Kohler 40-150EOZDJ, 40-150EOZCJ, 33-125EFOZDJ, 33-125EFOZCJ Installation Manual

Page 1
Installation
Marine Generator Sets
Pleasure Craft Models:
40--150EOZDJ
33--125EFOZDJ
Commercial Models:
40--150EOZCJ
33--125EFOZCJ
Controller:
TP-6862 6/14a
Page 2
TP-6862 6/142
Page 3
Table of Contents
Safety Precautions and Instructions 5.........................................................
Section 1 Introduction 9.....................................................................
Section 2 Location and Mounting 11...........................................................
2.1 General Considerations 1 1................................................
2.2 Location 11..............................................................
2.3 Mounting 11.............................................................
Section 3 Cooling System 13..................................................................
3.1 Ventilation 13............................................................
3.2 Cooling System Components 13............................................
3.2.1 Intake Through-Hull Strainer (Seacock Cover) 13.....................
3.2.2 Seacock 14......................................................
3.2.3 Seawater Strainer 14.............................................
3.2.4 Water Lines 14...................................................
3.2.5 Closed Heat Exchanger 14........................................
Section 4 Exhaust System 17..................................................................
4.1 Types 17................................................................
4.2 Exhaust Lines 17.........................................................
4.3 Sound Shielded Units with Dry Exhaust 18...................................
4.4 Exhaust System Location, Mounting, and Installation 18.......................
4.4.1 Above-Waterline Installation 19.....................................
4.4.2 Mid/Below-Waterline Installation 20.................................
Section 5 Fuel System 25.....................................................................
5.1 Fuel Tank 25.............................................................
5.2 Fuel Lines 26............................................................
5.3 Fuel Filters 26............................................................
5.4 Fuel/Water Separator 26..................................................
5.5 Fuel Pump Lift 26.........................................................
5.6 Fuel Consumption 26.....................................................
Section 6 Electrical System 29................................................................
6.1 AC Voltage Connections 29................................................
6.2 Circuit Protection 29......................................................
6.2.1 Circuit Breaker Considerations 29..................................
6.2.2 Circuit Breaker Installation 30......................................
6.3 Installation In Steel or Aluminum Vessels 32.................................
6.4 Installation Regulations 32.................................................
6.5 Battery 32...............................................................
6.6 Wiring 33................................................................
6.7 Remote Connection 33....................................................
6.8 Paralleling Generator Sets 33..............................................
Section 7 Installation Drawings 35.............................................................
Section 8 Reconnection/Adjustments 53.......................................................
8.1 Twelve-Lead Reconnection 55.............................................
Section 9 Paralleling Generator Sets 57........................................................
Introduction 57.................................................................
9.1 Paralleling Basics 58
9.1.1 Why Parallel Generator Sets 58....................................
9.1.2 Paralleling Functions 58...........................................
9.2 Paralleling Considerations 61..............................................
9.2.1 Generator Requirements 61.......................................
9.2.2 Paralleling Controller—PGEN 61...................................
TP-6862 6/14 Table of Contents 3
......................................................
Page 4
9.3 Paralleling Set Up 62.....................................................
9.3.1 PGEN Communication Wiring 62...................................
9.3.2 Decision-Makerr 3500 Paralleling Sequence of Operation 63...........
9.4 Troubleshooting When Breaker Does Not Close to Bus 64.....................
9.4.1 Faults Not Shown 64..............................................
9.4.2 Faults Shown 65.................................................
9.5 Troubleshooting When Breaker Does Close to Bus 67.........................
9.5.1 Faults Shown 67.................................................
9.6 Troubleshooting When Running in AUTO 71.................................
9.6.1 Faults Shown 71.................................................
9.7 Generator Management Setup 75..........................................
9.7.1 Manual Order Selection Setup: 75..................................
9.7.2 Run Time Order Selection Setup 75.................................
9.7.3 Fuel Level Selection Setup 75......................................
9.7.4 Paralleling Parameters 76.........................................
9.8 Load Add/Shed Configuration 77...........................................
9.8.1 Load Add/Shed Setup 77..........................................
Appendix A Generator Selection and Wattage Requirements 79.................................
Appendix B Abbreviations 80................................................................
TP-6862 6/14Table of Contents4
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the fuel system. A flash fire can cause severeinjury or death.
Do not smoke or permit flames or sparks near the fuel injection system, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner/silencer removed.
Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the generator set. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Catch fuels in an approved container. Wipe up spilled fuels and engine oil.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
TP-6862 6/14 5Safety Precautions and Instructions
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Page 6
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the
safety of the craft’s occupants, install a carbon monoxide detector. Never operate the generator set without a functioning carbon monoxide detector. Inspect the detector before each generator set use.
Operating the generatorset. Carbon monoxide can cause severe nausea, fainting, or death. Be especially
careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Donot operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when drainingthe fuel system. Wipe up spilled fuel after draining the system.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Hazardous Voltage/ Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect
the generator set from the load by turning off the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Moving parts.
TP-6862 6/146 Safety Precautions and Instructions
Page 7
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death.
Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is turned off. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry,approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
246242
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Fuse replacement. Replace fuses
with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
NOTICE
Saltwater damage. Saltwater quickly
deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
TP-6862 6/14 7Safety Precautions and Instructions
Page 8
Notes
TP-6862 6/148 Safety Precautions and Instructions
Page 9
Section 1 Introduction
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
The safe and successful operation of a marine power system depends primarily on the installation. See Figure 1-1. Use this manual as a guide to install the marine generator set. For operating instructions, refer to the operation manual.
13
21
20
19
18
2
Note: Only qualified persons should install the
generator set.
Marine generator set installations must comply with all applicable regulations and standards.
Use the specification sheets as a guide in planning your installation. Use current dimension drawings and wiring diagrams.
4
5
6
7
8
17
16
15
1. Exhaust mixer elbow (exhaust/water outlet)
2. Fuel return connection
3. Heat exchanger (not shown)
4. Fuel feed pump *
5. Fuel inlet connection
6. Seawater pump (seawater inlet)
7. Coolant recovery tank (located on the unit on some models)
8. Seawater strainer *
9. Seawater inlet c onnection
10. Seawater line *
11. Seacock *
14
13
12. Craft stringers
13. Fuel/water separator (see Section 5 for more information)
14. Fuel supply line *
15. Hose clamps
16. Fuel return line *
17. Mounting skid
18. Battery/battery storage box
19. Battery cables
20. Exhaust hose or exhaust line *
21. Electrical leads (AC output leads/remote start panel leads)
* Indicated components must conform to USCG regulations.
9
12
10
11
Figure 1-1 Typical Generator Set Location and Mounting (40EOZDJ Model Shown Without Sound Shield)
Note: See text for complete explanation of installation
requirements.
Note: Use two hose clamps on each end of all flexible
exhaust hose connections.
ADV8500-
TP-6862 6/14 9Section 1 Introduction
Page 10
Notes
TP-6862 6/1410 Section 1 Introduction
Page 11
Section 2 Location and Mounting
2.1 General Considerations
The key to installation is location. Before making final plans for locating a generator set, consider the following.
Installation Location Co n sid erations
1. Choose a location that allows adequate space for cooling and exhaust system installation, fuel system installation, ventilation, and service access to the generator set (engine and generator).
2. Use craft stringers or other available structural members capable of supporting the generator set’s weight.
3. Seal the generator set’s engine room from the cabin to prevent exhaust gases and fuel vapors from entering the cabin.
See the current generator set specification sheet or Section 7 of this manual for generator set dimensions and weights. See Figure 1-1 for a typical installation.
2.2 Location
Locate the generator set to allow easy service access to the generator set’s engine, controller, cooling, and fuel system components. The engine compartment is often the ideal location for the generator set if the propulsion engine(s) does not obstruct access to the generator set and controller.
Marine Generator Set Installations in European Union Member Countries
This generator set is specifically intended and approved for installation below the deck in the engine compartment. Installation above the deck and/or outdoors would constitute a violation of European Union Directive 2000/14/EC noise emission standard.
Allow clearance for vibration and cooling during operation. Allow a minimum of 38 mm (1.5 in.) clearance on all sides (top, front, rear, and sides) o f a generator set without an optional sound shield. For sound-shielded units, allow 305 mm (12 inches) minimum clearance for the left-rear door and front door (intake and discharge openings). Also, allow space for the power takeoff (PTO) option, if equipped.
Kohler ignition -protected generator sets carry a UL1500 marine mark (decal). Check for this mark to ensure that your specific model is ignition protected. USCG Regulation 183.410 requires ignition-protected devices only in gasoline/gaseous-fueled environments.
2.3 Mounting
Mount the generator set as high as possible to avoid contact with bilge splash and lower-lying vapors and to allow for downward pitch of the exhaust line toward the exhaust outlet.
Kohler Co. recommends mounting the generator set on a flat board attached to the craft stringers. Craft stringers generally provide the best generator set support. Ensure that the structural members can support the generator set’s weight and withstand its vibration.
The generator set includes vibration mounts and a mounting tray or skid. If desired, install additional vibration isolating pads underneath the generator set’s base. Use the four mounting holes in the mounting tray to mount the generator set securely to the craft.
For angular operating limits, consult the operation manual.
TP-6862 6/14 11Section 2 Location and Mounting
Page 12
Notes
TP-6862 6/1412 Section 2 Location and Mounting
Page 13
3.1 Ventilation
Section 3 Cooling System
Engine combustion, generator cooling, and expulsion of flammable and lethal fumes require ventilation. Provide ventilation compliant with USCG regulations governing the sizing of vents and other considerations.
As a rule, size each inlet- and outlet-vent area to a minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the craft’s beam. Should this rule conflict with USCG regulations, follow USCG regulations. For applications with screened inlets, double the size (4 sq. in. per ft.) of the hull/deck openings. Extend the vent ducts to bilges to expel heavier-than-air fumes.
For generator sets mounted in the engine compartment, increase the air flow to allow for the generator set’s requirements. Install optional detection devices to cause alarm, warning, or engine shutdown should dangerous fumes accumulate in the compartment.
See the generator set specification sheet that shipped with the generator set for air requirements. The air intake silencer/cleaner provides combustion air to the engine. Do not compromise the recommended minimum clearance (shown in Section 2) between a duct opening and enclosure wall. The engine/generator performance will decline if you compromise these guidelines. See Figure 3-1 for allowable intake restriction.
Note: ISO 3046 derates apply. See Appendix C.
1
2
4
1. Inside packing
2. Outside packing
3. Seacock c over
4. Direction of v essel movement
5. Typical intake through-hull strainers
5
3
5982--3.1
Figure 3-2 Seacock Installation
Do not align the strainer (in relation to the direction of travel) with any other through-hull intakes. See Figure 3-3. Flush mount the recommended through-hull strainer. Install slotted-hole-design strainers with the slots parallel to the direction of the vessel’s movement.
Model
40--150EOZDJ/EOZCJ 33--125EFOZDJ/EFOZCJ
Allowable
Intake Restriction
25 in. H2O
(6.25kPa)orless
1
or or
Figure 3-1 Combustion Air Intake Restriction
3 2
3.2 Cooling System Components
Design the marine generator set’s cooling system to include the following features.
Note: Position the intakes in relation to the vessel’s
3.2.1 Intake Through -Hull Strainer (Seacock Cover)
Install a screened-intake, through-hull strainer to prevent entry of foreign objects. Use perforated, slotted-hole, or unrestricted-hole design strainers. See Figure 3-2 for examples of typical strainers. The inner diameter of the strainer opening must be equal to or greater than the inner diameter of the water line hose to the seawater pump.
TP-6862 6/14 13Section 3 Cooling System
Figure 3-3 Intake Strainer
travel so neither is in the wake of the other.
1. Generator set intake
2. Aft (rearward)
3. Fore (forward)
5982--3.2
Page 14
Do not use a speed scoop or cup design intake through-hull strainer because it can cause a ramming effect and force water upward, past the seawater pump, and into the engine cylinders when the vessel is moving and the generator set is shut down.
Do not use hull designs incorporating sea chests or other designs that provide a positive pressure to the raw water pump for the intake through-hull strainers. Positive pressure forces water past the raw water pump and into the engine. A sea chest is a concave molded-in-the-hull chamber that aligns to the direction of travel. A sea chest configuration applies a positive pressure similar to a scoop-type through-hull strainer.
3.2.2 Seacock
Mount the seacock to the hull, assemble it to the intake, and ensure that it is accessible for operation. Figure 3-2 shows a typical installation.
Mount the seawater strainer to the seacock or permanent structure at a point not higher than the seawater pump. Ensure that the strainer is accessible for service. See Figure 3-4 for a typical installation.
Some seawater strainers include a seacock and an intake through-hull strainer.
Maximum seawater inlet pressure at the seawater pump is 34.5 kPa (5 psi). Excessive pressure will cause water ingestion.
3.2.4 Water Lines
Water lines from the seacock to the engine-driven seawater pump are usually constructed of flexible hose. Connect a flexible section of hose to the seawater pump to allow for vibrational motion of the generator set during operation. Support a nonflexible water line within 102 mm (4 in.) of its connection to the flexible section.
Avoid overcaulking the seacock. Excess caulk reduces water flow and, in some cases, develops a barrier that can force water upward, past the seawater pump, and into the engine cylinders when the vessel is moving and the generator set is shut down.
3.2.3 Seawater Strainer
123
Keep the seawater hose as straight and short as possible. If the hose is too long, usually over 4.6 m (15 ft.), water suction problems may occur. See Section 7 for the inlet water line hose size and the seawater connection to the seawater pump inlet. Avoid running the inlet pipe above the generator. See Figure 3-5 for the seawater inlet connection.
1
2
1. Seawater pump
2. Seawater inlet (opposite side)
ADV8500A-
Figure 3-5 Seawater Inlet Connection (Located on
non-service side), Typical
1. Seawater pump
2. Seawater strainer
3. Seacock
Figure 3-4 Seawater Strainer
3.2.5 Closed Heat Exchanger
5982--3.3
A closed heat exchanger is the best cooling method for most applications. See Figure 3-6 for a typical installation. Provide space to access the water-cooled exhaust manifold pressure cap.
TP-6862 6/1414 Section 3 Cooling System
Page 15
1
2
3
4
5
7
6
8
9
14
1. Oil cooler
2. Engine block
3. Thermostat
4. Water-cooled manifold
5. Heat exchanger
6. Exhaust mixer elbow
7. Water-cooled turbocharger
13
12
11
10
8. Silencer (customer -supplied)
9. Exhaust outlet
10. Intake strainer
11. Seacock
12. Seawater strainer
13. Engine-driven s eawater pump
14. Engine-driven water pump
Seawater
Freshwater (Coolant/Antifreeze)
TP-5592-6
Figure 3-6 Typical Closed/Heat Exchanger Cooling System (40--99EOZD(C)J/33--80EFOZD(C)J Models)
TP-6862 6/14 15Section 3 Cooling System
Page 16
Overflow bottle or tank with cap
1 1/4 in. (31.75 mm) ID fill/vent line with a slope not less than 30 degrees *
Bypass
Inlet Line
Engine Block & Exhaust Manifold
Return LineOutlet Line
Water pump
Hull
* If a single fill/vent line between the expansion tank and the engine cannot be used, separate lines must be used for filling and venting the
tank. A 1/4 in. (6 mm) vent line is routed from the engine top tank to the expansion tank. The expansion tank fill line goes from the bottom of the expansion tank to the top of the keel cooler return line. A separate line, dedicated to filling the system, must be sized to meet the fill rate requirements published by the engine manufacturer.
Keel Cooler
Figure 3-7 Keel Cooling System Installation (Single Fill/Vent Line)
Figure 3-8 Keel Cooling System Installation (Multiple Vent Lines)
1/4” max. vent lines from high points in system to top of tank.
3/4” min. fill line to water pump inlet. (Tee in as close to the engine pump inlet as practical in customer-supplied piping).
TP-6862 6/1416 Section 3 Cooling System
Page 17
Section 4 Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
4.1 Types
Kohlerr generator sets covered in this manual use either wet or dry exhaust systems. Dry exhaust systems are common in commercial applications. See the engine manual for specifications.
Note: Silencer selection is the responsibility of the
installer but must meet the parameters outlined in this manual.
4.2 Exhaust Lines
Use water-cooled exhaust lines in all marine installations. Keep the lines as short and straight as possible. NFPA 302 Fire Protection Standard for Pleasure and Commercial Motor Craft, Clause 4-3, recommends using two corrosion-resistant hose clamps with a minimum width of 13 mm (1/2 in.) on each end of the flexible exhaust hose connections. Kohler Co. requires a downward pitch of at least 13 mm per 30.5 cm (1/2 in. per running foot). Use a flexible exhaust hose that conforms to UL Standard 1129 for the engine’s wet exhaust components between the mixer elbow and the exhaust outlet.
See Figure 4-1 for minimum recommended exhaust line hose selection. See Section 7 for exhaust outlet size and location.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector. Never operate the generator set without a functioning carbon monoxide detector. Inspect the detector before each generator set use.
Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Be especially careful if
operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings.
Min.
Wet Exhaust
Hose
Diameter
Models
40EOZD(C)J 33EFOZD(C)J
40/50EFOZD(C)J 102 (4.0) 102 (4.0)
55/65EOZD(C)J 45/55EFOZD(C)J
80/99EOZD(C)J 70/80EFOZD(C)J
125/150EOZD(C)J 100/125EFOZD(C)J
mm (in.)
89 (3.5) 89 (3.5)
102 (4.0) 102 (4.0)
127 (5.0) 102 (4.0)
127 (5.0) 102 (4.0)
Min.
Dry Exhaust
Hose
Diameter
mm (in.)
Figure 4-1 Exhaust Hose Sizes (Minimum)
TP-6862 6/14 17Section 4 Exhaust System
Page 18
4.3 Sound Shielded Units with Dry
Exhaust
For units equipped with a dry exhaust and sound shield, insulate the exhaust system inside of the sound shield to the turbocharger/manifold. Use fiberglass exhaust tape/wrap (or equivalent) and secure with stainless wire (or material suitable for use in a marine environment). The exhaust system around the elbow inside of the sound shield must be insulated so that temperatures do not exceed 88_C (190_F). See Figure 4-2.
Alternator-End View
1
1
1. Dry exhaust elbow
2. Turbocharger
2
Figure 4-2 Dry Exhaust/Turbocharger Location
(Shown with Sound Shield removed)
4.4 Exhaust System Location,
Mounting, and Installation
Note: Should any information regarding installation
conflict with USCG regulations, follow USCG regulations.
Mount the silencer independently to eliminate stress on the exhaust system and the exhaust manifold/mixer elbow. See Section 7 for the mixer elbowwater line hose size. See Figure 4-3 for the exhaust connection to the mixer elbow. Provide an adequate hose length from the exhaust mixer to the silencer to allow for generator set movement.
1. Exhaust outlet
ADV8501B-
Figure 4-3 Mixer Elbow/Exhaust Connection,
Typical
Locate the exhaust outlet at least 10 cm (4 in.) above the waterline when the craft is loaded to maximum capacity. Install an exhaust port with the flap at the exhaust (transom) outlet to prevent water backup in following seas or when moving astern (backward). A lift in the exhaust piping before the piping exits the craft prevents backwash. See Figure 4-5, item 2. Support the exhaust lines to prevent the formation of water pockets.
Exhaust system installation guidelines for various generator set locations follow. Information and illustrations of stern- (rear) exhaust installations also apply to side-exhaust installations. Where exhaustlines require passage through bulkheads, use port (left)- or starboard (right)- side exhaust outlets, also in applications in which long exhaust lines to the transom (rear) could cause excessive back pressure. See Figure 4-4 for allowable back pressures.
Maximum Allowable
Exhaust Back
Model
40--150EOZDJ/EOZCJ 33--125EFOZDJ/EFOZCJ
* Under ALL engine loading conditions.
Pressure
(in. H
7.5 (30) *
kPa
2
,
O)
Figure 4-4 Allowable Exhaust Back Pressures
TP-6862 6/1418 Section 4 Exhaust System
Page 19
4.4.1 Above-Waterline Installation
Install a customer-supplied silencer with the silencer’s outlet at a maximum of 3 m (10 horizontal ft.) from the center of the engine’s exhaust outlet. See Figure 4-5. Mount a typical silencer with the inlet and outlet horizontal and with the drain plug down. Use an exhaust
Note: Data applies to both rear- and side-exhaust installations. Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
hose pitch of at least 13 mm per 30.5 cm (0.5 in. per running foot). Some silencers require two support brackets or hanger straps for installation to stringers or other suitable structure. Follow the instructions provided with the silencer. Install any lift (see Figure 4-5, item 2) in the exhaust line below the engine exhaust manifold outlet.
6
5
7
8
1
2
3
20
4
17
19
18
16
1. Minimum exhaust outlet distance above waterline of 10 cm (4 in.). Note: Vessel fully loaded
2. Slight lift improves silencing and prevents water backwash into the silencer (keep below the level of the exhaust manifold outlet)
3. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
4. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
5. Exhaust m anifold outlet
6. Exhaust mixer elbow
7. Heat exchanger (locations vary by model)
8. Coolant recovery tank (located on the unit on some models)
9. Locate the coolant recovery tank at the same height as the heat exchanger
15
9
10
14
11
13
12
10. Maximum seawater pump lift of 3 m (10 ft.)
11. Seawater strainer
12. Intake strainer
13. Seacock
14. Engine-driven s eawater pump
15. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.)
16. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
17. Silencer (customer -supplied)
18. Waterline
19. Maximum silencer vertical lift of 1.2 m (4 ft.)
20. Kohler recommends locating the generator set at elevation that exhaust mixer is above the highest point of the exhaust outlet hose.
Figure 4-5 Typical Above-Waterline Installation
TP-6862 6/14 19Section 4 Exhaust System
Page 20
4.4.2 Mid/Below-Waterline Installation
Follow USCG regulations for installing an antisiphon provision to prevent raw water entry into the engine. Use the siphon break if the exhaust manifold outlet is located less than 23 cm (9 in.) above the waterline when the craft is loaded to maximum capacity. Install the siphon break at least 31 cm (1 ft.) above the waterline using the instructions provided with the siphon break kit.
Note: An improperly installed siphon break will cause
engine damage and may void the warranty.
Install the siphon break above the highest point in the exhaust line between the heat exchanger and the exhaust mixer. See Figure 4-6 for the siphon break connection. Support the siphon break and hoses to maintain their position and function. Allow a slight offset to clear the stringers or other permanent structures. Protect the siphon break air inlet from dirt and debris.
Note: To prevent water leakage on the generator set, do
not mount the siphon break directly over the generator set.
Note: Ensure that the siphon break’s cap is tight before
operating the generator set.
Non-Service Side View
1
ADV8501B-
1. Cut hose and connect siphon break and hardware
Figure 4-6 Siphon Break Connection (Typical for
Non-Sound Shielded Units)
Mount a typical silencer’s base no more than 1.2 m (4 ft.) below the highest point in the exhaust line. Attach a separate wood mounting base to the hull stringers or other suitable structures. Use the silencer manufacturer’s recommendation for securing the silencer to the hull. Mount the silencer with the outlet not more than 3 m (10 horizontal ft.) from the engine’s exhaust manifold outlet. Use a USCG-type certified marine exhaust hose.
TP-6862 6/1420 Section 4 Exhaust System
Page 21
25
23
24
1
2
3
7
28
9
10
6
4
5
8
20
26
22
19
27
21
18
1. Cap
2. Reed valve
3. Mounting base
4. Maximum silencer vertical lift of 1.2 m (4 ft.)
5. Exhaust mixer elbow distance above waterline; if less than 23 cm (9 in.), a siphon break is required
6. Minimum siphon break distance above waterline of 30.5 cm (1 ft.)
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank (located on the unit on some models)
11. Indicates the coolant recovery tank is at the same height as the heat exchanger
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven s eawater pump
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
17. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.)
18. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
19. Silencer (customer -supplied)
20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
11
Waterline
16
12
15
13
17
21. Maximum distance between exhaust outlet and generator of
4.6 m (15 ft.)
22. Minimum exhaust outlet distance above waterline of 10 cm (4 in.)
23. Exhaust hose, exhaust gas outlet hose after separator. See Figure 4-1 for hose sizes.
24. Gas/water separator (optional). Install directly above the canister muffler.
25. Distance above waterline for drain outlet from silencer must be equal to or greater than water drain (item 26) to be greater than 30.5 cm (1 ft.)
26. Water drain distance below waterline
27. Water drain (separated water from item 24)
28. System installer is responsible for designing enough capacity into the lift muffler and plumbing to prevent engine water ingestion upon shutdown. Otherwise, water will drain back into item 19 on generator set shutdown.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Use two hose clamps on each end of all flexible exhaust
hose connections.
Note: Data applies to both rear- and side-exhaust installations. Note: Damage caused by water ingestion will not be covered by
the generator warranty.
14
Figure 4-7 Typical Mid- and Below-Waterline Installation with Optional Gas/Water Separator
TP-6862 6/14 21Section 4 Exhaust System
Page 22
Note: Data applies to both rear- and side-exhaust installations. Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
11
10
12
1
2
3
24
25
4
23
22
1. Minimum exhaust outlet distance above waterline of 10 cm (4 in.)
2. Exhaust hose (see Figure 4-1 for hose sizes)
3. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
4. Maximum silencer vertical lift of 1.2 m (4 ft.)
5. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
6. Exhaust mixer elbow distance above waterline; if less than 23 cm (9 in.), a siphon break is required
7. Minimum siphon break distance above waterline of 30.5 cm (1 ft.)
8. Exhaust mixer elbow
9. Siphon break
10. Cap
11. Reed valve
12. Mounting base
13. Heat exchanger (locations vary by model)
8
9
14
13
7
5
6
15
16
20
19
17
21
14. Coolant recovery tank (located on the unit on some models)
15. Indicates the coolant recovery tank is at the same height as the heat exchanger
16. Seawater strainer
17. Seacock
18. Intake strainer
19. Engine-driven s eawater pump
20. Install optional water lock here
21. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.)
22. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
23. Silencer (customer -supplied)
24. Waterline
25. Kohler recommends locating the generator set at elevation that exhaust mixer is above the highest point of the exhaust outlet hose.
18
Figure 4-8 Typical Mid- and Below-Waterline Installation
TP-6862 6/1422 Section 4 Exhaust System
Page 23
Note: Data applies to both rear- and side-exhaust installations. Note: Numbers in illustration refer to callouts below and not to
dimensions.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust hose
connections.
Note: Damage caused by water ingestion will not be covered by the
generator warranty.
1
2
3
7
9
10
8
19
25
16
4
22
20
16
18
21
1. Cap
2. Reed valve
3. Mounting base
4. Maximum silencer internal vertical lift of 1.2 m (4 ft.)
5. Exhaust mixer elbow distance above waterline; if less than 23 cm (9 in.), a siphon break is required
6. Minimum siphon break distance above waterline of 30.5 cm (1 ft.)
7. Siphon break
8. Exhaust mixer
9. Heat exchanger
10. Coolant recovery bottle
11. Indicates the coolant recovery tank is at the same height as the heat exchanger
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven s eawater pump
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
24
6
15
5
16
23
12
17
27
14
17. Maximum distance between silencer and exhaust mixer elbow of 3 m (10 ft.)
18. Water drain distance below waterline
19. Combination silencer that contains lift muffler and gas water separating sections in single component (customer-supplied)
20. Distance above waterline for drain outlet from silencer must be equal to or greater than water drain (item 18) to be greater than 30.5 cm (1 ft.)
21. Exhaust outlet to be diameter appropriate so exhaust back pressure does not exceed limit at engine exhaust manifold
22. Minimum exhaust outlet distance above waterline of 10 cm (4 in.)
23. Exhaust hose
24. Height of internal lift tube to be below generator exhaust manifold
25. Kohler recommends generator be located at elevation that exhaust mixer elbow is above silencer exhaust outlet
26. Seawater pump lift
27. Waterline
11
26
13
Figure 4-9 Exhaust System
TP-6862 6/14 23Section 4 Exhaust System
Page 24
Satisfactory generator set performance requires proper exhaust system installation. Figure 4-10 and Figure 4-11 show typical arrangements for commercial marine exhaust systems.
1
Ensure that there is a means to periodically drain condensation in exhaust, such as a silencer equipped with a drain plug (see Figure 4-12), or a wye- or tee-type condensation trap with a drain plug, or petcock installed between the engine and silencer (see Figure 4-13).
4
3
5
6
7
1. Supports
2. Pitch line downward
3. Silencer
4. Water trap
8
5. Drain petcock
6. Flexible section
7. Solid section 152 --203 mm (6--8 in.)
8. Manifold
NOTE: Horizontal silencer shown.
Figure 4-10 Exhaust System, End Inlet Silencer
1
8
1. Silencer
2. 45Y fitting
3. Water trap
4. Drain petcock
7
5
6
2
3
NOTE: Horizontal silencer shown.
4
5. Outer diameter adapter and clamp
6. Flexible section
7. Manifold
8. 45elbow
2
TP-5700-5
NOTE: Horizontal silencer shown.
1. Pipe Plug
1
Figure 4-12 Silencer Condensation Drain Plug
NOTE: Horizontal silencer shown.
1. Condensation trap
1
Figure 4-13 Condensation Trap
TP-5700-5
TP-5700-5
Figure 4-11 Exhaust System, Side Inlet Silencer
TP-6862 6/1424 Section 4 Exhaust System
Page 25
Section 5 Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements.
Note: Fuel system installations must conform to USCG
regulations.
5.1 Fuel Tank
Most marine generator sets draw fuel from the same fuel tank as the craft’s propulsion engine(s). If the tank’s fuel pickup opening allows a multiple dip tube, use a multiple dip tube arrangement. See Figure 5-1. The multiple dip tube arrangement incorporates a shorter dip tube for the generator set and a longer dip tube for the propulsion engine. With this arrangement, the generator set runs out of fuel before the propulsion engine during a low fuel supply situation. Equip the fuel system with a fuel/water separator to remove any accumulated dirt and water.
2
1
1-788
1. Fuel line to propulsion engine
2. Fuel line to generator set
Figure 5-1 Multiple Dip Tube Arrangement
m:is:102:001
TP-6862 6/14 25Section 5 Fuel System
Page 26
5.2 Fuel Lines
5.3 Fuel Filters
Return the generator set fuel return line to the fuel tank. Locate the fuel return line as far as practical from the fuel pickup to allow the tank fuel to cool the return fuel before delivery back to the fuel injectors. Incoming fuel cools the injectors to achieve maximum engine efficiency.
Note: Do not tee into the main propulsion engine’s fuel
line.
Under no circumstances should the propulsion engine and generator set share pickup or return lines (through a tee arrangement) that would allow the larger engine to starve fuel from the smaller engine. It is possible that the operation of either engine could completely drain the fuel line of the other engine and make starting difficult.
Use a flexible hose section to connect the metallic line from the fuel tank to the engine’s fuel pump inlet connection point. Also, use a flexible hose section to connect the metallic line from the fuel tank to the fuel return connection point. The flexible section allows vibrational motion of the generator set during operation.
Fuel Line
ID Size
Model
40--150EOZDJ/EOZCJ 40--125EFOZDJ/EFOCJ
mm (in.)
9.7 (3/8)
Figure 5-2 Fuel Line ID Size
See Figure 5-2 for the ID size of the customer-supplied fuel line that connects to the fuel pump and fuel return. Route the fuel lines from the fuel tank in a gradual incline to the engine. Do not exceed the height of the generator set and do not route fuel lines above the generator set. Comply with USCG regulation 46CFR182.20 regarding fuel lines and supports.
Conform to USCG regulations regarding inline fuel filters or strainers.
5.4 Fuel/Water Separator
A fuel/water separator is standard on 33--150 kW models. Consult the engine operation manual for service procedure.
5.5 Fuel Pump Lift
See Figure 5-3 for fuel pump lift capabilities.
Fuel Pump Lift
Model
Pleasure Craft: 40EOZDJ/33EFOZDJ 40EFOZDJ 50EFOZDJ Commercial Craft: 40EOZCJ/33EFOZCJ 40EFOZCJ 50EFOZCJ
Pleasure Craft: 55EOZDJ/45EFOZDJ 65EOZDJ/55EFOZDJ 80EOZDJ/70EFOZDJ 99EOZDJ/80EFOZDJ 125EOZDJ/100EFOZDJ 150EOZDJ/125EFOZDJ Commercial Craft: 55EOZCJ/45EFOZCJ 65EOZCJ/55EFOZCJ 80EOZCJ/70EFOZCJ 99EOZCJ/80EFOZCJ 125EOZCJ/100EFOZCJ 150EOZCJ/125EFOZCJ
Figure 5-3 Fuel Pump Lift
m (ft.)
3 (10)
2.4 (7.9)
See Section 7 for fuel feed pump inlet connection and fuel return line connection.
5.6 Fuel Consumption
Consult the current generator set specification sheets for generator set fuel consumption rates.
TP-6862 6/1426 Section 5 Fuel System
Page 27
1
2
2
3
5
4
14
1. Electric fuel or mechanical check valve
2. Permanent supports for fuel system components
3. Fuel lift pump
4. Flexible line
Figure 5-4 Fuel System, Typical
13
12
11
5. Fuel return line (diesels only)
6. Carburetor or injection pump
7. Secondary filter
8. Primary filter
9. Flexible fuel line
Fuel Return (Diesel Only) (Below Fluid Level)
Fuel Supply
8
7
9
6
10
10. Clamp
11. Support clamp
12. Metallic line
13. Dip tube
14. Fuel tank
Check Valve (Optional) *
Baffles
* Anti-siphon protection is required for gasoline-powered units if diptube opening is below the waterline.
12 in. min.
Main Fuel Tank
Figure 5-5 Fuel System, Typical
Fuel Lift
Drain Valve
TP-6862 6/14 27Section 5 Fuel System
Page 28
Notes
TP-6862 6/1428 Section 5 Fuel System
Page 29
Section 6 Electrical System
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is turned off. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Moving parts.
6.1 AC Voltage Connections
Make AC connections to the generator set inside the junction box. Typically, the generator set connects to a ship-to-shore transfer switch that allows the use of shore/utility power when docked or generator set power when docked or at sea. The wiring then connects to a main circuit breaker box (panel board) that distributes branch circuits throughout the craft. See Section 8 for reconnection of the generator set.
6.2 Circuit Protection
The AC circuit breakers (optional) protect the wiring from the AC circuit breakers to the vessel’s distribution panel. AC circuit breakers trip when they detect a fault in the output circuit.
After correcting the fault, reset the AC circuit breaker(s) by placing them in the ON position. Restart the unit. Do not start the unit under load. See Figure 6-1 and Figure 6-2 for AC circuit breaker ratings. The unit’s voltage configuration determines the circuit breaker selection.
6.2.1 Circuit Breaker Consideratio ns
Mounting location. Mount the circuit breakers in the
generator set’s junction box. See Section 6.2.2.
Sizing. Use the generator set voltage/frequency configuration to determine the circuit breaker amperage. If the generator set voltage configuration changes, change the circuit breaker to provide optimum protection.
For circuit breaker application and selection information, contact an authorized distributor/dealer.
Have a qualified electrician or technician install circuit breakers and reconnect the generator set. Comply with all governing standards and codes.
Max.
Amps
Figure 6-1 3-Pole AC Circuit Breaker Ratings
Vol ta ge
70 600 40EOZD(C)DJ, 33EFOZD(C)J
80 600 40EFOZD(C)J, 45EFOZD(C)J
90 480 40EFOZD(C)J, 45EFOZD(C)J
100 480 55EOZD(C)J, 45EFOZD(C)J, 50EFOZD(C)J
125 480 50EFOZD(C)J, 65EOZD(C)J, 55EFOZD(C)J
125 600 33EFOZD(C)J
150 480 80EOZD(C)J, 70EFOZD(C)J
150 600 40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J
175 480 99EOZD(C)J, 70EFOZD(C)J 80EFOZD(C)J
175 600
200 600 40EFOZD(C)J, 50EFOZD(C)J, 55EOZD(C)J
250 600
400 600
600 600
40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J,
50EFOZD(C)J, 55EOZD(C)J, 45EFOZD(C)J, 65EOZD(C)J, 55EFOZD(C)J, 125EOZD(C)J,
80EOZD(C)J, 70EFOZD(C)J, 99EOZD(C)J,
80EFOZD(C)J, 150EOZD(C)J,
100EFOZD(C)J, 125EFOZD(C)J
125EOZD(C)J 150EOZD(C)J,
100EFOZD(C)J, 125EFOZD(C)J
Model(s)
45EFOZD(C)J
100EFOZDJ(C)J
(33--150 kW Models), Listed By Amps
Note: Circuit breaker ampere rating and availability are
subject to change.
TP-6862 6/14 29Section 6 Electrical System
Page 30
Amps
63 33EFOZD(C)J
80
100
125
160
200
250
400
630
40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J,
40EFOZD(C)J, 50EFOZD(C)J, 55EOZD(C)J,
33EFOZD(C)J, 50EFOZD(C)J, 65EOZD(C)J,
40EOZD(C)J, 33EFOZD(C)J, 40EFOZD(C)J,
80EOZD(C)J, 70EFOZD(C)J
40EOZD(C)J. 40EFOZD(C)J, 50EFOZD(C)J,
55EOZD(C)J, 45EFOZD(C)J
50EFOZD(C)J, 55EOZD(C)J, 45EFOZD(C)J, 65EOZD(C)J, 55EFOZD(C)J, 125EOZD(C)J,
80EOZD(C)J, 70EFOZD(C)J, 100EFOZD(C)J,
150EOZD(C)J, 125EFOZD(C)J
125EOZD(C)J, 100EFOZD(C)J, 150EOZD(C)J,
Model(s)
45EFOZD(C)J
45EFOZD(C)J
55EFOZD(C)J
100EFOZD(C)J
125EFOZD(C)J
Figure 6-2 4-Pole AC Circuit Breaker Ratings
(33--150 kW Models), Listed By Amps
WARNING
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is turned off. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
6.2.2 Circuit Breaker Installation
1. Place the generator set master switch in the OFF position.
2. Disconnect the generator set engine starting battery, negative (--) lead first.
3. Remove the six screws from the right side junction box panel and remove the panel.
4. Install the circuit breaker on the new panel with the screws and washers. Position the ON side of the circuit breaker toward the rear of the junction box. SeeFigure6-3.
5. Attach stator leads L1, L2, and L3 to the extension leads (if supplied) or to the line side of the circuit breaker. See Figure 8-3.
Note: Insulate leads with electrical tape after
connecting extension leads to stator leads.
6. Connect the neutral connection stator leads to the L0 stud.
Note: Verify that terminal positions and previously
made line lead connections allow room for load connections to load studs.
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving parts.
7. Connect the load side of the circuit breaker to customer-supplied craft wiring. Connect the neutral lead to the L0 stud. See Figure 8-3.
8. Attach the new panel to the junction box using the original six screws. See Figure 6-3.
TP-6862 6/1430 Section 6 Electrical System
Page 31
9. Check that the generator set master switch is in the OFF position. Reconnect the generator set engine starting battery, negative (--) lead last.
1. Circuit breaker
2. Circuit breaker mounting panel
3. Load lead access panel
Figure 6-3 Circuit Breaker Mounting, Typical
TP-6862 6/14 31Section 6 Electrical System
JW250000
4. Bus
5. Hardware
6. Bus line
Page 32
6.3 Installation In Steel or Aluminum Vessels
Installation of a generator set in a vessel constructed of a material capable of conducting current (e.g., steel or aluminum) is subject to considerations not normally encountered in fiberglass or wood vessels. These differences include equipment grounding, grounding of neutral conductors, ground-fault protection, and isolation of galvanic currents.
Note: Isolated ground kits are available as options for
steel- or aluminum-hulled vessels. Consult your local dealer/distributor for more information.
The scope of these topics is too extensive to be fully discussed here. Consult your local marine authority for more information.
Before installing the generator set, check the available wiring diagrams in the operation manual to become familiar with the electrical system.
6.5 Battery
Batteries and their installation must conform to USCG Regulations 183.420 (a) through (g). Provide generator sets with batteries separate from the propulsion engine’s whenever possible. The starting/charging systems of both the generator set and the engine must have a common negative (--) ground.
USCG Regulation 183.415, Grounding, requires connection of a common conductor to each grounded cranking-motor circuit. Size the conductor to match the larger of the engine’s two battery cables. Figure 6-4 lists recommended minimum cable sizes for generator set battery connections at various generator set-to-battery distances. Connecting a common conductor to each grounded cranking motor circuit prevents the starting motor current from using alternative electrical paths should the cranking motor ground circuit be restrictedor open because of oxidation or loose hardware. Alternative electrical paths include metallic fuel lines that can pose a hazard. See Section 7 for locations of the battery connections to the generator set.
6.4 Installation Regulations
The U.S. Coast Guard governs generator set installation in U.S. pleasurecraft and commercial vessels. Refer to the applicable regulations below:
U.S. Pleasurecraft Installation Regulations
Title 33CFR, Chapter I, U.S. Coast Guard, Part 183
1. Subpart I—Electrical Equipment
2. Subpart J—Fuel Systems
U.S. Commercial Vessel Installation Regulations
Title 46CFR, Chapter I, U.S. Coast Guard
1. Part 111—Electrical Systems
2. Part 182—Machinery Installation
m:sc:001:001
Required Battery Cable
(Minimum)
Distance (from battery to generator set)
Battery Voltage 12V 24V 12V 24V
40--65EOZDJ/EOZCJ 33--50EFOZDJ/EFOZCJ
80--99EOZDJ/EOZCJ 70--80EFOZDJ/EFOZCJ
125--150EOZDJ/EOZCJ 100--125EFOZDJ/EFOZCJ
Figure 6-4 Battery Cable Sizing Recommendations
2.5 m (8.3 ft.) 5 m (16.4 ft.)
#0 #4 #3/0 #2
#2/0 #2 #4/0 #1/0
#2/0 #2 #4/0 #1/0
TP-6862 6/1432 Section 6 Electrical System
Page 33
Kohler Co. recommends using one 12-volt battery (or two for 24-volt systems, as the spec requires) to start the generator. See Figure 6-5 for minimum cold cranking amps (CCA) recommendations.
12-V olt Starting Battery Size CCA
at --18C(0F) or 100 Amp. Hr.
Models CCA
40EOZDJ and 33EFOZDJ 40EOZCJ and 33EFOZCJ
40EFOZDJ 40EFOZCJ 50EFOZDJ 50EFOZCJ 55EOZDJ and 45EFOZDJ 55EOZCJ and 45EFOZCJ 65EOZDJ and 55EFOZDJ 65EOZCJ and 55EFOZCJ
80EOZDJ and 70EFOZDJ 80EOZCJ and 70EFOZCJ 99EOZDJ and 80EFOZDJ 99EOZCJ and 80EFOZCJ 125EOZDJ and 100EFOZDJ 125EOZCJ and 100EFOZCJ 150EOZDJ and 125EFOZDJ 150EOZCJ and 125EFOZCJ
640
625
925
Note: Gauge senders. Gauge senders are available
for most generator sets. If using customer­supplied gauges, be sure they are compatible with generator set senders. Contact an authorized Kohlerr service distributor/dealer. Gauges and senders are available as service items from an authorized Kohlerr service distributor/dealer.
Various wiring harnesses, Y-connectors, pigtail harnesses, remote control panels, and remote annunciator panels are available.
6.8 Paralleling Generator Sets
See Section 9 for information on paralleling generator sets.
Figure 6-5 Battery Recommendations
6.6 Wiring
Use only stranded copper wire. Conform to USCG Regulations 183.425 through 183.460 for wire gauges and insulation, conductor temperature ratings, sheath stripping, conductor support and protection, conductor terminals and splices, and over-current protection (circuit breakers, fuses). Use rubber grommets and cable ties as necessary to protect and secure the wire from sharp objects, the exhaust system, and moving parts.
6.7 Remote Connection
Kohler Co. offers several remote panels for connection to the generator set. Contact your local Kohlerr distributor/dealer for detailed descriptions. Kohler Co. also offers wiring harnesses in various lengths with a connector keyed to the controller box connector. A “pigtail” harness is also offered which includes the appropriate connector on one end and has pigtails that the installer can use to connect to a customer-supplied start/stop switch or separate lights and hourmeter. Consult wiring diagrams, ADVs, and instruction sheets for connection information/details.
TP-6862 6/14 33Section 6 Electrical System
Page 34
Notes
TP-6862 6/1434 Section 6 Electrical System
Page 35
Section 7 Installation Drawings
Use the drawings in this section for installation purposes. Consult the supplier and verify that the drawings are the most current for your specifications. Installation drawings show exhaust outlet locations, fuel inlet and return connections, siphon break locations, and battery connections. See Figure 7-1 for installation drawing identification.
Model No. Drawing Page
40EOZD(C)J and 33EFOZD(C)J
open unit (sheet 1 of 2) ADV-8500A-A 36
open unit (sheet 2 of 2) ADV-8500B-A 37
with sound shield (not available on EOZCJ/ EFOZCJ models)
with radiator ADV-8505A-A 48
with electric clutch ADV-8505B-A 49
with keel cooling & dry exhaust ADV-8505C-A 50
40EFOZD(C)J 50EFOZD(C)J 55EOZD(C)J and 45EFOZD(C)J 65EOZD(C)J and 55EFOZD(C)J
open unit (sheet 1 of 2) ADV-8501A-A 39
open unit (sheet 2 of 2) ADV-8501B-A 40
with sound shield (not available on EOZCJ/ EFOZCJ models)
with radiator ADV-8505A-A 48
with electric clutch ADV-8505B-A 49
with keel cooling & dry exhaust ADV-8505C-A 50
80EOZD(C)J and 70EFOZD(C)J 99EOZD(C)J and 80EFOZD(C)J
open unit (sheet 1 of 2) ADV-8506A-B 42
open unit (sheet 2 of 2) ADV-8506B-B 43
with sound shield (not available on EOZCJ/ EFOZCJ models)
with radiator ADV-8505A-A 48
with electric clutch ADV-8505B-A 49
with keel cooling & dry exhaust ADV-8505C-A 50
125EOZD(C)J and 150EFOZD(C)J 100EOZD(C)J and 125EFOZD(C)J
open unit (sheet 1 of 2) ADV-8508A- 45
open unit (sheet 2 of 2) ADV-8508B- 46
with sound shield (not available on EOZCJ/ EFOZCJ models)
with radiator ADV-8505A-A 48
with electric clutch ADV-8505B-A 49
with keel cooling & dry exhaust ADV-8505D-A 51
ADV-8503- 38
ADV-8504- 41
ADV-8507-A 44
ADV-8509- 47
TP-6862 6/14 35Section 7 Installation Drawings
Figure 7-1 Installation Drawings
(33--150 kW Models)
Page 36
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-2 Dimension Drawing, 40EOZD(C)J & 33EFOZD(C)J (Open Unit Sheet 1 of 2)
ADV-8500A-A
TP-6862 6/1436 Section 7 Installation Drawings
Page 37
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-3 Dimension Drawing, 40EOZD(C)J & 33EFOZD(C)J (Open Unit Sheet 2 of 2)
TP-6862 6/14 37Section 7 Installation Drawings
ADV-8500B-A
Page 38
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-4 Dimension Drawing, 40EOZDJ & 33EFOZDJ (with Sound Shield)
ADV-8503-
TP-6862 6/1438 Section 7 Installation Drawings
Page 39
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-5 Dimension Drawing, 40/50EFOZD(C)J & 55/65EOZD(C)J & 45/55EFOZD(C)J (Open Unit Sheet 1 of 2)
TP-6862 6/14 39Section 7 Installation Drawings
ADV-8501A-A
Page 40
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-6 Dimension Drawing, 40/50EFOZD(C)J & 55/65EOZD(C)J & 45/55EFOZD(C)J (Open Unit Sheet 2 of 2)
ADV-8501B-A
TP-6862 6/1440 Section 7 Installation Drawings
Page 41
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-7 Dimension Drawing, 40/50EFOZDJ & 55/65EOZDJ & 45/55EFOZDJ (with Sound Shield)
TP-6862 6/14 41Section 7 Installation Drawings
ADV-8504-
Page 42
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-8 Dimension Drawing, 80/99EOZD(C)J & 70/80EFOZD(C)J (Open Unit Sheet 1 of 2)
ADV-8506A-B
TP-6862 6/1442 Section 7 Installation Drawings
Page 43
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-9 Dimension Drawing, 80/99EOZD(C)J & 70/80EFOZD(C)J (Open Unit Sheet 2 of 2)
TP-6862 6/14 43Section 7 Installation Drawings
ADV-8506B-B
Page 44
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-10 Dimension Drawing, 80/99EOZDJ & 70/80EFOZDJ (with Sound Shield)
ADV-8507-A
TP-6862 6/1444 Section 7 Installation Drawings
Page 45
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-11 Dimension Drawing, 125/150EOZD(C)J & 100/125EFOZD(C)J (Open Unit Sheet 1 of 2)
TP-6862 6/14 45Section 7 Installation Drawings
ADV-8508A-
Page 46
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-12 Dimension Drawing, 125/150EOZD(C)J & 100/125EFOZD(C)J (Open Unit Sheet 2 of 2)
ADV-8508B-
TP-6862 6/1446 Section 7 Installation Drawings
Page 47
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-13 Dimension Drawing, 125/150EOZD(C)J & 100/125EFOZD(C)J (with Sound Shield)
TP-6862 6/14 47Section 7 Installation Drawings
ADV-8509-
Page 48
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-14 Dimension Drawing, 40--150EOZD(C)J & 33--125EFOZD(C)J (with Unit-Mounted Radiator)
ADV-8505A-A
TP-6862 6/1448 Section 7 Installation Drawings
Page 49
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-15 Dimension Drawing, 40--150EOZD(C)J & 33--125EFOZD(C)J (with Electric Clutch PTO)
TP-6862 6/14 49Section 7 Installation Drawings
ADV-8505B-A
Page 50
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-16 Dimension Drawing, 40--99EOZD(C)J & 33--80EFOZD(C)J (with Keel Cooling & Dry Exhaust)
ADV-8505C-A
TP-6862 6/1450 Section 7 Installation Drawings
Page 51
NOTE: Dimensions in [ ] are inch equivalents.
Figure 7-17 Dimension Drawing, 125/150EOZD(C)J & 100/125EFOZD(C)J (with Keel Cooling & Dry Exhaust)
TP-6862 6/14 51Section 7 Installation Drawings
ADV-8505D-A
Page 52
Notes
TP-6862 6/1452 Section 7 Installation Drawings
Page 53
Section 8 Reconnection/Adjustments
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving parts.
TP-6862 6/14 53Section 8 Reconnection/Adjustments
Page 54
Electroswitch
L1
To Generator Set
L2
L1
To Generator Set
L2
2-Wire Generator Sets
2134
6578
To Load
To Shore Power
Kraus Naimler/American Solenoid
(Early Rectangular Design)
2-Wire Generator Sets
1265
348 7
To Shore Power
L1
L2
To Generator Set
L0
L1
L2
To Generator Set
L0
3-Wire Generator Sets
2134
657 8
10 9 11 12
To Load
3-Wire Generator Sets
1265
348 7
91014 13
To Shore Power
To Shore Power
To Load
Kraus Naimler/American Solenoid
(Newer Round Design)
2-Wire Generator Sets
L1
To Generator Set
L2
3241
768 5
To Load
To Shore Power
To Generator Set
Figure 8-1 Marine Manual (Ship-to-Shore) Transfer Switch
L2
L1
L0
To Load
3-Wire Generator Sets
3241
768 5
11 10 12 9
To Load
To Shore Power
TP-5399-5
TP-6862 6/1454 Section 8 Reconnection/Adjustments
Page 55
Kraus Naimler/American Solenoid
4-Wire, 3-Phase Generator Sets
L1
3241
L2
To Generator Set
L3
7685
11 10 12 9
L1
L2
To Shore Power
L3
NOTICE
Voltagereconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
Twelve-Lead Reconnection Procedure
1. Place the generator start/stop switch in the STOP position.
2. Disconnect generator set engine starting battery, negative (--) lead first.
L0
15 14 16 13
L2 L3 L0L1
To Load
L0
I-940
Figure 8-2 Marine Manual (Ship-to-Shore) Transfer
Switch, continued
8.1 Twelve-Lead Reconnection
The reconnection procedure details voltage reconnections only. If the generator set requires frequency changes, adjust the governor and voltage regulator. See the generator set service manual for information regarding frequency adjustment.
The following information illustrates the reconnection of twelve-lead generator sets. In all cases, conform to the National Electrical Code (NEC).
Reconnect the stator leads of the generator set to change output phase or voltage. Refer to the following procedure and connection schematics. Follow all safety precautions at the front of this manual and in the text during the reconnection procedure.
3. Disconnect power to battery charger, if equipped.
4. Use Figure 8-3 to determine the generator set voltage configuration. Note the original voltage and reconnect the generator set as needed. For units with current transformers, route leads through current transformers (CTs) and connect the leads according to the diagram for the desired phase and voltage.
TP-6862 6/14 55Section 8 Reconnection/Adjustments
Page 56
Figure 8-3 Generator Reconnection (ADV-5875F-R)
TP-6862 6/1456 Section 8 Reconnection/Adjustments
Page 57
Section 9 Paralleling Generator Sets
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
Introduction
Read and follow the safety precautions included in this manual. Pay attention to the decals on the equipment and follow the instructions below.
D All personnel involved in handling, site preparation,
installation, testing, operation, and maintenance should b e thoroughly familiar with the information in this manual and the customer drawings provided before working on this equipment.
D Never make interlocks inoperative or operate the
equipment with any safety barriers removed.
D Always assume that all high-voltage parts are
energized until it is certain that they are de-energized.
D Use only test equipment rated for the service
intended.
D Check interconnection diagrams and make sure
there are no potential backfeed sources.
D Never disconnect the main trip source of energized
equipment.
D Use out-of-service tags and padlocks when working
on equipment. Leave tags in place until the work is completed and the equipment is ready to be put back into service.
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving parts.
D The complete assembly arrangement determines if
the top or bottom contacts are the line side; both can be energized when the circuit breaker is removed from the compartment.
D Do not use liquid fire extinguishers or water on
electrical fires. Before extinguishing fires within the assembly, be absolutely certain that the main power source is disconnected and the main and all feeder breakers are tripped.
The Decision-Makerr 3500 generator set controller provides generator set advanced control, system monitoring, and system diagnostics for paralleling multiple generator sets.
The Decision-Maker r 3500 interfaces the generator set to other power system equipment and other network management systems using standard industry network communications.
The controller uses unique software logic to manage sophisticated functions, such as voltage regulation, synchronizing and load-sharing controls, and protective relays for paralleling up to eight generator sets.
TP-6862 6/14 57Section 9 Paralleling Generator Sets
Page 58
Decision-Makerr 3500 Controller Features Include:
D Isochronous (real and reactive) load sharing with other
Decision-Makerr 3500 equipped generator sets.
D Random first-on logic to prevent two or more
generator sets from closing to a dead bus.
D Automatic synchronizer with dead bus closing.
D Soft loading and unloading.
D Protective relay functions include:
D Loss of field D Over current D Over frequency D Over power D Over voltage D Reverse power D Under frequency D Under voltage
D Generator management allows unneeded
generators to be stopped to conserve fuel.
D Load control logic permits prioritization of supplied
loads, allowing critical load to retain power in a failure scenario.
A generator set needs to be configured and set up correctly to work in paralleling applications. This section covers:
D Paralleling Basics (see Section 9.1) D Paralleling Considerations (see Section 9.2) D Paralleling Set Up (see Section 9.3) D Paralleling Troubleshooting ( see Section 9.4,
Section 9.5, and Section 9.6)
D Generator Management Setup (see Section 9.7) D Load Add/Shed Configuration (see Section 9.8)
9.1 Paralleling Basics
9.1.2 Paralleling Functions
There are two methods of paralleling:
1. PGEN. The Decision-Makerr 3500 is a full-featured paralleling controller. It offers integrated control for synchronizing, load sharing, protective relays, generator management, and load add/shed. This functionality is performed automatically by the Decision-Makerr 3500 controller. PGEN requires an RS-485 between each of the paralleling generators for paralleling operation.
Note: If the controller loses PGEN
communications while the generator sets are operating, the Decision-Makerr 3500 controller will enter droop mode where the output frequency varies with the real load.
2. Remote Speed and Voltage Bias.The Decision-Makerr 3500 controller is also capable of accepting a speed and voltage bias from an external paralleling control. In these applications, the external paralleling control performs all of the required functionality and the Decision-Makerr 3500 controller merely provides a control interface and protective functions for the generator set.
Note: For external speed and voltage bias, the
PGEN communication’s cable should not be connected between generators.
TB13 is located inside the junction box and contains the connection points for external speed and voltage bias control and accommodates 0-- 5 volt input for active control. See the table below and the wiring diagrams in the Operation Manual for more information.
Connection
Speed Bias Negative (--) TB13-SBN
Speed Bias Positive (+) TB13-SBP
Voltage Bias Negative (--) TB13-VBN
Voltage Bias Positive (+) TB13-VBP
9.1.1 Why Parallel Generator Sets
Some reasons to parallel generator sets are:
D Redundancy D Increased power capacity D Decreased fuel consumption D Reduced chance of wet stacking/fuel on water D Increased reliability D Greater flexibility D Individual generators can be serviced in prime power
applications
Simple paralleling requires the external speed and voltage bias inputs to be enabled. Using SiteTecht, under the Synchronization Control parameter change the setting to the following:
External Bias Inputs: True
Note: For more information on SiteTecht,see
TP-6701t SiteTech Software Operation Manual.
TP-6862 6/1458 Section 9 Paralleling Generator Sets
Page 59
With the external bias enabled, the engine speed is set based on the voltage between SBP and SBN:
D Voltage < 0.5V: Engine Run Speed
D Voltage = 0.5V: 95% of Engine Run Speed
D Voltage = 2.5V: Engine Run Speed
D Voltage = 4.5V: 105% of Engine Run Speed
D Voltage > 4.5V: Engine Run Speed
With the external bias enabled, the output voltage is set based on the voltage between VBP and VBN:
D Voltage < 0.5V: Voltage Regulator Average
Voltage Adjustment
D Voltage = 0.5V: 90% of Voltage Regulator
Average Voltage Adjustment
D Voltage = 2.5V: Voltage Regulator Average
Voltage Adjustment
D Voltage = 4.5V: 110% of Voltage Regulator
Average Voltage Adjustment
D Voltage > 4.5V: Voltage Regulator Average
Voltage Adjustment
The Decision-Makerr 3500 controller reads the voltage on the speed and voltage bias inputs every 50 ms (20 times per second) and passes the new target to the voltage regulator and the ECM.
Speed Bias is the amount that the controller is attempting to adjust the output frequency of the generator (100% bias = +5% on the engine speed,
--100% = --5% on the engine speed). The controller adjusts the Speed Bias to match frequency and phase with the paralleling bus.
Note: The Speed Bias can also be controlled by an
external device if the External Bias Inputs Enabled parameter is true, the Stand Alone Operation parameter is false, no generators are visible on the PGEN communications channel, and the voltage applied to the speed bias input is between 0.5V and 4.5V.
The External Speed Bias Input (SBP and SBN) is a voltage measuring channel capable of reading from --10V to 30V DC. The input is normally pulled down to --3.3V, but can be overridden by applying a voltage to the input.
The voltage that the controller sees on the voltage measuring channels is visible in the Analog
Voltage Input Metered Relative Value under the Programmable Analog Voltage Input 108
parameter heading. The input is polarity sensitive.
The Speed Bias is interpreted by the controller as shown in Figure 9-1.
Reactive droop should be enabled on the Decision-Makerr 3500 when paralleling with another generator set (either in simple or intelligent paralleling). The slope should be identical on all generators in the paralleling system (the default is
1.0%). Reactive droop can be configured using either SiteTecht or the User Interface (UI) at the controller: Using SiteTecht, under the Reactive Power Load Sharing parameter. Using the UI , under the
Generator Info -> Voltage Regulation Menu and Generator Info -> Paralleling Operation -> Sharing Setup Menus.
Note: Non-ECM engines will require an electronic
governor (Woodward APECs) and an appropriate Kohler governor calibration in order to permit speed adjustment.
Range: -100.00% – 100.00% Default: 0.00% **Not Writable**
Figure 9-1 Speed Bias
TP-6862 6/14 59Section 9 Paralleling Generator Sets
Page 60
Voltage Bias is the amount that the controller is attempting to adjust the output voltage (100% bias = +10% on the output voltage, --100% = --10% on the output voltage). The controller adjusts the voltage bias to match the generator voltage to the bus voltage.
Note: The Voltage Bias can also be controlled by
an external device if the External Bias Inputs Enabled parameter is true, the Stand Alone Operation parameter is false, no generators are visible on the PGEN communications channel, and the voltage applied to the voltage bias input is between 0.5V and 4.5V.
The External Voltage Bias Input (VBP and VBN) is a voltage measuring channel capable of reading from --10V to 30V DC. The input is normally pulled down to --3.3V, but can be overridden by applying a voltage to the input.
The voltage that the controller sees on the voltage measuring channels is visible in the Analog
Voltage Input Metered Relative Value under the Programmable Analog Voltage Input 107
parameter heading. The input is polarity sensitive.
The Voltage Bias is interpreted by the controller as shown in Figure 9-2
Synchronizing
Before a generator set can operate in parallel with another generator set, its electrical output must be synchronized (matched) to the power source it will parallel. The parameters that must be matched are:
D Frequency D Phase Angle D Voltage D Phase Rotation
The synchronizer will issue a breaker close command when the frequency difference, phase angle, and voltage difference are within an acceptable range and the phase rotation matches.
For PGEN paralleling, the synchronizing is handled within the Decision-Makerr 3500 controller.
For Remote Speed and Voltage Bias paralleling, the synchronizing is handled by an external controller, typically supplied on switchgear.
Real (kW) Load Control
When generator sets are running in parallel (electrically connected), the load controller controls the generator sets so each generator set is supplying its proportional share of power to the load while maintaining rated frequency. This is isochronous load sharing.
Range: -100.00% – 100.00% Default: 0.00%
Figure 9-2 Voltage Bias
**Not Writable**
The load controller communicates (analog or digital) to the other load controllers and determines how much power each generator set should supply.
For PGEN paralleling, the load controller is within the Decision-Makerr 3500 controller.
For Remote Speed and Voltage Bias paralleling, the load controller is performed by an external controller, typically supplied on switchgear.
Reactive (kVAR) Control (Isolated Bus)
When generator sets are paralleled, the voltage output of each generator set must be equal. Reactive power control is needed between the generator sets to ensure that each is supplying its share of the reactive load and to minimize circulating currents. This can be done in one of two ways:
1. Active Control (Used in PGEN Paralleling and
Remote Speed and Voltage Bias Paralleling).
The reactive load controller communicates (analog or digital) to the other reactive load controllers to maintain the same proportional kVAR output while maintaining the system’s nominal voltage.
TP-6862 6/1460 Section 9 Paralleling Generator Sets
Page 61
2. Passive Control (Used in Droop Paralleling). The voltage regulators are connected in droop or cross current compensation. There is no active control from the controller.
Voltage Regulator
The voltage regulator is integral to the Decision-Makerr 3500 controller and is capable of accepting remote input for voltage adjustment. It adjusts to:
9.2 Paralleling Considerations
9.2.1 Generator Requirements
Alternator and Connections
Units to be paralleled must have the same frequency, the same number of phases, the same voltage, and the same phase rotation. The latter merely means that the voltages across the terminals must reach their maximum and minimum values in the same order. Otherwise, the magnetic forces would try to turn the rotors in opposite directions.
The pitch of the paralleled alternators needs to be the same or excessive circulating currents may occur.
Motorized Paralleling Circuit Breaker
The Decision-Makerr 3500 controller provides control of a single motor-operator breaker to selectively close on or off the bus. For motorized paralleling breakers, there are two options:
D On the generator set, pre-wired from the factory.
D Remotely mounted. Customer needs to wire to
status, trip, close, charge motor, and bus sensing. See the wiring diagram in the operation manual for more information.
Speed Control (Required for Paralleling Done Via Remote Speed and Voltage Bias Method)
D 0.5 -- 4.5 volts ±10% (values supplied outside of this
range will default the setting to nominal)
Generator Set Protection
A reverse power relay senses the direction of power flow. Each generator’s Decision-Makerr 3500 controller contains a reverse power relay. If any unit in the system has a malfunction such as a loss of fuel causing current to flow into the generator, the reverse power relay will sense the reverse power and disconnect the unit from the system. If reverse power relays are not used, units still running will drive the unit that has stopped as a motor.
9.2.2 Paralleling Controller—PGEN
Starting and Stopping Generator Set
The Decision-Makerr 3500 controller has supervisory control over paralleling. There are several methods that can be used to start and stop the generator set (consult the operation manual for more detail):
D CAN gauge
D Modbusr
D Kohler SiteTecht software
D AUTO--RUN/AUTO--OFF button
D RUN button
D Contacts 3 and 4 for remote signal
Frequency and Real (kW) Power
The Decision-Makerr 3500 controller will accept an input from the paralleling controller. This is the way the paralleling controller adjusts the frequency and controls the power output of the generator set.
The Decision-Makerr 3500 controller has the ability to accept a remote speed adjust input of:
D 0.5 -- 4.5 volts ±5% (values supplied outside of this
range will default the setting to nominal)
Note: Some engines may limit this speed adjust to no
more than approx. +3.5%.
Modbusr is a registered trademark of Schneider Electric.
TP-6862 6/14 61Section 9 Paralleling Generator Sets
Depending on the state of the paralleling motorized breaker, the Decision-Makerr 3500 controls the frequency or kW output of the generator set by sending a signal to the engine governor over J1939 (CAN).
D Motorized Paralleling Breaker Open. The
generator set speed (frequency) will vary with this signal. This would be the case while synchronizing.
D Motorized Paralleling Breaker Closed. If the
generator set parallel motorized breaker is closed and the generator set is operating in parallel with another power source, this signal will control the kW load provided by the generator.
Page 62
Voltage and Reactive (kVAR) Power
The Decision-Makerr 3500 controls the generator set’s output voltage.
9.3 Paralleling Set Up
9.3.1 PGEN Communication Wiring
The generator set response to the signal varies depending on the state of its paralleling motorized breaker.
D Motorized Paralleling Circuit Breaker Open. If the
motorized circuit breaker is open, the output voltage will change. This would be the case while synchronizing.
D Motorized Paralleling Circuit Breaker Closed. If
the motorized circuit breaker is closed and the generator set is operating in parallel with another power source, this signal will control the kVAR load provided by the generator.
TB12 TB12 TB12 TB12
In order to parallel two or more generator sets using PGEN, a communication wire is required. Use a Belden cable #9841 (or equivalent) shielded twisted-pair communication cable. Connect the shield to ground at one end only. Tighten the connections to 0.5 Nm (4.4 in. lbs.). The PGEN connection between the generator sets is always required when the generator sets connect to a common bus. See Figure 9-3.
Figure 9-3 Paralleling System Interconnection Diagram
PGEN connections are made on terminal block TB12. TB12 is located in the generator set junction box. See Figure 9-5 for TB12 location. See Figure 9-4 for PGEN connection locations. A small portion of the wiring diagram is shown in Figure 9-4. See the operation manual for the complete wiring diagram.
1
2
ADV-8535-A
1. PGEN (+) connection on TB12
2. PGEN (-- ) connection on TB12
1
GM86968-
1. TB12 location
Figure 9-5 TB12 Terminal Block Location
Figure 9-4 Terminal Block TB12 PGEN Connections
TP-6862 6/1462 Section 9 Paralleling Generator Sets
Page 63
9.3.2 Decision-Makerr 3500 Paralleling Sequence of Operation
Note: Sequence of operation
is for unit-mounted breakers. Additional steps for remote-mounted breakers are shown in:
Install generators
Connect circuit
breaker control and
status wiring
Connect bus sensing
Connect output leads
to the paralleling bus
Connect PGEN
communication wiring
All generators in OFF
Confirm dead bus
Start generator 1 using RUN button
Follow the instructions provided earlier in this manual.
Consult the wiring diagrams provided in the operation manual.
Consult the wiring diagrams provided in the operation manual.
Consult the wiring diagrams provided in the operation manual.
See Section 9.3.1 in this manual.
If the engine does not start, consult the operation manual for troubleshooting information.
automatically closes
to bus. The breaker
closes, reopens, and
closes again.
Generator operates
without any faults or
Generator 1 in OFF
Generator 1 in OFF
Repeat for each
generator individually
Place all generators
in AUTO and give
Generator
warnings
start signal
If breaker does not close or reopen, see Section 9.4.
If faults or warnings are displayed on the Decision-Makerr 3500 controller, see Section 9.5.
If faults or warnings are displayed on the Decision-Makerr 3500 controller or if the generator set does not function correctly, see Section 9.6.
Figure 9-6 Sequence of Operation
TP-6862 6/14 63Section 9 Paralleling Generator Sets
Page 64
9.4 Troubleshooting When Breaker Does Not Close to Bus
9.4.1 Faults Not Show n
Step Potential Cause Explanation Troubleshooting
1 PGEN
communication not operational
2 Single generator
application
3 PGEN wiring not
connected correctly
4 Baud rate
misconfigured
5 Interference The PGEN network is seeing noise which
6 Short circuit in
communication wiring
7 Intermittent
connection in PGEN wiring
8 Unable to establish
first-on lock
The controller must have seen PGEN communication with at least one other node at some time since the last power cycle event before it will close the breaker.
There is only one generator on site, but the controller is expecting to see PGEN communication. The controller supports this scenario if the controller is configured in Standalone mode. Standalone mode can be set using the standalone input to the controller or in Kohler SiteTech
PGEN communicates over an RS-485 connection. RS-485 requires that the network be connected in a daisy-chain configuration, terminated at 120 Ohms at either end of the network and that positive (B) and negative (A) polarity be maintained.
One of the controllers on the network is attempting to communicate at a different baud rate than the other controllers. This results in collisions on the communication bus and incorrect interpretation of the data.
makes it difficult for the generator controllers to communicate.
The RS-485 communication wires are short-circuited together.
Although the generator controllers can occasionally communicate, the connection is unreliable. This can be caused by a short or open circuit.
The generator is trying to close to a dead bus but it is not receiving permission from one of the other nodes to allow it to do so. This can occur if one of the other nodes has seen a node removed from the network.
t.
In Controller Config --> Communication Setup, verify the PGEN Nodes Online is at least 2. If so, continue troubleshooting at Step 8 otherwise, continue on to Step 2.
Configure a digital input to Standalone mode and assert it, or set Standalone mode in Kohler SiteT e cht. Note, Standalone mode should only be asserted if there is only one generator set at the site.
Verify wiring, all PGEN + connections should be connected with daisy-chain wire (Belden #9841 or equivalent). Verify terminations are at the end of the network. Verify that there are no unintentional or loose connections.
In Controller Config --> Communication Setup, verify that the baud rate of all generators on the network matches. Default is 57,600 baud.
Verify that PGEN network uses Belden #9841 or equivalent. Verify that the shield drain for the cable is grounded at only one end.
In Controller Config --> Communication Setup, verify the PGEN Node ID is less than 16. If not, check the PGEN wiring for short circuits. Otherwise, continue troubleshooting to Step 7.
It is not uncommon for small communications wire to not connect directly to a terminal block well. Verify there are no loose wiring connections or “whiskers” at the PGEN terminal blocks. “Fork”, “ring”, or “crow’s feet” connectors are preferred for terminal block connections.
Cycle power on all generators.
TP-6862 6/1464 Section 9 Paralleling Generator Sets
Page 65
9.4.2 Faults Shown
Step Potential Cause Explanation Troubleshooting
Fault: System Voltage Mismatch Between Generators
1 System voltage is not
equivalent
Fault: System Frequency Mismatch B etween Generators
1 System frequency is not
equivalent
Fault: Phase Connection Mismatch Between Generators
1 Phase connection is not
equivalent
Fault: Live Bus Sensed When Dead Bus Expected
1 Bus is considered to be
live
2 Bus sensing is not
connected
Fault: Close Attempt Fault: Fail to Close
1 Breaker is unable to
close
2 Trip is not removed from
the circuit breaker
3 CB trip relay is wired as
normally open
4 Incorrect wiring between
the CB trip relay and the trip coil on the breaker
5 Close is not applied to
the circuit breaker
6 Breaker is not charged The breaker is receiving the signal to close
One of the controllers on the network is configured differently than the other controllers. This will inhibit any of the generators from closing to the bus.
One of the controllers on the network is configured differently than the other controllers. This will inhibit any of the generators from closing to the bus.
One of the controllers on the network is configured differently than the other controllers. This will inhibit any of the generators from closing to the bus.
The controller is measuring voltage on the paralleling bus. This will inhibit the breaker from closing.
The controller may see voltage on the paralleling bus when the generator is operating and the bus sensing is disconnected.
The controller is attempting to close the circuit breaker but the breaker is not closing.
The controller is attempting to close the circuit breaker but the breaker is not closing because the trip coil is still energized.
The controller is expecting that the trip on the circuit breaker is a normally-closed contact. This is intentional as it holds a trip on the breaker if the controller is removed.
The CB trip relay is operating correctly but the trip coil on the breaker is remaining energized. This could be due to incorrect wiring between the generator controller and the circuit breaker.
The breaker trip is removed but the controller is not able to close the breaker.
but the energizing spring is not charged.
Verify the system voltage of all the generators match the requirements of the site.
Verify the system frequency of all the generators match the requirements of the site.
Verify the phase connection of all the generators match the requirements of the site.
Check bus for residual voltage (sometimes induced by large transformers or motors). Possibly, adjust the Dead Bus Threshold to accommodate the residual voltage.
Verify the bus sensing wiring is connected to the load side of the motor-operated breaker for this generator.
Watch the ready flag on the motor operator of the circuit breaker. If it indicates not ready when the engine is stopped and toggles to the ready state when the generator is trying to close the breaker, the trip coil is acting correctly. Continue at Step 5 otherwise, continue on to Step 2.
If the ready flag of the motor operator indicates ready when the engine is stopped, continue at Step 3 otherwise, continue on to Step 4.
VerifytheCBtriprelayiswiredtoholda trip on the breaker when the relay is not energized.
Verify the wiring to the circuit breaker.
Verify the wiring between the generator controller and the circuit breaker close coil. Check the close coil to ensure that it is not defective.
Verify the motor operator is receiving voltage at the appropriate contacts to allow it to wind the spring.
TP-6862 6/14 65Section 9 Paralleling Generator Sets
Page 66
Step Potential Cause Explanation Troubleshooting
Fault: Close Attempt Fault: Fail to Close (Continued)
7 Breaker is not powered The 24V electronics on the circuit breaker
require an external 24V source on a 12V generator.
8 Wiring to power is not
complete
There is no voltage to the CB close relay on this circuit breaker.
Verify the 24V input which exists on paralleling generators is receiving 24VDC in the correct polarity.
Connect the supply to the CB close relay to either 24V from wire #70 or an external 24VDC supply (with battery storage).
9 Breaker status feedback
is not valid, no bus sensing
The breaker closes but the controller does not see a change in status. The controller cannot see the bus is energized as the bus sensing is not connected correctly on any generators on the network.
Verify the wiring on the circuit breaker to ensure that it is connected correctly. Verify bus wiring for all nodes. Verify the generator output is connected to the line side of the generator breaker.
Fault: CB Status Warning: Bus Sensing Not Connected
1 Breaker status feedback
is not valid, no bus sensing
The breaker closes but the controller does not see a change in status. The controller cannot see the bus is energized as the bus
Verify the wiring on the circuit breaker to ensure that it is connected correctly. Verify
bus wiring for this generator. sensing is not connected correctly on this generator, but another generator is connected.
Fault: CB Status
1 Breaker status feedback
is not valid
The breaker closes but the controller does not see a change in status. The controller
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. sees the bus is now live.
TP-6862 6/1466 Section 9 Paralleling Generator Sets
Page 67
9.5 Troubleshooting When Breaker Does Close to Bus
9.5.1 Faults Shown
Step Potential Cause Explanation Troubleshooting
Fault: Close Attempt Fault: Fail to Close
1 Breaker status feedback
is not valid, no bus sensing
Fault: CB Status
1 Breaker status feedback
is not connected
2 Breaker status is short
circuited
3 Breaker status feedback
is connected to the wrong contacts
4 Breaker status feedback
is connected to a latching contact
Fault: Bus Phase Rotation Mismatch
1 All of the bus sensing
wires are incorrectly connected
2 The phase connections
on the paralleling breaker are inconsistent with the generator
3 Generator sensing is
connected incorrectly
4 Breaker to bus wiring is
inconsistent
The breaker closes but the controller does not see a change in status. The controller cannot see the bus is energized as the bus sensing is not connected correctly on any generators on the network.
The breaker closes but the controller does not see a change in status. The controller sees the bus is now live.
The controller sees the breaker is closed even when it is not trying to open it.
The controller sees open status for the breaker after telling it to close, closed status after telling it to open.
The breaker status indicated that it closed when it was triggered to close but it did not indicate that it was open when the breaker opened. This fault will only occur if the bus sensing is connected correctly (the controller sees the voltage go to 0 when the breaker is triggered to open).
The bus sensing wires must be connected to phase A, phase B, and phase C of the bus. If any two connections are reversed, the controller can detect the reversed connections. This fault will only occur if all three wires are incorrectly connected.
The power leads from the generator to the paralleling circuit breaker must be connected consistently. Phase A from the generator must go to phase A of the line side of the paralleling (motor operated) breaker, phase B from the generator to phase B of the breaker and phase C of the generator to phase C of the breaker.
The controller measurement leads are not connected to the appropriate output phases or the phases are incorrectly labeled.
In applications where the bus sensing is taken from a location other than the load side of the paralleling breaker, it is possible to connect the wiring incorrectly between the load side of the output breaker and the paralleling bus.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. Verify
bus wiring for all nodes. Verify the
generator output is connected to the line
side of the generator breaker.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly.
Verify connection of the breaker status
wiring at the circuit breaker.
The controller is expecting the breaker
status to be an “A” contact. Verify the
circuit breaker auxiliary contacts are either:
11 and 14
21 and 24
31 and 34 or
41 and 44.
Verify the breaker status input to the
controller is connected directly to an
auxiliary contact on the circuit breaker.
Verify the bus metering connections.
Verify the output cable connections.
Verify the sensing leads from the controller
are connected to the appropriate output
leads from the generator. L1 should
connect to phase A, L2 to phase B, L3 to
phase C, L0 to neutral.
Verify the cable connections from the
paralleling breaker to the paralleling bus.
TP-6862 6/14 67Section 9 Paralleling Generator Sets
Page 68
Step Potential Cause Explanation Troubleshooting
Fault: Bus Voltage Amplitude Mismatch--Phase A
1 The phase A voltage of
the bus does not match the generator
The voltage measured on the bus sensing for phase A does not match the voltage measured on phase A of the generator.
Verify the bus sensing wire for phase A is
connected to phase A of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch--Phase B
1 The phase B voltage of
the bus does not match the generator
The voltage measured on the bus sensing for phase B does not match the voltage measured on phase B of the generator.
Verify the bus sensing wire for phase B is
connected to phase B of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch--Phase C
1 The phase C voltage of
the bus does not match the generator
The voltage measured on the bus sensing for phase C does not match the voltage measured on phase C of the generator.
Verify the bus sensing wire for phase C is
connected to phase C of the load side of
the paralleling breaker and there are no
breaks in the wire.
Fault: Bus Voltage Amplitude Mismatch
1 The bus metering is not
connected correctly
The bus metering is not connected to the appropriate lugs of the load side of the paralleling breaker (but there is some voltage present).
Verify the bus sensing wire for all three
phases is connected to the appropriate
lugs on the load side of the paralleling
breaker and there are no breaks in any of
the wires.
2 The generator metering
is not connected correctly
The generator metering is not connected to the output of the generator.
Verify the generator metering is sensed at
the output of the generators. A common
mistake is to connect the metering to the
center tap voltages V7, V8, V9.
Fault: Phase Angle Mismatch
1 All of the bus sensing
wires are incorrectly connected
The bus sensing wires must be connected to phase A, phase B and phase C of the bus. If any two connections are reversed,
Verify the bus metering connections.
the controller can detect the reversed connections. This fault will only occur if all three wires are incorrectly connected.
2 The phase connections
on the paralleling breaker are inconsistent with the generator
The power leads from the generator to the paralleling circuit breaker must be connected consistently. Phase A from the generator must go to phase A of the line
Verify the output cable connections.
side of the paralleling (motor operated) breaker, phase B from the generator to phase B of the breaker, and phase C of the generator to phase C of the breaker.
3 Generator sensing is
connected incorrectly
The controller measurement leads are not connected to the appropriate output phases or the phases are incorrectly labeled.
Verify sensing leads from the controller are
connected to the appropriate output leads
from the generator. L1 should connect to
phase A, L2 to phase B, L3 to phase C, L0
to neutral.
4 Breaker to bus wiring is
inconsistent
In applications where the bus sensing is taken from a location other than the load
Verify cable connections from the
paralleling breaker to the paralleling bus. side of the paralleling breaker, it is possible to connect the wiring incorrectly between the load side of the output breaker and the paralleling bus.
Fault: Bus Frequency Mismatch
1 Abnormal condition Bus frequency is not similar to generator
frequency with breaker closed.
Verify bus metering is connected correctly.
Reset the controller.
TP-6862 6/1468 Section 9 Paralleling Generator Sets
Page 69
Step Potential Cause Explanation Troubleshooting
Fault: Bus Sensing Phases A and B are Reversed
1 The bus sensing for
phase A is connected to
Phase angle from generator to bus is about 180_ and bus rotation is backwards.
Verify wiring between bus sensing inputs
and load side of paralleling breaker.
phase B of the paralleling bus and vice versa
2 The wiring between the
generator and the
Phase angle from generator to bus is about 180_ and bus rotation is backwards.
Verify wiring between generator and
paralleling breaker.
paralleling breaker is incorrect
3 The generator metering
is not connected correctly
Phase angle from generator to bus is about 180_ and bus rotation is backwards.
Verify metering connections on the
generator. L1 should connect to the
phase A output lead. L2 to phase B, L3 to
phase C, L0 to neutral.
Fault: Bus Sensing Phases B and C are Reversed
1 The bus sensing for
phase B is connected to
Phase angle from generator to bus is about
--120_ and bus rotation is backwards.
Verify wiring between bus sensing inputs
and load side of paralleling breaker.
phase C of the paralleling bus and vice versa
2 The wiring between the
generator and the
Phase angle from generator to bus is about
--120_ and bus rotation is backwards.
Verify wiring between generator and
paralleling breaker.
paralleling breaker is incorrect
3 The generator metering
is not connected correctly
Phase angle from generator to bus is about
--120_ and bus rotation is backwards.
Verify metering connections on the
generator. L1 should connect to the
phase A output lead. L2 to phase B, L3 to
phase C, L0 to neutral.
Fault: Bus Sensing Phases C and A are Reversed
1 The bus sensing for
phase A is connected to
Phase angle from generator to bus is about 120_ and bus rotation is backwards.
Verify wiring between bus sensing inputs
and load side of paralleling breaker.
phase C of the paralleling bus and vice versa
2 The wiring between the
generator and the
Phase angle from generator to bus is about 120_ and bus rotation is backwards.
Verify wiring between generator and
paralleling breaker.
paralleling breaker is incorrect
3 The generator metering
is not connected correctly
Phase angle from generator to bus is about 120_ and bus rotation is backwards.
Verify metering connections on the
generator. L1 should connect to the
phase A output lead. L2 to phase B, L3 to
phase C, L0 to neutral.
Fault: Bus Sensing Not Connected
1 No wires connect the
bus sensing on the generator to the load
Wiring not connected between load side of the paralleling breaker and the bus metering.
Verify that the bus sensing is connected.
side of the paralleling breaker
2 No leads connect the
generator output to the line side of the
The leads connecting the output of the generator to the paralleling breaker are not connected.
Verify that the leads connecting the
generator to the paralleling breaker are
connected.
paralleling breaker
3 The line circuit breaker is
open
The line circuit breaker (at the generator) is open, disconnecting the output from the
Verify that the line circuit breaker is closed.
generator from the line side of the paralleling breaker.
TP-6862 6/14 69Section 9 Paralleling Generator Sets
Page 70
Step Potential Cause Explanation Troubleshooting
Fault: Bus Sensing Connected to Generator Side of Breaker
1 Bus metering is
connected to the wrong side of the paralleling breaker
2 Breaker is closed and
status feedback is not connected
The controller sees the bus voltage always matches the generator voltage, even when the breaker contacts indicate that the breaker is open.
The controller sees that the bus voltage always matches the generator voltage, even when the breaker contacts indicate
Verify the bus metering is connected on the
load side of the paralleling breaker.
Verify the paralleling breaker control wiring
is connected correctly and the status
feedback is connected to an “A” contact. that the breaker is open.
Fault: Failure to Open
1 Wiring between CB trip
relay and trip coil is not connected
2 CB trip relay is not
receiving 24V power
The CB trip relay is releasing, but the coil in the breaker is not energizing, hence the breaker is not opening.
The CB trip relay is releasing, but there is no voltage to apply to the trip coil. This is most likely to occur when the generator has
Verify wiring to the trip coil (A4) is
connected correctly.
Verify the CB trip relay has a 24VDC
supply which is common to the CB close
relay and charge motor. a 12V battery and there is an external battery bank to operate the circuit breaker.
TP-6862 6/1470 Section 9 Paralleling Generator Sets
Page 71
9.6 Troubleshooting When Running in AUTO
9.6.1 Faults Shown
Step Potential Cause Explanation Troubleshooting
Fault: Generator Phase Rotation Mismatch
1 This generator is wired
with the opposite phase rotation of all the other generators on the paralleling bus
2 The wiring between the
paralleling breaker and the paralleling bus is incorrectly connected (two phases are reversed)
3 The generator which is
connected to the paralleling bus has the opposite phase rotation of this generator and all others
Fault: Dead Bus Sensed When Live Bus Expected
1 The wiring was not
connected between the load side of the paralleling breaker for this generator and the paralleling bus
2 The wiring was not
connected between the load side of the paralleling breaker for the other generator and the paralleling bus
Fault: Bus Voltage Out of Spec
1 The generators which
are connected to the paralleling bus are overloaded
2 Excessive cable lengths
from generators to paralleling bus
The controller has validated that the bus metering is accurate relative to this generator, if the bus phase rotation is backwards to the generator, the phase rotation must really be different.
Voltage from other generators comes into this generator as incorrect phase rotation because the wiring connections to the paralleling bus are reversed, even though the rotation of the other generators is identical to the rotation of this generator.
Voltage from the other generator comes into this generator as incorrect phase rotation because the wiring connections from the other generator to the paralleling bus are reversed, even though the rotation of the other generators is identical to the rotation of this generator.
This generator controller observed accurate bus voltage when it closed the breaker, the other generator controller did the same, but the bus of this generator is not connected to the bus of the other generator. The other generator is energizing the load, this generator cannot energize the load as there is a disconnected wiring between this generator and the paralleling bus.
This generator controller observed accurate bus voltage when it closed the breaker, the other generator controller did the same, but the bus of this generator is not connected to the bus of the other generator. The other generator is not energizing the load because it is not connected to it—this generator may be able to energize the load, but there is no simple way of telling this without connecting the output of the other generator.
When the generators which are supplying a load are overloaded, their engine speed will decrease, resulting in a decrease in output voltage. Sometimes this decrease in output voltage is sufficient to allow the generators to recover.
Although a single generator can handle the load, the cables which connect the generator to the paralleling bus are too long or too small of gauge, resulting in insufficient bus voltage.
Verify wiring between this generator and
the paralleling breaker. It may be
necessary to reverse two phases between
the generator and the paralleling breaker
and then to reverse the sensing at the bus
to match. This generator should be started
and closed to a dead bus again to validate
the changes.
Verify wiring between the paralleling
breaker and the paralleling bus. It may be
necessary to reverse the connection of two
of the leads. This generator should be
started and closed to a dead bus again to
validate the changes.
Verify wiring between the paralleling
breaker and the paralleling bus of the other
generator. It may be necessary to reverse
two phases between the paralleling breaker
and the paralleling bus on the other
generator. The other generator should be
started and closed to a dead bus again to
validate the changes.
Verify wiring between the paralleling
breaker and the paralleling bus of this
generator.
Verify wiring between the paralleling
breaker and the paralleling bus of the other
generator.
Verify the load requirements are met by a
single generator. If not, it may be
necessary to connect several low priority
loads to load shed outputs from the
paralleling generators to avoid overloading
a single generator.
Increase wire size on the generator
connection leads.
TP-6862 6/14 71Section 9 Paralleling Generator Sets
Page 72
Step Potential Cause Explanation Troubleshooting
Fault: Bus Frequency Out of Spec
1 The generators which
are connected to the paralleling bus are overloaded
When the generators which are supplying a load are overloaded, their engine speed will decrease, resulting in a decrease in output voltage. Sometimes this decrease in output voltage is sufficient to allow the generators to recover.
Verify the load requirements are met by a
single generator. If not, it may be
necessary to connect several low priority
loads to load shed outputs from the
paralleling generators to avoid overloading
a single generator.
Fault: Failure to Synchronize
1 Varying load
requirements drive generator frequency unstable
Heavy variations in the load on a generator will cause the speed of the generator to vary significantly. It can be difficult to synchronize with a generator with
Adjustment of synchronizing dwell time or
synchronizing gains may improve ability to
synchronize.
continuously changing frequency.
2 Fuel variations or other
environmental factors cause the generator frequency regulation to suffer
When the frequency regulation is impeded by atmospheric conditions or fuel quality, the ability to synchronize may be affected. Not only is the bus varying more than normal, but it is more difficult for the
It may be necessary to adjust the
synchronizing gains.
generator to control speed while synching.
3 Different sized units or
units of different fuel types
The factory synchronizing gains were calibrated for equal-sized units. The response of a large unit to a small one is
It may be necessary to adjust the
synchronizing gains.
slightly different than two small units. A diesel generator has significantly better frequency regulation than a natural gas generator.
Fault: Generator Disabled Due to High Voltage
1 Metering calibration
issue
All the generators on the paralleling bus attempt to control to the same voltage. If
Verify the controller is measuring voltage
accurately. If not, re-calibrate it. one has incorrect calibration, it may see this voltage as a much higher level than the other generators, resulting in a protective relay trip.
2 Voltage drop on
generator connection leads
If the generator is sourcing high current through too small of output leads, the voltage drop in these cables may require the generator to run at an increased
Install oversized connecting leads for the
generator to minimize voltage drop
between the generator and the paralleling
bus. voltage to supply the necessary current to the paralleling bus.
3 Attempting to operate a
generator in base-load mode while it is connected to a variable load
The speed bias and voltage bias control real and reactive load in base-load mode against a source with a nearly constant frequency and voltage (such as a utility source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and voltage will deviate to either extreme of the bias range, depending on the target load and the actual load.
Fault: Generator Disabled Due to Low Voltage
1 Metering calibration
issue
All the generators on the paralleling bus attempt to control to the same voltage. If one
Verify the controller is measuring voltage
accurately. If not, re-calibrate it. has incorrect calibration, it may see this voltage as a much lower level than the other generators, resulting in a protective relay trip.
2 Attempting to operate a
generator in base-load mode while it is connected to a variable load
The speed bias and voltage bias control real and reactive load in base-load mode against a source with a nearly constant frequency and voltage (such as a utility source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and voltage will deviate to either extreme of the bias range, depending on the target load and the actual load.
TP-6862 6/1472 Section 9 Paralleling Generator Sets
Page 73
Step Potential Cause Explanation Troubleshooting
Fault: Generator Disabled Due to High Frequency
1 Attempting to operate a
generator in base-load mode while it is connected to a variable load
The speed bias and voltage bias control real and reactive load in base-load mode against a source with a nearly constant frequency and voltage (such as a utility source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and voltage will deviate to either extreme of the bias range, depending on the target load and the actual load.
Fault: Generator Disabled Due to Low Frequency
1 Attempting to operate a
generator in base-load mode while it is connected to a variable load
The speed bias and voltage bias control real and reactive load in base-load mode against a source with a nearly constant frequency and voltage (such as a utility source). If the generator is disconnected
Install contacts in series with the base-load
mode input to the controller which are
disconnected when the utility source is
disconnected from the paralleling bus.
from the utility source, the speed and voltage will deviate to either extreme of the bias range, depending on the target load and the actual load.
Fault: Generator Disabled Due to Over Power
1 Continuous overload The generator breaker will trip to protect
the generator from damage due to
Ensure that the load is low enough for a
single generator to support it. excessive loads.
Fault: Generator Disabled Due to Reverse Power
1 Loss of fuel pressure The generator breaker will trip to prevent
generator operation. Otherwise, power could be absorbed from other generators causing potential damage to the fuel
Ensure that the generator has sufficient
fuel to support load. Connect a fuel level
sensor and place Generator Management
in Fuel Level Equalization mode. system by operating without lubrication.
2 Quick ramp rate settings The real power may overshoot when in a
real power control situation such as base
It may be necessary to adjust the load
control gains. load or system control.
3 Different sized units or
units of different fuel types.
4 Different engine speed
adjust settings
The real power may overshoot when in a real power control situation such as a load ramp or a quickly changing customer load.
Setting the Engine Speed Adjust parameter high on a generator will result in that
It may be necessary to adjust the kW load
sharing gains.
Set the engine speed adjustment similarly
on all generators. generator providing more real power than the other generators. It is possible to drive the other generators offline in light loading conditions.
Fault: Generator Disabled Due to Over Current
1 Excessive reactive load The generator breaker will trip to prevent
the generator from damage due to
Ensure that the load is low enough for a
single generator to support it. excessive stator current. Note, the controller also has a heat-model-based alternator protection algorithm (which will shut the generator down).
TP-6862 6/14 73Section 9 Paralleling Generator Sets
Page 74
Step Potential Cause Explanation Troubleshooting
Fault: Generator Disabled Due to Reverse VARs
1 Different sized units The reactive power may overshoot when in
a power control situation such as a load
It may be necessary to adjust the kVAR
load sharing gains. ramp or a quickly changing customer load.
2 Different automatic
voltage regulator settings
Setting the Engine Speed Adjust parameter high on a generator will result in that generator providing more real power than
Set the voltage regulator average voltage
adjustment to the same value on all
connected generators. the other generators. It is possible to drive the other generators offline in light loading conditions.
3 Different voltage
calibrations
Because each generator will attempt to match the target output voltage, generators
Verify the controller is measuring voltage
accurately, If not, re-calibrate. with incorrect calibration may be targeting a different output voltage, thus generating or absorbing VARs.
4 Failure in voltage
regulator or activator board
The generator breaker will trip to prevent the generator from absorbing VARs from the other generators. Providing power while
Verify the voltage regulator and activator
are ok. Perform load tests to verify.
absorbing VARs may cause that alternator to slip a pole—potentially damaging the rotor or crankshaft.
Fault: Generator Management Config Mismatch
1 Two generators that are
communicating on the network have different
Generator management will not operate if any generators on the PGEN network have different Order Selection modes.
Adjust the Order Selection mode on any
generator on the network to set the Order
Selection mode in all controllers.
Order Selection modes
2 Two generators that are
communicating on the network have different
Generator management will not operate if any generators on the PGEN network have different Stability delays.
Adjust the Order Selection mode on any
generator on the network to set the Stability
delay in all controllers.
Stability delays
3 Two generators that are
communicating on the network have different Redundancy
Generator management will not operate if any generators on the PGEN network have different Redundancy Requirements.
Adjust the Order Selection mode on any
generator on the network to set the
Redundancy Requirements in all
controllers.
Requirements
4 Two generators that are
communicating on the network have different Maximum Run Time
Generator management will not operate if any generators on the PGEN network have different Maximum Run Time Hour Difference Thresholds.
Adjust the Order Selection mode on any
generator on the network to set the
Maximum Run Time Hour Difference
Threshold in all controllers.
Hour Difference Thresholds
5 Two generators that are
communicating on the network have different Maximum Fuel Level
Generator management will not operate if any generators on the PGEN network have different Maximum Fuel Level Difference Thresholds.
Adjust the Order Selection mode on any
generator on the network to set the
Maximum Fuel Level Difference Threshold
in all controllers.
Difference Thresholds
TP-6862 6/1474 Section 9 Paralleling Generator Sets
Page 75
9.7 Generator Management Setup
Generator Management starts and stops generators based on the requirements of the load. The order in which the generators are started or stopped is determined according to one of the following:
D Manual/Fixed—The starting order of the generators
is determined at the time of configuration (It is adjustable at a later time through the menu on the controller display). The controllers automatically negotiate to ensure that no two units have the same order number -- setting the order number on one controller which conflicts with the order of another controller will cause the two controllers to exchange order numbers.
D Run Time—The starting order of the generators is
determined based on the run time hours on the generators. The generator with the most run time hours will stop first and start last. Generators which are already running are allowed to continue to run until their run time hours exceed stopped the run time hours of a stopped generator by an adjustable threshold.
Typical Applications for Fuel Level Order Selection Mode:
D Prime power applications where the generators have
individual fuel tanks and have level indication on the fuel tanks.
D Standby applications where the generators have
individual fuel tanks and have level indication on the fuel tanks.
9.7.1 Manual Order Selection Setup:
The Generator Management order should be configured so that the generator which is preferred to run has the lowest order. If the controllers are communicating over PGEN, changing the order on one generator will cause the order of the other generators to rearrange to accommodate the changed order of the one generator.
The Manual Start order can be changed through the menu on the controller d isplay at any time after the commissioning of the site is complete.
D Fuel Level—The starting order of the generators is
determined based on the fuel level remaining in the supply tanks for the generators. This option is only valid if the generators have indication of fuel.
Typical Applications for Manual Order Selection Mode:
D Units of various sizes are operated in a prime power
application and the generator management settings are optimized for minimal fuel consumption.
D An older unit is intended to accumulate most of the
run time hours because it is scheduled for replacement soon.
D Some units are quieter or located more remotely than
other units, making them more desirable to operate.
D A unit is in need of maintenance but is still
operational—this unit can be used if necessary, but should not operate more than is necessary.
Typical Applications for Run Time Order Selection Mode:
D Normal Standby Power systems without special
requirements.
9.7.2 Run Time Order Selection Setup
When Run Time Order Selection Mode is selected, Generator Management will automatically adjust the order of the connected generators based on their run time hours. The order of each should reflect the relative run time of that generator if all the generators are running or all the generators are stopped. The generator with the lowest run time will be started first.
Because a generator will not be accumulating run time when it is stopped, it is necessary to add a stability threshold to each generator which is not running or the generators will start 12 minutes after they stop (0.2 hours). This threshold is called the Generator Management Run Time Threshold.
Configure the threshold to allow the generators to equalize run time without starting and stopping each generator unnecessarily. The factory default is 12.0 hours—one of the running generators will have to have
12.0 fewer hours than the generator that is stopped before the generator will start. Once that generator is online, the generator with the most run time hours will stop.
9.7.3 Fuel Level Selection Setup
D Multiple generator system where all generators are of
identical size and age, where the generator run time should remain essentially identical.
D Prime power applications where the generators are
all of similar size.
TP-6862 6/14 75Section 9 Paralleling Generator Sets
When Run Time Order Selection Mode is selected, Generator Management will automatically adjust the order of the connected generators based on their fuel level. The order of each should reflect the relative fuel level of that generator if all the generators are running or
Page 76
all the generators are stopped. The generator with the most fuel will be started first.
Because a generator will not be consuming fuel when it is stopped, it is necessary to add a stability threshold to each generator which is not running or the generators will start as soon as 1% of the running generator’s fuel is consumed. This threshold is called the Generator Management Fuel Level Threshold.
Configure the threshold to allow the generators to equalize run time without starting and stopping each generator unnecessarily. The factory default is 10% of fuel level—one of the running generators will have to have 10% less fuel than the generator that is stopped before the generator will start. Once that generator is online, the generator with the least fuel will stop.
Generator Start Percentage
The Generator Start Percentage is the percent load on the running generators above which this generator will begin timing for the Generator Start Delay.
The default setting is 80%, this means that the other generators will have more than80% load on them before this generator will begin timing for the Generator Start Delay.
Generator Stop Percentage
The Generator Stop Percentage is the percent load on the other running generators below which this generator will begin timing for the Generator Stop Delay. The Stop percentage is calculated as if this generator was not running (the percent load on the remaining generators).
9.7.4 Paralleling Parameters
Generator Management Enabled
Set this to true if Generator Management is desired for this application
Generator Management Stability Delay
The Stability Delay is intended to ensure that all loads have returned to their normal demand before Generator Management considers stopping a generator.
All generators will be told to run until the Stability Delay has expired.
Generator Management Minimum Gens Online
The Minimum Gens Online parameter will allow the system to be configured to require at least 1 generator or to require at least 2 generators. If set to 2 Generators, the system will always keep one more generator online than is required.
Note: The default setting is 2.
Generator Management Min Load Shed Priority
The Minimum Load Shed Priority is the priority which has to be online to allow Generator management to become active (start the stability timer). This parameter should match the maximum load shed priority that is connected to an actual load.
The default setting is 6 (load priority 6 must be online before generator management becomes active).
The default setting is 60%, this means that the total load on all the running generators is low enough that all the running generators other than this one will have less than 60% load on them if they were supporting the load. The order 1 generator does not stop.
Generator Start kW
The Generator Start kW is calculated based on the Start kWs of each of the generators with a lower order number and the Start percentage for this generator. The Start kW is the total load on the bus above which this generator will begin timing for the Generator Start Delay.
Generator Stop kW
The Generator Stop kW is calculated based on the Stop kWs of each of the generators with a lower order number and the Stop percentage for this generator. The Stop kW is the total load on the bus below which this generator will begin timing for the Generator Stop Delay.
Generator Start Delay
The Generator Start Delay is the time delay in seconds for this generator to start. Because the start delay is actually a curve based on the difference between the actual kW and the start kW of this generator, the start delay is actually the time for the generator to start with a 10% overload.
Generator Stop Delay
The Generator Stop Delay is the time delay in seconds for this generator to stop. Because the stop delay is actually a curve based on the difference between the actual kW and the stop kW of this generator, the start delay is actually the time for the generator to start with 10% less load than the stop kW.
TP-6862 6/1476 Section 9 Paralleling Generator Sets
Page 77
9.8 Load Add/Shed Configuration
The Load Add/Shed configuration (also known as load control) is intended to remove non-critical loads from the generator in the event of a condition where the generator capacity is insufficient to support the load. This allows the critical loads to receive power until the load decreases or the capacity increases.
9.8.1 Load Add/Shed Setup
Generator Maximum Percent Capacity
This is the maximum load on the generator which the Load Add/Shed will automatically allow. If the load exceeds this level, no additional loads will be added until the load decreases below this level. The time to add a load increases as the load approaches this level.
Generator Overloaded Percent
This is the maximum load that the generator will support before it begins to shed load. The time to shed a load decreases as the load on the generator increases.
Load Priority Configuration
The Load Shed priorities are events which can be assigned to programmable IO. Priorities 1 and 2 are defaulted to RDO outputs 3 and 4. The priorities can be configured to outputs on the 14 relay dry contact kit or each controller on the network can be given consecutive assignments to the existing IO.
For Example: Generator #1—Load Shed Priority 1 and Load Shed Priority 2 Generator #2—Load Shed Priority 3 and Load Shed Priority 4 Generator #3—Load Shed Priority 5 and Load Shed Priority 6
Note: The load control outputs behave similarly on
each of the generators. If an output is configured for Load Shed Priority 1 on all generators, they will all shed and add at the same time.
Note: The advantage of setting a few load shed outputs
on each controller is that if one generator has the battery removed for service, the load control outputs on the other controllers are still able to shed loads (allowing the system to shed non-critical loads and continue supplying critical loads with power). The priorities that are shed may be more important than the priorities that are controlled by the disconnected generator but at least the critical loads will not lose power due to an overload condition.
TP-6862 6/14 77Section 9 Paralleling Generator Sets
Page 78
Notes
TP-6862 6/1478 Section 9 Paralleling Generator Sets
Page 79
Appendix A Generator Selection and Wattage Requirements
Consider total wattage requirements (lights, motors, appliances) when selecting a generator set or when sizing wattage usage in which available space and construction limit the size of the generator set.
Motors
When figuring generator set capacity requirements for loads that include electric motors, consider the high current demanded by the motors during startup. The inrush or starting current is typically 2--3 times higher than that required when the motor reaches normal operating speed. Allow reserve for inrush demands plus other loads which could be on the line as the electric motor starts. Use Figure 1 as a guide when selecting generator set capacity requirements involving motor loads.
Motor
HP
1/4 750 330
1/3 1000 400
1/2 1500 600
3/4 2000 750
1 3300 1100
2 4000 2000
3 5000 3000
Starting (Inrush)
Watts
Running
Watts
Figure 1 Motor Requirements
Lighting
To calculate lighting load, add the wattage of each generator set-operated lamp. Note that not all of the lights or lamps are on the generator set AC circuit; some
are DC powered by a 12-volt battery. Make sure the calculated total wattage includes only lights actually on the generator set AC circuit.
Air Conditioners
The starting characteristics of air conditioners vary greatly; one 12,000 Btu unit has, for example, lower starting requirements than a 10,000 Btu unit of another variety. When using only one unit, there is usually no starting problem, provided the lighting and appliance load is not too high when starting the unit.
Simultaneous starting of two air conditioning units, however, can present problems if the generator set capacity is marginal. Because of the variation in starting characteristics among air conditioners, this publication makes no statements regarding multiple-motor starting capabilities of the generator set covered. Consider delayed starting or use of easy-starting devices on air conditioner units whenever simultaneously starting more than one motor.
See Figure 2 for typical air conditioner requirements. Information will vary with manufacturer.
Appliances
Generator sets often furnish AC for appliances such as TV, stereo, electric water heater, etc. With the exception of the resistance-type loads such as the water heater, requirements for appliances are usually low. Do not overlook such loads when figuring total requirements. Allow reserve capacity for anticipated appliance loads to avoid overloading a generator set.
Voltage 115 230 115 230 115 230 11 5 230 230
Full load amps 9.3 4.8 9.9 5.0 11.8 6.3 16.3 8.0 11. 6
Rated load amps 7.7 4.0 7.0 3.5 8.9 4.8 13.0 6.2 10.2
Locked rotor amps 34.0 20.0 40.0 20.0 50.0 31.0 75.0 36.0 56.0
Starting (inrush) watts 3910 4600 4600 4600 5750 7130 8630 8280 12,900
Running watts 886 920 805 805 1020 1100 1500 1430 2350
Figure 2 Typical Marine Air Conditioner Requirements, 60 Hz
TP-6862 6/14 79Appendix
Air Conditioner Size (Btu/Hr.)
7,000 9,000 12,000 16,000 24,000
Page 80
Appendix B Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC advanced digital control;
adj. adjust, adjustment ADV advertising dimensional
Ah amp-hour AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only APDC Air Pollution Control District API American Petroleum Institute approx. approximate, approximately APU Auxiliary Power Unit AQMD Air Quality Management District AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CAN controller area network CARB California Air Resources Board CAT5 Category 5 (network cable) CB circuit breaker CC crank cycle cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CSA Canadian Standards
CT current transformer Cu copper cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator
2
E
PROM, EEPROM
E, emer. emergency (power source) ECM electronic control module,
EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth)
substrate (semiconductor)
Association
Laboratories
Laboratories
e. V. (also Deutsche Industrie Normenausschuss)
electrically-erasable programmable read-only memory
engine control module
Association
Association
Agency
engineered special
exh. exhaust ext. external F Fahrenheit, female FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ftp file transfer protocol ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temp., high
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IBC International Building Code IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP internet protocol ISO International Organization for
J joule JIS Japanese Industry Standard k kilo (1000) Kkelvin kA kiloampere KB kilobyte (2 KBus Kohler communication protocol kg kilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
10
bytes)
TP-6862 6/1480 Appendix
Page 81
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
LWL low water level
sound power level, A weighted
LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
/hr. cubic meters per hour
3
m
/min. cubic meters per minute
units), male
cubic meter
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mmilliohm MOhm, Mmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second mtg. mounting MTU Motoren-und Turbinen-Union MW megawatt mW milliwatt F microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas
NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
NFPA National Fire Protection
Manufacturers Association
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter
(screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay rms root mean square rnd. round RO read only ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTDs Resistance Temperature
Detectors
RTU remote terminal unit RTV room temperature vulcanization RW read/write SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SMTP simple mail transfer protocol SN serial number SNMP simple network management
protocol SPDT single-pole, double-throw SPST single-pole, single-throw spec specification specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SMS short message service SS stainless steel std. standard stl. steel tach. tachometer TB terminal block TCP transmission control protocol TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal THD total harmonic distortion TIF telephone influence factor tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UIF user interface UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal URL uniform resource locator
(web address) US undersize, underspeed UV ultraviolet, undervoltage Vvolt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency Wwatt WCR withstand and closing rating w/ with WO write only w/o without wt. weight xfmr transformer
TP-6862 6/14 Appendix 81
Page 82
TP-6862 6/1482
Page 83
TP-6862 6/14 83
Page 84
TP-6862 6/14a
E 2013 and 2014 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...