Appendix A Generator Selection and Wattage Requirements79.................................
Appendix B Abbreviations80................................................................
TP-6862 6/14Table of Contents4
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanicalequipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthat willcause severe
personal injury, death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazard thatcan cause severe
personal injury, death, or substantial
property damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set off/reset
button to shut down the generator set.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the fuel system. A flash
fire can cause severeinjury or death.
Do not smoke or permit flames or
sparks near the fuel injection system,
fuel line, fuel filter, fuel pump, or other
potential sources of spilled fuels or fuel
vapors. Catch fuels in an approved
container when removing the fuel line
or fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner/silencer
removed.
Combustible materials. A sudden
flash fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the generator set. Keep
the compartment and the generator set
clean and free of debris to minimize the
risk of fire. Catch fuels in an approved
container. Wipe up spilled fuels and
engine oil.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
TP-6862 6/145Safety Precautions and Instructions
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Page 6
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystem mustbe
leakproof and routinely inspected.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Inspecting the exhaust system.
Carbon monoxide can cause severe
nausea, fainting, or death. For the
safety of the craft’s occupants, install a
carbon monoxide detector.Never
operate the generator set without a
functioning carbon monoxide detector.
Inspect the detector before each
generator set use.
Operating the generatorset. Carbon
monoxide can cause severe nausea,
fainting, or death.Be especially
careful if operating the generator set
when moored or anchored under calm
conditionsbecausegasesmay
accumulate. If operating the generator
set dockside, moor the craft so that the
exhaust discharges on the lee side (the
side sheltered from the wind). Always
be aware of others, making sure your
exhaust is directed away from other
boats and buildings.
Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Donot operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Draining the fuel system. Explosive
fuel vapors can cause severe injury
or death. Spilled fuel can cause an
explosion. Use a container to catch fuel
when drainingthe fuel system. Wipe up
spilled fuel after draining the system.
Hazardous Noise
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Hazardous Voltage/
Moving Parts
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodes andstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Disconnecting the electrical load.
Hazardousvoltagecancause
severe injury or death. Disconnect
the generator set from the load by
turning off the line circuit breaker or by
disconnecting the generator set output
leads from the transfer switch and
heavily taping the ends of the leads.
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not
disconnect the generator set from the
load.
Moving parts.
TP-6862 6/146Safety Precautions and Instructions
Page 7
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Connect the generator set to the
building/marina electrical system only
through an approved device and after
the building/marina main switch is
turned off. Backfeed connections can
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
electricalsystem.Installa
ship-to-shore transfer switch to prevent
interconnection of the generator set
power and shore power.
Testing liveelectricalcircuits.
Hazardous voltage or current can
cause severe injury or death. Have
trained and qualified personnel take
diagnosticmeasurements oflive
circuits.Use adequately rated test
equipment with electrically insulated
probes and follow the instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests: (1) Remove all jewelry.
(2) Stand on a dry,approved electrically
insulated mat. (3) Do not touch the
enclosure or components inside the
enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
Notice
NOTICE
This generator set has been
rewired from its nameplate voltage
to
246242
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate.Order
voltage reconnection decal 246242
fromanauthorizedservice
distributor/dealer.
NOTICE
Fuse replacement.Replace fuses
with fuses of the same ampere rating
and type (for example: 3AB or 314,
ceramic).Do not substitute clear
glass-type fuses for ceramic fuses.
Refer to the wiring diagram when the
ampereratingisunknownor
questionable.
NOTICE
Saltwater damage. Saltwater quickly
deteriorates metals. Wipe up saltwater
on and around the generator set and
remove salt deposits from metal
surfaces.
Hot Parts
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
TP-6862 6/147Safety Precautions and Instructions
Page 8
Notes
TP-6862 6/148Safety Precautions and Instructions
Page 9
Section 1 Introduction
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
The safe and successful operation of a marine power
system depends primarily on the installation.See
Figure 1-1. Use this manual as a guide to install the
marine generator set. For operating instructions, refer
to the operation manual.
13
21
20
19
18
2
Note: Only qualified persons should install the
generator set.
Marine generator set installations must comply with all
applicable regulations and standards.
Use the specification sheets as a guide in planning your
installation. Use current dimension drawings and wiring
diagrams.
4
5
6
7
8
17
16
15
1. Exhaust mixer elbow (exhaust/water outlet)
2. Fuel return connection
3. Heat exchanger (not shown)
4. Fuel feed pump *
5. Fuel inlet connection
6. Seawater pump (seawater inlet)
7. Coolant recovery tank (located on the unit on some models)
8. Seawater strainer *
9. Seawater inlet c onnection
10. Seawater line *
11. Seacock *
14
13
12. Craft stringers
13. Fuel/water separator (see Section 5 for more information)
* Indicated components must conform to USCG regulations.
9
12
10
11
Figure 1-1 Typical Generator Set Location and Mounting (40EOZDJ Model Shown Without Sound Shield)
Note: See text for complete explanation of installation
requirements.
Note: Use two hose clamps on each end of all flexible
exhaust hose connections.
ADV8500-
TP-6862 6/149Section 1 Introduction
Page 10
Notes
TP-6862 6/1410 Section 1 Introduction
Page 11
Section 2 Location and Mounting
2.1General Considerations
The key to installation is location. Before making final
plans for locating a generator set, consider the
following.
Installation Location Co n sid erations
1. Choose a location that allows adequate space for
cooling and exhaust system installation, fuel
system installation, ventilation, and service access
to the generator set (engine and generator).
2. Use craft stringers or other available structural
members capable of supporting the generator set’s
weight.
3. Seal the generator set’s engine room from the
cabin to prevent exhaust gases and fuel vapors
from entering the cabin.
See the current generator set specification sheet or
Section 7 of this manual for generator set dimensions
and weights. See Figure 1-1 for a typical installation.
2.2Location
Locate the generator set to allow easy service access to
the generator set’s engine, controller, cooling, and fuel
system components. The engine compartment is often
the ideal location for the generator set if the propulsion
engine(s) does not obstruct access to the generator set
and controller.
Marine Generator Set Installations in
European Union Member Countries
This generator set is specifically intended and approved
for installation below the deck in the engine
compartment.Installation above the deck and/or
outdoors would constitute a violation of European Union
Directive 2000/14/EC noise emission standard.
Allow clearance for vibration and cooling during
operation.Allow a minimum of 38 mm (1.5 in.)
clearance on all sides (top, front, rear, and sides) o f a
generator set without an optional sound shield. For
sound-shielded units, allow 305 mm (12 inches)
minimum clearance for the left-rear door and front door
(intake and discharge openings). Also, allow space for
the power takeoff (PTO) option, if equipped.
Kohler ignition -protected generator sets carry a UL1500
marine mark (decal). Check for this mark to ensure that
your specific model is ignition protected.USCG
Regulation 183.410 requires ignition-protected devices
only in gasoline/gaseous-fueled environments.
2.3Mounting
Mount the generator set as high as possible to avoid
contact with bilge splash and lower-lying vapors and to
allow for downward pitch of the exhaust line toward the
exhaust outlet.
Kohler Co. recommends mounting the generator set on
a flat board attached to the craft stringers.Craft
stringers generally provide the best generator set
support.Ensure that the structural members can
support the generator set’s weight and withstand its
vibration.
The generator set includes vibration mounts and a
mounting tray or skid.If desired, install additional
vibration isolating pads underneath the generator set’s
base. Use the four mounting holes in the mounting tray
to mount the generator set securely to the craft.
For angular operating limits, consult the operation
manual.
TP-6862 6/1411Section 2 Location and Mounting
Page 12
Notes
TP-6862 6/1412 Section 2 Location and Mounting
Page 13
3.1Ventilation
Section 3 Cooling System
Engine combustion, generator cooling, and expulsion of
flammable and lethal fumes require ventilation. Provide
ventilation compliant with USCG regulations governing
the sizing of vents and other considerations.
As a rule, size each inlet- and outlet-vent area to a
minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the
craft’s beam.Should this rule conflict with USCG
regulations, follow USCG regulations. For applications
with screened inlets, double the size (4 sq. in. per ft.) of
the hull/deck openings. Extend the vent ducts to bilges to
expel heavier-than-air fumes.
For generator sets mounted in the engine compartment,
increase the air flow to allow for the generator set’s
requirements.Install optional detection devices to
cause alarm, warning, or engine shutdown should
dangerous fumes accumulate in the compartment.
See the generator set specification sheet that shipped
with the generator set for air requirements. The air intake
silencer/cleaner provides combustion air to the engine.
Do not compromise the recommended minimum
clearance (shown in Section 2) between a duct opening
and enclosure wall. The engine/generator performance
will decline if you compromise these guidelines. See
Figure 3-1 for allowable intake restriction.
Note: ISO 3046 derates apply. See Appendix C.
1
2
4
1. Inside packing
2. Outside packing
3. Seacock c over
4. Direction of v essel movement
5. Typical intake through-hull strainers
5
3
5982--3.1
Figure 3-2 Seacock Installation
Do not align the strainer (in relation to the direction of
travel) with any other through-hull intakes.See
Figure 3-3. Flush mount the recommended through-hull
strainer. Install slotted-hole-design strainers with the
slots parallel to the direction of the vessel’s movement.
Model
40--150EOZDJ/EOZCJ
33--125EFOZDJ/EFOZCJ
Allowable
Intake Restriction
25 in. H2O
(6.25kPa)orless
1
oror
Figure 3-1 Combustion Air Intake Restriction
32
3.2Cooling System Components
Design the marine generator set’s cooling system to
include the following features.
Note: Position the intakes in relation to the vessel’s
3.2.1Intake Through -Hull Strainer
(Seacock Cover)
Install a screened-intake, through-hull strainer to
prevent entry of foreign objects.Use perforated,
slotted-hole, or unrestricted-hole design strainers. See
Figure 3-2 for examples of typical strainers. The inner
diameter of the strainer opening must be equal to or
greater than the inner diameter of the water line hose to
the seawater pump.
TP-6862 6/1413Section 3 Cooling System
Figure 3-3 Intake Strainer
travel so neither is in the wake of the other.
1. Generator set intake
2. Aft (rearward)
3. Fore (forward)
5982--3.2
Page 14
Do not use a speed scoop or cup design intake
through-hull strainer because it can cause a ramming
effect and force water upward, past the seawater pump,
and into the engine cylinders when the vessel is moving
and the generator set is shut down.
Do not use hull designs incorporating sea chests or
other designs that provide a positive pressure to the raw
water pump for the intake through-hull strainers.
Positive pressure forces water past the raw water pump
and into the engine.A sea chest is a concave
molded-in-the-hull chamber that aligns to the direction
of travel. A sea chest configuration applies a positive
pressure similar to a scoop-type through-hull strainer.
3.2.2Seacock
Mount the seacock to the hull, assemble it to the intake,
and ensure that it is accessible for operation. Figure 3-2
shows a typical installation.
Mount the seawater strainer to the seacock or
permanent structure at a point not higher than the
seawater pump. Ensure that the strainer is accessible
for service. See Figure 3-4 for a typical installation.
Some seawater strainers include a seacock and an
intake through-hull strainer.
Maximum seawater inlet pressure at the seawater pump
is 34.5 kPa (5 psi). Excessive pressure will cause water
ingestion.
3.2.4Water Lines
Water lines from the seacock to the engine-driven
seawater pump are usually constructed of flexible hose.
Connect a flexible section of hose to the seawater pump
to allow for vibrational motion of the generator set during
operation.Support a nonflexible water line within
102 mm (4 in.) of its connection to the flexible section.
Avoid overcaulking the seacock. Excess caulk reduces
water flow and, in some cases, develops a barrier that
can force water upward, past the seawater pump, and
into the engine cylinders when the vessel is moving and
the generator set is shut down.
3.2.3Seawater Strainer
123
Keep the seawater hose as straight and short as
possible. If the hose is too long, usually over 4.6 m
(15 ft.), water suction problems may occur.See
Section 7 for the inlet water line hose size and the
seawater connection to the seawater pump inlet. Avoid
running the inlet pipe above the generator.See
Figure 3-5 for the seawater inlet connection.
1
2
1. Seawater pump
2. Seawater inlet (opposite side)
ADV8500A-
Figure 3-5 Seawater Inlet Connection (Located on
non-service side), Typical
1. Seawater pump
2. Seawater strainer
3. Seacock
Figure 3-4 Seawater Strainer
3.2.5Closed Heat Exchanger
5982--3.3
A closed heat exchanger is the best cooling method for
most applications.See Figure 3-6 for a typical
installation. Provide space to access the water-cooled
exhaust manifold pressure cap.
TP-6862 6/1414 Section 3 Cooling System
Page 15
1
2
3
4
5
7
6
8
9
14
1. Oil cooler
2. Engine block
3. Thermostat
4. Water-cooled manifold
5. Heat exchanger
6. Exhaust mixer elbow
7. Water-cooled turbocharger
13
12
11
10
8. Silencer (customer -supplied)
9. Exhaust outlet
10. Intake strainer
11. Seacock
12. Seawater strainer
13. Engine-driven s eawater pump
14. Engine-driven water pump
Seawater
Freshwater (Coolant/Antifreeze)
TP-5592-6
Figure 3-6 Typical Closed/Heat Exchanger Cooling System (40--99EOZD(C)J/33--80EFOZD(C)J Models)
TP-6862 6/1415Section 3 Cooling System
Page 16
Overflow bottle or
tank with cap
1 1/4 in. (31.75 mm) ID fill/vent line with
a slope not less than 30 degrees *
Bypass
Inlet Line
Engine Block &
Exhaust Manifold
Return LineOutlet Line
Water pump
Hull
* If a single fill/vent line between the expansion tank and the engine cannot be used, separate lines must be used for filling and venting the
tank. A 1/4 in. (6 mm) vent line is routed from the engine top tank to the expansion tank. The expansion tank fill line goes from the bottom of
the expansion tank to the top of the keel cooler return line. A separate line, dedicated to filling the system, must be sized to meet the fill rate
requirements published by the engine manufacturer.
Keel Cooler
Figure 3-7 Keel Cooling System Installation (Single Fill/Vent Line)
Figure 3-8Keel Cooling System Installation (Multiple Vent Lines)
1/4” max. vent lines
from high points in
system to top of tank.
3/4” min. fill line
to water pump inlet.
(Tee in as close to the engine
pump inlet as practical in
customer-supplied piping).
TP-6862 6/1416 Section 3 Cooling System
Page 17
Section 4 Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystem mustbe
leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases.Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning.Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
4.1Types
Kohlerr generator sets covered in this manual use
either wet or dry exhaust systems. Dry exhaust systems
are common in commercial applications.See the
engine manual for specifications.
Note: Silencer selection is the responsibility of the
installer but must meet the parameters outlined in
this manual.
4.2Exhaust Lines
Use water-cooledexhaust lines inall marine
installations. Keep the lines as short and straight as
possible.NFPA 302 Fire Protection Standard for
Pleasure and Commercial Motor Craft, Clause 4-3,
recommends using two corrosion-resistant hose
clamps with a minimum width of 13 mm (1/2 in.) on each
end of the flexible exhaust hose connections.
Kohler Co. requires a downward pitch of at least 13 mm
per 30.5 cm (1/2 in. per running foot). Use a flexible
exhaust hose that conforms to UL Standard 1129 for the
engine’s wet exhaust components between the mixer
elbow and the exhaust outlet.
See Figure 4-1 for minimum recommended exhaust line
hose selection. See Section 7 for exhaust outlet size
and location.
Inspecting the exhaust system. Carbon monoxide can
cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector.
Never operate the generator set without a functioning carbon
monoxide detector.Inspect the detector before each
generator set use.
Operating the generator set. Carbon monoxide can cause
severe nausea, fainting, or death. Be especially careful if
operating the generator set when moored or anchored under
calm conditions because gases may accumulate. If operating
the generator set dockside, moor the craft so that the exhaust
discharges on the lee side (the side sheltered from the wind).
Always be aware of others, making sure your exhaust is
directed away from other boats and buildings.
Min.
Wet Exhaust
Hose
Diameter
Models
40EOZD(C)J
33EFOZD(C)J
40/50EFOZD(C)J102 (4.0)102 (4.0)
55/65EOZD(C)J
45/55EFOZD(C)J
80/99EOZD(C)J
70/80EFOZD(C)J
125/150EOZD(C)J
100/125EFOZD(C)J
mm (in.)
89 (3.5)89 (3.5)
102 (4.0)102 (4.0)
127 (5.0)102 (4.0)
127 (5.0)102 (4.0)
Min.
Dry Exhaust
Hose
Diameter
mm (in.)
Figure 4-1 Exhaust Hose Sizes (Minimum)
TP-6862 6/1417Section 4 Exhaust System
Page 18
4.3Sound Shielded Units with Dry
Exhaust
For units equipped with a dry exhaust and sound shield,
insulate the exhaust system inside of the sound shield to
the turbocharger/manifold.Use fiberglass exhaust
tape/wrap (or equivalent) and secure with stainless wire
(or material suitable for use in a marine environment).
The exhaust system around the elbow inside of the
sound shield must be insulated so that temperatures do
not exceed 88_C (190_F). See Figure 4-2.
Alternator-End View
1
1
1. Dry exhaust elbow
2. Turbocharger
2
Figure 4-2 Dry Exhaust/Turbocharger Location
(Shown with Sound Shield removed)
4.4Exhaust System Location,
Mounting, and Installation
Note: Should any information regarding installation
conflict with USCG regulations, follow USCG
regulations.
Mount the silencer independently to eliminate stress on
the exhaust system and the exhaust manifold/mixer
elbow. See Section 7 for the mixer elbowwater line hose
size. See Figure 4-3 for the exhaust connection to the
mixer elbow. Provide an adequate hose length from the
exhaust mixer to the silencer to allow for generator set
movement.
1. Exhaust outlet
ADV8501B-
Figure 4-3 Mixer Elbow/Exhaust Connection,
Typical
Locate the exhaust outlet at least 10 cm (4 in.) above the
waterline when the craft is loaded to maximum capacity.
Install an exhaust port with the flap at the exhaust
(transom) outlet to prevent water backup in following
seas or when moving astern (backward). A lift in the
exhaust piping before the piping exits the craft prevents
backwash. See Figure 4-5, item 2. Support the exhaust
lines to prevent the formation of water pockets.
Exhaust system installation guidelines for various
generator set locations follow.Information and
illustrations of stern- (rear) exhaust installations also
apply to side-exhaust installations. Where exhaustlines
require passage through bulkheads, use port (left)- or
starboard (right)- side exhaust outlets, also in
applications in which long exhaust lines to the transom
(rear) could cause excessive back pressure.See
Figure 4-4 for allowable back pressures.
Maximum
Allowable
Exhaust Back
Model
40--150EOZDJ/EOZCJ
33--125EFOZDJ/EFOZCJ
* Under ALL engine loading conditions.
Pressure
≤
(in. H
7.5 (30) *
kPa
2
,
O)
Figure 4-4 Allowable Exhaust Back Pressures
TP-6862 6/1418 Section 4 Exhaust System
Page 19
4.4.1Above-Waterline Installation
Install a customer-supplied silencer with the silencer’s
outlet at a maximum of 3 m (10 horizontal ft.) from the
center of the engine’s exhaust outlet. See Figure 4-5.
Mount a typical silencer with the inlet and outlet
horizontal and with the drain plug down. Use an exhaust
Note: Data applies to both rear- and side-exhaust installations.
Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
hose pitch of at least 13 mm per 30.5 cm (0.5 in. per
running foot).Some silencers require two support
brackets or hanger straps for installation to stringers or
other suitable structure.Follow the instructions
provided with the silencer.Install any lift (see
Figure 4-5, item 2) in the exhaust line below the engine
exhaust manifold outlet.
6
5
7
8
1
2
3
20
4
17
19
18
16
1. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.). Note: Vessel fully loaded
2. Slight lift improves silencing and prevents water backwash
into the silencer (keep below the level of the exhaust
manifold outlet)
3. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
4. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
5. Exhaust m anifold outlet
6. Exhaust mixer elbow
7. Heat exchanger (locations vary by model)
8. Coolant recovery tank (located on the unit on some models)
9. Locate the coolant recovery tank at the same height as the
heat exchanger
15
9
10
14
11
13
12
10. Maximum seawater pump lift of 3 m (10 ft.)
11. Seawater strainer
12. Intake strainer
13. Seacock
14. Engine-driven s eawater pump
15. Maximum distance between silencer and exhaust mixer
elbow of 3 m (10 ft.)
16. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
17. Silencer (customer -supplied)
18. Waterline
19. Maximum silencer vertical lift of 1.2 m (4 ft.)
20. Kohler recommends locating the generator set at elevation
that exhaust mixer is above the highest point of the exhaust
outlet hose.
Figure 4-5 Typical Above-Waterline Installation
TP-6862 6/1419Section 4 Exhaust System
Page 20
4.4.2Mid/Below-Waterline Installation
Follow USCG regulations for installing an antisiphon
provision to prevent raw water entry into the engine.
Use the siphon break if the exhaust manifold outlet is
located less than 23 cm (9 in.) above the waterline when
the craft is loaded to maximum capacity. Install the
siphon break at least 31 cm (1 ft.) above the waterline
using the instructions provided with the siphon break kit.
Note: An improperly installed siphon break will cause
engine damage and may void the warranty.
Install the siphon break above the highest point in the
exhaust line between the heat exchanger and the
exhaust mixer. See Figure 4-6 for the siphon break
connection. Support the siphon break and hoses to
maintain their position and function. Allow a slight offset
to clear the stringers or other permanent structures.
Protect the siphon break air inlet from dirt and debris.
Note: To prevent water leakage on the generator set, do
not mount the siphon break directly over the
generator set.
Note: Ensure that the siphon break’s cap is tight before
operating the generator set.
Non-Service Side View
1
ADV8501B-
1. Cut hose and connect siphon break and hardware
Figure 4-6 Siphon Break Connection (Typical for
Non-Sound Shielded Units)
Mount a typical silencer’s base no more than 1.2 m (4 ft.)
below the highest point in the exhaust line. Attach a
separate wood mounting base to the hull stringers or
othersuitablestructures.Usethesilencer
manufacturer’s recommendation for securing the
silencer to the hull. Mount the silencer with the outlet not
more than 3 m (10 horizontal ft.) from the engine’s
exhaust manifold outlet. Use a USCG-type certified
marine exhaust hose.
TP-6862 6/1420 Section 4 Exhaust System
Page 21
25
23
24
1
2
3
7
28
9
10
6
4
5
8
20
26
22
19
27
21
18
1. Cap
2. Reed valve
3. Mounting base
4. Maximum silencer vertical lift of 1.2 m (4 ft.)
5. Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
6. Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank (located on the unit on some models)
11. Indicates the coolant recovery tank is at the same height as the
heat exchanger
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven s eawater pump
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
17. Maximum distance between silencer and exhaust mixer elbow
of 3 m (10 ft.)
18. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
19. Silencer (customer -supplied)
20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
(0.5 in. per ft.)
11
Waterline
16
12
15
13
17
21. Maximum distance between exhaust outlet and generator of
4.6 m (15 ft.)
22. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
23. Exhaust hose, exhaust gas outlet hose after separator. See
Figure 4-1 for hose sizes.
24. Gas/water separator (optional). Install directly above the
canister muffler.
25. Distance above waterline for drain outlet from silencer must be
equal to or greater than water drain (item 26) to be greater
than 30.5 cm (1 ft.)
26. Water drain distance below waterline
27. Water drain (separated water from item 24)
28. System installer is responsible for designing enough capacity
into the lift muffler and plumbing to prevent engine water
ingestion upon shutdown. Otherwise, water will drain back
into item 19 on generator set shutdown.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Use two hose clamps on each end of all flexible exhaust
hose connections.
Note: Data applies to both rear- and side-exhaust installations.
Note: Damage caused by water ingestion will not be covered by
the generator warranty.
14
Figure 4-7 Typical Mid- and Below-Waterline Installation with Optional Gas/Water Separator
TP-6862 6/1421Section 4 Exhaust System
Page 22
Note: Data applies to both rear- and side-exhaust installations.
Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
11
10
12
1
2
3
24
25
4
23
22
1. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
2. Exhaust hose (see Figure 4-1 for hose sizes)
3. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
4. Maximum silencer vertical lift of 1.2 m (4 ft.)
5. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
6. Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
7. Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
8. Exhaust mixer elbow
9. Siphon break
10. Cap
11. Reed valve
12. Mounting base
13. Heat exchanger (locations vary by model)
8
9
14
13
7
5
6
15
16
20
19
17
21
14. Coolant recovery tank (located on the unit on some models)
15. Indicates the coolant recovery tank is at the same height as
the heat exchanger
16. Seawater strainer
17. Seacock
18. Intake strainer
19. Engine-driven s eawater pump
20. Install optional water lock here
21. Maximum distance between silencer and exhaust mixer
elbow of 3 m (10 ft.)
22. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
23. Silencer (customer -supplied)
24. Waterline
25. Kohler recommends locating the generator set at elevation
that exhaust mixer is above the highest point of the exhaust
outlet hose.
18
Figure 4-8 Typical Mid- and Below-Waterline Installation
TP-6862 6/1422 Section 4 Exhaust System
Page 23
Note: Data applies to both rear- and side-exhaust installations.
Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
1
2
3
7
9
10
8
19
25
16
4
22
20
16
18
21
1. Cap
2. Reed valve
3. Mounting base
4. Maximum silencer internal vertical lift of 1.2 m (4 ft.)
5. Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
6. Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
7. Siphon break
8. Exhaust mixer
9. Heat exchanger
10. Coolant recovery bottle
11. Indicates the coolant recovery tank is at the same height as
the heat exchanger
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven s eawater pump
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
24
6
15
5
16
23
12
17
27
14
17. Maximum distance between silencer and exhaust mixer elbow
of 3 m (10 ft.)
18. Water drain distance below waterline
19. Combination silencer that contains lift muffler and gas water
separating sections in single component (customer-supplied)
20. Distance above waterline for drain outlet from silencer must
be equal to or greater than water drain (item 18) to be greater
than 30.5 cm (1 ft.)
21. Exhaust outlet to be diameter appropriate so exhaust back
pressure does not exceed limit at engine exhaust manifold
22. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
23. Exhaust hose
24. Height of internal lift tube to be below generator exhaust
manifold
25. Kohler recommends generator be located at elevation that
exhaust mixer elbow is above silencer exhaust outlet
26. Seawater pump lift
27. Waterline
11
26
13
Figure 4-9 Exhaust System
TP-6862 6/1423Section 4 Exhaust System
Page 24
Satisfactory generator set performance requires proper
exhaustsysteminstallation.Figure 4-10and
Figure 4-11 show typical arrangements for commercial
marine exhaust systems.
1
Ensure that there is a means to periodically drain
condensation in exhaust, such as a silencer equipped
with a drain plug (see Figure 4-12), or a wye- or tee-type
condensation trap with a drain plug, or petcock installed
between the engine and silencer (see Figure 4-13).
4
3
5
6
7
1. Supports
2. Pitch line downward
3. Silencer
4. Water trap
8
5. Drain petcock
6. Flexible section
7. Solid section 152 --203 mm (6--8 in.)
8. Manifold
NOTE: Horizontal
silencer shown.
Figure 4-10 Exhaust System, End Inlet Silencer
1
8
1. Silencer
2. 45 Y fitting
3. Water trap
4. Drain petcock
7
5
6
2
3
NOTE: Horizontal
silencer shown.
4
5. Outer diameter adapter and clamp
6. Flexible section
7. Manifold
8. 45 elbow
2
TP-5700-5
NOTE: Horizontal
silencer shown.
1. Pipe Plug
1
Figure 4-12 Silencer Condensation Drain Plug
NOTE: Horizontal
silencer shown.
1. Condensation trap
1
Figure 4-13 Condensation Trap
TP-5700-5
TP-5700-5
Figure 4-11 Exhaust System, Side Inlet Silencer
TP-6862 6/1424 Section 4 Exhaust System
Page 25
Section 5 Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
Do not modify the tank or the propulsion engine fuel
system. Equip the craft with a tank that allows one of the
two pickup arrangements.
Note: Fuel system installations must conform to USCG
regulations.
5.1Fuel Tank
Most marine generator sets draw fuel from the same fuel
tank as the craft’s propulsion engine(s). If the tank’s fuel
pickup opening allows a multiple dip tube, use a multiple
dip tube arrangement. See Figure 5-1. The multiple dip
tube arrangement incorporates a shorter dip tube for the
generator set and a longer dip tube for the propulsion
engine. With this arrangement, the generator set runs
out of fuel before the propulsion engine during a low fuel
supply situation. Equip the fuel system with a fuel/water
separator to remove any accumulated dirt and water.
2
1
1-788
1. Fuel line to propulsion engine
2. Fuel line to generator set
Figure 5-1 Multiple Dip Tube Arrangement
m:is:102:001
TP-6862 6/1425Section 5 Fuel System
Page 26
5.2Fuel Lines
5.3Fuel Filters
Return the generator set fuel return line to the fuel tank.
Locate the fuel return line as far as practical from the fuel
pickup to allow the tank fuel to cool the return fuel before
delivery back to the fuel injectors. Incoming fuel cools
the injectors to achieve maximum engine efficiency.
Note: Do not tee into the main propulsion engine’s fuel
line.
Under no circumstances should the propulsion engine
and generator set share pickup or return lines (through a
tee arrangement) that would allow the larger engine to
starve fuel from the smaller engine. It is possible that the
operation of either engine could completely drain the
fuel line of the other engine and make starting difficult.
Use a flexible hose section to connect the metallic line
from the fuel tank to the engine’s fuel pump inlet
connection point. Also, use a flexible hose section to
connect the metallic line from the fuel tank to the fuel
return connection point. The flexible section allows
vibrational motion of the generator set during operation.
Fuel Line
ID Size
Model
40--150EOZDJ/EOZCJ
40--125EFOZDJ/EFOCJ
mm (in.)
9.7 (3/8)
Figure 5-2 Fuel Line ID Size
See Figure 5-2 for the ID size of the customer-supplied
fuel line that connects to the fuel pump and fuel return.
Route the fuel lines from the fuel tank in a gradual incline
to the engine. Do not exceed the height of the generator
set and do not route fuel lines above the generator set.
Comply with USCG regulation 46CFR182.20 regarding
fuel lines and supports.
Conform to USCG regulations regarding inline fuel
filters or strainers.
5.4Fuel/Water Separator
A fuel/water separator is standard on 33--150 kW
models.Consult the engine operation manual for
service procedure.
See Section 7 for fuel feed pump inlet connection and
fuel return line connection.
5.6Fuel Consumption
Consult the current generator set specification sheets
for generator set fuel consumption rates.
TP-6862 6/1426 Section 5 Fuel System
Page 27
1
2
2
3
5
4
14
1. Electric fuel or mechanical check valve
2. Permanent supports for fuel system
components
3. Fuel lift pump
4. Flexible line
Figure 5-4 Fuel System, Typical
13
12
11
5. Fuel return line (diesels only)
6. Carburetor or injection pump
7. Secondary filter
8. Primary filter
9. Flexible fuel line
Fuel Return (Diesel Only)
(Below Fluid Level)
Fuel Supply
8
7
9
6
10
10. Clamp
11. Support clamp
12. Metallic line
13. Dip tube
14. Fuel tank
Check Valve
(Optional) *
Baffles
* Anti-siphon protection is required for gasoline-powered units if diptube opening is below the waterline.
12 in.
min.
Main Fuel Tank
Figure 5-5 Fuel System, Typical
Fuel Lift
Drain Valve
TP-6862 6/1427Section 5 Fuel System
Page 28
Notes
TP-6862 6/1428 Section 5 Fuel System
Page 29
Section 6 Electrical System
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is turned off. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to
prevent interconnection of the generator set power and shore
power.
Moving parts.
6.1AC Voltage Connections
Make AC connections to the generator set inside the
junction box. Typically, the generator set connects to a
ship-to-shore transfer switch that allows the use of
shore/utility power when docked or generator set power
when docked or at sea. The wiring then connects to a
main circuit breaker box (panel board) that distributes
branch circuits throughout the craft. See Section 8 for
reconnection of the generator set.
6.2Circuit Protection
The AC circuit breakers (optional) protect the wiring
from the AC circuit breakers to the vessel’s distribution
panel. AC circuit breakers trip when they detect a fault in
the output circuit.
After correcting the fault, reset the AC circuit breaker(s) by
placing them in the ON position. Restart the unit. Do not
start the unit under load. See Figure 6-1 and Figure 6-2
for AC circuit breaker ratings.The unit’s voltage
configuration determines the circuit breaker selection.
6.2.1Circuit Breaker Consideratio ns
Mounting location. Mount the circuit breakers in the
generator set’s junction box. See Section 6.2.2.
Sizing.Use the generator set voltage/frequency
configurationtodeterminethecircuitbreaker
amperage. If the generator set voltage configuration
changes, change the circuit breaker to provide optimum
protection.
Forcircuitbreakerapplicationandselection
information, contact an authorized distributor/dealer.
Have a qualified electrician or technician install circuit
breakers and reconnect the generator set. Comply with
all governing standards and codes.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is turned off. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to
prevent interconnection of the generator set power and shore
power.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
WARNING
6.2.2Circuit Breaker Installation
1. Place the generator set master switch in the OFF
position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Remove the six screws from the right side junction
box panel and remove the panel.
4. Install the circuit breaker on the new panel with the
screws and washers. Position the ON side of the
circuit breaker toward the rear of the junction box.
SeeFigure6-3.
5. Attach stator leads L1, L2, and L3 to the extension
leads (if supplied) or to the line side of the circuit
breaker. See Figure 8-3.
Note: Insulate leads with electrical tape after
connecting extension leads to stator leads.
6. Connect the neutral connection stator leads to the
L0 stud.
Note: Verify that terminal positions and previously
made line lead connections allow room for
load connections to load studs.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Moving parts.
7. Connect the load side of the circuit breaker to
customer-supplied craft wiring.Connect the
neutral lead to the L0 stud. See Figure 8-3.
8. Attach the new panel to the junction box using the
original six screws. See Figure 6-3.
TP-6862 6/1430 Section 6 Electrical System
Page 31
9. Check that the generator set master switch is in the
OFF position. Reconnect the generator set engine
starting battery, negative (--) lead last.
1. Circuit breaker
2. Circuit breaker mounting panel
3. Load lead access panel
Figure 6-3 Circuit Breaker Mounting, Typical
TP-6862 6/1431Section 6 Electrical System
JW250000
4. Bus
5. Hardware
6. Bus line
Page 32
6.3Installation In Steel or
Aluminum Vessels
Installation of a generator set in a vessel constructed of
a material capable of conducting current (e.g., steel or
aluminum) is subject to considerations not normally
encountered in fiberglass or wood vessels.These
differences include equipment grounding, grounding of
neutral conductors,ground-fault protection, and
isolation of galvanic currents.
Note: Isolated ground kits are available as options for
steel- or aluminum-hulled vessels. Consult your
local dealer/distributor for more information.
The scope of these topics is too extensive to be fully
discussed here. Consult your local marine authority for
more information.
Before installing the generator set, check the available
wiring diagrams in the operation manual to become
familiar with the electrical system.
6.5Battery
Batteries and their installation must conform to USCG
Regulations 183.420 (a) through (g). Provide generator
sets with batteries separate from the propulsion
engine’s whenever possible.The starting/charging
systems of both the generator set and the engine must
have a common negative (--) ground.
USCG Regulation 183.415, Grounding, requires
connection of a common conductor to each grounded
cranking-motor circuit. Size the conductor to match the
larger of the engine’s two battery cables. Figure 6-4 lists
recommended minimum cable sizes for generator set
battery connections at various generator set-to-battery
distances. Connecting a common conductor to each
grounded cranking motor circuit prevents the starting
motor current from using alternative electrical paths
should the cranking motor ground circuit be restrictedor
open because of oxidation or loose hardware.
Alternative electrical paths include metallic fuel lines
that can pose a hazard. See Section 7 for locations of
the battery connections to the generator set.
6.4Installation Regulations
The U.S. Coast Guard governs generator set
installation in U.S. pleasurecraft and commercial
vessels. Refer to the applicable regulations below:
U.S. Pleasurecraft Installation
Regulations
Title 33CFR, Chapter I, U.S. Coast Guard, Part 183
1. Subpart I—Electrical Equipment
2. Subpart J—Fuel Systems
U.S. Commercial Vessel Installation
Regulations
Title 46CFR, Chapter I, U.S. Coast Guard
1. Part 111—Electrical Systems
2. Part 182—Machinery Installation
m:sc:001:001
Required Battery Cable
(Minimum)
Distance (from battery to
generator set)
Battery Voltage12V24V12V24V
40--65EOZDJ/EOZCJ
33--50EFOZDJ/EFOZCJ
80--99EOZDJ/EOZCJ
70--80EFOZDJ/EFOZCJ
125--150EOZDJ/EOZCJ
100--125EFOZDJ/EFOZCJ
Figure 6-4 Battery Cable Sizing Recommendations
2.5 m (8.3 ft.) 5 m (16.4 ft.)
#0#4#3/0#2
#2/0#2#4/0 #1/0
#2/0#2#4/0 #1/0
TP-6862 6/1432 Section 6 Electrical System
Page 33
Kohler Co. recommends using one 12-volt battery (or
two for 24-volt systems, as the spec requires) to start the
generator. See Figure 6-5 for minimum cold cranking
amps (CCA) recommendations.
12-V olt Starting Battery Size CCA
at --18C(0F) or 100 Amp. Hr.
ModelsCCA
40EOZDJ and 33EFOZDJ
40EOZCJ and 33EFOZCJ
40EFOZDJ
40EFOZCJ
50EFOZDJ
50EFOZCJ
55EOZDJ and 45EFOZDJ
55EOZCJ and 45EFOZCJ
65EOZDJ and 55EFOZDJ
65EOZCJ and 55EFOZCJ
80EOZDJ and 70EFOZDJ
80EOZCJ and 70EFOZCJ
99EOZDJ and 80EFOZDJ
99EOZCJ and 80EFOZCJ
125EOZDJ and 100EFOZDJ
125EOZCJ and 100EFOZCJ
150EOZDJ and 125EFOZDJ
150EOZCJ and 125EFOZCJ
640
625
925
Note: Gauge senders. Gauge senders are available
for most generator sets.If using customersupplied gauges, be sure they are compatible
with generator set senders.Contact an
authorized Kohlerr service distributor/dealer.
Gauges and senders are available as service
items from an authorized Kohlerr service
distributor/dealer.
Variouswiringharnesses,Y-connectors,pigtail
harnesses, remote control panels,and remote
annunciator panels are available.
6.8Paralleling Generator Sets
See Section 9 for information on paralleling generator
sets.
Figure 6-5 Battery Recommendations
6.6Wiring
Use only stranded copper wire. Conform to USCG
Regulations 183.425 through 183.460 for wire gauges
and insulation, conductor temperature ratings, sheath
stripping, conductor support and protection, conductor
terminals and splices, and over-current protection
(circuit breakers, fuses). Use rubber grommets and
cable ties as necessary to protect and secure the wire
from sharp objects, the exhaust system, and moving
parts.
6.7Remote Connection
Kohler Co. offers several remote panels for connection
to the generator set.Contact your local Kohlerr
distributor/dealer for detailed descriptions. Kohler Co.
also offers wiring harnesses in various lengths with a
connector keyed to the controller box connector.A
“pigtail” harness is also offered which includes the
appropriate connector on one end and has pigtails that
the installer can use to connect to a customer-supplied
start/stop switch or separate lights and hourmeter.
Consult wiring diagrams, ADVs, and instruction sheets
for connection information/details.
TP-6862 6/1433Section 6 Electrical System
Page 34
Notes
TP-6862 6/1434 Section 6 Electrical System
Page 35
Section 7 Installation Drawings
Use the drawings in this section for installation
purposes.Consult the supplier and verify that the
drawings are the most current for your specifications.
Installation drawings show exhaust outlet locations, fuel
inlet and return connections, siphon break locations,
and battery connections. See Figure 7-1 for installation
drawing identification.
Model No.DrawingPage
40EOZD(C)J and 33EFOZD(C)J
open unit (sheet 1 of 2)ADV-8500A-A36
open unit (sheet 2 of 2)ADV-8500B-A37
with sound shield
(not available on EOZCJ/
EFOZCJ models)
with radiatorADV-8505A-A48
with electric clutchADV-8505B-A49
with keel cooling & dry exhaust ADV-8505C-A50
40EFOZD(C)J
50EFOZD(C)J
55EOZD(C)J and 45EFOZD(C)J
65EOZD(C)J and 55EFOZD(C)J
open unit (sheet 1 of 2)ADV-8501A-A39
open unit (sheet 2 of 2)ADV-8501B-A40
with sound shield
(not available on EOZCJ/
EFOZCJ models)
with radiatorADV-8505A-A48
with electric clutchADV-8505B-A49
with keel cooling & dry exhaust ADV-8505C-A50
80EOZD(C)J and 70EFOZD(C)J
99EOZD(C)J and 80EFOZD(C)J
open unit (sheet 1 of 2)ADV-8506A-B42
open unit (sheet 2 of 2)ADV-8506B-B43
with sound shield
(not available on EOZCJ/
EFOZCJ models)
with radiatorADV-8505A-A48
with electric clutchADV-8505B-A49
with keel cooling & dry exhaust ADV-8505C-A50
125EOZD(C)J and 150EFOZD(C)J
100EOZD(C)J and 125EFOZD(C)J
open unit (sheet 1 of 2)ADV-8508A-45
open unit (sheet 2 of 2)ADV-8508B-46
with sound shield
(not available on EOZCJ/
EFOZCJ models)
with radiatorADV-8505A-A48
with electric clutchADV-8505B-A49
with keel cooling & dry exhaust ADV-8505D-A51
ADV-8503-38
ADV-8504-41
ADV-8507-A44
ADV-8509-47
TP-6862 6/1435Section 7 Installation Drawings
Figure 7-1 Installation Drawings
(33--150 kW Models)
Page 36
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-2 Dimension Drawing, 40EOZD(C)J & 33EFOZD(C)J (Open Unit Sheet 1 of 2)
ADV-8500A-A
TP-6862 6/1436 Section 7 Installation Drawings
Page 37
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-3 Dimension Drawing, 40EOZD(C)J & 33EFOZD(C)J (Open Unit Sheet 2 of 2)
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Moving parts.
TP-6862 6/1453Section 8 Reconnection/Adjustments
Page 54
Electroswitch
L1
To Generator
Set
L2
L1
To Generator
Set
L2
2-Wire Generator Sets
2134
6578
To Load
To Shore
Power
Kraus Naimler/American Solenoid
(Early Rectangular Design)
2-Wire Generator Sets
1265
348 7
To Shore
Power
L1
L2
To Generator
Set
L0
L1
L2
To Generator
Set
L0
3-Wire Generator Sets
2134
657 8
1091112
To Load
3-Wire Generator Sets
1265
348 7
91014 13
To Shore
Power
To Shore
Power
To Load
Kraus Naimler/American Solenoid
(Newer Round Design)
2-Wire Generator Sets
L1
To Generator
Set
L2
3241
768 5
To Load
To Shore
Power
To Generator
Set
Figure 8-1 Marine Manual (Ship-to-Shore) Transfer Switch
L2
L1
L0
To Load
3-Wire Generator Sets
3241
768 5
1110129
To Load
To Shore
Power
TP-5399-5
TP-6862 6/1454 Section 8 Reconnection/Adjustments
Page 55
Kraus Naimler/American Solenoid
4-Wire, 3-Phase Generator Sets
L1
3241
L2
To Generator
Set
L3
7685
1110129
L1
L2
To Shore
Power
L3
NOTICE
Voltagereconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
Twelve-Lead Reconnection Procedure
1. Place the generator start/stop switch in the STOP
position.
2. Disconnect generator set engine starting battery,
negative (--) lead first.
L0
15141613
L2L3 L0L1
To Load
L0
I-940
Figure 8-2 Marine Manual (Ship-to-Shore) Transfer
Switch, continued
8.1Twelve-Lead Reconnection
Thereconnectionproceduredetailsvoltage
reconnections only.If the generator set requires
frequency changes, adjust the governor and voltage
regulator. See the generator set service manual for
information regarding frequency adjustment.
The following information illustrates the reconnection of
twelve-lead generator sets. In all cases, conform to the
National Electrical Code (NEC).
Reconnect the stator leads of the generator set to
change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
precautions at the front of this manual and in the text
during the reconnection procedure.
3. Disconnect power to battery charger, if equipped.
4. Use Figure 8-3 to determine the generator set
voltage configuration. Note the original voltage
and reconnect the generator set as needed. For
units with current transformers, route leads
through current transformers (CTs) and connect
the leads according to the diagram for the desired
phase and voltage.
TP-6862 6/1455Section 8 Reconnection/Adjustments
Page 56
Figure 8-3 Generator Reconnection (ADV-5875F-R)
TP-6862 6/1456 Section 8 Reconnection/Adjustments
Page 57
Section 9 Paralleling Generator Sets
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Introduction
Read and follow the safety precautions included in this
manual. Pay attention to the decals on the equipment
and follow the instructions below.
D All personnel involved in handling, site preparation,
installation, testing, operation, and maintenance
should b e thoroughly familiar with the information in
this manual and the customer drawings provided
before working on this equipment.
D Never make interlocks inoperative or operate the
equipment with any safety barriers removed.
D Always assume that all high-voltage parts are
energized until it is certain that they are de-energized.
D Use only test equipment rated for the service
intended.
D Check interconnection diagrams and make sure
there are no potential backfeed sources.
D Never disconnect the main trip source of energized
equipment.
D Use out-of-service tags and padlocks when working
on equipment. Leave tags in place until the work is
completed and the equipment is ready to be put back
into service.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Moving parts.
D The complete assembly arrangement determines if
the top or bottom contacts are the line side; both can
be energized when the circuit breaker is removed
from the compartment.
D Do not use liquid fire extinguishers or water on
electrical fires. Before extinguishing fires within the
assembly, be absolutely certain that the main power
source is disconnected and the main and all feeder
breakers are tripped.
The Decision-Makerr 3500 generator set controller
provides generator set advanced control, system
monitoring, and system diagnostics for paralleling
multiple generator sets.
The Decision-Maker r 3500 interfaces the generator set
to other power system equipment and other network
management systems using standard industry network
communications.
The controller uses unique software logic to manage
sophisticated functions, such as voltage regulation,
synchronizing and load-sharing controls, and protective
relays for paralleling up to eight generator sets.
D Isochronous (real and reactive) load sharing with other
Decision-Makerr 3500 equipped generator sets.
D Random first-on logic to prevent two or more
generator sets from closing to a dead bus.
D Automatic synchronizer with dead bus closing.
D Soft loading and unloading.
D Protective relay functions include:
D Loss of field
D Over current
D Over frequency
D Over power
D Over voltage
D Reverse power
D Under frequency
D Under voltage
D Generatormanagementallowsunneeded
generators to be stopped to conserve fuel.
D Load control logic permits prioritization of supplied
loads, allowing critical load to retain power in a failure
scenario.
A generator set needs to be configured and set up
correctly to work in paralleling applications. This section
covers:
D Paralleling Basics (see Section 9.1)
D Paralleling Considerations (see Section 9.2)
D Paralleling Set Up (see Section 9.3)
D ParallelingTroubleshooting ( seeSection 9.4,
Section 9.5, and Section 9.6)
D Generator Management Setup (see Section 9.7)
D Load Add/Shed Configuration (see Section 9.8)
9.1Paralleling Basics
9.1.2Paralleling Functions
There are two methods of paralleling:
1. PGEN.TheDecision-Makerr3500isa
full-featured paralleling controller.It offers
integrated control for synchronizing, load sharing,
protective relays, generator management, and
load add/shed.This functionality is performed
automatically by the Decision-Makerr 3500
controller. PGEN requires an RS-485 between
each of the paralleling generators for paralleling
operation.
Note: IfthecontrollerlosesPGEN
communications while the generator sets
are operating, the Decision-Makerr 3500
controller will enter droop mode where the
output frequency varies with the real load.
2. Remote Speed and Voltage Bias.The
Decision-Makerr 3500 controller is also capable of
accepting a speed and voltage bias from an
external paralleling control. In these applications,
the external paralleling control performs all of the
required functionality and the Decision-Makerr
3500 controller merely provides a control interface
and protective functions for the generator set.
Note: For external speed and voltage bias, the
PGEN communication’s cable should
not be connected between generators.
TB13 is located inside the junction box and
contains the connection points for external speed
and voltage bias control and accommodates 0-- 5
volt input for active control. See the table below
and the wiring diagrams in the Operation Manual
for more information.
Connection
Speed Bias Negative (--)TB13-SBN
Speed Bias Positive (+)TB13-SBP
Voltage Bias Negative (--)TB13-VBN
Voltage Bias Positive (+)TB13-VBP
9.1.1Why Parallel Generator Sets
Some reasons to parallel generator sets are:
D Redundancy
D Increased power capacity
D Decreased fuel consumption
D Reduced chance of wet stacking/fuel on water
D Increased reliability
D Greater flexibility
D Individual generators can be serviced in prime power
applications
Simple paralleling requires the external speed and
voltage bias inputs to be enabled.Using
SiteTecht, under the Synchronization Control
parameter change the setting to the following:
With the external bias enabled, the engine speed is
set based on the voltage between SBP and SBN:
D Voltage < 0.5V: Engine Run Speed
D Voltage = 0.5V: 95% of Engine Run Speed
D Voltage = 2.5V: Engine Run Speed
D Voltage = 4.5V: 105% of Engine Run Speed
D Voltage > 4.5V: Engine Run Speed
With the external bias enabled, the output voltage
is set based on the voltage between VBP and VBN:
D Voltage < 0.5V: Voltage Regulator Average
Voltage Adjustment
D Voltage = 0.5V: 90% of Voltage Regulator
Average Voltage Adjustment
D Voltage = 2.5V: Voltage Regulator Average
Voltage Adjustment
D Voltage = 4.5V: 110% of Voltage Regulator
Average Voltage Adjustment
D Voltage > 4.5V: Voltage Regulator Average
Voltage Adjustment
The Decision-Makerr 3500 controller reads the
voltage on the speed and voltage bias inputs every
50 ms (20 times per second) and passes the new
target to the voltage regulator and the ECM.
Speed Bias is the amount that the controller is
attempting to adjust the output frequency of the
generator (100% bias = +5% on the engine speed,
--100% = --5% on the engine speed). The controller
adjusts the Speed Bias to match frequency and
phase with the paralleling bus.
Note: The Speed Bias can also be controlled by an
external device if the External Bias Inputs
Enabled parameter is true, the Stand Alone
Operation parameter is false, no generators
are visible on the PGEN communications
channel, and the voltage applied to the
speed bias input is between 0.5V and 4.5V.
The External Speed Bias Input (SBP and SBN) is a
voltage measuring channel capable of reading
from --10V to 30V DC. The input is normally pulled
down to --3.3V, but can be overridden by applying a
voltage to the input.
The voltage that the controller sees on the voltage
measuring channels is visible in the Analog
Voltage Input Metered Relative Value under the
Programmable Analog Voltage Input 108
parameter heading. The input is polarity sensitive.
The Speed Bias is interpreted by the controller as
shown in Figure 9-1.
Reactive droop should be enabled on the
Decision-Makerr 3500 when paralleling with
another generator set (either in simple or intelligent
paralleling). The slope should be identical on all
generators in the paralleling system (the default is
1.0%). Reactive droop can be configured using
either SiteTecht or the User Interface (UI) at the
controller:
Using SiteTecht, under the Reactive PowerLoad Sharing parameter.
Using the UI , under the
Generator Info -> Voltage Regulation Menu and
Generator Info -> Paralleling Operation ->
Sharing Setup Menus.
Note: Non-ECM engines will require an electronic
governor (Woodward APECs) and an
appropriate Kohler governor calibration in
order to permit speed adjustment.
Voltage Bias is the amount that the controller is
attempting to adjust the output voltage (100% bias
= +10% on the output voltage, --100% = --10% on
the output voltage). The controller adjusts the
voltage bias to match the generator voltage to the
bus voltage.
Note: The Voltage Bias can also be controlled by
an external device if the External Bias Inputs
Enabled parameter is true, the Stand Alone
Operation parameter is false, no generators
are visible on the PGEN communications
channel, and the voltage applied to the
voltage bias input is between 0.5V and 4.5V.
The External Voltage Bias Input (VBP and VBN) is
a voltage measuring channel capable of reading
from --10V to 30V DC. The input is normally pulled
down to --3.3V, but can be overridden by applying a
voltage to the input.
The voltage that the controller sees on the voltage
measuring channels is visible in the Analog
Voltage Input Metered Relative Value under the
Programmable Analog Voltage Input 107
parameter heading. The input is polarity sensitive.
The Voltage Bias is interpreted by the controller as
shown in Figure 9-2
Synchronizing
Before a generator set can operate in parallel with
another generator set, its electrical output must be
synchronized (matched) to the power source it will
parallel. The parameters that must be matched are:
D Frequency
D Phase Angle
D Voltage
D Phase Rotation
The synchronizer will issue a breaker close command
when the frequency difference, phase angle, and
voltage difference are within an acceptable range and
the phase rotation matches.
For PGEN paralleling, the synchronizing is handled
within the Decision-Makerr 3500 controller.
For Remote Speed and Voltage Bias paralleling, the
synchronizing is handled by an external controller,
typically supplied on switchgear.
Real (kW) Load Control
When generator sets are running in parallel (electrically
connected), the load controller controls the generator
sets so each generator set is supplying its proportional
share of power to the load while maintaining rated
frequency. This is isochronous load sharing.
Range: -100.00% – 100.00%
Default: 0.00%
Figure 9-2 Voltage Bias
**Not Writable**
The load controller communicates (analog or digital) to
the other load controllers and determines how much
power each generator set should supply.
For PGEN paralleling, the load controller is within the
Decision-Makerr 3500 controller.
For Remote Speed and Voltage Bias paralleling, the
load controller is performed by an external controller,
typically supplied on switchgear.
Reactive (kVAR) Control (Isolated Bus)
When generator sets are paralleled, the voltage output
of each generator set must be equal. Reactive power
control is needed between the generator sets to ensure
that each is supplying its share of the reactive load and
to minimize circulating currents. This can be done in one
of two ways:
1.Active Control (Used in PGEN Paralleling and
Remote Speed and Voltage Bias Paralleling).
The reactiveload controller communicates
(analog or digital) to the other reactive load
controllers to maintain the same proportional kVAR
output while maintaining the system’s nominal
voltage.
2.Passive Control (Used in Droop Paralleling).
The voltage regulators are connected in droop or
cross current compensation. There is no active
control from the controller.
Voltage Regulator
The voltage regulator is integral to the Decision-Makerr
3500 controller and is capable of accepting remote input
for voltage adjustment. It adjusts to:
9.2Paralleling Considerations
9.2.1Generator Requirements
Alternator and Connections
Units to be paralleled must have the same frequency,
the same number of phases, the same voltage, and the
same phase rotation. The latter merely means that the
voltages across the terminals must reach their
maximum and minimum values in the same order.
Otherwise, the magnetic forces would try to turn the
rotors in opposite directions.
The pitch of the paralleled alternators needs to be the
same or excessive circulating currents may occur.
Motorized Paralleling Circuit Breaker
The Decision-Makerr 3500 controller provides control
of a single motor-operator breaker to selectively close
on or off the bus. For motorized paralleling breakers,
there are two options:
D On the generator set, pre-wired from the factory.
D Remotely mounted.Customer needs to wire to
status, trip, close, charge motor, and bus sensing.
See the wiring diagram in the operation manual for
more information.
Speed Control (Required for Paralleling Done Via
Remote Speed and Voltage Bias Method)
D 0.5 -- 4.5 volts ±10% (values supplied outside of this
range will default the setting to nominal)
Generator Set Protection
A reverse power relay senses the direction of power
flow.Each generator’s Decision-Makerr 3500
controller contains a reverse power relay. If any unit in
the system has a malfunction such as a loss of fuel
causing current to flow into the generator, the reverse
power relay will sense the reverse power and
disconnect the unit from the system. If reverse power
relays are not used, units still running will drive the unit
that has stopped as a motor.
9.2.2Paralleling Controller—PGEN
Starting and Stopping Generator Set
The Decision-Makerr 3500 controller has supervisory
control over paralleling. There are several methods that
can be used to start and stop the generator set (consult
the operation manual for more detail):
D CAN gauge
D Modbusr
D Kohler SiteTecht software
D AUTO--RUN/AUTO--OFF button
D RUN button
D Contacts 3 and 4 for remote signal
Frequency and Real (kW) Power
The Decision-Makerr 3500 controller will accept an
input from the paralleling controller. This is the way the
paralleling controller adjusts the frequency and controls
the power output of the generator set.
The Decision-Makerr 3500 controller has the ability to
accept a remote speed adjust input of:
D 0.5 -- 4.5 volts ±5% (values supplied outside of this
range will default the setting to nominal)
Note: Some engines may limit this speed adjust to no
more than approx. +3.5%.
Modbusr is a registered trademark of Schneider Electric.
Depending on the state of the paralleling motorized
breaker, the Decision-Makerr 3500 controls the
frequency or kW output of the generator set by sending a
signal to the engine governor over J1939 (CAN).
D Motorized Paralleling Breaker Open.The
generator set speed (frequency) will vary with this
signal. This would be the case while synchronizing.
D Motorized Paralleling Breaker Closed.If the
generator set parallel motorized breaker is closed
and the generator set is operating in parallel with
another power source, this signal will control the kW
load provided by the generator.
Page 62
Voltage and Reactive (kVAR) Power
The Decision-Makerr 3500 controls the generator set’s
output voltage.
9.3Paralleling Set Up
9.3.1PGEN Communication Wiring
The generator set response to the signal varies
depending on the state of its paralleling motorized
breaker.
D Motorized Paralleling Circuit Breaker Open. If the
motorized circuit breaker is open, the output voltage
will change.This would be the case while
synchronizing.
D Motorized Paralleling Circuit Breaker Closed. If
the motorized circuit breaker is closed and the
generator set is operating in parallel with another
power source, this signal will control the kVAR load
provided by the generator.
TB12TB12TB12TB12
In order to parallel two or more generator sets using
PGEN, a communication wire is required. Use a Belden
cable #9841 (or equivalent) shielded twisted-pair
communication cable. Connect the shield to ground at
one end only. Tighten the connections to 0.5 Nm
(4.4 in. lbs.).The PGEN connection between the
generator sets is always required when the generator
sets connect to a common bus. See Figure 9-3.
Figure 9-3 Paralleling System Interconnection Diagram
PGEN connections are made on terminal block TB12.
TB12 is located in the generator set junction box. See
Figure 9-5 for TB12 location. See Figure 9-4 for PGEN
connection locations. A small portion of the wiring
diagram is shown in Figure 9-4. See the operation
manual for the complete wiring diagram.
9.4Troubleshooting When Breaker Does Not Close to Bus
9.4.1Faults Not Show n
StepPotential CauseExplanationTroubleshooting
1PGEN
communication not
operational
2Single generator
application
3PGEN wiring not
connected correctly
4Baud rate
misconfigured
5InterferenceThe PGEN network is seeing noise which
6Short circuit in
communication
wiring
7Intermittent
connection in PGEN
wiring
8Unable to establish
first-on lock
The controller must have seen PGEN
communication with at least one other node
at some time since the last power cycle event
before it will close the breaker.
There is only one generator on site, but the
controller is expecting to see PGEN
communication. The controller supports this
scenario if the controller is configured in
Standalone mode. Standalone mode can be
set using the standalone input to the
controller or in Kohler SiteTech
PGEN communicates over an RS-485
connection. RS-485 requires that the
network be connected in a daisy-chain
configuration, terminated at 120 Ohms at
either end of the network and that positive (B)
and negative (A) polarity be maintained.
One of the controllers on the network is
attempting to communicate at a different
baud rate than the other controllers. This
results in collisions on the communication
bus and incorrect interpretation of the data.
makes it difficult for the generator controllers
to communicate.
The RS-485 communication wires are
short-circuited together.
Although the generator controllers can
occasionally communicate, the connection is
unreliable. This can be caused by a short or
open circuit.
The generator is trying to close to a dead bus
but it is not receiving permission from one of
the other nodes to allow it to do so. This can
occur if one of the other nodes has seen a
node removed from the network.
t.
In Controller Config --> Communication Setup,
verify the PGEN Nodes Online is at least 2. If
so, continue troubleshooting at Step 8
otherwise, continue on to Step 2.
Configure a digital input to Standalone mode
and assert it, or set Standalone mode in
Kohler SiteT e cht. Note, Standalone mode
should only be asserted if there is only one
generator set at the site.
Verify wiring, all PGEN + connections should
be connected with daisy-chain wire (Belden
#9841 or equivalent). Verify terminations are
at the end of the network. Verify that there
are no unintentional or loose connections.
In Controller Config --> Communication Setup,
verify that the baud rate of all generators on
the network matches. Default is 57,600
baud.
Verify that PGEN network uses Belden #9841
or equivalent. Verify that the shield drain for
the cable is grounded at only one end.
In Controller Config --> Communication Setup,
verify the PGEN Node ID is less than 16. If
not, check the PGEN wiring for short circuits.
Otherwise, continue troubleshooting to Step 7.
It is not uncommon for small communications
wire to not connect directly to a terminal block
well. Verify there are no loose wiring
connections or “whiskers” at the PGEN
terminal blocks. “Fork”, “ring”, or “crow’s feet”
connectors are preferred for terminal block
connections.
Fault: System Frequency Mismatch B etween Generators
1System frequency is not
equivalent
Fault: Phase Connection Mismatch Between Generators
1Phase connection is not
equivalent
Fault: Live Bus Sensed When Dead Bus Expected
1Bus is considered to be
live
2Bus sensing is not
connected
Fault: Close Attempt
Fault: Fail to Close
1Breaker is unable to
close
2Trip is not removed from
the circuit breaker
3CB trip relay is wired as
normally open
4Incorrect wiring between
the CB trip relay and the
trip coil on the breaker
5Close is not applied to
the circuit breaker
6Breaker is not chargedThe breaker is receiving the signal to close
One of the controllers on the network is
configured differently than the other
controllers. This will inhibit any of the
generators from closing to the bus.
One of the controllers on the network is
configured differently than the other
controllers. This will inhibit any of the
generators from closing to the bus.
One of the controllers on the network is
configured differently than the other
controllers. This will inhibit any of the
generators from closing to the bus.
The controller is measuring voltage on the
paralleling bus. This will inhibit the breaker
from closing.
The controller may see voltage on the
paralleling bus when the generator is
operating and the bus sensing is
disconnected.
The controller is attempting to close the
circuit breaker but the breaker is not
closing.
The controller is attempting to close the
circuit breaker but the breaker is not
closing because the trip coil is still
energized.
The controller is expecting that the trip on
the circuit breaker is a normally-closed
contact. This is intentional as it holds a trip
on the breaker if the controller is removed.
The CB trip relay is operating correctly but
the trip coil on the breaker is remaining
energized. This could be due to incorrect
wiring between the generator controller and
the circuit breaker.
The breaker trip is removed but the
controller is not able to close the breaker.
but the energizing spring is not charged.
Verify the system voltage of all the
generators match the requirements of the
site.
Verify the system frequency of all the
generators match the requirements of the
site.
Verify the phase connection of all the
generators match the requirements of the
site.
Check bus for residual voltage (sometimes
induced by large transformers or motors).
Possibly, adjust the Dead Bus Threshold to
accommodate the residual voltage.
Verify the bus sensing wiring is connected
to the load side of the motor-operated
breaker for this generator.
Watch the ready flag on the motor operator
of the circuit breaker. If it indicates not
ready when the engine is stopped and
toggles to the ready state when the
generator is trying to close the breaker, the
trip coil is acting correctly. Continue at
Step 5 otherwise, continue on to Step 2.
If the ready flag of the motor operator
indicates ready when the engine is
stopped, continue at Step 3 otherwise,
continue on to Step 4.
VerifytheCBtriprelayiswiredtoholda
trip on the breaker when the relay is not
energized.
Verify the wiring to the circuit breaker.
Verify the wiring between the generator
controller and the circuit breaker close coil.
Check the close coil to ensure that it is not
defective.
Verify the motor operator is receiving
voltage at the appropriate contacts to allow
it to wind the spring.
Fault: Close Attempt
Fault: Fail to Close
(Continued)
7Breaker is not poweredThe 24V electronics on the circuit breaker
require an external 24V source on a 12V
generator.
8Wiring to power is not
complete
There is no voltage to the CB close relay
on this circuit breaker.
Verify the 24V input which exists on
paralleling generators is receiving 24VDC
in the correct polarity.
Connect the supply to the CB close relay to
either 24V from wire #70 or an external
24VDC supply (with battery storage).
9Breaker status feedback
is not valid, no bus
sensing
The breaker closes but the controller does
not see a change in status. The controller
cannot see the bus is energized as the bus
sensing is not connected correctly on any
generators on the network.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. Verify
bus wiring for all nodes. Verify the
generator output is connected to the line
side of the generator breaker.
Fault: CB Status
Warning: Bus Sensing Not Connected
1Breaker status feedback
is not valid, no bus
sensing
The breaker closes but the controller does
not see a change in status. The controller
cannot see the bus is energized as the bus
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. Verify
bus wiring for this generator.
sensing is not connected correctly on this
generator, but another generator is
connected.
Fault: CB Status
1Breaker status feedback
is not valid
The breaker closes but the controller does
not see a change in status. The controller
Verify the wiring on the circuit breaker to
ensure that it is connected correctly.
sees the bus is now live.
on the paralleling
breaker are inconsistent
with the generator
3Generator sensing is
connected incorrectly
4Breaker to bus wiring is
inconsistent
The breaker closes but the controller does
not see a change in status. The controller
cannot see the bus is energized as the bus
sensing is not connected correctly on any
generators on the network.
The breaker closes but the controller does
not see a change in status. The controller
sees the bus is now live.
The controller sees the breaker is closed
even when it is not trying to open it.
The controller sees open status for the
breaker after telling it to close, closed
status after telling it to open.
The breaker status indicated that it closed
when it was triggered to close but it did not
indicate that it was open when the breaker
opened. This fault will only occur if the bus
sensing is connected correctly (the
controller sees the voltage go to 0 when
the breaker is triggered to open).
The bus sensing wires must be connected
to phase A, phase B, and phase C of the
bus. If any two connections are reversed,
the controller can detect the reversed
connections. This fault will only occur if all
three wires are incorrectly connected.
The power leads from the generator to the
paralleling circuit breaker must be
connected consistently. Phase A from the
generator must go to phase A of the line
side of the paralleling (motor operated)
breaker, phase B from the generator to
phase B of the breaker and phase C of the
generator to phase C of the breaker.
The controller measurement leads are not
connected to the appropriate output phases
or the phases are incorrectly labeled.
In applications where the bus sensing is
taken from a location other than the load
side of the paralleling breaker, it is possible
to connect the wiring incorrectly between
the load side of the output breaker and the
paralleling bus.
The voltage measured on the bus sensing
for phase A does not match the voltage
measured on phase A of the generator.
Verify the bus sensing wire for phase A is
connected to phase A of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch--Phase B
1The phase B voltage of
the bus does not match
the generator
The voltage measured on the bus sensing
for phase B does not match the voltage
measured on phase B of the generator.
Verify the bus sensing wire for phase B is
connected to phase B of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch--Phase C
1The phase C voltage of
the bus does not match
the generator
The voltage measured on the bus sensing
for phase C does not match the voltage
measured on phase C of the generator.
Verify the bus sensing wire for phase C is
connected to phase C of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch
1The bus metering is not
connected correctly
The bus metering is not connected to the
appropriate lugs of the load side of the
paralleling breaker (but there is some
voltage present).
Verify the bus sensing wire for all three
phases is connected to the appropriate
lugs on the load side of the paralleling
breaker and there are no breaks in any of
the wires.
2The generator metering
is not connected
correctly
The generator metering is not connected to
the output of the generator.
Verify the generator metering is sensed at
the output of the generators. A common
mistake is to connect the metering to the
center tap voltages V7, V8, V9.
Fault: Phase Angle Mismatch
1All of the bus sensing
wires are incorrectly
connected
The bus sensing wires must be connected
to phase A, phase B and phase C of the
bus. If any two connections are reversed,
Verify the bus metering connections.
the controller can detect the reversed
connections. This fault will only occur if all
three wires are incorrectly connected.
2The phase connections
on the paralleling
breaker are inconsistent
with the generator
The power leads from the generator to the
paralleling circuit breaker must be
connected consistently. Phase A from the
generator must go to phase A of the line
Verify the output cable connections.
side of the paralleling (motor operated)
breaker, phase B from the generator to
phase B of the breaker, and phase C of the
generator to phase C of the breaker.
3Generator sensing is
connected incorrectly
The controller measurement leads are not
connected to the appropriate output phases
or the phases are incorrectly labeled.
Verify sensing leads from the controller are
connected to the appropriate output leads
from the generator. L1 should connect to
phase A, L2 to phase B, L3 to phase C, L0
to neutral.
4Breaker to bus wiring is
inconsistent
In applications where the bus sensing is
taken from a location other than the load
Verify cable connections from the
paralleling breaker to the paralleling bus.
side of the paralleling breaker, it is possible
to connect the wiring incorrectly between
the load side of the output breaker and the
paralleling bus.
Fault: Bus Frequency Mismatch
1Abnormal conditionBus frequency is not similar to generator
with the opposite phase
rotation of all the other
generators on the
paralleling bus
2The wiring between the
paralleling breaker and
the paralleling bus is
incorrectly connected
(two phases are
reversed)
3The generator which is
connected to the
paralleling bus has the
opposite phase rotation
of this generator and all
others
Fault: Dead Bus Sensed When Live Bus Expected
1The wiring was not
connected between the
load side of the
paralleling breaker for
this generator and the
paralleling bus
2The wiring was not
connected between the
load side of the
paralleling breaker for
the other generator and
the paralleling bus
Fault: Bus Voltage Out of Spec
1The generators which
are connected to the
paralleling bus are
overloaded
2Excessive cable lengths
from generators to
paralleling bus
The controller has validated that the bus
metering is accurate relative to this
generator, if the bus phase rotation is
backwards to the generator, the phase
rotation must really be different.
Voltage from other generators comes into
this generator as incorrect phase rotation
because the wiring connections to the
paralleling bus are reversed, even though
the rotation of the other generators is
identical to the rotation of this generator.
Voltage from the other generator comes
into this generator as incorrect phase
rotation because the wiring connections
from the other generator to the paralleling
bus are reversed, even though the rotation
of the other generators is identical to the
rotation of this generator.
This generator controller observed
accurate bus voltage when it closed the
breaker, the other generator controller did
the same, but the bus of this generator is
not connected to the bus of the other
generator. The other generator is
energizing the load, this generator cannot
energize the load as there is a
disconnected wiring between this generator
and the paralleling bus.
This generator controller observed
accurate bus voltage when it closed the
breaker, the other generator controller did
the same, but the bus of this generator is
not connected to the bus of the other
generator. The other generator is not
energizing the load because it is not
connected to it—this generator may be
able to energize the load, but there is no
simple way of telling this without
connecting the output of the other
generator.
When the generators which are supplying a
load are overloaded, their engine speed will
decrease, resulting in a decrease in output
voltage. Sometimes this decrease in output
voltage is sufficient to allow the generators
to recover.
Although a single generator can handle the
load, the cables which connect the
generator to the paralleling bus are too
long or too small of gauge, resulting in
insufficient bus voltage.
are connected to the
paralleling bus are
overloaded
When the generators which are supplying a
load are overloaded, their engine speed will
decrease, resulting in a decrease in output
voltage. Sometimes this decrease in output
voltage is sufficient to allow the generators
to recover.
Verify the load requirements are met by a
single generator. If not, it may be
necessary to connect several low priority
loads to load shed outputs from the
paralleling generators to avoid overloading
a single generator.
Fault: Failure to Synchronize
1Varying load
requirements drive
generator frequency
unstable
Heavy variations in the load on a generator
will cause the speed of the generator to
vary significantly. It can be difficult to
synchronize with a generator with
Adjustment of synchronizing dwell time or
synchronizing gains may improve ability to
synchronize.
continuously changing frequency.
2Fuel variations or other
environmental factors
cause the generator
frequency regulation to
suffer
When the frequency regulation is impeded
by atmospheric conditions or fuel quality,
the ability to synchronize may be affected.
Not only is the bus varying more than
normal, but it is more difficult for the
It may be necessary to adjust the
synchronizing gains.
generator to control speed while synching.
3Different sized units or
units of different fuel
types
The factory synchronizing gains were
calibrated for equal-sized units. The
response of a large unit to a small one is
It may be necessary to adjust the
synchronizing gains.
slightly different than two small units. A diesel
generator has significantly better frequency
regulation than a natural gas generator.
Fault: Generator Disabled Due to High Voltage
1Metering calibration
issue
All the generators on the paralleling bus
attempt to control to the same voltage. If
Verify the controller is measuring voltage
accurately. If not, re-calibrate it.
one has incorrect calibration, it may see
this voltage as a much higher level than the
other generators, resulting in a protective
relay trip.
2Voltage drop on
generator connection
leads
If the generator is sourcing high current
through too small of output leads, the
voltage drop in these cables may require
the generator to run at an increased
Install oversized connecting leads for the
generator to minimize voltage drop
between the generator and the paralleling
bus.
voltage to supply the necessary current to
the paralleling bus.
3Attempting to operate a
generator in base-load
mode while it is
connected to a variable
load
The speed bias and voltage bias control
real and reactive load in base-load mode
against a source with a nearly constant
frequency and voltage (such as a utility
source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and
voltage will deviate to either extreme of the
bias range, depending on the target load
and the actual load.
Fault: Generator Disabled Due to Low Voltage
1Metering calibration
issue
All the generators on the paralleling bus
attempt to control to the same voltage. If one
Verify the controller is measuring voltage
accurately. If not, re-calibrate it.
has incorrect calibration, it may see this
voltage as a much lower level than the other
generators, resulting in a protective relay trip.
2Attempting to operate a
generator in base-load
mode while it is
connected to a variable
load
The speed bias and voltage bias control
real and reactive load in base-load mode
against a source with a nearly constant
frequency and voltage (such as a utility
source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and
voltage will deviate to either extreme of the
bias range, depending on the target load
and the actual load.
generator in base-load
mode while it is
connected to a variable
load
The speed bias and voltage bias control
real and reactive load in base-load mode
against a source with a nearly constant
frequency and voltage (such as a utility
source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and
voltage will deviate to either extreme of the
bias range, depending on the target load
and the actual load.
Fault: Generator Disabled Due to Low Frequency
1Attempting to operate a
generator in base-load
mode while it is
connected to a variable
load
The speed bias and voltage bias control
real and reactive load in base-load mode
against a source with a nearly constant
frequency and voltage (such as a utility
source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and
voltage will deviate to either extreme of the
bias range, depending on the target load
and the actual load.
Fault: Generator Disabled Due to Over Power
1Continuous overloadThe generator breaker will trip to protect
the generator from damage due to
Ensure that the load is low enough for a
single generator to support it.
excessive loads.
Fault: Generator Disabled Due to Reverse Power
1Loss of fuel pressureThe generator breaker will trip to prevent
generator operation. Otherwise, power
could be absorbed from other generators
causing potential damage to the fuel
Ensure that the generator has sufficient
fuel to support load. Connect a fuel level
sensor and place Generator Management
in Fuel Level Equalization mode.
system by operating without lubrication.
2Quick ramp rate settingsThe real power may overshoot when in a
real power control situation such as base
It may be necessary to adjust the load
control gains.
load or system control.
3Different sized units or
units of different fuel
types.
4Different engine speed
adjust settings
The real power may overshoot when in a
real power control situation such as a load
ramp or a quickly changing customer load.
Setting the Engine Speed Adjust parameter
high on a generator will result in that
It may be necessary to adjust the kW load
sharing gains.
Set the engine speed adjustment similarly
on all generators.
generator providing more real power than
the other generators. It is possible to drive
the other generators offline in light loading
conditions.
Fault: Generator Disabled Due to Over Current
1Excessive reactive loadThe generator breaker will trip to prevent
the generator from damage due to
Ensure that the load is low enough for a
single generator to support it.
excessive stator current. Note, the
controller also has a heat-model-based
alternator protection algorithm (which will
shut the generator down).
Generator Management starts and stops generators
based on the requirements of the load. The order in
which the generators are started or stopped is
determined according to one of the following:
D Manual/Fixed—The starting order of the generators
is determined at the time of configuration (It is
adjustable at a later time through the menu on the
controller display). The controllers automatically
negotiate to ensure that no two units have the same
order number -- setting the order number on one
controller which conflicts with the order of another
controller will cause the two controllers to exchange
order numbers.
D Run Time—The starting order of the generators is
determined based on the run time hours on the
generators. The generator with the most run time
hours will stop first and start last. Generators which are
already running are allowed to continue to run until
their run time hours exceed stopped the run time hours
of a stopped generator by an adjustable threshold.
Typical Applications for Fuel Level Order
Selection Mode:
D Prime power applications where the generators have
individual fuel tanks and have level indication on the
fuel tanks.
D Standby applications where the generators have
individual fuel tanks and have level indication on the
fuel tanks.
9.7.1Manual Order Selection Setup:
The Generator Management order should be configured
so that the generator which is preferred to run has the
lowest order. If the controllers are communicating over
PGEN, changing the order on one generator will cause
the order of the other generators to rearrange to
accommodate the changed order of the one generator.
The Manual Start order can be changed through the
menu on the controller d isplay at any time after the
commissioning of the site is complete.
D Fuel Level—The starting order of the generators is
determined based on the fuel level remaining in the
supply tanks for the generators. This option is only
valid if the generators have indication of fuel.
Typical Applications for Manual Order Selection
Mode:
D Units of various sizes are operated in a prime power
application and the generator management settings
are optimized for minimal fuel consumption.
D An older unit is intended to accumulate most of the
run time hours because it is scheduled for
replacement soon.
D Some units are quieter or located more remotely than
other units, making them more desirable to operate.
D A unit is in need of maintenance but is still
operational—this unit can be used if necessary, but
should not operate more than is necessary.
Typical Applications for Run Time Order Selection
Mode:
D Normal Standby Power systems without special
requirements.
9.7.2Run Time Order Selection Setup
When Run Time Order Selection Mode is selected,
Generator Management will automatically adjust the
order of the connected generators based on their run
time hours. The order of each should reflect the relative
run time of that generator if all the generators are
running or all the generators are stopped. The generator
with the lowest run time will be started first.
Because a generator will not be accumulating run time
when it is stopped, it is necessary to add a stability
threshold to each generator which is not running or the
generators will start 12 minutes after they stop
(0.2 hours). This threshold is called the Generator
Management Run Time Threshold.
Configure the threshold to allow the generators to
equalize run time without starting and stopping each
generator unnecessarily. The factory default is 12.0
hours—one of the running generators will have to have
12.0 fewer hours than the generator that is stopped
before the generator will start. Once that generator is
online, the generator with the most run time hours will
stop.
9.7.3Fuel Level Selection Setup
D Multiple generator system where all generators are of
identical size and age, where the generator run time
should remain essentially identical.
D Prime power applications where the generators are
When Run Time Order Selection Mode is selected,
Generator Management will automatically adjust the
order of the connected generators based on their fuel
level. The order of each should reflect the relative fuel
level of that generator if all the generators are running or
Page 76
all the generators are stopped. The generator with the
most fuel will be started first.
Because a generator will not be consuming fuel when it
is stopped, it is necessary to add a stability threshold to
each generator which is not running or the generators
will start as soon as 1% of the running generator’s fuel is
consumed. This threshold is called the Generator
Management Fuel Level Threshold.
Configure the threshold to allow the generators to
equalize run time without starting and stopping each
generator unnecessarily. The factory default is 10% of
fuel level—one of the running generators will have to
have 10% less fuel than the generator that is stopped
before the generator will start. Once that generator is
online, the generator with the least fuel will stop.
Generator Start Percentage
The Generator Start Percentage is the percent load on
the running generators above which this generator will
begin timing for the Generator Start Delay.
The default setting is 80%, this means that the other
generators will have more than80% load on them before
this generator will begin timing for the Generator Start
Delay.
Generator Stop Percentage
The Generator Stop Percentage is the percent load on
the other running generators below which this generator
will begin timing for the Generator Stop Delay. The Stop
percentage is calculated as if this generator was not
running (the percent load on the remaining generators).
9.7.4Paralleling Parameters
Generator Management Enabled
Set this to true if Generator Management is desired for
this application
Generator Management Stability Delay
The Stability Delay is intended to ensure that all loads
have returned to their normal demand before Generator
Management considers stopping a generator.
All generators will be told to run until the Stability Delay
has expired.
Generator Management Minimum Gens Online
The Minimum Gens Online parameter will allow the
system to be configured to require at least 1 generator or
to require at least 2 generators. If set to 2 Generators,
the system will always keep one more generator online
than is required.
Note: The default setting is 2.
Generator Management Min Load Shed Priority
The Minimum Load Shed Priority is the priority which
has to be online to allow Generator management to
become active (start the stability timer). This parameter
should match the maximum load shed priority that is
connected to an actual load.
The default setting is 6 (load priority 6 must be online
before generator management becomes active).
The default setting is 60%, this means that the total load
on all the running generators is low enough that all the
running generators other than this one will have less
than 60% load on them if they were supporting the load.
The order 1 generator does not stop.
Generator Start kW
The Generator Start kW is calculated based on the Start
kWs of each of the generators with a lower order number
and the Start percentage for this generator. The Start
kW is the total load on the bus above which this
generator will begin timing for the Generator Start Delay.
Generator Stop kW
The Generator Stop kW is calculated based on the Stop
kWs of each of the generators with a lower order number
and the Stop percentage for this generator. The Stop kW
is the total load on the bus below which this generator
will begin timing for the Generator Stop Delay.
Generator Start Delay
The Generator Start Delay is the time delay in seconds
for this generator to start. Because the start delay is
actually a curve based on the difference between the
actual kW and the start kW of this generator, the start
delay is actually the time for the generator to start with a
10% overload.
Generator Stop Delay
The Generator Stop Delay is the time delay in seconds
for this generator to stop. Because the stop delay is
actually a curve based on the difference between the
actual kW and the stop kW of this generator, the start
delay is actually the time for the generator to start with
10% less load than the stop kW.
The Load Add/Shed configuration (also known as load
control) is intended to remove non-critical loads from the
generator in the event of a condition where the
generator capacity is insufficient to support the load.
This allows the critical loads to receive power until the
load decreases or the capacity increases.
9.8.1Load Add/Shed Setup
Generator Maximum Percent Capacity
This is the maximum load on the generator which the
Load Add/Shed will automatically allow. If the load
exceeds this level, no additional loads will be added until
the load decreases below this level. The time to add a
load increases as the load approaches this level.
Generator Overloaded Percent
This is the maximum load that the generator will support
before it begins to shed load. The time to shed a load
decreases as the load on the generator increases.
Load Priority Configuration
The Load Shed priorities are events which can be
assigned to programmable IO. Priorities 1 and 2 are
defaulted to RDO outputs 3 and 4. The priorities can be
configured to outputs on the 14 relay dry contact kit or
each controller on the network can be given consecutive
assignments to the existing IO.
For Example:
Generator #1—Load Shed Priority 1 and Load Shed Priority 2
Generator #2—Load Shed Priority 3 and Load Shed Priority 4
Generator #3—Load Shed Priority 5 and Load Shed Priority 6
Note: The load control outputs behave similarly on
each of the generators. If an output is configured
for Load Shed Priority 1 on all generators, they
will all shed and add at the same time.
Note: The advantage of setting a few load shed outputs
on each controller is that if one generator has the
battery removed for service, the load control
outputs on the other controllers are still able to
shed loads (allowing the system to shed
non-critical loads and continue supplying critical
loads with power). The priorities that are shed
may be more important than the priorities that are
controlled by the disconnected generator but at
least the critical loads will not lose power due to
an overload condition.
Appendix A Generator Selection and Wattage Requirements
Consider total wattage requirements (lights, motors,
appliances) when selecting a generator set or when
sizing wattage usage in which available space and
construction limit the size of the generator set.
Motors
When figuring generator set capacity requirements for
loads that include electric motors, consider the high
current demanded by the motors during startup. The
inrush or starting current is typically 2--3 times higher
than that required when the motor reaches normal
operating speed. Allow reserve for inrush demands plus
other loads which could be on the line as the electric
motor starts. Use Figure 1 as a guide when selecting
generator set capacity requirements involving motor
loads.
Motor
HP
1/4750330
1/31000400
1/21500600
3/42000750
133001100
240002000
350003000
Starting (Inrush)
Watts
Running
Watts
Figure 1Motor Requirements
Lighting
To calculate lighting load, add the wattage of each
generator set-operated lamp. Note that not all of the
lights or lamps are on the generator set AC circuit; some
are DC powered by a 12-volt battery. Make sure the
calculated total wattage includes only lights actually on
the generator set AC circuit.
Air Conditioners
The starting characteristics of air conditioners vary
greatly; one 12,000 Btu unit has, for example, lower
starting requirements than a 10,000 Btu unit of another
variety. When using only one unit, there is usually no
starting problem, provided the lighting and appliance
load is not too high when starting the unit.
Simultaneous starting of two air conditioning units,
however, can present problems if the generator set
capacity is marginal. Because of the variation in starting
characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
capabilities of the generator set covered. Consider
delayed starting or use of easy-starting devices on air
conditioner units whenever simultaneously starting
more than one motor.
See Figure 2 for typical air conditioner requirements.
Information will vary with manufacturer.
Appliances
Generator sets often furnish AC for appliances such as
TV, stereo, electric water heater, etc. With the exception
of the resistance-type loads such as the water heater,
requirements for appliances are usually low. Do not
overlook such loads when figuring total requirements.
Allow reserve capacity for anticipated appliance loads to
avoid overloading a generator set.
Figure 2Typical Marine Air Conditioner Requirements, 60 Hz
TP-6862 6/1479Appendix
Air Conditioner Size (Btu/Hr.)
7,0009,00012,00016,00024,000
Page 80
Appendix B Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
APUAuxiliary Power Unit
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CAT5Category 5 (network cable)
CBcircuit breaker
CCcrank cycle
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
exh.exhaust
ext.external
FFahrenheit, female
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
IBCInternational Building Code
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPinternet protocol
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
KBusKohler communication protocol
kgkilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6862 6/1480 Appendix
Page 81
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, k kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
Fmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
NFPANational Fire Protection
Manufacturers Association
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROread only
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTDsResistance Temperature
Detectors
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SMTPsimple mail transfer protocol
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SMSshort message service
SSstainless steel
std.standard
stl.steel
tach.tachometer
TBterminal block
TCPtransmission control protocol
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
UIFuser interface
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
URLuniform resource locator
(web address)
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
WOwrite only
w/owithout
wt.weight
xfmrtransformer
TP-6862 6/14Appendix 81
Page 82
TP-6862 6/1482
Page 83
TP-6862 6/1483
Page 84
TP-68626/14a
E 2013 and 2014 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.