltage
Figure 19 Fault Codes Displayed on the Gauge (for
Units Equipped with an ADC 2100 Controller)
Description
Units with ADC II or ADC IId Controller
Digital Gauge
Display
LOP Low Oil Pressure
OC Over Crank
OS Over Speed
AF Auxiliary Input Fault
HE High Engine Temperature
OU Over Voltage
UU Under Voltage
OF Over Frequency
UF Under Frequency
LB Low Battery Voltage
HB High Battery Voltage
Description
Figure 20 Fault Codes Displayed on the Gauge (for
Units Equipped with an ADC II or ADC IId Controller)
Units with Decision-Makerr 3500 Controller
Digital Gauge
Display
LOP Low Oil Pressure
OS Over Speed
AF Auxiliary Input Fault
HE High Engine Temperature
OU Over Voltage
UU Under Voltage
OF Over Frequency
UF Under Frequency
For other possible fault codes, the gauge displays:
SHdn (for a Shutdown) or Alrt (for an Alert/Warning).
Check the interface on the Decision-Makerr 3500 Controller for more details.
Description
Figure 21 Fault Codes Displayed on the Gauge (for
Units Equipped with an Decision-Makerr 3500 Controller)
10 TT-1379 5/16
Notes
TT-1379 5/16 11
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Availability is subject to change without notice. Kohler Co. reserves the right tochange the design or specifications without noticeand withoutany obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability.
2004, 2006, 2012, and 2016 by Kohler Co. All rights reserved.
12 TT-1379 5/16
Loading...