Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory NumberAccessory Description
Engine Identification
Record the product identification information from the
engine nameplate.
Manufacturer
Model Designation
Serial Number
x:in:007:001
Page 3
Table of Contents
Product Identification InformationInside front cover............................................
Safety Precautions and InstructionsI........................................................
Appendix A. AbbreviationsA-1...............................................................
Appendix B. Operating Hour Service LogA-3..................................................
Table of ContentsTP-6068 10/02
Page 4
Page 5
Safety Precautions and Instructions
IMPORTANTSAFETY
INSTRUCTIONS. Electromechanical
equipment, including generator sets,
transfer switches, switchgear, and
accessories, can cause bodily harm
and pose life-threatening danger when
improperly installed,operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
personal injury, death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazardthatcan causesevere
personal injury, death,or substantial
property damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working onthe generatorset.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Place the generator set start/stop
switchintheSTOPposition.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted
sulfuric acid. Battery acidcan cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery.Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid inthe case
of eye contact. Never add acid to a
battery after placing the battery in
service, asthis mayresult inhazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
containerwith4L(1gal.)ofwaterand
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove alljewelry beforeservicing the
equipment. Discharge static electricity
from your bodybefore touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
TP-6068 10/02Safety Precautions and Instructions I
Page 6
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set withthe aircleaner/silencer
removed.
Combustible materials. A sudden
flash fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the fuel system. Keep
the compartment and the generator set
clean and free of debris to minimize the
risk of fire. Wipe up spilled fuels and
engine oil.
Combustible materials. A fire can
cause severeinjury ordeath.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaustsystem mustbe
leakproof and routinely inspected.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases.Carbon monoxide
poisoning symptoms include but are
not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improvewithin minutesof breathing
fresh air.
Copper tubing exhaust systems.
Carbon monoxide can cause severe
nausea, fainting, or death. Do not
use copper tubing in diesel exhaust
systems.Sulfur in diesel exhaust
causes rapid deterioration of copper
tubing exhaust systems, resulting in
exhaust/water leakage.
Inspecting the exhaust system.
Carbon monoxide can cause severe
nausea, fainting, or death. For the
safety of the craft’s occupants, install a
carbon monoxidedetector. Consult the
boat builder or dealer for approved
detector location andinstallation.
Inspect the detector before each
generator set use. In addition to routine
exhaust system inspection, test the
carbon monoxide detector per the
manufacturer’s instructions and keep
the detector operational at all times.
is an odorless, colorless, tasteless,
nonirritating gasthat cancause death if
inhaled for even a short time. Use the
following precautions when installing
and operating the generator set. Do not
install the exhaustoutlet where exhaust
can be drawn in through portholes,
vents, or air conditioners.If the
generator set exhaust discharge outlet
is near the waterline, water could enter
the exhaust discharge outlet and close
or restrict the flow of exhaust. Never
operate the generator set without a
functioning carbon monoxide detector.
Be especially careful if operating the
generatorsetwhenmooredor
anchoredundercalmconditions
because gases may accumulate. If
operating the generator set dockside,
moor the craft so that the exhaust
discharges on the lee side (the side
sheltered from the wind). Always be
aware of others, making sure your
exhaust is directed away from other
boats and buildings. Avoidoverloading
the craft.
TP-6068 10/02II Safety Precautions and Instructions
Page 7
Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
WARNING
Explosion.
Gasolinevaporscancause
explosion and severe injury or
death.
Before starting the generator set,
operate the blower 4 minutes and
check the engine compartment for
gasoline vapors.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
inawell-ventilatedareaawayfrom
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do notoperate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Draining the fuel system. Explosive
fuel vapors can cause severe injury
or death. Spilled fuel can cause an
explosion. Use acontainer tocatch fuel
when draining the fuel system. Wipe up
spilled fuel after draining the system.
Installing the fuel system. Explosive
fuel vapors can cause severe injury
or death. Fuel leakage can cause an
explosion. Do not modify the tank or
the propulsion engine fuel system.
Equip the craft with a tank that allows
one of the two pickup arrangements
described in the installation section.
The tank and installation must conform
to USCG Regulations.
Pipe sealant. Explosive fuel vapors
can cause severe injury or death.
Fuel leakage can cause an explosion.
Use pipesealant onall threadedfittings
to prevent fuel leakage.Use pipe
sealant that resists gasoline, grease,
lubrication oil, common bilge solvents,
salt deposits, and water.
Ignition-protectedequipment.
Explosive fuel vapors can cause
severe injury or death.Gasoline
vapors can cause an explosion.
USCG Regulation 33CFR183 requires
that all electrical devices (ship-to-shore
transfer switch, remote start panel,
etc.) must be ignition protected when
used in a gasoline and gaseous-fueled
environment. The electrical devices
listed above are not ignition protected
and are not certified to operate in a
gasolineandgaseous-fueled
environment such as an engineroom or
near fuel tanks. Acceptable locations
are the wheelhouse and other living
areas sheltered from rain and water
splash.
Hazardous Noise
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposureto noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage/
Electrical Shock
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding electricalequipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present.Open the main circuit
breakers of all power sources before
servicing theequipment. Configure the
installation to electrically ground the
generator set, transfer switch, and
relatedequipmentandelectrical
circuits to complywith applicablecodes
andstandards.Nevercontact
electrical leads or appliances when
standing in water or on wet ground
because these conditions increase the
risk of electrocution.
Disconnecting the electrical load.
Hazardousvoltagecancause
severe injury or death. Disconnect
the generator set from the load by
opening the line circuit breaker or by
disconnecting the generator set output
leads from the transfer switch and
heavily taping the ends of the leads.
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not
disconnect the generator set from the
load.
Moving rotor.
TP-6068 10/02Safety Precautions and Instructions III
Page 8
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove alljewelry beforeservicing the
equipment.
Testingthevoltageregulator.
Hazardousvoltagecancause
severe injury or death. High voltage
is present at the voltage regulator heat
sink. To prevent electrical shock do not
touch the voltage regulator heat sink
when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and
PowerBoostt Vvoltageregulator
models only)
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severeinjury ordeath.
Connect the generator set to the
building/marina electrical system only
through an approved device and after
the building/marina main switch is
opened. Backfeed connections can
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
electricalsystem.Installa
ship-to-shore transfer switch to prevent
interconnection of the generator set
power and shore power.
Testingliveelectricalcircuits.
Hazardous voltage or current can
cause severe injury or death. Have
trained and qualified personnel take
diagnosticmeasurementsoflive
circuits.Use adequately rated test
equipment with electrically insulated
probes and followthe instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests: (1) Remove all jewelry.
(2) Stand on a dry, approvedelectrically
insulated mat. (3) Do not touch the
enclosure or components inside the
enclosure.(4) Be prepared for the
system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Checking the coolant level.Hot
coolant can cause severe injury or
death.Allow the engine to cool.
Release pressure from the cooling
system before removing the pressure
cap. To release pressure, cover the
pressure capwith a thick cloth and then
slowly turn the cap counterclockwiseto
the first stop. Remove the cap after
pressurehasbeencompletely
released and the engine has cooled.
Check thecoolant levelat thetank ifthe
generator set has a coolant recovery
tank.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Moving Parts
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and coversare in
place.
Wear protective goggles andclothing
when using power tools, hand tools,
or compressed air.
Tightening the hardware.Flying
projectiles can cause severe injury
or death. Loose hardware can cause
the hardware or pulley to release from
the generator setengine and can cause
personalinjury.Retorqueall
crankshaft and rotor hardware after
servicing. Do not loosen the crankshaft
hardware or rotor thrubolt when making
adjustments or servicing the generator
set. Rotate the crankshaft manually in
a clockwise direction only. Turning the
crankshaftbolt orrotorthrubolt
counterclockwisecan loosenthe
hardware.
Moving rotor.
TP-6068 10/02IV Safety Precautions and Instructions
Page 9
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Sound shield removal.Exposed
moving parts can cause severe
injury or death. The generator set
must be operating in order to perform
somescheduledmaintenance
procedures. Be especially careful ifthe
sound shield has been removed,
leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been
rewired fromits nameplate voltage
to
246242
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate.Order
voltage reconnection decal 246242
fromanauthorizedservice
distributor/dealer.
NOTICE
Hardware damage. The engine and
generator set may use both American
Standard and metric hardware. Use
the correct size tools to prevent
rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not
substitutewithinferiorgrade
hardware.Screws and nuts are
available in different hardness ratings.
Toindicatehardness,American
Standard hardware uses a series of
markings, and metric hardware uses a
numeric system. Check the markings
on the bolt heads and nuts for
identification.
NOTICE
Fuse replacement.Replace fuses
with fuses of the same ampere rating
and type (for example: 3AB or 314,
ceramic).Do not substitute clear
glass-type fuses for ceramic fuses.
Refer to the wiring diagram when the
ampereratingisunknownor
questionable.
NOTICE
Saltwater damage. Saltwater quickly
deteriorates metals. Wipe up saltwater
on and around the generator set and
remove salt deposits from metal
surfaces.
TP-6068 10/02Safety Precautions and Instructions V
Page 10
Notes
TP-6068 10/02VI Safety Precautions and Instructions
Page 11
Introduction
This manualprovides operationinstructionsfor
4--27EFOZ/5--32EOZ model generator sets.
Refer to the engine operation manual for generator set
engine scheduled maintenance information.
This manual may be used for models not listed on the
front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Forprofessionaladviceongeneratorpower
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Obtainservicefromanauthorizedservice
distributor/dealer to keep equipment in top condition.
Before installing a marine generator set, obtain the
most current installation manual from your local
distributor/dealer. Only qualified persons should
install the generator set.
x:in:001:002:a
Service Assistance
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
D VisittheKohlerPowerSystems websiteat
KohlerPowerSystems.com
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product
D Call toll free in the US and Canada 1-800-544-2444
D Outside the US and Canada, call the nearest regional
office
Africa, Europe, Middle East
London Regional Office
Langley, Slough, England
Phone: (44) 1753-580-771
Fax:(44) 1753-580-036
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 264-6422
Fax:(65) 264-6455
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
X:in:008:001a
TP-6068 10/02Introduction i
Page 12
Maintenance and Service Parts/Related Literature
Maintenance and Service Parts
Figure 1 identifies maintenance and service parts for your generator set. Obtain a complete list of maintenance and
service parts from your authorized generator distributor/dealer.
Models
8.5EFOZ,
4EFOZ/
Part Description
Air Cleaner
Air Filter Element278612278858278858250902
Battery Charging Fuse
(10 amp)
DC Circuit Breaker (10 amp)250719250719250719250719250719
Figure 2 identifies related literature available for the generator sets covered in this manual. Only trained and qualified
personnel should install or service the generator set.
Models
8.5EFOZ,
4/9EFOZ,
and
Literature Type
Installation ManualTP-6069TP-6069TP-6069TP-6069
Operation ManualTP-6068TP-6068TP-6068TP-6068
Parts Catalog*TP-5616
Service Manual (Engine)TP-5876TP-5876TP-5876TP-6054
Service Manual (Generator)TP-6053TP-6053TP-6071TP-5936
* Includes the generator and engine information.
5/10EOZ
(4EFOZ/5EOZ)
TP-5587
(8.5EFOZ,
9EFOZ/
10EOZ)
6.5EFOZ
and
8EOZ
TP-5616
Figure 2Generator Set Literature
11--20EFOZ
and
13--24EOZ
TP-5591
(11--13EFOZ/
13--15.5EOZ)
TP-5593
(16--20EFOZ/
20--24EOZ)
23/27EFOZ
and
28/32EOZ
TP-5998
x:in:001:005
TP-6068 10/02Introduction iii
Page 14
Notes
TP-6068 10/02iv Introduction
Page 15
22
23
Section 1 Service Views
4
2
1
5
3
START
DC--CIRCUIT
BREAKER
STOP/
PREHEAT
6
HOUR
METER
AC--CIRCUIT
BREAKER
9
7
8
10
11
12
13
14
15
16
17
21
20
19
29
18
30
31
28
DRAIN
WATER
27
1. Controller
26
2. Start/Stop switch
3. Hourmeter
4. DC circuit breaker
5. AC load lead connector (rear)
6. Nameplate (top)
7. Remote start connector (rear)
8. AC circuit breaker
9. Air intake silencer
10. Lifting eye
11. Fuel filter
12. Oil fill
13. Pressure cap
14. Overflow tube
15. Oil fill
16. Seawater pump (water inlet)
17. Lube oil filter
NOTICE
CHECKZINCANODE
EVERY100 HOURS
OR3 MONTHS.
25
24
11--20EFOZ and 13--24EOZ Models Only
18. Oil check
19. Oil drain valve and hose
20. Fuel feed pump
21. Mixing elbow (water outlet/exhaust outlet)
22. Cooling air inlet
23. Coolant overflow bottle (location varies by model)
Consult installation drawings in the spec sheet or installation manual for fuel and battery connection points. Consult an authorized
Note:
distributor/dealer or the service manual for items not shown.
ADV-6285A-A
GB-250000-A
DA-250000
TP-6068 10/021Section 1 Service Views
Page 16
Notes
TP-6068 10/022Section 1 Service Views
Page 17
Section 2 Operation
2.1Prestart Checklist
To ensure continued satisfactory operation perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Air Shrouding.Check for securely installed and
positioned air shrouding.
Battery. Check for tight battery connections. Consult
the batterymanufacturer’s instructionsregarding
battery care and maintenance.
Coolant Level. Check the coolant level according to
the cooling system maintenance information.
Drive Belts. Check the belt condition and tension of the
water pump and battery charging alternator belt(s).
D Ensure that the carbon monoxide detector(s) is (1) in
the craft, (2) functional, and (3) energized whenever
the generator set operates.
Note: Never operate the generator set without a
functioning carbon monoxide detector.
Fuel Level. Check the fuel level and keep the tank(s)
full to ensure adequate fuel supply.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area.Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
Seawater Pump Priming. Prime the seawater pump
before initial startup. To prime the pump: (1) close the
seacock, (2) remove the hose from the water-filter
outlet, (3) fill the hose and seawater pump with clean
water, (4) reconnect the hose to the water filter outlet,
and (5) open the seacock.Confirm seawater pump
operation on startup as indicated by water discharge
from the exhaust outlet.
Exhaust System.Check for exhaust leaks and
blockages. Check the silencer and piping condition and
check for tight exhaust system connections.
Inspect the the exhaust system components (exhaust
manifold, mixing elbow, exhaust line, hose clamps,
silencer, and outlet flapper) for cracks, leaks, and
corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metalparts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps and/or hangers
as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
TP-6068 10/023Section 2 Operation
Page 18
2.2Marine Inspection
Kohler Co. recommends that all boat owners have their
vessels—especially the exhaust system attached to the
generator set—inspected at the start of each boating
season by the local Coast Guard Auxiliary. If there is no
Coast Guard Auxiliary in the area, contact an authorized
Kohlerr distributor/dealer for the inspection.
m:op:001:003
2.3Angular Operation
See Figure 2-1 for angular operation limits for units
covered in this manual.
Continuous
25_30_
Maximum value for all directions
Intermittent—
3 minutes or less
Figure 2-1Angular Operation
m:op:001:004
2.4Operation in European Union
Member Countries
This generator set is specifically intended and approved
for operation below the deck in the enginecompartment.
Operation above the deck and/or outdoors would
constitute a violation of European Union Directive
2000/14/EC noise emission standard.
2.6Starting and Stopping
Procedure
Note: Opening seacock. Before starting the generator
set, open the seacock to allow cooling water
passage. Failure to do so could damage the
seawater pump impeller and cause serious
engine overheating damage.
Note: Transfer switch.Check that the marine
ship-to-shore transfer switch, if equipped, is in
the ship position.
Note: Close seacock if engine fails to start. If the
engine fails to start after the first attempt, close
the seacock before the next starting attempt.
Failure to close the seacock may cause seawater
to enter the exhaust piping, silencer, and/or
engine.A water-filled exhaust piping and
silencer may further hinder generator starting
and cause seawater entry into the engine
cylinders through the exhaust valve.Water
ingested into the engine may cause major engine
damage that the Kohler Co. warranty does not
cover.
Note: Close seacock if water enters the exhaust
system.If water enters the exhaust system,
close the seacock and drain the water from the
exhaust system at the silencer’s drain plugbefore
attempting to start the generator set. If excessive
cranking is a chronic problem, have the unit,
including the exhaust system, serviced by an
authorized Kohlerr distributor/dealer.
2.5Exercising the Generator Set
Operate the generator set under load once each week
for one hour with an operator present.
The operator should perform all of the prestart checks
before starting the exercise procedure.Start the
generator set according to the starting procedure in the
controller section of this manual. While the generator
set is operating, listen for a smooth-running engine and
visually inspect the generator set for fluid or exhaust
leaks.
x:op:001:005
Note: Starter motor cooldown.Do not crank the
engine continuously for more than 10 seconds at
a time.Allow a 60-second cooldown period
between cranking attempts if the engine does not
start. If the unit fails to start after 3 attempts,
contact an authorized Kohlerr distributor/ dealer
for repair. Failure to follow these guidelines may
result in starter motor burnout.
The following table describes the allowable cranking
time:
Cranking
Attempts
1Openup to 10 seconds
2Closeup to 10 seconds
3Closeup to 10 seconds
Allow a 60-second cooldown period between cranking
attempts.
If the units fails to start after 3 attempts, contact an
authorized Kohler
Once unit is running, immediately open the seacock.
Seacock
Position
Cranking
r distributor/dealer for repair.
Time
TP-6068 10/024Section 2 Operation
Page 19
2.6.1Controls and Indicators
A
A
2.6.3Remote Panel Gauge Operation
The following table describes the controls and indicators
located at the controller:
NameDescription
Start/Stop SwitchUse this switch to start and stopthe
AC Circuit Breaker
(optional)
DC Circuit BreakerThe circuit breaker trips when a
Remote Start
Connector
HourmeterThe meter records total generator
generator set. Press the switch to
theSTARTpositiontostartthe
generator set. Press the switch to
theSTOPpositiontostopthe
generator set.
The circuit breaker trips when a
fault occurs in the output circuit.
During maintenance of craft or
generator set wiring, the circuit
breaker disconnects the generator
set. Place the circuit breaker(s) in
the ON position to close the circuit
breaker.
fault occurs in the controller circuit.
After afault correction,depress the
circuit breaker’s center button to
reset the circuit breaker.
A 6-pin connector on the
controller’s back panel allows the
connection of (optional) remote
start kits
set operating hours for reference
in maintenance scheduling.
.
2.6.2Starting the Generator Set
If the generator set has an optional remote panel with
gauges, observe the gauges upon engine startup. If
gauge readings are not within the ranges specified,
contact an authorized service distributor/dealer.
GaugeNormal Operating Range
Oil pressure276--414 kPa (40--60 psi )*
Water temperature
DC voltmeter12--14 volts
*50 Hz models show a slightly lower pressure range.
77--91°C (170--195°F)
2.6.4Stopping the Generator Set
The following table describes the actions required to
stop the generator set.
Step
1Cooldown
Run the generator set at no load for 5 minutes to
ensure adequate engine cooldown.
2Stopping
Place the controller start/stop switch or remote
start/stop switch in the STOP position.
NOTE: Do not place the start/stop-preheat switch,
if equipped, in the STOP-PREHEAT position for
more than 30 seconds or damage to the preheat
feature may occur.
3Fuel shutoff valve
Close the manual fuel shutoff valve, if equipped.
ction
The following table describes the actions required to
start the generator set.
Step
1Preheat/cold weather starts
During cold weather starts** place the controller’s
start/stop switch in the STOP/PREHEAT position for
15--20 seconds before attempting to start the
generator set to energize the air heater coil
(8.5--27EFOZ and 10--32EOZ) or glow plugs
(4--6.5EFOZ and 5--8EOZ). Do not energize the
preheat feature for more than 30 seconds or
damage to the preheat feature may occur.
NOTE: All controller start/stop switches indicate
preheat; however, an optional preheat kit is required
to make the preheat feature functional.
2Fuel shutoff valve
Open the manual fuel shutoff valve, if equipped.
3Starting
Hold the generator set controllerstart/stop switch or
the remote start/stop switch in the START position
until the generator set starts.
**Below --5_C(23_F) 4/8.5/9/23/27EFOZ and 5/10/28/32EOZ
Below 5_C(41_F) 6.5EFOZ/8EOZ
Below 4_C(40_F) 11--20EFOZ and 13--24EOZ
ction
TP-6068 10/025Section 2 Operation
Page 20
Notes
TP-6068 10/026Section 2 Operation
Page 21
Section 3 Scheduled Maintenance
3.1General Maintenance
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working onthe generatorset.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set asfollows: (1) Place the generator set start/stop
switch in the STOP position. (2) Disconnect the power to the
battery charger, if equipped. (3) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
NOTICE
Hardware damage. The engine and generator set may use
both American Standardand metrichardware. Use the correct
size tools to prevent rounding of the bolt heads and nuts.
See the Safety Precautions and Instructions at the
beginning of this manual before attempting to service,
repair, or operate the generator set. Have an authorized
distributor/dealer perform generator set service.
Engine Service. Perform generator set engine service
at the intervals specified by the engine operation
manual.
Generator Set Service. Perform generator set service
at the intervals specified by the generator set operation
manual.
If the generator set operates under dusty or dirty
conditions, use dry compressed air to blow dust out of
the alternator. With the generator set running, direct the
stream of air in through the cooling slots at the alternator
end.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and coversare in
place.
Servicing the generator set when it isoperating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Sound shield removal. Exposed moving parts can cause
severe injury or death. The generator set must be operating
in orderto performsome scheduled maintenance procedures.
Be especially careful if the sound shield has been removed,
leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Routine Maintenance. Refer to the following generator
set service schedule, the engine service schedule, and
the hourmeter located on the generator set controller to
determine when to schedule routine maintenance.
Service more frequently generator sets that are subject
to extreme weather or dusty or dirty conditions.
Service Log. Use the Operating Hour Service Log
located in the back of this manual to document
performed services.
Service Schedule. Perform maintenance on each item
in the service schedule at the designated intervals for
the life of the generator set. For example, an item
requiring service every 100 hours or 3 months also
requires service after 200 hours or 6 months, 300 hours
or 9 months, and so on.
x:sm:004:001
TP-6068 10/027Section 3 Scheduled Maintenance
Page 22
3.2Service Schedule—4--20EFOZ and 5--24EOZ Models
Perform Service at Intervals
Indicated (X)
Reference
Section
Daily
Every
50 Hrs.
or 1
Month
Every
200 Hrs.
or 3
Months
400 Hrs.
Months
FUEL SYSTEM
X
Check the fuel level and fill as necessary3.5
(Before
operation)
X
Check for any abnormal fuel injection sound [
(During
operation)
Remove the sediment from the fuel tank and drain
the fuel tank [w
Clean the fuel filter *
(4/6.5EFOZ and 5/8EOZ models only)
3.5.2X
X
Replace the fuel filter element *3.5.2X
Check the fuel injection nozzles/check the injection
spray condition *[]
Check the fuel injection timing *[]
Check the fuel injection pump *[]
LUBRICATION SYSTEM
Check the crankcase oil level and add oil as
necessary
3.4.2
X
(Before
operation)
X
Replace the oil in the crankcase *3.4.3
(Break-in
X
period)
X
Replace the lube oil filter element *3.4.3
(Break-in
period)
COOLING SYSTEM
X
Check the coolant level and fill as necessary *3.8.2
(Before
operation)
Check the seawater outlet and clean as necessary3.7X
X
Adjust the seawater pump belt tension *3.9.1
(Break-in
X
period)
Check the function of the siphon break, if equipped3.8.6X
Check the heat exchanger anticorrosion zinc
condition, if equipped *
Check/replace the seawater pump impeller *[
Replace the coolant *[
Replace the heat exchanger anticorrosion zinc
anode, if equipped *[
*Requires removal of the sound shield door, if installed
[Consult your local distributor/dealer for service
]Read the WARNING found at the beginning of the manual regarding moving parts
wConsult the operating instructions supplied with the craft
3.8.7X
3.8.5
(Check)X(Replace)
3.8.3X
3.8.7X
Every
or 6
X
X
X
X
Every
1000 Hrs.
or Yearly
X
TP-6068 10/028Section 3 Scheduled Maintenance
Page 23
Service Schedule—4--20EFOZ and 5--24EOZ Models, continued
Perform Service at Intervals
Indicated (X)
Reference
Section
Daily
Every
50 Hrs.
or 1
Month
Every
200 Hrs.
or 3
Months
Every
400 Hrs.
or 6
Months
1000 Hrs.
or Yearly
INTAKE/EXHAUST SYSTEM
X
Inspect the exhaust system components *[
3.7
(Before
operation)
Check the exhaust gas condition. If the exhaust is
blue or black, contact your local distributor/dealer
Clean the intake silencer element *
(11--20EFOZ and 13--24EOZ models)
Clean the intake silencer element *
(4--9EFOZ and 5--10EOZ models)
3.7
3.6X
3.6X
X
(During
operation)
Replace the intake silencer element *3.6X
Clean the exhaust/water mixing elbow *[
Check the breather pipe for obstructions *[
Inspect the turbocharger compressor, if equipped *[
Check for abnormal turbocharger rotor noise during
operation, if equipped *[
3.7X
X
X
X
Check the turbo rotor shaft for wear, if equipped *[
Inspect the complete exhaust system k2.2X
ELECTRICAL SYSTEM
X
Keep the battery charged and in good condition w3.10
(Before
operation)
X
Adjust the alternator driving belt tension *3.9.2
(Break-in
X
period)
Check and tighten the electrical connections *X
Clean the battery cables [
ENGINE AND MOUNTING
X
Check for water, fuel, coolant, and oil leakage *[]
(After
operation)
X
Retighten any loose nuts and bolts *
(Before
operation)
Check the mounting bolts/vibromounts and tighten if
necessary *
X
Adjust the intake/exhaust valve clearance *[X
Check the compartment condition (fuel, oil, or water
leaks)
X
(Before
operation)
REMOTE CONTROL SYSTEM
X
Check the remote control operation2.6.3
(Break-in-
period)
GENERATOR
Test run the generator set2.5
Blow dust out of the generator *[
*Requires removal of the sound shield door, if installed
[Consult your local distributor/dealer for service
]Read the WARNING found at the beginning of the manual regarding moving parts
wConsult the battery manufacturer’s instructions
kShould be performed by your local distributor/dealer
3.1X
X
(Weekly)
Every
X
X
X
TP-6068 10/029Section 3 Scheduled Maintenance
Page 24
3.3Service Schedule—23/27EFOZ, 28/32EOZ Models
Perform Service at Intervals
Indicated (X)
Reference
Section
Before
Starting
Every
50 Hrs.
or 1
Month
Every
200 Hrs.
or 3
Months
400 Hrs.
Months
FUEL SYSTEM
Check the fuel level and fill as necessary3.5X
Remove the sediment from the fuel tank [w
X
X
Check for any abnormal fuel-injection sound [
During
operation
Clean the fuel filter *3.5.2X
Replace the fuel filter element *3.5.2X
Check the fuel injection nozzles/check the injection
spray condition *[]
Check the fuel injection timing *[]
Check the fuel injection pump *[]
Check the governor operation and adjust as
necessary *[]
LUBRICATION SYSTEM
Check the crankcase oil level and add oil as
necessary
3.4.2X
X
Replace the oil in the crankcase *3.4.3
(Break-in
X
period)
X
Replace the lube oil filter element *3.4.3
(Break-in
period)
COOLING SYSTEM
Check the coolant level and fill as necessary *3.8.2X
Check the seawater outlet and clean as necessary3.7X
Check the function of the siphon break, if equipped3.8.6X
X
Adjust the seawater pump belt tension *3.9.1
(Break-in
X
period)
Check the heat exchanger anticorrosion zinc
condition *
Replace the seawater pump impeller *[
3.8.7X
3.8.5
Check the thermostat function *[
Flush the cooling system *[
Replace the heat exchanger anticorrosion zinc
anode *[
*Requires removal of the sound shield door, if installed
[Consult your local distributor/dealer for service
]Read the WARNING found at the beginning of the manual regarding moving parts
wConsult the operating instructions supplied with the craft
3.8.7X
Every
or 6
X
X
Check
Every
1000 Hrs.
or Yearly
X
X
X
X
X
X
X
TP-6068 10/0210 Section 3 Scheduled Maintenance
Page 25
Service Schedule—23/27EFOZ, 28/32EOZ Models, continued
Perform Service at Intervals
Indicated (X)
Reference
Section
Before
Starting
Every
50 Hrs.
or 1
Month
Every
200 Hrs.
or 3
Months
Every
400 Hrs.
or 6
Months
1000 Hrs.
or Yearly
INTAKE/EXHAUST SYSTEM
Inspect the exhaust system components *[
Check the exhaust gas condition. If the exhaust is
blue or black, contact your local distributor/dealer
3.7X
3.7
During
operation
X
Replace the intake silencer *3.6X
Clean the exhaust/water mixing elbow *[
Check the breather pipe for obstructions *[
3.7X
X
Inspect the complete exhaust system k2.2X
ELECTRICAL SYSTEM
Keep the battery charged and in good condition w3.10X
X
Adjust the alternator driving belt tension *3.9.2
(Break-in
X
period)
Check and tighten the electrical connections *X
Clean the battery cables [
ENGINE AND MOUNTING
Check for water, fuel, coolant, and oil leakage *[]
XX
Retighten all major nuts and bolts *XX
Check the mounting bolts/vibromounts and tighten if
necessary *
X
Adjust the intake/exhaust valve clearance *[X
Check the compartment condition (fuel, oil, or water
leaks)
X
REMOTE CONTROL SYSTEM
X
Check the remote control operation2.6.3
(Break-in
X
period)
GENERATOR
Test run the generator set2.5
Blow dust out of the generator *[
*Requires removal of the sound shield door, if installed
[Consult your local distributor/dealer for service
]Read the WARNING found at the beginning of the manual regarding moving parts
wConsult the battery manufacturer’s instructions
kHave performed by the your local distributor/dealer
3.1X
X
(Weekly)
Every
X
TP-6068 10/0211Section 3 Scheduled Maintenance
Page 26
3.4Lubrication System
3.4.2Oil Check
See the Scheduled Maintenance section for oil change
and oil filter replacement intervals. See Section 1 for the
oil drain, oil check, oil fill, and oil filter locations.
x:sm:001:002:
3.4.1Oil Specifications
Use oil that meets the American Petroleum Institute
(API) classification of CD, CC/CD, or CC.Using an
unsuitable oil or neglecting an oil change may result in
damage and a shorter engine life. Figure 3-1 shows the
recommended Society of Automotive Engineers (SAE)
viscosity designation for given operating temperature
ranges.
SAE
Service
Grade
5W20
20W40
10W30
20W20
20W30
Check the oil level in the crankcase daily or before each
startup to ensure that the level is in the safe range. To
check the oil level, remove the dipstick and wipe the end
clean, reinsert as far as possible, and remove. Maintain
the oil level between the Min and Max marks on the
dipstick, as shown in Figure 3-2. See Section 1 for
dipstick location.
2
1. Min mark
2. Max mark
1
TP-5586-3
Figure 3-2Oil Level Check Marks
Note: Do not operate the set if the oil level is below the
Min mark or above the Max mark.
20W40
°C°F-- 30-- 2 0 -- 1001 02 03 04 0
0204060 80 100°C°F
Operating Temperature
TP-5856-1
Figure 3-1Engine Oil Selection
Note: Failure to observe the oil specifications may
cause inadequate lubrication/oil pressure and
cold-starting difficulties.
TP-6068 10/0212 Section 3 Scheduled Maintenance
Page 27
3.4.3Oil Change
g. Close the oil drain valve.
Change the oil more frequently if the generator operates
under dirty, dusty conditions.See Figure 3-3 for oil
capacities.
ModelL (Qts.)
4EFOZ and 5EOZ3.0 (3.2)
6.5EFOZ and 8EOZ2.3 (2.4)
8.5EFOZ, 9EFOZ and 10EOZ5.2 (5.5)
1 1/11.5/13EFOZ and 13/14/15.5EOZ4.7 (5.0)
16/17.5/19/20EFOZ and 20/23/24EOZ5.8 (6.1)
23/27EFOZ and 28/32EOZ10.2 (10.8)
Figure 3-3Oil Capacities
Oil Change Procedure
Whenever possible, drain the oil while it is still warm.
1. Drain the oil.
a. Place the generator set start/stop switch in the
STOP position.
b. Disconnect the power to the battery charger, if
equipped.
h. Replace the cap on the oil drain hose. Replace
theoildrainhoseinitsretainingclip.
2. Replace the oil filter.
a. Removetheoilfilterbyrotatingit
counterclockwise with an oil filter wrench.
b. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
c. Install the new oil filter following the instructions
provided with the filter.
Note: Dispose of all waste materials (engine
oil, fuel, filter, etc.) in an environmentally
safe manner.
3. Fill with oil. Add new oil of the weight, grade, and
quantity specified in Section 3.4.
Electric Oil Drain/Oil Fill Pump Procedure:
Disconnect the pump. Close the oil drain valve.
Replace the cap on the oil drain hose.
4. Check for leaks.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the oil drain hose from its retaining
clip. Remove the cap from the oil drain hose
and lower the hose into an oil collection
container.
Electric Oil Drain/Oil Fill Pump Procedure:
Connect the pump to the end of the oil drain
hose. Place the outlet of the pump into an oil
collection container. Remove the oil fill cap(s).
e. Open the oil drain valve on the engine.
f. Allow time for the engine oil to drain completely.
Electric Oil Drain/Oil Fill Pump Procedure:
Activate the pump until all of the oil is removed.
Go to step 2.
a. Check that the generator set start/stop switch is
in the STOP position.
b. Reconnect the generator set engine starting
battery, negative (--) lead last.
c. Reconnect the power to the battery charger, if
equipped.
d. Start the generator set and check for leaks
around the oil filter.
e. Stop the generator set and tighten the oil filter to
stop any leaks.
x:sm:001:003:
TP-6068 10/0213Section 3 Scheduled Maintenance
Page 28
3.5Fuel System
3.5.1Fuel Specifications
Use a clean, good quality diesel fuel oil with a cetane
number of 45 or greater. Clean fuel prevents the diesel
fuel injectors and pumps from clogging.
Fuel Recommendations
United StatesISO 8217 DMA, BS 2869 Part 1 Class A1
or Part 2 Class A2
United Kingdom BS 2869-1983, Part 2 Class A2
GermanyDIN 51 601-1978
Note: Never store diesel fuel in galvanized containers;
diesel fuel and the galvanized coating react
chemically to produce flaking that quickly clogs
filters or causes fuel pump or injector failure.
Note: Avoid storing fuel for more than one month. Take
special precautions to keep all dirt, water, and
other contaminants out of fuel to prevent the
growth of microbes. Microbes form slime that
clogs the fuel filter and lines.
3. Remove the filter bowl and fuel filter. Clean the fuel
filter with fresh fuel oil and blow compressed air
from the inside outward. Replace a damaged fuel
filter. Dispose of the fuel filter in an approved
manner.
4. Wipe off all parts with a clean rag.Inspect all
mating surfaces and threads for damage; replace
as necessary.
5. Place the fuel filter into the filter bowl and lubricate
the rubber seal with fresh fuel oil. Wash hands after
any contact with fuel oil.
6. With the collar against the filter bowl flange,
position the fuel filter against the adapter and
hand-tighten the collar.
7. Open the fuel supply valve.
8. Bleed the system. See Section 3.5.3, Bleeding the
Fuel System.
8.5--27EFOZ and 10--32EOZ Models:
1. Close the fuel supply valve.
Note: Do not run the generator set out of fuel because
the fuel lines will draw in air and necessitate
bleeding the fuel system before restarting the
unit.
3.5.2Fuel Filter
The quality and condition of the fuel largely determine
the filter’s useful life. Replace the fuel filter element as
listed in the service schedule. Section 1 shows the
typical location of a fuel filter.Use the applicable
procedure below to replace the fuel filter.
Fuel Filter Cleaning/Replacement Procedure
4/6.5EFOZ and 5/8EOZ Models:
1. Close the fuel supply valve.
2. Remove the collar from the fuel filter adapter while
holding the filter bowl in place.
2. Loosen the fuel filter by turning it counterclockwise.
Remove the fuel filter and use rags to clean up
spilled fuel oil.Dispose of the fuel filter in an
approved manner.
3. Clean the contact surface of the fuel oil filter
adapter.
4. Lightly lubricate the gasket surface of the new fuel
filter with fresh fuel oil. Thread the filter on the
adapteruntilthegasketmakescontact;
hand-tighten the filter an additional one-half turn.
Wash hands after any contact with fuel oil.
5. Open the fuel supply valve.
6. Bleed the system. See Section 3.5.3, Bleeding the
Fuel System.
TP-6068 10/0214 Section 3 Scheduled Maintenance
Page 29
3.5.3Bleeding the Fuel System
Bleed air from the fuel system to prevent startingfailures
and/or erratic operation. One or more of the following
causes air to collect in the fuel system:
D Operating the generator set until the fuel supply is
emptied.
D Developing air leaks in the suction side of the fuel
system.
Note: Wipe up all spilled diesel fuel after bleeding
the system. Wash hands after any contact
with fuel oil.
4/6.5EFOZ and 5/8EOZ Models
1
2
D Replacing the fuel filter.
Note: Connect the battery during the priming procedure
to allow engine cranking.Do not allow the
engine/generator to start. To prevent starting,
toggle the start/stop switch by momentarily
placing the start/stop switch in the START
position for a few seconds and then placing the
switch in the STOP position. Close the seacock
during bleeding.
Procedure to Bleed the Fuel System
1. Loosen the fuel filter screw at position 1. See
Figure 3-4.
2. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 1.
Tighten the screw.
3. Loosen the fuel filter screw at position 2.
4. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 2.
Tighten the screw.
3
8.5--27EFOZ and 10--32EOZ Models
1
2
3
5
4
TP-5586-3
5. Loosen the fuel injection pump screw at position 5.
6. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 5.
Tighten the screw.
5
1. Vent screw, position 1
2. Vent screw, position 2
3. Fuel filter
4. Fuel injection pump
5. Vent screw, position 5
4
TP-5592-3
Figure 3-4Fuel System (Typical)
TP-6068 10/0215Section 3 Scheduled Maintenance
Page 30
3.6Air Intake Silencer/Cleaner
At the interval specified in the service schedule, clean or
replace the air intake silencer. Clean the silencer more
frequently if the generator set operates in dirty, dusty
conditions. Follow one of the procedures described
below.
3. Wash the element in mild detergent and water
solution.Rinse and air dry the element.See
Figure 3-5.
4. Wipe the intake silencer cover and base with a
clean rag to remove any dirt. Check the base for
damage; replace as necessary.
A dry-type air cleaner silences and filters the intake air.
The air intake silencer assembly connects to the intake
manifold via a flexible hose.
1. Release the spring clips to open the housing and
remove the air silencer element.
2. Tap the element lightly against a flat surface to
dislodge loose surface dirt. Do not clean in any
liquid or use compressed air as these will damage
the filter element.
3. Examine the element and housing for damage and
wear. Replace the element or housing if necessary.
1
1. Element
Figure 3-5Element Washing
(11.5/13EFOZ and 14/15.5EOZ Models)
5. Reassemble the element and cover assembly to
the intake silencer base.Make sure that the
sealing surfaces fit and reattach the spring clips.
The air intake silencer duct should be at the 5
o’clock position as viewed from the generator end.
4. Wipe the cover and base with a clean rag to remove
any dirt. Make sure that the sealing surfaces fit
correctly, and reattach the spring clips.
11.5/13EFOZ and 14/15.5EOZ Models:
A round air cleaner silences and filters the intake air.
Replace a damaged or dirt-contaminated air silencer.
See Section 1 and refer to the following procedure:
1. Release the two spring clips and remove the intake
silencer cover.
2. Remove the element from the cover and inspect. If
the element is not damaged, continue with step 3.
If the element is damaged, replace it, skip step 3,
and go to step 4.
The air cleaner silences and filters the intake air. The air
intake silencer assembly connects to the air intake
manifold.
1. Release the clamp (two clamps if equipped with a
sound shield).
2. Remove the air intake silencer assembly.
3. Replace with a new air intake silencer assembly.
4. Wipe the cover and base with a clean rag to remove
any dirt. Make sure that the sealing surfaces fit
correctly and reattach the clamp(s).
TP-6068 10/0216 Section 3 Scheduled Maintenance
Page 31
3.7Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaustsystem mustbe
leakproof and routinely inspected.
Inspecting the exhaust system. Carbon monoxide can
cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector.
Consult the boat builder or dealer for approved detector
location and installation. Inspect the detector before each
generator set use. In addition to routine exhaust system
inspection, test the carbon monoxide detector per the
manufacturer’s instructions and keep the detector operational
at all times.
At the interval specified in the service schedule, inspect
the exhaust system. See Section 1 for the exhaust
outlet location.
Inspection Points
Inspect the the exhaust system components (exhaust
manifold, mixing elbow, exhaust line, hose clamps,
silencer, and outlet flapper) for cracks, leaks, and
corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metalparts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps and/or hangers
as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
D Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional, and (3) energized whenever the
generator set operates.
x:op:001:002
TP-6068 10/0217Section 3 Scheduled Maintenance
Page 32
3.8Cooling System
3.8.1Closed Heat Exchanger
In a closed cooling system, the seawater circulates
through separate chambers within the heat exchanger or
manifold to cool the engine water . The seawater then
mixes with the engine exhaust and ejects out of the
exhaust outlet.See Figure 3-6 for coolant capacities
(include coolant recovery tank capacity of 0.24 L (8 oz.).
ModelL (Qts.)
4EFOZ and 5EOZ1.8 (1.9)
6.5EFOZ and 8EOZ3.9 (4.1)
8.5EFOZ, 9EFOZ and 10EOZ2.5 (2.6)
1 1/11.5/13EFOZ and 13/14/15.5EOZ4.4 (4.6)
16/17.5/19/20EFOZ and 20/23/24EOZ6.0 (6.3)
23/27EFOZ and 28/32EOZ7.6 (8.0)
Figure 3-6Coolant Capacities
coolant level on closed systems by removing the
pressure cap. Do not rely solely on the level in the
coolant recovery tank. Add fresh coolant until the level is
just below the overflow tube opening.
Note: A coolant solution of 50% ethylene glycol
provides freezing protection to --37°C(--34°F)
and overheating protection to 129°C (265°F). A
coolant solution with less than 50% ethylene
glycol may not provide adequate freezing and
overheating protection. A coolant solution with
more than 50% ethylene glycol can cause engine
or component damage. Do not use alcohol or
methanol antifreeze or mix them with the
specifiedcoolant.Consulttheengine
manufacturer’s operation manual for engine
coolant specifications.
Note: Do not add coolant to a hot engine.Adding
coolant to a hot engine can cause the cylinder
block or cylinder head to crack. Wait until the
engine has cooled.
3.8.2Checking and Filling Coolant
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
Checking the coolant level. Hot coolantcan cause severe
injury or death. Allow the engine to cool. Release pressure
from thecooling systembefore removing the pressure cap. To
release pressure, cover the pressure cap with a thick cloth and
then slowly turn the cap counterclockwise to the first stop.
Remove the cap after pressure has been completely released
and theengine hascooled. Check thecoolant level at the tank
if the generator set has a coolant recovery tank.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
Maintain the coolant level in the coolant recovery tank at
approximately 1/4 full. Before filling the cooling system,
close all petcocks and tighten all hose clamps. Use a
solution of 50% ethylene glycol and 50% clean,
softened water to inhibit rust/corrosion and prevent
freezing. Add additional coolant solution, as necessary,
to the coolant recovery tank. Periodically check the
Note: Pay special attention to the coolant level. After
the coolant drains, allow time when re-filling the
coolant for a complete refill of the engine water
jacket. Check the coolant level as prescribed in
the Prestart Checklist.
3.8.3Flushing and Cleaning
For optimum protection, drain, flush, and refill the
cooling system at the interval listed in the service
schedule.
Flushing and Cleaning Procedure
1. Open the pressure cap and open petcocks located
at the heat exchanger, engine block, and cooling
system, and let the system drain completely. Some
models may have petcocks located behind the belt
guard.Remove the pressure cap to simplify
draining.
2. Drain, clean, and flush the coolant recovery tank.
3. Flush the system with clean water.
4. Fill the system with recommended coolant.
3.8.4Pressure Cap
Closed heat exchanger systems utilize a pressure cap
to raise the boiling point of the coolant, enabling higher
operating temperatures. If the cap leaks, replace it with
a cap of the same rating. The pressure cap typically has
the pressure rating stamped on the cap body.
TP-6068 10/0218 Section 3 Scheduled Maintenance
Page 33
3.8.5Seawater Pump
The belt-driven seawater pump is located on the service
side of the generator set.Check and change the
seawater pump impeller at the interval specified in the
service schedule. Follow the instructions included with
the impeller kit. If the instructions are not included with
the kit, use the following procedure:
Impeller Inspection and Replacement Procedure:
1
2
3
1. Close the seacock.
2. Remove the seawater pump coverplate.See
Figure 3-7.
3. Remove the impeller.
4. Inspect the impeller for damaged, cracked, broken,
missing or flattened vanes. The impeller vanes
should be straight and flexible. See Figure 3-8.
Replace the impeller if it is damaged.
1
11
2
10
9
1. Seawater pump
2. Coverplate
3. Gasket
4. Impeller
5. Bearing
6. Housing
5
6
78
7. Pulley
8. Drive shaft
9. Washer
10. Nut
11. Mechanical seal,
3
4
TP-6053
if equipped
1. Flattened vane
TP-6053
2. Crack
3. Broken vane
Figure 3-8Worn Impeller
5. Lubricate the impeller with soapy water before
installation.
6. Install the impeller.
Note: During installation push and rotate the
impeller in the same direction as the engine
rotation until it is thoroughly seated in the
impeller housing.
7. Inspect the coverplate and gasket for corrosion
and/ordamage.Replacecomponentsas
necessary.
8. Lubricate the gasket with silicon grease and attach
the gasket and coverplate to the seawater pump
housing.
9. Open the seacock.
10. Start the generator set and check for leaks.
11. Stop the generator set and repair leaks or replace
damaged or worn components.
m:sm:003:008
Figure 3-7Seawater Pump, Typical
TP-6068 10/0219Section 3 Scheduled Maintenance
Page 34
3.8.6Siphon Break
A siphon break prevents seawater entry into the
generator set’s engine when the engine exhaust
manifold outlet is less than 230 mm (9 in.) above the
waterline of a fully loaded, docked or stationary craft.
See Figure 3-10. The siphon break may malfunction
when the generator set operates while the craft is in
contaminated waters or saltwater. Use the following
procedure to inspect the siphon break at the intervals
listed in the service schedule.
Siphon Break Inspection
6. Install the reed valve into the mounting base with
the valve downward. See Figure 3-9, item 3.
7. Install and only finger tighten the retaining cap. Do
not overtighten it.
2
3
1. Stop the generator set.
2. Remove the retaining cap and remove the reed
valve for inspection. See Figure 3-9.
3. Use a mild detergent to remove residue and
oxidation from the reed valve.
4. Clear blockage from the reed valve opening.
5. Replace the siphon break if the reed valve is
cracked or if the reed valve material has hardened
or deteriorated.
1
1. Mounting base
2. Retaining cap
3. Reed valve
Figure 3-9Siphon Break
TP-5856-3
m:sm:003:007
TP-6068 10/0220 Section 3 Scheduled Maintenance
Page 35
4
5
6
7
3
2
Waterline
17
1
18
16
1. Silencer vertical lift 1.2 m (4 ft.) max.
2. Exhaust mixer elbow distance above waterline. If less than
23 cm (9 in.), a siphon break is required.
3. Siphon break distance above waterline 30.5 cm (1 ft.) min.
4. Siphon break
5. Exhaust mixer elbow
6. Heat exchanger (locations vary by model)
7. Coolant recovery tank
8. Locate coolant recovery tank at the same height as the heat
exchanger
13. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
14. Water lock (optional)
15. Silencer distance from exhaust mixer elbow 3 m (10 ft.) max.
16. Silencer (customer supplied)
17. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
18. Exhaust outlet distance above the waterline 10 cm (4 in.) min.
TP-5586-3
Note: Consult the installation manual for complete
explanation of dimensions and other installation
considerations.
TP-6068 10/0221Section 3 Scheduled Maintenance
Page 36
3.8.7Anticorrosion Zinc Anode
The heat exchanger on models 4--9EFOZ, 5--10EOZ,
23/27EFOZ, and 28/32EOZ contains an anticorrosion
zinc anode (plug) to prevent electrolytic corrosion by
seawater.
Check and replace the anticorrosion zinc anode at
intervals recommended in the service schedule.
Depending upon operating conditions and seawater
properties, the anticorrosion zinc anode may require
more frequent replacement.See Section 1 for the
location and use the following procedure.
Anticorrosion Zinc Anode Replacement
1. With the generator set cooled, close the seacock,
open the petcock on the engine, and drain the
coolant into a suitable container.
1
2
TP-5586-3
1. Diameter: 9 mm (0.34 in.)
2. Length: 43 mm (1.7 in.) for 4-9EFOZ/EOZ models or
19 mm (0.75 in.) for 23/27EFOZ, 28/32EOZ models
Figure 3-12 Anticorrosion Zinc Anode (Plug)
4. Clean the threaded hole of the heat exchanger and
coat the threads of the anticorrosion zinc anode
(plug) with pipe sealant suitable for marine
applications.Cut the anticorrosion zinc to the
correct length. Install the anticorrosion zinc anode
into the heat exchanger.
2. Remove the anticorrosion zinc anode (plug) from
the heat exchanger.
3. Use a wire brush to remove the loose corrosion on
the anticorrosion zinc anode. Replace the anode
according to Figure 3-11 and Figure 3-12.
Anticorrosion Zinc Anode Replacement
Replace When
Percent of Zinc
Remaining Is:
<50% of
length/diameter
<50% of
length/diameter
Models
4--9EFOZ
5--10EOZ
23/27EFOZ
28/32EOZ
New Anode
Dimensions mm (in.)
9 (0.34) x 43 (1.7)
9 (0.34) x 19 (0.75)
Figure 3-11 Anticorrosion Zinc Anode (Plug)
Measurements
5. Close the petcock on the engine and open the
seacock. Refill the cooling system.
6. Start the generator set and check for leaks at the
anticorrosion zinc anode location. The pump is
operating if the cooling water flows from the
exhaust outlet. If water is not discharging at the
exhaustoutlet,seeSection2.1,Prestart
Checklist—Seawater Pump Priming.
TP-6068 10/0222 Section 3 Scheduled Maintenance
Page 37
3.9Belt Tension
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and coversare in
place.
Servicing the generator set when it isoperating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
3.9.1Seawater Pump Belt Tensioning
Procedure
1. Remove the belt guard.
2. Check the belt tension at the midpoint of the
longest span of the belt using a belt-tensioning tool
set to 55 ft. lbs. See Figure 3-13. Recheck a new
belt tension after 10 minutes of operation.
Note: If the belt tension is not within specifications,
go to step 3. If the belt tension is within
specifications, go to step 7.
3. Loosen the pivot and adjusting screws.
4. While prying the seawater pump outward, tighten
the adjusting screw.
5. Tighten the pivot screw.
6. Recheck and adjust as necessary.
Check the belt tensions at the interval specified in the
service schedule. If tensions are not within the
specifications, adjust as necessary using the following
procedures.
4
1
2
3
5
11
10
9
1. Engine-driven water pump pulley
2. Adjusting arm pivot screw
3. Battery charging alternator pulley
4. Alternator adjusting screw
5. Alternator pivot screw
6. Check the alternator belt tension here
7. Crankshaft pulley
8. Check the seawater pump belt tension here
9. Seawater pump adjusting screw
10. Seawater pump pulley
11. Pivot screw
8
6
7
TP-5586-3
7. Replace the belt guard.
3.9.2Battery Charging Alternator Belt
Tensioning Procedure
1. Remove the belt guard.
2. Check the belt tension at the midpoint of the
longest span of the belt by pressing with your
finger. See Figure 3-13 and Figure 3-14. If the belt
is not within the specifications, go to step 3. If the
belt is within the specifications, go to step 7.
Belt TypeDeflection mm (in.)
New7--9 (0.3--0.4)
Used10--15 (0.4--0.6)
Figure 3-14 Belt Specifications
3. Loosen the adjusting arm pivot screw, alternator
pivot screw, and alternator adjusting screw.
4. While prying the alternator outward, tighten the
alternator adjusting screw.
5. Tighten the adjusting arm pivot screw and
alternator pivot screw.
6. Recheck and adjust as necessary.
7. Replace the belt guard.
Figure 3-13 Belt Tension (Typical)
TP-6068 10/0223Section 3 Scheduled Maintenance
Page 38
3.10 Battery
3.11 Generator Storage Procedure
Consultthebatterymanufacturer’sinstructions
regarding battery care and maintenance.
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a batteryafter placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Keep the craft afloat for generator operation during the
storage procedure. Follow the procedure below when
storing your generator set for 3 months or more.
Generator Set Storage Procedure
1. Start and run the generator set until it reaches
operating temperature or about 15 minutes.
2. Stop the generator set.
3. Change the oil and oil filter. See Section 3.4.3.
4. Close the seacock and remove the hose at the
seacock. Place the hose in a container having
approximately 3.7--7.5 L (1--2 U.S. gallons) of
coolant/antifreeze. Kohler Co. recommends using
an environmentally friendly potable antifreeze
such as PeakR RV/marine propylene glycol/water
mix or equivalent.
5. With a suitable container at the exhaust outlet, run
the generator set until coolant discharges at the
exhaust outlet or until the coolant mixture is
depleted. Do not allow coolant mixture to flow into
waterways.
6. Stop the generator set.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly whenit ischarging. Do not dispose of a battery in a
fire.To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
7. Connect a hose to the seacock. Leave theseacock
closed.
8. Check the coolant level of the heat exchanger and
add coolant if necessary.
Note: Use antifreeze capable of withstanding the
lowest possible temperatures.
9. Clean the exterior of the generator set and spread
a light film of oil or silicon spray over any exposed
surfaces that may be subject to rust or corrosion.
10. Disconnect and remove the battery.Place the
battery in a warm, dry location for the storage
period. Recharge the battery once a month to
maintain a full charge.
11. Select a well-ventilated (not humid or dusty)
location to store the generator.
12. Cover the entire unit with a dust cover.
Note: Run the generator set once a month
whenever possible.
TP-6068 10/0224 Section 3 Scheduled Maintenance
Page 39
Section 4 Troubleshooting
This section contains generator set troubleshooting,
diagnostic, and repair information.
Use the following chart as a quick troubleshooting
reference. The table groups generator set faults and
suggests likely causes and remedies. The table also
refers you to more detailed information including
sections of this manual, the generator set service
manual (S/M), the generator set installation manual
(I/M), and the engine service manual (Engine S/M) to
correct the indicated problem.
Corrective action and testing often require knowledge of
electrical and electronic circuits. To avoid additional
problems caused by incorrect repairs, have an
authorized service distributor/dealer perform service.
NOTICE
Fuse replacement. Replace fuses with fuses of the same
ampere rating and type (for example: 3AB or 314, ceramic).
Do not substitute clear glass-type fuses for ceramic fuses.
Refer to the wiring diagram when the ampere rating is
unknown or questionable.
Maintain a record of repairs and adjustments performed
on the equipment. If the procedures in this manual do
not explain how to correct the problem, contact an
authorized distributor/dealer. Use the record to help
describe the problem and repairs or adjustments made
to the equipment.
x:gt:001:002a:
TP-6068 10/0225Section 4 Troubleshooting
Page 40
Section or
Reference*
Publication
Section 2, W/D
Gen. S/M
Sec. 3, Eng. O/M
Trouble Symptoms
Probable CausesRecommended Actions
abnormal noise
Excessive or
consumption
High fuel
pressure
Low oil
Overheats
Lacks power
suddenly
Stops
output voltage
No or low
Move the controller start/stop switch to the START position.Section 2
Controller start/stop switch in the
STOP position
troubleshoot the controller.[
Controller fuse blownReplace the blown controller fuse. If the fuse blows again,
Replace the controller master or start/stop switch.—
Troubleshoot the controller.[
Controller master or start/stop switch
inoperative
xController fault
xxAir openings cloggedClean the air openings.—
system.
Restore the coolant to normal operating level.Section 3
High temperature shutdownAllow the engine to cool down. Then troubleshoot the cooling
Low coolant level shutdown, if
equipped
xImpeller inoperativeReplace the impellerSection 3
xxSeawater strainer clogged or restricted Clean the strainer.Section 3
x
xCoolant level lowRestore the coolant to normal operating level.Section 3
xThermostat inoperativeReplace the thermostat.Eng. S/M
xCooling water pump inoperativeTighten or replace the belt. Replace the water pump.Eng. O/M or S/M
x
Starts hard
does not start
Cranks but
crank
Does not
26 Section 4 Troubleshooting
x
Controller
xxx
xxController circuit breaker trippedReset the controller circuit breaker.Section 2
x
xxController circuit board(s) inoperativeReplace the controller circuit board.Gen. S/M
Cooling System
S/S—Spec Sheet; W/D—Wiring Diagram
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
[ Have an authorized service distributor/dealer perform this service.
TP-6068 10/02
Page 41
Sectionor
Section or
Reference*
Reference*
Publication
Publication
RecommendedActionsProbableCauses
Recommended ActionsProbable Causes
Section 3, S/S
W/D
Eng. S/M
I/M
Section 3, I/M
Section 3, I/M
Gen. S/M
Eng. S/M
Trouble Symptoms
abnormal noise
Excessive or
consumption
High fuel
pressure
Low oil
Overheats
Lacks power
suddenly
Stops
output voltage
No or low
Verify that the battery connections are correct, clean, and tight.Section 3
Battery connections loose, corroded,
or incorrect
Battery weak or deadRecharge or replace the battery. The spec sheet provides
recommended battery CCA rating.
Disconnect the engine harness connector(s) then reconnect it to
Engine harness connector(s) not
the controller.
locked tight
TP-606810/02
xFault shutdownReset the fault switches and troubleshoot the controller.Section 2
Replace the inoperative switch.Gen. S/M or W/D
High exhaust temperature switch
inoperative
x
Replace the inoperative switch.Gen. S/M
High water temperature switch
inoperative
x
Clean or replace the filter element.Section 2
Air cleaner/backfire flame arrestor
clogged
Check the compression.[
manual for wattage specifications.
Engine overloadReduce the electrical load. See the generator set installation
xxxxx
system components.[
Exhaust system leakInspect the exhaust system. Replace the inoperative exhaust
x
components.[
Exhaust system not securely installed Inspect the exhaust system. Tighten the loose exhaust system
x
Adjust the governor.[
Adjust the valves.[
xVibration excessiveTighten all loose hardware.—
xxValve clearance incorrect
Starts hard
does not start
Cranks but
crank
Does not
xx
Electrical System (DC circuits)
xx
xx
xxStarter/starter solenoid inoperativeReplace the starter or starter solenoid.Eng. S/M
xxxx
Engine
xxxxxCompression weak
xxxxGovernor inoperative
S/S—Spec Sheet; W/D—Wiring Diagram
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
[ Have an authorized service distributor/dealer perform this service.
27Section 4 TroubleshootingTP-6068 10/02
Page 42
Sectionor
Section or
Reference*
Reference*
Publication
Publication
RecommendedActionsProbableCauses
Recommended ActionsProbable Causes
Eng. S/M
Troubleshoot the fuel solenoid.[
Eng. S/M
Clean, test, and/or replace the inoperative fuel injector.[
Eng. S/M
Adjust the fuel injection timing.[
Eng. S/M
Rebuild or replace the injection pump.[
—
Gen. S/M
Gen. S/M
—
Gen. S/M
side of the circuit breaker.
Move the transfer switch test switch to the AUTO position.ATS O/ M
Check for continuity.Gen. S/M, W/D
Test and/or replace the rotor.[
Test and/or replace the stator.[
Tighten loose components.[
troubleshoot the voltage regulator.
Eng. O/M
Change the oil. Use oil with a viscosity suitable for the operating
climate.
abnormal noise
Excessive or
consumption
High fuel
pressure
Low oil
Overheats
Lacks power
suddenly
Stops
output voltage
Trouble Symptoms
28 Section 4 Troubleshooting
No or low
Starts hard
does not start
Cranks but
crank
Does not
xxFuel tank empty or fuel valve shut offAdd fuel and move the fuel valve to the ON position.—
Fuel System
xxxxFuel filter restrictionClean or replace the fuel filter.Eng. O/M
xFuel solenoid inoperative
xxxAir in fuel system (diesel only)Bleed the diesel fuel system.Eng. O/M
Fuel or fuel injectors dirty or faulty
(diesel only)
xxx
Fuel injection timing out of adjustment
(diesel only)
Fuel feed or injection pump inoperative
(diesel only)
xxxx
xxx
AC output circuit breaker openReset the breaker and check for AC voltage at the generator
x
Generator
Transfer switch test switch in the OFF
position
x
Wiring, terminals, or pin in the exciter
field open
x
Main field (rotor) inoperative (open or
grounded)
x
xVibration excessive
xStator inoperative (open or grounded)
xxVoltage regulator out of adjustmentAdjust the voltage regulator.Gen. S/M
Voltage regulator inoperativeReplace the voltage regulator fuse, If the fuse blows again,
xx
xxxOil level lowRestore the oil level. Inspect the generator set for oil leaks.Eng. O/M
Lube System
Crankcase oil type incorrect for
xLow oil pressure shutdownCheck the oil level.Eng. O/M
ambient temperature
xxxx
S/S—Spec Sheet; W/D—Wiring Diagram
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
TP-6068 10/02
[ Have an authorized service distributor/dealer perform this service.
Page 43
Section 5 Wiring Diagrams
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working onthe generatorset.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set asfollows: (1) Place the generator set start/stop
switch in the STOP position. (2) Disconnect the power to the
battery charger, if equipped. (3) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present.Open the main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits tocomply withapplicable codesand standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.
Moving rotor.
TP-6068 10/0229Section 5 Wiring Diagrams
Page 44
Figure 5-1Schematic Wiring Diagram—4/6.5/9EFOZ and 5/8/10EOZ (1-Phase Models)
229294-L
TP-6068 10/0230 Section 5 Wiring Diagrams
Page 45
Figure 5-2Point-to-Point Wiring Diagram—4/6.5/9EFOZ and 5/8/10EOZ (1-Phase Models)
Figure 5-5Schematic Wiring Diagram—11/13/16/19/23/27EFOZ and 13/15.5/20/23/28/32EOZ
(1-Phase Models)
229937-D
TP-6068 10/0234 Section 5 Wiring Diagrams
Page 49
Figure 5-6Point-to-Point Wiring Diagram—11/13/16/19/23/27EFOZ and 13/15.5/20/23/28/32EOZ
(1-Phase Models)
TP-6068 10/0235Section 5 Wiring Diagrams
229937-D
Page 50
Figure 5-7Schematic Wiring Diagram—11.5/17.5/20/23/27EFOZ and 14/20/24/28/32EOZ
(3-Phase Models)
229938-B
TP-6068 10/0236 Section 5 Wiring Diagrams
Page 51
Figure 5-8Point-to-Point Wiring Diagram—11.5/17.5/20/23/27EFOZ and 14/20/24/28/32EOZ
(3-Phase Models)
TP-6068 10/0237Section 5 Wiring Diagrams
229938-B
Page 52
Notes
TP-6068 10/0238 Section 5 Wiring Diagrams
Page 53
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCanalog to digital converter
adj.adjust, adjustment
ADVadvertising dimensional
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APIAmerican Petroleum Institute
approx.approximate, approximately
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
A/Vaudiovisual
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CARBCalifornia Air Resources Board
CBcircuit breaker
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cfhcubic feet per hour
cfmcubic feet per minute
drawing
temperature
Institute
Institute
(formerly American Standards
Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
CTcurrent transformer
Cucopper
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dBAdecibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., °degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
DIPdual inline package
DPDTdouble-pole, double-throw
DPSTdouble-pole, single-throw
DSdisconnect switch
DVRdigital voltage regulator
E, emer. emergency (power source)
EDIelectronic data interchange
EFRemergency frequency relay
e.g.for example (exempli gratia)
EGelectronic governor
EGSAElectrical Generating Systems
fglass.fiberglass
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lbs.foot pounds (torque)
ft./min.feet per minute
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temperature
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lbs.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPiron pipe
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
ground
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6068 10/02Appendix A-1
Page 54
kgkilogram
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, kW kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
ld. shd.load shed
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
sound power level, A weighted
LWLlow water level
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
bytes)
MCMone thousand circular mils
MCCBmolded-case circuit breaker
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mW
milliohm
MOhm, MW
megohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
m/sec.meters per second
MTBFmean time between failure
MTBOmean time between overhauls
mtg.mounting
MWmegawatt
mWmilliwatt
mFmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
Manufacturers Association
NFPANational Fire Protection
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
PHCPhillips head crimptite (screw)
PHHPhillips hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent-magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTVroom temperature vulcanization
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SNserial number
SPDTsingle--pole, double--throw
SPSTsingle--pole, single--throw
spec, specs
specification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SSstainless steel
std.standard
stl.steel
tach.tachometer
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
TIFtelephone influence factor
TIRtotal indicator reading
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
w/owithout
wt.weight
xfmrtransformer
TP-6068 10/02A-2 Appendix
Page 55
Appendix B Operating Hour Service Log
Use the log below to keep a cumulative record of
operating hours on your generator set and the dates
OPERATING HOURSSERVICE RECORD
DATE
RUN
HOURS
RUN
TOTAL
HOURS
SERVICE
DATE
required services were performed. Enter hours to the
nearest quarter hour.
SERVICE
TP-6068 10/02Appendix A-3
Page 56
Page 57
Page 58
Page 59
Page 60
TP-606810/02b
E 2000, 2001, and 2002 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPowerSystems.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65)264-6422, Fax (65)264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.