Subject: Siphon Break Kit GM60007-KP1 for Sound Shielded Units
TT-15094/14a
INSTALLATION INSTRUCTIONS
Introduction
Use these instructions to install a siphon break on
sound-shielded generator sets.A siphon break
prevents seawater entry into the generator set engine
when the engine exhaust manifold outlet is less than
230 mm (9 in.) above the waterline of a fully loaded
docked or stationary craft.
Read the entire installation procedure. Perform the
steps in the order shown.
Note: Install this siphon break kit on generator sets
equipped with the sound shield kits specified in
Figure 1. Do not install these siphon break kits on
generator sets without sound shields.
Factory
Model
5EKD/4EFKD
7.5EKD/6EFKD
10EKD/8EFKDGM55219-KA2 GM55219-KP2
Installed Kit
GM55219-KA1 GM55219-KP1
Field
Installed Kit
Figure 1Sound Shield Kits
Safety Precautions
WARNING
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Moving parts.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Installation Procedure
1.Remove the generator set from service.
1.1Press the start/stop button to stop the generator
set. The engine stops.
1.2Press the power button to turn off the controller.
1.3Disconnect the power to the battery charger, if
equipped.
1.4Disconnect the generator set engine starting
battery, the negative (--) lead first.
Page 2
2.Remove the sound shield.
2.1Remove the sound shield’s exhaust panel,
generator-end door,and roof (if necessary) to gain
access to the generator set hoses inside. See
Figure 2.
3
3.5Route the hose from the seawater flow switch to
the left hole in the sound shield’s exhaust panel.
Secure the hose with the other hose clamp.
3.6Rotate the fitting on the exhaust catalyst and
secure the hose (X-312-61) to the exhaust catalyst
using a hose clamp (X-426-12). See Figure 6.
Note: 5/7.5EKD and 4/6EFKD Models: Cut the hose
(X-312-61) to fit.
2
1
1. Exhaust panel
2. Generator-end door
3. Roof
Figure 2Sound Shield Removal
3.Install the siphon break.
3.1Remove the 2 button plugs from the exhaust panel
on the sound shield.
3.2Install the 2 grommets (X-284-7) and 2 hose
connectors (344934) to the openings in the
exhaust panel. See Figure 7.
3.3Find and remove the molded hose located
between the seawater flow switch and the exhaust
catalyst. Save the hose clamps.
1
3.7Route the hose from the exhaust catalyst to the
remaining hole in the sound shield’s exhaust
panel.Secure the hose with a hose clamp
(X-426-12).
Note: Because of the variety of possible installations,
this kit does not include hoses to connect to the
siphon break. See Figure 4 for an ID-size hose
selection. Use coolant hoses (SAE 20R1, class B
or equivalent) and hoses suitable for marine use.
Use corrosion-resistant or stainless steel hose
clamps on all fittings.
ID-Size Hose
Kit Number
GM60007-KP115.9 (5/8)
mm (in.)
Figure 4Hose Selection
3.8Determine the required length of hose from each
hose connector to the siphon break. Cut two
pieces of the customer-supplied hose to the
determined length. See Figure 7.
Note: The siphon break must be at least 30 cm (12 in.)
above the waterline during maximum load and
generator shutdown condition.
OUT
IN
2
1. Remove molded hose (GM55092) and save hose clamps
(X-426-12 qty. 2).
2. Seawater flow switch
GM58158-M
Figure 3Hose Removal
3.4Secure the hose (X-312-16) to the seawater flow
switch using the hose clamp saved in step 3.3.
SeeFigure6.
Note: 5/7.5EKD and 4/6EFKD Models: Cut the hose
(X-312-16) to fit.
2
3.9Use the customer-supplied hose clamps to
connect the hoses to the hose connectors. Locate
the hose clamps 12.7 mm (1/2 in.) from each end
of the hose and tighten the clamps. See Figure 7.
3.10 Use customer-supplied hose clamps to connect
the siphon break (GM32985) to the hoses. Locate
the hose clamps 12.7 mm (1/2 in.) from each end
of the hose and tighten the clamps.
3.11 Mount the siphon break to the engine stringer or
other rigid structure. Keep the siphon break reed
valve in a vertical position.
Note: Correct functioning of the reed valve requires
clean operating conditions. Locate the top of the
siphon break (reed valve) away from possible
accumulated dirt and other contaminants.
Note: Toprevent water leakage on the generator set, do
not mount the siphon break over the generator
set.
TT-1509 4/14
Page 3
3.12 Connecttheclearflexibleplastictubing
(GM34883) to the siphon break cap using a hose
clamp (X-426-9) to secure. Route the tubing to a
convenient location. This allows the seawater to
drip into the bilge and not on the generator set.
3.13 Siphonbreakmounting varieswith each
application.Generally, use brass or stainless
steel screws and mount the siphon break using
the mounting tabs.Otherwise, use a nylon
(conduit-type) pipe clamp.
Note: Mount the siphon break in a location easily
accessable for inspection and servicing.
Note: Ensure that the siphon break cap is tight before
operating the generator set.
4.Restore the generator set to service.
4.1Check that the generator set is OFF.
2.Inspect the siphon break.
2.1Remove the retaining cap and remove the reed
valve for inspection. See Figure 5.
2.2Use a mild detergent to remove residue and
oxidation from the reed valve.
2.3Clear blockage from the reed valve opening.
2.4Replace the siphon break if the reed valve is
cracked or if the reed valve material has hardened
or deteriorated.
2.5Install the reed valve into the mounting base with
the valve downward. See Figure 5, item 3.
2.6Install and only finger tighten the retaining cap. Do
not overtighten it.
1
4.2Reconnect the generator set engine starting
battery, the negative (--) lead last.
4.3Reconnect the power to the battery charger, if
equipped.
4.4Start the generator set and check for water leaks.
4.5Stop the generator set.
4.6Replace the sound shield’s exhaust panel, door,
and roof.
Inspection/Maintenance
Service the siphon break during regular exhaust system
component inspection. See the generator set operation
manual for the service schedule.
Note: The generator set must not be running during the
siphon break inspection.
1.Remove the generator set from service.
1.1Press the start/stop button to stop the generator
set. The engine stops.
1.2Press the power button to turn off the controller.
1.3Disconnect the power to the battery charger, if
equipped.
1.4Disconnect the generator set engine starting
battery, the negative (--) lead first.
2
3
1. Cap
2. Siphon reed valve
3. Mounting base
Figure 5Siphon Break
3.Restore the generator set to service.
3.1Check that the generator set is OFF.
3.2Reconnect the generator set engine starting
battery, the negative (--) lead last.
3.3Reconnect the power to the battery charger, if
equipped.
Parts List
Siphon Break Kit
Kit: GM60007-KP1
Qty. DescriptionUnique Parts
2 Grommet, roundX-284-7
1 Hose, 0.63 in. ID (11.5 in.)X-312-16
1 Hose, 0.63 in. ID (8.0 in.)X-312-61
2 Clamp, hose (0.69/1.25 in.)X-426-12
1 Valve, siphon breakGM32985
2 Connector, hose344934
1 Tubing, clear flexible plasticGM34883
1 Clamp, hose (0.25/0.70 in.)X-426-9
TT-1509 4/14
3
Page 4
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Service-Side View
2
Top View
1
6
4
5
2
4
3
1
3
4
Generator-End View
5
GM60007-A
1. Hose connectors (344934 qty. 2)
2. Hose (X-312-16). Route the hose to the seawater flow switch
and use existing hose clamps. Remove molded hose. Cut
hose to fit for 5/7.5EKD and 4/6EFKD models.
3. Rotate the fittings on the exhaust catalyst.
4. Hose (X-312-61) and hose clamps (X-426-3 qty. 2). Cut hose
to fit for 5/7.5EKD and 4/6EFKD.
5. Grommets (X-284-7 qty. 2)
Figure 6Hose Locations
1. Exhaust panel
2. Hose connectors, qty. 2
3. Grommets, qty. 2
4. Customer-supplied hose clamps
5. Customer-supplied hoses
6. Siphon break valve
Figure 7Siphon Break, Installed
Availability is subject to change without notice. Kohler Co. reserves the
right to change the design or specifications without notice and without any
obligation or liability whatsoever. Contact your local Kohlerr generator
set distributor for availability.
2009 and 2014 by Kohler Co. All rights reserved.
4
TT-1509 4/14