Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts.
Record the product identificationnumbersin the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory NumberAccessory Description
Controller Identification
Record the controller description from the generator set
operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the
engine nameplate.
Appendix A Abbreviations61................................................................
TP-6810 11/13Table of Contents4
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanicalequipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthat willcause severe
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set off/reset
button to shut down the generator set.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid.Battery acid can
cause severe injury or death. Battery
acid can cause blindness and burn
skin. Always wear splashproof safety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
TP-6810 11/135Safety Precautions and Instructions
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the fuel system. A flash
fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystem mustbe
leakproof and routinely inspected.
Generator set operation.Carbon
monoxidecancausesevere
nausea, fainting, or death. Carbon
monoxide is an odorless, colorless,
tasteless, nonirritating gas that can
cause death if inhaled for even a short
time. Avoid breathing exhaust fumes
when working on or near the generator
set. Never operate the generator set
inside a building. Never operate the
generator set where exhaust gas could
seep inside or be drawn into a
potentially occupied building through
windows, air intake vents, or other
openings.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Carbonmonoxidedetectors.
Carbon monoxide can cause severe
nausea, fainting, or death. Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequatelywarnthebuilding’s
occupants of the presence of carbon
monoxide.Keep thedetectors
operational at all times. Periodically
test and replace the carbon monoxide
detectorsaccordingtothe
manufacturer’s instructions.
Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
TP-6810 11/136Safety Precautions and Instructions
Explosive fuel vapors can cause
severe injury or death.Take
additional precautions when using the
following fuels:
Propane (LP)—Adequate ventilation
is mandatory. Because propane is
heavier than air, install propane gas
detectors low in a room. Inspect the
detectors perthe manufacturer’s
instructions.
Natural Gas—Adequate ventilation is
mandatory. Because natural gas rises,
install natural gas detectors high in a
room. Inspect the detectors per the
manufacturer’s instructions.
Gas fuel leaks.Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ouncespersquareinch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Moving parts.
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodesandstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Disconnecting the electrical load.
Hazardousvoltagecancause
severe injury or death. Disconnect
the generator set from the load by
turning off the line circuit breaker or by
disconnecting the generator set output
leads from the transfer switch and
heavily taping the ends of the leads.
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not
disconnect the generator set from the
load.
Hazardous Noise
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection ofstandbyand
normal sources of supply.
CAUTION
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Welding on the generator set. Can
cause severe electrical equipment
damage.Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnectthebatterycorrectly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).Haveaqualified
electrician install the battery(ies).
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
TP-6810 11/137Safety Precautions and Instructions
Engine block heater.Hazardous
voltage can cause severe injury or
death. The engine block heater can
cause electrical shock. Remove the
engine block heater plug from the
electrical outlet before working on the
block heater electrical connections.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeed intoa utility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
WARNING
Airborne particles.
Can cause severe injury or blindness.
Wear protective goggles and clothing
when using power tools, hand tools,
or compressed air.
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
Hot Parts
WARNING
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the alternator. Hot parts
can cause severe injury or death.
Avoid touching the alternator field or
exciter armature. When shorted, the
alternator field and exciter armature
become hot enough to cause severe
burns.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
NOTICE
Electrostatic discharge damage.
Electrostaticdischarge(ESD)
damages electronic circuit boards.
Preventelectrostaticdischarge
damage by wearing an approved
grounding wrist strap when handling
electronic circuit boards or integrated
circuits. An approved grounding wrist
strap provides a high resistance (about
1 megohm), not a direct short,to
ground.
TP-6810 11/138Safety Precautions and Instructions
Introduction
This manual provides operation instructions for Model
38RCL,48RCL,and60RCLresidential/light
commercial generator sets equipped with the RDC2
generator set/transfer switch controller.
This generator set is approved for use in stationary
applications in locations served by a reliable utility
power source. Have the generator set installed by an
authorizedKohlerdistributor/dealerorservice
technician.Refer to the Installation Manual for
installation instructions.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment maintenance requirements are very
important for safe and efficient operation. Inspect the
parts often and perform required maintenance at the
prescribed intervals. Obtain service from an authorized
Kohler distributor/ dealer or service technician to keep
equipment in top condition.
Nameplate
Figure 2 shows a typical generator set nameplate.
Copy the model, serial, and specification numbers from
the nameplate into the spaces provided in the product
information section on the inside front cover of this
manual. See the service view in Section 1 for the
nameplate location.
GM12070
Figure 2 Nameplate, Typical
Figure 1 Model 48RCL Generator Set
TP-6810 11/139Introduction
List of Related Literature
Figure 3 identifies related literature available for the
generator sets covered in this manual. Only trained and
qualified personnel should install or service the
generator set.
Literature TypePart Number
Specification Sheet, 38RCLG4-214
Specification Sheet, 48RCLG4-211
Specification Sheet, 60RCLG4--233
Installation Manual, Generator SetTP-6809
Operation Manual, EngineTP-6101
Service Manual, Generator SetTP-6811
Service Manual, 38RCL Engine
Mechanical
Service Manual, 48/60RCL Engine
Mechanical
Service Manual, Engine ECM
Diagnostics
Service Manual, Alternator, 38RCLTP-6353
Service Manual, Alternator, 48/60RCLTP-6783
Parts Catalog, 38RCL EngineTP-6730
Parts Catalog, 48/60RCL EngineTP-6731
Parts Catalog, Generator SetTP-6812
Installation Instructions, Load Control
Module (LCM)
For professional advice on generator set power
requirements and conscientious service, please contact
your nearest authorized Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems Netherlands B.V.
Kristallaan 1
4761 ZC Zevenbergen
The Netherlands
Phone: (31) 168 331630
Fax:(31) 168 331631
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6810 11/1311Service Assistance
Notes
TP-6810 11/1312 Service Assistance
Section 1 Service Views
16
15
14
17
13
18
12
1
11
SERVICE SIDE
19
10
423
5
6
8
9
20
21
7
28
27
29
30
27
31
GM85088
26
ADV-8494
24
25
7
23
22
Cooling System Detail
NON-SERVICE SIDE
1. Nameplate location
2. Engine ECM and EPR (electronic fuel pressure regulator)
12. Fuel solenoid valves (two required for UL 2200)
13. Customer load lead access
14. Customer connection access panel
15. Load circuit breaker
16. Generator set master control buttons (on RDC2 controller)
22
8
21
28
29
30
27
27
31
ADV-8545
GM85088
Cooling System Detail
17. RDC2 controller
18. Cooling air inlet (remove this panel to access coolant drain)
19. Access to coolant fill
20. Oil fill (on valve cover)
21. Fan fuses
22. Battery
23. Lube oil filter
24. Oil drain valve
25. Block heater connection valve
26. Coolant drain
27. Fans (qty. 3)
28. Radiator
29. Pressure cap (engine coolant fill)
30. Coolant overflow tube
31. Coolant overflow bottle
Figure 1-2 60RCL Service Views
TP-6810 11/1314 Section 1 Service Views
Section 2 Generator Set Operation
2.1Operating Area
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystem mustbe
leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases.Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning. Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
Keep the generator set area clear. Maintain at least
0.9 m (3 ft.) of clearance on all sides of the generator
set. Verify that there are no windows, air vents, or other
openings in the building within 1.5 m (5 ft.) of the
generator set exhaust outlet in any direction.
Notice
Do not locate patios, decks, play areas, or animal
shelters near the generator set. Keep items such as
lawn furniture, toys, sports equipment, and all
combustible materials away from the generator set
exhaust outlet. Remind family members, children,
and visitors to use caution near the generator set.
2.2Prestart Checklist
To ensure continued satisfactory operation perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for obstructions that could block the
flow of cooling air. Keep the air intake area clean. Do not
leave rags, tools, or debris on or near the generator set.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Coolant Level. Check the coolant level according to the
cooling system maintenance information.
Note: Block heater damage. The block heater will fail
if the energized heater element is not immersed
in coolant. Fill the cooling system before turning
on the block heater. Run the engine until it is
warm, and refill the radiator to purge the air from
the system before energizing the block heater.
Drive Belt(s). Check the belt condition of the water
pump and battery charging alternator belt(s).
Exhaust System.Check for exhaust leaks and
blockages. Check the silencer and piping condition and
check for tight exhaust system connections.
Inspect the exhaust system components for cracks and
corrosion (exhaust manifold, exhaust pipe, exhaust
clamps, and silencer).
D Check for corroded or broken metal parts and replace
them as needed.
D Check that there are no combustible materials near
the exhaust outlet.
D Check that the exhaust outlet is unobstructed.
Generator sets connected to automatic transfer
switches start automatically during exercise periods
andpoweroutages.Somegeneratorset
components become hot when the generator set is
running and remain hot for a time after the generator
set shuts down.
TP-6810 11/1315Section 2 Generator Set Operation
Carbon Monoxide Detectors.Check for the
installation and operation of carbon monoxide (CO)
detectors on each level of any building near the
generator set.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
2.3Exercising the Generator Set
2.4.5Engine Cooldown
Operate the generator set without load every week or
every other week for 20 minutes. Perform all of the
prestart checks before starting the exercise procedure.
See Section 2.5 for instructions to set the automatic
exerciser.
2.4Generator Set Operation
2.4.1Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.2Automatic Starting and Stopping
An automatic transfer switch monitors the utility power
and signals the generator set to start when utility power
is lost. The ATS then transfers the load to the generator
set.
When utility power is restored, the transfer switch
transfers the load back to utility, runs the generator set
with no load to cool down the engine, and then stops the
generator set engine. The electric fans continue to run
for two minutes after the engine shuts down to evacuate
the engine compartment.
The engine cooldown time delay allows the engine to
run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The
engine stops before the cooldown time delay expires if
the temperature dropsbelow thecooled-down
temperature level, or if the temperature rises above the
high limit during the cooldown cycle.
The electric fans continue to run for two minutes after the
engineshutsdowntoevacuatetheengine
compartment.
If a transfer switch other than the Model RXT is used, an
additional engine cooldown time delay may be
programmed on the transfer switch. To allow the smart
engine cooldown on the RDC2 controller to operate
most efficiently, set the cooldown time on the transfer
switch controller to zero or the minimum time allowed.
Refer to the instructions provided with the transfer
switch for more information.
2.4.6Automatic Operation with Model
RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2
controller through the ATS interface board on the
transfer switch. Also see Section 2.7, Model RXT
Transfer Switch Operation.
The RDC2 controller must be in AUTO mode for
automatic transfer switch operation.
2.4.3Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.4Engine Start Crank Cycle
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an overcrank
fault. See Section 2.6.
Pressing the OFF button during the crank cycle stops
the cranking.No other buttons are acknowledged
during the crank cycle.
Automatic Start
The RDC2 controller receives utility source voltage
sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an
acceptable level, the controller starts the engine
start time delay.
2. If the utility source is not restored before the time
delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the
ATS is signaled to transfer the load to the
emergency source.
TP-6810 11/1316 Section 2 Generator Set Operation
Automatic Stop
1. Whentheutilitysourceisrestored,the
Emergency-to-Normal time delay starts.
If a Model RDT or RSB transfer switch is used, refer to
the instructions provided with the transfer switch to set a
loaded exercise at the ATS, if desired.
2. When the Emergency-to-Normal time delay
expires, the load is transferred to the utility.
3. The generator set stops.
2.4.7Automatic Operation with Model
RDT or RSB Transfer Switches
If a Kohler Model RDT or RSB transfer switch is used,
the engine start contacts from the ATS must be
connected to engine start leads 3 and 4 on the generator
set.
The RDC2 generator set controller must be in AUTO
mode to respond to remote start/stop signals from an
ATS or remote switch. Press the AUTO button on the
RDC2 controller to put the generator set into automatic
mode.
Automatic Start
The engine start contacts on the ATS close to signal the
generator set to start, and remain closed while the
generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the
generator set to stop.
2.5.1Unload ed Cycle Exercise with
Complete System Diagnostics
An unloaded cycle exercise runs the generator set
without signalling the transfer switch to transfer the
electrical load from the utility source to the generator set.
The Unloaded Cycle exercise with diagnostics is the
recommended exercise mode and is the factory-default
exercise setting.
The Unloaded Cycle exercise runs the engine for
20 minutes in the cycle shown in Figure 2-1 and
described below.
D Runs at reduced speed for 10 minutes to warm up
and exercise the engine.
D Ramps up and runs at full speed for 3 minutes.
Engine diagnostics are performed during this
full-speed portion of the cycle, which provides the
best test of engine and alternator power backup
capability. Diagnostic tests at full speed can identify
potential problems with the power output and alert the
operator before an emergency event.
D Ramps down and runs at reduced speed for
5 minutes to cool down the engine before shutting
down automatically.
2.5Exercise
The RDC2 controller can be set to automatically run the
generator set at the same time and day every week or
every other week. Exercising the generator set every
week or every two weeks is required in order to keep the
engine and alternator in good operating condition.
Three exercise modes are available: unloaded cycle,
unloaded full speed, and loaded full speed.See
Sections 2.5.1 through 2.5.3 for information about the
exercise modes. A loaded exercise can be set at the
RDC2 controller only if a Model RXT transfer switch is
connected.
Note: With the RDT and RSB transfer switches, it is
possible to have two exercise settings (one
unloaded exercise set at the generator set
controller, and another exercise set at the ATS
controller). If the exercise times overlap, the ATS
exercise setting takes priority.
3min.
1min.
Engine Speed, RPM
10 min.5 min.
Engine
Exercise
Full-Speed
Diagnostics
1min.
Cooldown
Figure 2-1 Unloaded Exercise Cycle
System Diagnostics
During the unloaded cycle exercise, the controller
monitors the following data.The controller display
indicates an unloaded exercise run during the
diagnostics, unless a fault is detected as described
below.
TP-6810 11/1317Section 2 Generator Set Operation
D ATS connection. The controller verifies that the
Model RXT ATS interface board is connected.
D Battery voltage. Battery voltage is checked before
exercise to verify engine starting capability. Battery
voltage provides a measurement of battery health. If
the controller detects low battery voltage, low battery
or low charging battery is displayed and the exercise
does not start.
generator set. To set a loaded exercise, follow the
procedure in Section 2.5.8 and select Exercise Type:
Loaded.
For a loaded exercise with a transfer switch other than a
Kohlerr Model RXT, program the exercise at the
transfer switch controller. Refer to the transfer switch
operation manual for instructions.
D Coolant level check. The coolant level is checked.
D Communication integrity tests.J1939, RBUS,
Ethernet, and USB are monitored for messages
indicating that the controller and wiring are reliable.
D Engine speed. Engine speed is measured at low
speed and full speed. An overspeed or underspeed
condition will result in a fault condition and shutdown.
D Generator output frequency and voltage.
Operating the generator at full speed allows the
RDC2 controller to check the output power for correct
voltage, frequency, and stability. When the engine is
running at full speed, the controller verifies that the
voltage and frequency are within acceptable limits. A
fault message is displayed if the voltage or frequency
is out of range.
D Oil pressure. Oil pressure is verified to ensure
proper lubrication of critical engine components.
Pressure is monitored at both low and full speeds. If
the oil pressure is low, low oil pressure is displayed
and the generator set shuts down.
2.5.2Unloaded Full-Speed Exercise
The unloaded full speed exercise runs the generator set
at full speed for 20 minutes without transferring the load.
To set an unloaded full speed exercise, follow the
procedure in Figure 2-3 and select Exercise Mode:
Unloaded Full.
2.5.4Shutdown During Exercise
The following advanced diagnostic operation applies to
RDC2 controllers with firmware versions 5.04 and
higher.
If the generator set shuts down on a fault during an
exercise, the controller will try to restart the engine. If the
engine starts, the generator set will run at full speed for
two minutes and then stop. The event history will show
Advanced Diagnostic Active. The exercise schedule is
maintained.
If the engine does not start, the shutdown message will
be displayed. Correct the fault condition and reset the
fault as described in Section 2.6.
2.5.5Power Failure During Exercise
If the utility power is lost during an unloaded exercise,
the ATStransfers to the emergency source, the exercise
is ended and the control remains in the AUTO mode.
If the utility power is lost during a loaded exercise, the
exercise is ended. The ATS remains in the emergency
position and the control goes into the AUTO mode.
The generator set continues to run and supply power to
the load for the duration of the utility power outage.
When Utility power is restored, the ATS will re-transfer to
the utility source through normal timing sequences.
2.5.6Exerciser Reset
2.5.3Loaded Full-Speed Exercise (with
RXT only)
A loaded exercise starts the generator set, ramps up to
full speed, and then transfers the electrical load from the
utility source to the generator set.The load is
transferred back to the utility source before the
generator set shuts down.
Note: With a loaded exercise, power to the building is
lost for up to 10 seconds during load transfer.
For a loaded exercise controlled by the RDC2 controller,
a Model RXT transfer switch must be connected to the
To reset the exerciser to run at a different day and/or
time or to change the exercise mode, follow the
procedure in Section 2.5.7 to change the exerciser
settings.
2.5.7Setting the Exerciser at Power-up
When power is connected to the controller, you will be
prompted to set the date, time, and exercise schedule.
1. At power--up, the date is displayed with the year
flashing. Use the up or down arrow key to step to
the current year.
TP-6810 11/1318 Section 2 Generator Set Operation
2. Press Select button to save the year and move to
the month.
2. Press the Select button to go to the main menu.
SeeFigure2-2.
3. Use the arrow and select buttons to set the month
and the day.
4. The time is displayed with the hour flashing. Use
the up or down arrow key to step to the current hour
and am or pm setting.
Note: Check the am/pm setting displayed. If pm is
displayed and you need to change it to am,
use the down arrow button to step down in
time until the correct hour and am are
displayed.
5. Press the Select button to save the hour and move
to minutes.
6. Use the up or down arrow button to change the
minutes.
7. Press Select to save the time and move to the next
screen.
8. Next Exercise is displayed. Use the up, down, and
select buttons to set the exercise time and date. Be
sure to set a time and date in the future.
3. Press the down arrow button to step to the Genset
System menu.
4. Press the Select button to enter the Genset system
menu. See Figure 2-3.
5. Use the down arrow button to step to the next
Exercise menu.
6. Press the Select button. The setting flashes to
show that it can be changed. For example, the hour
flashes to show that the hour can be changed.
7. Press the UP or Down arrow buttons to change the
setting.
8. Press the Select button to save the setting and
move to the next. For example, save the hour
setting and move to minutes.
9. Repeat steps 5 through 8 to change the next item
on the line until the desired settings are displayed.
10. Press Select to save after all settings have been
selected. Settings will stop flashing.
9. Press Select. The controller exits the exercise
menu.
10. Press the Auto button and verify that the AUTO
LED is lit. The generator set must be in automatic
mode for the exercise to run as scheduled.
Theexercisewillrunevery7daysatthesametime,
starting on the date set. To change the exerciser to run
every other week or on a different day and time, use the
following procedure.
2.5.8Changing the Exercise Setting
Set the date and time on the controller before setting the
exercise schedule. Set the exerciser to automatically
run the generator set for 20 minutes every week or every
two weeks. Follow the procedure below and see the
flowchart in Figure 2-3 to set the exercise time and date,
mode, and frequency.
Procedure to Change the Exercise Setting
1. Press the AUTO button on the controller.
11. If the generator set is connected to a Kohlerr Model
RXT transfer switch, the exercise can be changed
to a loaded exercise. Set the Exercise Mode to
loaded full speed, unloaded full speed, or unloaded
cycle as shown in Figure 2-3.
12. Set the exercise frequency (weekly or every two
weeks). Weekly exercises are recommended.
13. Press the down arrow button to step to the Return
menu. Press the Select button to return to the main
menu.
14. Check that the AUTO LED is lit. The generator set
must be in automatic mode for the exercise to run
as scheduled.
After a scheduled exercise run, the next exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Other transfer switches: For a loaded exercise with a
transfer switch other than a Kohlerr Model RXT,
program the exercise at the transfer switch controller.
Refer to the transfer switch operation manual for
instructions.
TP-6810 11/1319Section 2 Generator Set Operation
Status
Displays
Overview -- -->
1.2 h
Engine---->
Metering
Generator---->
Metering
Genset-- -->
Information
Genset-- -->
Run Time
Genset-- -->
System
ATS-- - ->
Status
ATS-- - ->
Configuration
D a t e-- -- >
and Time
Network ---->
Information
PIM---->
Status
Load---->
Control
Event Log-- -->
tp6810
Figure 2-2 RDC2 Main Menu
TP-6810 11/1320 Section 2 Generator Set Operation
Genset-- -->
System
System Voltage:
240 V
System Freq:
60 Hz
VR Voltage Adj:
240.0V
System Phase:
Single
System Battery:
12 V
Next Exercise *
HR:MN PM MM/DD/YY
Exercise Mode:
Unloaded Cycle
Exercise Freq:
Weekly
Meas. System:
English
Next Exercise
HR:MN PM MM/DD/YY
Exercise Mode:
None/Unloaded Full Sp/
Unloaded Cycle/Loaded Full SP
Exercise Freq:
Weekly/Every Other Week
See Section 2.5.8, Changing
the Exercise Setting
Contrast:
50
<-- -- Return
* If the exerciser has not been set, No Exercise Sch will be displayed.
Figure 2-3 Procedure to Set the Exerciser
TP-6810 11/1321Section 2 Generator Set Operation
tp6809
2.6Faults
Selected fault conditions are shown in Figure 2-5. Fault
conditions are classified as warnings or shutdowns. If a
fault occurs that is not listed in the table, contact an
authorized distributor/dealer for service.
the transfer switch has been lost. Check the connection
to the ATS interface board.
2.6.4Resetting the Controller after a
Fault Shutdown
If a programmable interface module (PIM) is connected
to the generator set controller, additional faults can be
activated by customer-supplied equipment.See
TT-1584, Installation Instructions for the Programmable
Interface Module, for available inputs and outputs.
2.6.1Warnings
The controller displays a fault message but the
generator set does not shut down on a warning. The
controller resets automatically after a warning condition
is corrected.
2.6.2Shutdowns
Under a fault shutdown condition, the generator set
shuts down automatically and the controller displays a
fault message. The OFF LED flashes. See Figure 2-5.
Shutdown switches (such as the low coolant level switch
or high engine temperature switch) on the generator set
will automatically reset when the problem is corrected.
However, the fault condition at the controller does not
clear until the controller is reset.
Always identify and correct the cause of a fault
shutdown before resetting the controller. Check the
fault message displayed on the controller and refer to
Figure 2-5 to identify and correct the fault condition
beforeproceeding.Contactanauthorized
distributor/dealer for service, if necessary.
Press the OFF button to reset the controller, or follow the
procedure below. See Figure 2-4.
Procedure to Reset the Controller after a Fault
Shutdown
1. Press the Select button to go to the Overview
menu.
2. Press Select again. The active fault is displayed.
3. Press Select.Confirm Clear Fault: NO is
displayed.
4. Press the Up arrow button. Confirm Clear Fault:
YES is displayed.
5. Press the Select button to enter YES and clear the
fault.
The generator set cannot be restarted until the fault
condition is corrected and the controller is reset. See
Section 2.6.4 to reset the controller after a fault
shutdown.
2.6.3ATS Communication Errors
When a Model RXT transfer switch is used, an ATS fault
indicates that the connection to the interface board on
Fault Message
Figure 2-4 Clearing a Fault
Overview -- -->
1.2 h
6. Press the Select Button to return to the overview
menu.
7. Press AUTO to put the generator set into automatic
mode.
Fault MessageConfirm Clear
Fault: NO
Press Up
arrow button.
Confirm Clear
Fault: YES
tp6810
TP-6810 11/1322 Section 2 Generator Set Operation
Warning (W) or
Fault
AC Sens LostW(1sec.)
Shutdown (SD)
SD (3 sec.)
ConditionCheck
AC Sensing Lost. In Auto mode, generator
output AC sensing is lost. Starts 10 seconds
after crank disconnect.
Warning: after 1 second if no output detected
after crank disconnect.
Shutdown: after 3 seconds if voltage was
present and then lost.
Accy PwrOver
Warning
WAccessory Power Overload. An over current
fault (short circuit) on the accessory controller
power output.
Alt Protect
Shtdwn
SDHigh generator current has been detected. The
generator set shuts down to protect the
alternator from damage caused by overheating
the windings. (38RCL only)
ATS Com ErrorWAts Communication Error. Warning is displayed
if RXT interface connection is lost. See
Section 2.6.3.
ATS PhaseRotWATS Phase Rotation Mismatch. Transfer switch
phase rotation does not match. ATS will not
transfer.
Aux InputSDAuxiliary Input. An optional customer-connected
input is closed. (Digital input from optional PIM.)
Batt Chg FltWBattery charger fault. Input to PIM from an
external battery charger (not the built-in battery
charger).
Battery Voltage
High
WEngine starting battery voltage rises above
125% of the battery voltage setting for more than
10 seconds. Inhibited during the engine crank
cycle.
Clears when the battery voltage returns to an
acceptable level.
Battery Voltage
Low
WEngine starting battery voltage falls below the
battery voltage setting (typically 12.5 volts) for
more than 90 seconds when the engine is not
running. Inhibited during the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
CAN comm
SDEngine CAN communications fault.Check wiring to ECM.
fault
Engine Coolant
Temperature
High
Engine Oil
Pressure Low
SDEngine coolant temperature exceeds the
maximum temperature for more than 5 seconds.
Function becomes active after crank disconnect.
SDThe engine ECM indicates low oil pressure for
more than 5 seconds. Function becomes active
30 seconds after crank disconnect (30 second
inhibit).
Note: The low oil pressure shutdown does not
protect against low oil level. Check the engine
oil level regularly as recommended in Section 4.
EngineSpeed
High
EngineSpeed
Low
SDEngine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
SDEngine speed drops below 85% of the normal
running speed for more than 3 seconds.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Check communication wiring between
transfer switch interface board and
generator set.
Correct the ATS connection. Refer to
the ATS Installation manual, wiring
diagrams, and labels on the transfer
switch.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Check power to ECM.
Check for blocked air inlets and
exhaust outlets.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Contact an authorized
distributor/dealer for service.
TP-6810 11/1323Section 2 Generator Set Operation
Warning (W) or
Fault
Exer Not SchWExercise Not Scheduled. No exercise has been
Shutdown (SD)
ConditionCheck
scheduled on the RDC2 controller.
See Section 2.5 for instructions to set
the exerciser.
Generator
Frequency High
Generator
Frequency Low
Generator
VoltageL1-L2
High
Generator
VoltageL1-L2
Low
Lo Crank VltWLow cranking voltage. Battery voltage falls
Locked RotorSDNo engine rotation is sensed during cranking.
MainPwrOverL
Shutdown
Not in AutoWThe generator set is not in Automatic (standby)
SDGoverned frequency exceeds 110% of the
system’s frequency setpoint for more than 10
seconds. Function becomes active 10 seconds
after engine start (10 second inhibit).
SDGoverned frequency falls below 90% of the
system frequency setting for more than
10 seconds, or 1 Hz below the system frequency
setting for more than 60 seconds.
Function becomes active 10 seconds after
engine start (10 second inhibit).
SDGenerator Voltage High. Output voltage
exceeds 120% of the system nominal voltage for
more than 2 seconds.
SDGenerator V oltage Low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
below 60% of system battery voltage for more
than 6 seconds while the starter is engaged.
Shuts down 3 seconds after the fault is detected.
SDMain power overload. An over current fault on
the 70 controller power output (short circuit).
mode. Remote start and stop commands from a
transfer switch or remote switch will be ignored.
Contact an authorized
distributor/dealer for service.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service.
Charge or replace the battery.
Check the battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Press AUTO to place the generator
set in Automatic mode, when
appropriate.
Over CrankSDThree unsuccessful starting attempts.Check the fuel supply, spark plug,
Speed Sensor
Fault
Total Power
High ShtDwn
SDEngine speed sensor has failed or engine
stalled.
SDMeasured load is greater than 102% of the
generator set power rating for more than 1
minute. (38RCL only)
and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Figure 2-5 Controller Fault Messages
TP-6810 11/1324 Section 2 Generator Set Operation
2.6.5Event Log
The event log displays up to 1000 controller faults and
notices, starting with the most recent event. Events are
numbered 1--1000, with 1 being the most recent. Each
event is displayed with the date and time of the event,
the number of the event, a code to indicate whether the
event was a warning (W), shutdown (S), or
informational notice (I), the engine hours at the time of
the event, and the event description.
2.7Model RXT Transfer Switch
Operation
The RDC2 generator set/transfer switch controller
manages automatic transfer switch (ATS) functions
when connected to a Kohlerr Model RXT transfer switch
through the ATS interface board. Refer to the Model
RXT Operation/Installation Manual for information
about the transfer switch operation.
Procedure to View Event History
1. Press Select to enter the main menu.
2. Press the down a rrow to step down to the event log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Use the up and down arrow buttons to view events.
6. Press the Select button to exit the event log.
To stop viewing the event history before the last event,
press the select button to return to the main menu.
Date MO/DA/YEAR
Event Log ---->
Press UP and Down arrow
buttons to scroll through events
time HR:MN
event number, W/S/I, engine hours
event name
2.7.1Source Availability
The Model RXT transfer switch supplies voltage
sensing data to the RDC2 controller through the ATS
interface board. If the source voltage falls below the
undervoltage dropout setting, the source is considered
to have failed. See Figure 2-7.
ItemSetting
Accuracy±5%
Undervoltage Dropout90% of Pickup
Undervoltage Pickup90% of Nominal
Figure 2-7 Voltage Sensing Parameters
The RDC2 controller also has a set of power system
LEDs below the pushbuttons. The power system LEDs
indicate which power sources are available and which
source is supplying power to the building.See
Figure 3-1.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected. They will not
operate if a Model RDT or RSB transfer switch is
used.
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours
event name
Press Select button at any time to
return to the main menu.
Event codes:
W=Warning
S = Shutdown
I = Informational Notice
tp6810
Figure 2-6 Event Log
TP-6810 11/1325Section 2 Generator Set Operation
2.7.2ATS Control Sequence of
Operation
See Figure 2-8 for time delay settings.
Preferred Source Fails:
1. The load control contact opens.
2. The engine start time delay times out.
2.7.3Time Delays
Time delays are factory-set to the values shown in
Figure 2-8. An authorized distributor/dealer can adjust
time delays using a personal computer and Kohlerr
SiteTecht software.
Time delays described in this section operate only when
the controller is connected to a Kohlerr Model RXT
transfer switch.
3. The generator set is signaled to start.
The engine start and load transfer time delays prevent
engine start and load transfer caused by brief variations
4. The generator starts and the emergency source
in the utility power source.
becomes available.
5. The normal-to-emergency time delay times out.
2.7.4ATS Load Control Relay Time
Delay
6. The transfer switch transfers to the emergency
source.
7. The load control contact time delay times out.
8. The load control contact closes.
Normal Source Returns:
1. The emergency-to-normal time delay times out.
2. The contactor transfers to the normal source.
3. The engine cooldown time delay times out.
4. The generator is signaled to stop.
Time DelaySettingDescription
Engine Start3 secondsTime delay after utility source is lost until the engine start cycle begins.
Guards against starting the generator set because of a brief change in
the utility source.
Transfer, Normal to Emergency3 secondsTime delay after emergency source becomes available until transfer to
emergency source.
Transfer, Emergency to Normal2 minutesTime delay after the utility source returns until transfer back to normal.
Ensures that the the utility source is stable before transferring from the
emergency source.
Load Control5 minutesSee Section 2.7.4. Allows delayed connection of selected loads to the
generator set to prevent simultaneous starting of large motors after
transfer to the emergency source. Recommended for delayed starting
of air conditioners.
The load control time delay allows delayed starting of
large motor loads (such as air conditioners), preventing
simultaneous starting of large motors after transfer to
the generator set. The load control time delay is fixed at
5 minutes. It is not adjustable.
The load must be connected to the load control output
on the interface board of the Model RXT transfer switch.
See the transfer switch operation and installation
manual for connection instructions.
Figure 2-8 Time Delays
TP-6810 11/1326 Section 2 Generator Set Operation
Section 3 RDC2 Controller Operation
3.1RDC2 Generator Set/Transfer
Switch Controller
Model 38 RCL, 48RCL, and 60RCL generator sets are
equipped with the RDC2 generator set/transfer switch
controller. The RDC2 controls the following power
system components:
D Model 38RCL, 48RCL, or 60RCL generator set
D Model RXT automatic transfer switch (ATS)
D Load control module (LCM) or load shed kit
D Programmable interface module (PIM)
RDC2 Controller features include:
D Two-line x 16 character backlit LCD display with
adjustable contrast
D OFF, AUTO, and RUN generator set master control
buttons
D Generator set status indicating LEDs (OFF, AUTO,
RUN)
D Up, Down, and Select buttons for navigation through
menus and adjustments
1
11
10
1. 2-line LCD display
2. Up button
3. Select button
4. Down button
5. RUN button and LED
6. Generator power available LED *
7. Generator supplying power to the building LED *
8. Utility supplying power to the building LED *
9. Utility power available LED *
10. OFF button and LED
11. AUTO button and LED
* These LEDs operate only if a Model RXT transfer switch is
connected.
6789
GM77569
2
3
4
5
D Power system indicator LEDs to show utility and
generator source status, and to show which source
(utility or generator) is supplying power to the building
3.2Controls and Indicators
Figure 3-1 illustrates the keypad, display, and indicators
on the controller’s user interface.
The Run, Off, and Auto buttons control the generator set
as described in Figure 3-2. Use the Select, Up arrow,
LEDs above the RUN, OFF, and AUTO buttons indicate
the mode of operation as shown in Figure 3-2.
and Down arrow buttons to navigate through the menus
and change settings, if necessary. See Section 2.4 for
operation instructions.
The RDC2 controller also has a set of power system
LEDs below the pushbuttons. The power system LEDs
indicate which power sources are available and which
source is supplying power to the building (based on the
position of the Model RXT transfer switch).See
Figure 3-1.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected. They will not
operate if a Model RDT or RSB transfer switch is
used.
ButtonButton Function
RUNStarts the generator set. The engine start time delay is ignored.
OFFStops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the crank cycle.
Press OFF to clear faults and reset the controller.
AUTOPlaces the generator set in Automatic (standby) mode.
Down arrow
Select
Up arrow
Use to navigate through menus and change settings. This manual contains instructions to navigate the
controller menus and adjust settings on the RDC2 controller.
Figure 3-2 Pushbutton Operation
LEDLED Operation
RUNLights when the generator set has been started locally by pressing the RUN button.
OFF
AUTOLights when the generator is in automatic (standby) mode. Generator set will respond to
Utility Power Available *Lights when utility power is available.
Building on Utility Power *Lights when the building load is connected to utility power through the RXT transfer
Generator Power Available *Lights when generator power is available.
Building on Generator Power *Lights when the building load is connected to generator power through the RXT transfer
* These LEDs operate only if a Model RXT transfer switch is connected.
Remote start and stop commands are ignored.
Lights for 2 seconds, then flashes every 2 seconds when the generator set and
controller are off. Remote start/stop commands have no effect. The exercise cycle will
not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required.
Identify and correct the fault condition before resetting the controller.
engine start and stop commands from the controller (for example, exercise start and
stop commands), an ATS, or OnCuer. Time delays operate as described in Section 2.4.
The controller is equipped with a two-line x 16 character
backlit liquid crystal diode (LCD) display with adjustable
contrast. When the generator is running, the controller
automatically scrolls through the displays shown in
Figure 3-4. When the system is in AUTO, the LCD
display scrolls through the status messages shown in
Figure 3-5.
When a fault or warning condition exists, the controller
will show the corresponding message. See Section 2.6
for more information on fault and warning messages.
Controller menus display power system information,
including status information for the engine, generator,
and optional RBUS accessories, exercise settings, and
event history.Some menus allow changes to the
controller settings. See Sections 3.6 through 3.19 for
menu diagrams.
Active Alert
The display contrast is adjustable. Navigate to the
Genset System menu and step down to the Contrast
screen. Press the Select button, and then use the up
and down arrow buttons to adjust the contrast. See
Section 3.5, Changing Settings, and Section 3.11,
Generator Set System Menu.
The display backlight turns off after about a minute of no
activity. The backlight turns on when a button is pressed
The RDC2 controller is powered by the generator set
engine starting battery and the built-in battery charger.
Note: To disconnect controller power, disconnect the
battery and the utility power to the generator set.
If controller power is disconnected and reconnected,
you will be prompted to set the time, date, and exerciser.
The first setting will flash. Press the Up and Down arrow
buttons to change the setting. Press Select to save the
setting and move on to the next. Repeat until all settings
are saved and the controller returns to the main menu.
See Section 3.5 for more detailed instructions to change
settings on the RDC2. See Section 2.5 for more detailed
instructions to set the exerciser or change the exercise
settings.
The following procedure explains how to change
settings. See Figure 3-6 for an example using the Date
and Time settings.
Note: Use caution when navigating the controller
menus and changing the settings.In some
menus, pressing the Select button can enable
editing of the controller settings. Changing some
settings to incorrect values can adversely affect
generator set operation or render the unit
inoperable.
Procedure to Change Settings
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired menu
is displayed. The Date and Time menu is used for
the example in Figure 3-6.
3.4Battery Charging
The controller includes a built-in battery charger to
maintain the engine starting battery.The RDC2
controller monitors the battery voltage and provides a
constant 14 ±2% VDC voltage and maximum 2.5 amps
to charge the battery.
The installer must connect 120 VAC/60Hz utility power
provided from the building on a breaker-protected circuit
for the built-in battery charger. See the Installation
Manual for instructions to connect the utility power for
the battery charger.
3.5Changing Settings
Some settings can be changed from the controller
keypad.The controller settings and generator set
output are factory-set and should not require field
adjustment under normal circumstances. Check and
adjust the settings and/or output when:
D The controller has been replaced.
D The voltage requires adjustment for a particular
application.
D Troubleshooting generator set problems.
3. Press the Select button to enter the selected menu.
SeeFigure3-6.
4. Press the down arrow button to step through the
parameters in the selected menu.
5. To change a setting, press the Select button. The
selected setting flashes.
6. Press the up or down arrow buttons to increase or
decrease the setting.
7. When the desired setting is shown, press Select.
The value stops flashing. If there are additional
adjustable settings on the screen, the next setting
flashes. For example, in the date menu, the year,
month, and day can be adjusted.
8. Repeat steps 5 through 7 for each setting on the
screen.
9. Press the down arrow to step to the next screen.
10. To exit, press the down arrow button until Return is
displayed. Press the Select button to exit the
menu.
11. Press the AUTO or OFF button to exit the main
menu.
Have controller setup and adjustment performed only by
an authorized Kohler distributor/dealer or authorized
representative.
Note: If no buttons are pushed, the controller exits the
menus and returns to the generator set status
display after 5 minutes.
The following sections show the RDC2 controller menus
and submenus. Use the Select button and the up and
down arrow buttons to navigate the menus as shown in
the diagrams.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings.Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
If a setting on the controller display is flashing, edit mode
has been enabled. Press the OFF or AUTO button to
exit the edit mode.
Status
Displays
Press the Up and Down arrow buttons
to move between menus.
Press OFF or AUTO to exit the menus.
Overview -- -->
1.2 h
Engine---->
Metering
Press the Select button once to bring up the main menu.
Overview is displayed. See Figure 3-7. Press the down
arrow button to step to the next menu, Engine Metering.
Use the UP and DOWN arrow buttons to step up and
down through the menus shown in Figure 3-7.
The controller will exit the main menu after 5 minutes if
no buttons are pressed.To exit the main menu
immediately, press the controller’s OFF or AUTO
button.
ATS-- - ->
Configuration *
Generator---->
Metering
Genset-- -->
Information
Genset-- -->
Run Time
Genset-- -->
System
ATS-- - ->
Status
* ATS configuration appears only if a Model RXT transfer switch is connected.
The engine metering menu displays engine status
information as shown in Figure 3-9. This menu displays
status information only. No settings can be changed
from this menu.
The generator set model number and serial numbers
are displayed. No changes are allowed from this menu.
Model and serial numbers are factory set and should not
require changes in the field, except in the event that the
controller is being replaced.A personal computer
running Kohler r SiteTecht software is required to enter
the generator set model number and serial numbers on
a replacement controller. Contact an authorized Kohler
distributor/dealer for service.
Genset ---->
Information
Genset M/N:
48RCL
3.12 Genset Run Time Menu
The data shown in Figure 3-12 are displayed.No
changes are allowed from this menu.
The Next Maintenance menu shows the number of
hours of generator set operation until maintenance is
required. The estimated date for the next scheduled
maintenance is also displayed.The maintenance
reminderintervalsarebasedontheengine
manufacturer’s recommendation for changing the oil.
Refer to Section 4, Scheduled Maintenance, for
maintenance instructions.
Afterchangingtheoilandperformingother
recommended maintenance, go to the Overview menu
to reset the maintenance timer. See Section 4.3.4 for
instructions to reset the maintenance timer.
The genset system menu displays the system
information shown in Figure 3-13. Generator sets are
factory set and should not require changesto the system
settings in the field.
A Kohler authorized distributor or dealer can adjust
these settings, if necessary. If the generator set is
reconnected to a different voltage or the system settings
require adjustment for some other reason, see Section
3.5 for instructions to enable editing and change the
system settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings.Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
Voltage Regulator (VR) Voltage Adjust
The generator set voltage is factory set and typically
does not require adjustment in the field. If voltage
adjustment is required, contact a Kohler authorized
distributor or dealer for service. Refer to the generator
set Installation Manual for instructions to adjust the
voltage.
Setting the Exerciser
Genset-- -->
System
System Voltage:
240 V
System Freq:
60 Hz
VR Voltage Adj:
240.0V
System Phase:
Three-Delta
System Battery:
12 V
Next Exercise
06:30p 15Dec2011
Exercise Mode:
Unloaded Cycle
Use the Genset System menus to set the generator set
exerciser. Refer to Section 2.5 for instructions to set the
exerciser and for more information about exercising the
generator set.
After a scheduled exercise run, the Next Exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Adjusting the Display Contrast
To adjust the display contrast, use the down arrow
button to step to the Contrast menu. Press the Select
button, and then use the up and down arrow buttons to
adjust the contrast. Press the Select button to save the
contrast setting.
ATS menus appear if a Model RXT transfer switch is
connected to the generator set. If no transfer switch is
connected, or another model ATS is connected to the
engine start connections, Remote ATS is displayed on
the ATS Status screen.
The ATS Status menu displays Model RXT transfer
switch and source information.
The voltage shown in these menus can be calibrated.
Contact an authorized distributor or dealer for service if
calibration is required.
ATS- --- >
Status
ATS Position:
Normal
Normal Status:
Not/Acceptable
Emerg. Status:
Standby
Single-phase
Voltage:
Frequency:
240V
60.0 Hz
Note: If there is no Model RXT transfer
switch connected to the generator set,
Remote ATSis displayed and the other
screens on this page do not appear.
Note: The ATS Configuration menu appears only if a
Model RXT transfer switch is connected.
Use the ATSConfiguration submenu to check the Model
RXT transfer switch system settings and time delays,
and change the settings, if necessary.
Changing ATS Configuration Settings
To enable editing, press the select button. The value
flashes to indicate that it can be changed. Press the up
and down arrow buttons to change the value. Press the
Select button to save the value shown.
Use the up and down arrow buttons to move to the next
value to be changed. Repeat the adjustment process
until all values are correct.
Press the down arrow until Return is displayed. Press
the select button to return to the main menu.
The date and time will typically be set at controller
power-up. To change the date, time, or time format
(12 hour or 24 hour), use the Date and Time menu.
See Figure 3-16.
Date and
Time
To change the date and time, press the Select button
See Figure 3-6 for instructions.
Use the networking menus to view and adjust
communication settings for systems with remote RBUS
devices such as a PIM or LCM, and for systems that use
the Kohlerr OnCuer Home Generator Management
System. RBUS is a proprietary RS-485 communication
protocol.
The Networking Information menu leads to submenus
for network and RBUS communication settings.
The Networking Status submenu contains settings for
OnCuer. See the OnCue Software Operation Manual
for information about the appropriate network settings
for OnCue.
If DHCP is enabled, IP parameters are not displayed. If
DHCP is disabled (i.e., if a static IP address is used), the
IP parameters are displayed.
To enable or disable DHCP and change the IP settings,
go to the Networking Configuration menu.See
Section 3.17.2.
The networking Configuration menu includes settings
used for communication with the Kohlerr OnCuer
Home Generator Management System.
OnCue Password
For the initial OnCue setup, you will be required to reset
the OnCue password on the RDC2 controller, and then
enter it into the OnCue software. To reset the password,
follow the instructions in Figure 3-19.
For most applications, DHCP is enabled and the IP
settings cannot be changed from the controller keypad.
If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is
required), then the IP parameters can be modified. For
applications that require static IP addresses, press and
hold the select button to enable editing, disable DHCP,
and then step to the next parameters and enter the
information.
If an error occurs while setting a parameter, an error
message is displayed and then the controller exits the
edit mode. Previous settings are preserved.
Networking-- -->
Information
Networking-- -->
Status
Networking
Configuration
Reset OnCue
Password
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial
number.
A new password is generated each time the reset
password procedure is performed. If the password is
reset after the OnCue system has been set up, the
connection will be lost. Enter the new password in
OnCue to reconnect.
HOLD
Reset OnCue
Password? No
UP arrow for YES,
Down arrow for NO.
Figure 3-19 Network Configuration Submenu
DHCP:
Enabled
<-- -- Return
Reset OnCue
Password? Yes
Press Select to enter YES
or NO as displayed. New
password is displayed for
approximately 10 seconds.
The RBUS Information menu contains settings for
remote modules that communicate with the RDC2
controller using RBUS protocol.This includes the
following optional modules:
The PIM status menu displays the status of inputs and
outputs connected to the programmable interface
module (PIM). This is a status display menu only. Input
and output settings cannot be changed from the RDC2
controller’s user interface.
A personal computer running Kohlerr SiteTecht
software is required to change the input and output
settings. Contact an authorized distributor or dealer for
service.
The Kohlerr OnCuer Home Management System can
be used to turn outputs on and off. See the OnCue
Software Operation Manual for instructions.
PIM
Status:
P I M 1-- -- >
<-- -- Return
Input 1
In/Active
Input 2
In/Active
Output 1:
In/Active
Output 2:
In/Active
Output 3:
In/Active
Output 4:
In/Active
Output 5:
In/Active
Output 6:
In/Active
<-- -- Return
Figure 3-22 Programmable Interface Module (PIM) Status Menu
The generator set may be connected to a Load Control
Module (LCM) or a Model RXT transfer switch equipped
with a Load Shed kit. The Load Control menu displays
the status of the load control inputs and outputs, and
allows a test of the load control output relays.
Generator current is displayed as a percent of the
maximum generator capacity. The load control module
adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their
priority.
For detailed information about load control operation,
refer to TT-1574, provided with the LCM kit, or TT-1609,
provided with the Load Shed kit.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
The engine and generator set may use both American
Standard and metric hardware. Use the correct size
tools to prevent rounding of the bolt heads and nuts.
See the Safety Precautions and Instructions at the
beginning of this manual before attempting to service,
repair,or operate the generator set. Have an authorized
Kohler distributor/dealer perform generator set service.
Engine Service. Perform generator set engine service
at the intervals specified by the engine operation
manual.
Moving parts.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
Generator Set Service. Perform generator set service
at the intervals specified by the generator set operation
manual.
Routine Maintenance. Refer to the following generator
set service schedule, the engine service schedule, and
the runtime hours shown on the RDC2 controller to
determine when to schedule routine maintenance.
Service generator sets that are subject to extreme
weather or dusty or dirty conditions more frequently.
Maintenance and Service Parts. Obtain maintenance
andservicepartsfromanauthorizedKohler
distributor/dealer.
TP-6810 11/1347Section 4 Scheduled Maintenance
4.2Service Schedule
Perform maintenance on each item in the service schedule at the designated intervals for the life of the generator set.
Every
OperationDaily
GENERAL MAINTENANCE
Check for fluid leaksX
Check coolant level *X
Check engine oil levelX
Check all bolts and nuts for tightness ]
Change engine oil and filter [
Check fuel system for leaks ]
Check belts and belt tensionX
Inspect wiring for cuts, abrasions, or corrosionX
Inspect vacuum lines and fittingsX
AIR INTAKE SYSTEM
Inspect and clean air cleaner element [
Replace air cleaner element [
Check air induction for leaksX
Check intake manifold for vacuum leaksX
COOLING SYSTEM
Inspect and clean radiator exterior ]
Replace engine coolant w
Inspect coolant hosesX
ELECTRICAL SYSTEM
Check battery charge and fluid level ]
Inspect electrical systemX
Clean battery cables ]
EXHAUST SYSTEM
Inspect exhaust manifold for leaksX
Inspect exhaust piping for leaksX
Check HEGO (oxygen) sensor connections and wiresX
FUEL SYSTEM
Check fuel shutoff valve for leaks and functionX
Check fuel regulator pressureX
Test fuel lines for leaksX
Inspect/drain vaporizer for oil buildupX
IGNITION SYSTEM
Check spark plug wires for cuts, abrasions, or hardeningX
Clean secondary ignition coil wiresX
Replace distributor cap and rotorX
Replace spark plugsXX
Replace spark plug wiresX
* Check engine coolant condition and protection, hoses, and clamps annually (prior to cold weather).
[ More frequent intervals may be required in dusty or dirty operating conditions.
] Seasonal or as required.
w Long-life coolant is recommended. When long-life coolant is used, the change interval is 5000 hours or 5 years. Do not mix coolant
types.
100 Hr.
XXX
Every
150 Hr.
X
XX
XX
XX
Every
400 Hr.
XX
Every
1000 Hr.
X
Every
1500 Hr.
Every
2000 Hr.AsReq’d
X
X
TP-6810 11/1348 Section 4 Scheduled Maintenance
4.3Lubrication System
4.3.1Oil Specifications
Use oil that displays the American Petroleum Institute
(API) Starburst certification mark FOR GASOLINE
ENGINES on the container. Do not use straight-weight
oils recommended for industrial or stationary engines.
CC or CD classification oils, even when labeled Heavy
Duty or For Natural Gas Engines are not acceptable.
Multi-viscosity oils are recommended.Figure 4-1
shows the recommended Society of Automotive
Engineers (SAE) viscosity designation for a given
operating temperature.
Ambient T emperatureEngine Oil Type
-- 1 8 _C(0_F) and above
Below --18_C(0_F)
Figure 4-1 Engine Oil Selection
SAE 10W-30
SAE 5W-30
4.3.3Oil Additions
Adding some oil between oil changes is normal. The
amount varies with generator set usage. Open the oil fill
cap and pour in a small amount of oil using a funnel or
other suitable pouring device. See Section 1, Service
Views, for the oil check and oil fill locations.
4.3.4Oil and Filter Ch an ge
Change the oil according to the service schedule or
before generator set storage. Change the oil more
frequently if the generator set operates under dirty,
dusty conditions. Change the oil while the engine is still
warm. See Section 1, Service Views,for oil fill, oil check,
and oil filter locations.
Dispose of all waste materials (engine oil, fuel, filter,
etc.) in an environmentally safe manner.
Note: Reset the maintenance timer on the RDC2
controller after changing the oil.
4.3.2Oil Check
Check the oil level in the crankcase every 24 hours of
operation or before the engine is started each day. Do
not check the oil level while operating the unit. Stop the
generator set and keep the generator set level to get an
accurate reading. To check the oil level, remove the
dipstick and wipe the end clean. Reinsert the dipstick
and wait at least 30 seconds. Remove the dipstick and
check the level. Maintain the oil level between the Full
and Add marks on the dipstick, as shown in Figure 4-2.
See Section 1, Service Views for the dipstick location.
Note: Do not operate the set if the oil level is below the
Add mark or above the Full mark on the dipstick.
1
1. Full mark
2. Add mark
2
TP-5586-3
Oil Change Procedure
Whenever possible, drain the oil while it is still warm.
1. Drain the oil.
a. Press the OFF button on the RDC2 generator
set controller.
b. Disconnect the power for the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the housing side panel.
e. Remove the plug from the oil drain fitting and
install a drain hose.
f. Open the oil drain valve on the engine.
g. Allow time for the engine oil to drain completely.
h. Close the oil drain valve.
i. Replace the oil drain plug.
Figure 4-2 Oil Level Check
2. Replace the oil filter.
a. Removetheoilfilterbyrotatingit
counterclockwise with an oil filter wrench.
b. Clean the contact surface of the oil filter
adapter.
c. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
TP-6810 11/1349Section 4 Scheduled Maintenance
d. Install the new oil filter following the instructions
provided with the filter.
3. Fill with oil. See Figure 4-1 for oil selection and
Figure 4-3 for oil capacity.
ModelOil Capacity , L (qt.)
38RCL, 48RCL, and 60RCL
4.7 (5.0)
Figure 4-3 Oil Capacity
4. Check for leaks.
a. Press the OFF button on the RDC2 generator
set controller.
b. Reconnect the generator set engine starting
battery, negative (--) lead last.
c. Reconnect the power for the battery charger.
d. Start the generator set and check for leaks
around the oil filter.
4.4Air Cleaner
At the interval specified in the service schedule, inspect
and clean or replace the air cleaner element. Clean the
element more frequently in dirty, dusty conditions.
Check the element for accumulated oil or dirt that could
cause poor performance.Replace a damaged air
cleaner element.Follow the procedure described
below.
Air Cleaner Service Procedure
A dry-type air cleaner silences and filters the intake air.
The air intake silencer assembly connects to the intake
manifold via a rubber hose. Refer to Figure 4-4 during
this procedure.
e. Stop the generator set and tighten the oil filter to
stop any leaks.
f. Reinstall the housing side panel.
5. Stop the generator set. Check the oil level. Add
oil, as necessary, to bring the level up to the Full
mark.
Note: Too high an oil level causes high oil
consumption and engine carbonizing. Too
low a level damages the engine.
6. Reset the maintenance timer on the RDC2.
a. In the Overview menu, step down to the Next
Maintenance screen.
b. Press the Select button.
c. Press the Up arrow button so that Reset Maint
Timer? Yes is displayed.
d. Press the Select button. The next maintenance
interval and date will be displayed.
A--253104
38RCL
60RCL
A--273699
48RCL
GM90280
Figure 4-4 Air Cleaners
1. Remove the cover from the air cleaner housing.
2. Remove the air cleaner element.
3. Examine the element and housing for damage.
Replace the element and housing if damaged.
4. Tap the element lightly against a flat surface to
dislodge loose surface dirt.Do not clean the
element in any liquid or use compressed air as
these will damage the filter element. Replace the
element and precleaner at the intervals shown in
the service schedule.
5. Wipe the cover and housing with a clean rag to
remove dirt. Make sure the sealing surfaces fit
correctly.
6. Replace the air cleaner cover.
TP-6810 11/1350 Section 4 Scheduled Maintenance
4.5Exhaust System
4.6Cooling System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystem mustbe
leakproof and routinely inspected.
Carbon monoxide detectors.Carbon monoxide can
cause severe nausea, fainting, or death. Install carbon
monoxide detectors on each level of the building. Locate the
detectors to adequately warn the building’s occupants of the
presence of carbon monoxide. Keep the detectors operational
at all times. Periodically test and replace the carbon monoxide
detectors according to the manufacturer’s instructions.
At the interval specified in the service schedule, inspect
the exhaust system components (exhaust manifold,
exhaust outlet, exhaust line, exhaust clamps, and
muffler) for cracks, leaks, and corrosion.
Exhaust System Inspection Points
D Check for corroded or broken metal parts and replace
them as needed.
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
Allow the engine to cool. Release pressure from the
cooling system before removing the pressure cap. To
release pressure, cover the pressure cap with a thick
cloth and then slowly turn the cap counterclockwise to
the first stop. Remove the cap after pressure has been
completely released and the engine has cooled. Check
the coolant level at the tank if the generator set has a
coolant recovery tank.
Note: Block heater damage. The block heater will fail
if the energized heater element is not immersed
in coolant. Fill the cooling system before turning
on the block heater. Run the engine until it is
warm and refill the radiator to purge the air from
the system before energizing the block heater.
D Check that the exhaust outlet is unobstructed.
D Check the exhaust gas color. If the exhaust is blue or
black, contact your local authorized Kohler distributor/
dealer.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
D Check that all covers and doors are undamaged, in
place, and locked.
D Check for the installation and operation of carbon
monoxide (CO) detectors on each level of any
building near the generator set.
4.6.1Checking and Filling C oolant
Maintain the coolant level in the coolant overflow bottle
between the High and Low markings. See Section 1,
Service Views, for the coolant overflow bottle location.
Note: Periodically check the coolant level by removing
the radiator’s pressure cap. Do not rely solely on
the level in the coolant overflow bottle.
Ethyleneglycol-basedlong-lifecoolantis
recommended. Use a coolant mixture of 50% long-life
coolant and 50% clean, softened water to inhibit
rust/corrosion and prevent freezing. Add fresh coolant
until the level is just below the overflow tube opening.
A coolant solution of 50% ethylene glycol-based coolant
provides freezing protection to --37C(--34F) and
overheating protection to 129C (265F). A coolant
solution with less than 50% ethylene glycol may not
provide adequate freezing and overheating protection.
A coolant solution with more than 50% ethylene glycol
can cause engine or component damage. Do not mix
long-life coolant and conventional coolants. Do not use
alcohol or methanol antifreeze or mix them with the
specified coolant.
TP-6810 11/1351Section 4 Scheduled Maintenance
4.6.2Cooling System Inspection
4.6.4Flushing and Cleaning
To prevent generator shutdown or damage because of
overheating:
D Keep the cooling air inlets clean and unobstructed
D Inspect the radiator’s exterior for obstructions and
remove dirt and foreign material with a soft brush or
cloth to avoid damaging the radiator fins.
D Check the hoses and connections for leaks and
replace any cracked, frayed, or spongy hoses.
D Check the condition and tension of the radiator water
pump belt(s).
D Check the rubber seal of the radiator’s pressure cap
and replace a cracked or deteriorated cap. Remove
dirt and other debris from the pressure cap and filler
neck. The pressure cap raises the boiling point of the
coolant, enabling higher operating temperatures. If
the cap leaks, replace it with the same rating type of
cap. Find the pressure cap rating in Figure 4-5.
ItemRating
Pressure cap97 kPa (14 psi)
Figure 4-5 Pressure Cap Rating
4.6.3Draining Cooling System
The radiator contains a coolant drain valve to drain the
cooling system. When draining the coolant, remove the
radiator’s pressure cap, which will allow the entire
system to drain and will prevent air pockets from forming
and restricting coolant passage to the block.
1. De--energize the block heater, if equipped.
For optimum protection, drain, flush, and refill the
cooling system at the interval listed in the service
schedule.
Flushing and Cleaning Procedure
1. Flush the system with clean water.
2. Drain, clean, and flush the coolant overflow bottle.
3. Refill the cooling system as instructed in
Section 4.6.5.
4.6.5Filling Cooling System
Coolant Capacity, L (qt.)
Model
38RCL15.5 (16.4)17.0 (18.0)
48RCL17.5 (18.5)19.0 (20.1)
60RCL17.5 (18.5)19.0 (20.1)
Figure 4-6 Coolant Capacity
Note: Do not add coolant to a hot engine. Adding
coolant to a hot engine can cause the cylinder
block or cylinder head to crack. Wait until engine
has cooled.
1. Close the radiator’s coolant drain valve and tighten
the hose clamps.
2. Fill the radiator with the recommended coolant
mixture of 50% ethylene glycol and 50% clean,
softened water to inhibit rust/corrosion and prevent
freezing.The coolant capacity is shown in
Figure 4-6.
Generator SetWith Block Heater
2. Remove the pressure cap to allow the entire
system to drain and prevent air pockets from
restricting coolant flow through the engine block.
3. Open the coolant drain valve and allow the system
to drain.
4. If the inside of the radiator has mineral deposits or
the used coolant contains dirt or grease, go to
Section 4.6.4, Flushing and Cleaning. If the cooling
system does not have mineral deposits, refill the
cooling system as instructed in Section 4.6.5,
Filling Cooling System.
3. Operate the engine with the radiator cap removed
until the thermostat opens and the upper radiator
hose becomes hot.
4. Stop the engine and allow it to cool.
5. Add coolant to the radiator to just below the
overflow tube on the filler neck. See Section 1,
Service Views, for the overflow tube location.
6. Replace the radiator’s pressure cap.
7. Maintain the coolant level in the coolant overflow
bottle between the High and Low markings. See
Section 1, Service Views, for the coolant overflow
bottle location.
8. Re--energize the block heater, if equipped.
TP-6810 11/1352 Section 4 Scheduled Maintenance
4.7Ignition System
Service the spark plugs at the interval specified in the
service schedule using the following procedure.
Note: Do not sandblast, wire brush, scrape, or
otherwise service spark plugs in poor
condition.Obtain a new plug for best
results.
1. Press the OFF button on the RDC2 controller.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Remove spark plug wires by grasping the spark
plug boot and turning slightly while pulling. Do not
pull the wire. Pulling on the wire rather than the
boot may damage the wire or terminal.
5. Loosen the spark plug with a ratchet and 5/8-in.
spark plug socket with a rubber insert to prevent
spark plug damage.
6. Use compressed air to remove dirt from around
each spark plug to prevent dirt particles from falling
into the combustion chamber.
7. Remove spark plugs, one at a time, and examine.
Identify a normal spark plug in good operating
condition by observing a light tan or gray deposit on
firing tip.See Figure 4-9 to evaluate engine
condition by color/condition of a problem spark plug.
8. Clean spark plugs by wiping them with a rag. File
the center electrode to keep it parallel to the side
electrode.
9. Check the spark plug gap before installing any
spark plug. See Figure 4-7 and Figure 4-8. Attain
a correct gap when the feeler (or wire) passes
between the spark plug electrode. It should pass
easily but with some resistance or drag; otherwise
adjust as necessary.
ModelSpark plug gap
38 RCL, 48RCL, and 60RCL0.9 mm (0.035 in.)
Figure 4-7 Recommended Spark Plug Gap
1
2
1-514
1. 0.9 mm (0.035 in.) gap
2. Spark plug electrodes
Figure 4-8 Spark Plug Gap Inspection
Problem/ConditionMeans of IdentificationPossible Cause/Solution
Gap-bridged spark
plug
Oil-fouled spark plugWet, black deposits on the insulator shell, bore,
Carbon-fouled spark
plug
Lead-fouled spark plug Dark gray, black, yellow, or tan deposits; or a
Pre-ignition damaged
spark plug
Overheated spark plug White or light gray insulator with small black or
Worn spark plugSeverely eroded or worn electrodes.Caused by normal wear and failure to replace
Built-up deposits and gap between electrodes
closing.
and electrodes.
Black, dry, fluffy carbon deposits on insulator
tips, exposed shell surfaces and electrodes.
glazed coating on the insulator tip.
Melted electrodes and possibly blistered
insulator. Metallic deposits on insulator suggest
internal engine damage.
gray/brown spots with bluish (burned)
appearance on electrodes.
Oil or carbon fouling. Clean and regap the spark
plug.
Excessive oil entering combustion chamber
through worn rings and pistons, excessive
clearance between valve guides and stems, or
worn or loose bearings. Replace the spark plug.
Incorrect spark plug, weak ignition, clogged air
intake, overrich fuel mixture, or excessive
no-load operation. Clean and regap the spark
plug.
Caused by highly leaded fuel. Replace the
spark plug.
Wrong type of fuel, incorrect timing or advance,
too hot a plug, burned valves, or engine
overheating. Replace the spark plug.
Engine overheating, wrong type of fuel, loose
spark plugs, too hot a plug, low fuel pressure or
incorrect ignition timing. Replace the spark plug.
spark plug at prescribed interval. Replace the
spark plug.
Figure 4-9 Engine Evaluation Using Spark Plug Condition
TP-6810 11/1353Section 4 Scheduled Maintenance
10. Use a gapping tool to gently bend the side
electrode closer to or farther from the center
electrode to set the correct gap. See Figure 4-10.
Position the side electrode directly over the center
electrode.
4.8Battery
Consultthebatterymanufacturer’sinstructions
regarding battery care and maintenance.
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
1-511
Figure 4-10 Spark Plug Gap Adjustment
11. Reinstall the spark plug.Do not bump the
electrode against the cylinder head. Rotate the
spark plug clockwise until you feel resistance.
12. Use a torque wrench to torque each spark plug to
25 Nm (18 ft. lbs.). Otherwise, hand-tighten the
spark plug until you feel resistance.
13. Use a ratchet wrench to final tighten an additional
1/4 turn. Do not overtighten, as doing so may strip
the threads or alter the electrode gap setting.
14. Check the spark plug wire connector in the boot for
accumulated dirt, grease, and other debris, and
clean as necessary.
15. Firmly push the spark plug boot onto the spark
plug.
16. Reconnect the generator set engine starting
battery, negative (--) lead last.
17. Reconnect the power for the battery charger.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with4L(1gal.)ofwaterandmixthe
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
TP-6810 11/1354 Section 4 Scheduled Maintenance
Battery short circuits. Explosion can cause severe injury
or death.Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery.Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--)
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting
the terminals together.
4.9Storage Procedure
Follow the procedure below when storing your
generator set for a long period (3 months or more).
1. Start and run the generator set until it reaches
operating temperature or about 15 minutes.
5. Keep spark plugs in their holes or seal spark plug
holes with suitable threaded metal plugs.
6. Clean the exterior of the generator set and spread a
light film of oil or silicon spray over any exposed
surfaces that may be subject to rust or corrosion.
7. Seal the air inlet, exhaust pipe, and fuel tank cap
with tape.
8. Disconnect and remove the battery. Place the
battery in a warm, dry location for the storage
period. Recharge the battery once a month to
maintain a full charge.
9. Select a well-ventilated (not humid or dusty)
location to store the generator.
10. Cover the entire unit with a dust cover.
2. Stop the generator set.
3. Change the oil and oil filter; see Section 4.3.4, Oil
and Filter Change.
Use the troubleshooting charts in this section to
diagnose and correct common problems. First check for
simple causes such as a dead engine starting battery,
loose connections, or an open circuit breaker. The
charts include a list of common problems, possible
causes of the problem, and recommended corrective
actions.
If the procedures in this manual do not explain how to
correct the problem, contact an authorized Kohler
distributor/dealer. Maintain a record of repairs and
adjustments performed on the equipment. Use the
record to help describe the problem and repairs or
adjustments made to equipment.
5.2USB Port
A USB port is located on the front of the controller. Use a
USB cable with a mini-B connector to connect the
controller to your personal computer (laptop).
Some controller settings can be adjusted using a laptop
computer with Kohlerr SiteTecht software. SiteTech
software is available to Kohler authorized distributors
and dealers.See TP-6701, SiteTe cht Software
Operation Manual, for more information.
5.4.1Load Circuit Breaker
The load circuit breaker interrupts the generator output
in the event of a fault in the wiring between the generator
and the load. If the circuit breaker trips, reduce the load
and switch the breaker back to the ON position. Refer to
the service views in Section 1 for the location of the
circuit breaker.
5.4.2Fuses
Always identify and correct the cause of a blown fuse
before restarting the generator set. Refer to Figure 5-1,
Troubleshooting Chart, for conditions that may indicate
a blown fuse. Obtain replacement parts and service
from an authorized Kohler distributor/dealer.
Fan Fuses. Three 30 amp fan fuses are located in the
fan fuse and relay box. See Section 1, Service Views,
for location.
Engine Fuses. Engine fuses are located in the engine
fuse box.
D Fuse F1, 5 amps
D Fuse F2, ECM 10 amps
D Fuse M3, battery charging alternator, 70 amps
5.3Fault Messages
The RDC2 controller displays fault messages to aid in
troubleshooting. Fault messages, descriptions, and
recommended checks are listed in Figure 2-5.
Identify and correct the cause of the fault condition.
Then reset the controller after a fault shutdown. See
Section 2.6.4.
5.4Circuit Protection
If the generator set circuit breaker trips or the fuses blow
repeatedly, contact an authorized Kohler distributor/
dealer for service.
D Fuse F4, ignition,15 amps.
D Fuse F6, starter, 20 amps.
5.4.3Controller Internal Circuit
Protection
The controller is equipped with internal circuit
protection. Press OFF to reset.
TP-6810 11/1357Section 5 Troubleshooting
5.5Generator Set Troubleshooting
Figure 5-1 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections
before replacing parts.
ProblemPossible CauseCorrective Action
The generator
set does not
crank.
The generator
set cranks but
does not start,
starts hard,
lacks power, or
operates
erratically.
No AC output.
Low output or
excessive drop
in voltage.
Generator set
stops suddenly.
Fans run after
engine shuts
down.
Battery weak or dead.Recharge or replace the battery.
Battery connections reversed or poor.Check the connections.
Blown fuse(s).Replace the fuse. Contact an authorized Kohler
Generator set is OFF.Press the RUN button to start the engine or press AUTO
Air cleaner clogged.Clean and/or replace the air cleaner.
Battery weak or dead.Recharge or replace the battery.
Battery connection poor.Clean and tighten the battery connections.
Spark plug wire connection loose.Check the spark plug wires.
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if
Fuel pressure insufficient.Check the fuel supply and valves.
Engine fuse blown.Replace the fuse. If the fuse blows again, contact an
Engine malfunction.Contact an authorized Kohler distributor/dealer.
AC circuit breaker in the OFF position.Place the circuit breaker in the ON position.
AC circuit breaker tripping because of overload. Reduce the load on the generator set.
AC circuit breaker tripping because of short
circuit.
Engine fuse blown.Replace the fuse. Contact an authorized Kohler
Generator set overloaded.Reduce the load.
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if
Outoffuel.Check fuel supply.
Overcrank shutdown.Reset the controller. If the overcrank fault occurs again,
Blown fuse(s).Replace the fuse. If the fuse blows again, contact an
Overspeed shutdown.Reset the controller. If the overspeed fault occurs again,
Generator set is OFF.Press the RUN button to start the engine or press AUTO
Remote stop command received from a remote
switch, ATS, or OnCuer.
Engine malfunction.Contact an authorized Kohler distributor/dealer.
The fans continue to run for 2 minutes after the
engine shuts down to evacuate the engine
compartment.
distributor/dealer for service if fuse blows repeatedly.
to allow remote starting.
necessary.
authorized Kohler distributor/dealer.
Contact an authorized Kohler distributor/dealer for
service.
distributor/dealer for service if fuse blows repeatedly.
necessary.
contact an authorized Kohler distributor/dealer.
authorized Kohler distributor/dealer.
contact an authorized Kohler distributor/dealer.
to allow remote starting.
Check the remote switch position.
None.
Figure 5-1 General Troubleshooting Chart
TP-6810 11/1358 Section 5 Troubleshooting
5.6Controller Troubleshooting
Figure 5-2 contains basic troubleshooting information for the RDC2 controller.
ProblemPossible CauseCorrective Action
Controller LCD
displayisoff.
Controller display
backlight is off.
Loss of
communication to
accessory modules
LCM relays do not
operate.
Date is flashing.Controller power was disconnected and then
Low or no battery voltage.Check connections.
Backlight turns off after about 1 minute with no
activity.
Bad connections.Check wiring and connections. Verify that cable
Low or no battery voltage.Check battery connections.
Bad connections.Check wiring and connections. Verify that cable
Low or no battery voltage.Check battery connections.
reconnected.
Check generator set battery. See Figure 5-1.
Backlight will turn on when a button is pressed or
the generator set starts.
size and length of run comply with the instructions in
the Installation manual.
Check generator set battery. See Figure 5-1.
size and length of run comply with the instructions in
the Installation manual.
Check generator set battery. See Figure 5-1.
Check battery connections. See Figure 5-1.
Check utility power connection for the built-in battery
charger.
Reset the time, date, and exercise schedule. See
Section 2.5.7, Setting the Exerciser at Power-Up.
Figure 5-2 RDC2 Troubleshooting Chart
TP-6810 11/1359Section 5 Troubleshooting
Notes
TP-6810 11/1360 Section 5 Troubleshooting
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
APUAuxiliary Power Unit
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CAT5Category 5 (network cable)
CBcircuit breaker
CCcrank cycle
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
exh.exhaust
ext.external
FFahrenheit, female
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
IBCInternational Building Code
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPinternet protocol
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
KBusKohler communication protocol
kgkilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6810 11/13Appendix 61
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, k kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
3
m
3
m
3
m
units), male
cubic meter
/hr.cubic meters per hour
/min.cubic meters per minute
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
Fmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RBUSRS-485 proprietary
communications
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROread only
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTDsResistance Temperature
Detectors
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SMTPsimple mail transfer protocol
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SMSshort message service
SSstainless steel
std.standard
stl.steel
tach.tachometer
TBterminal block
TCPtransmission control protocol
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
UIFuser interface
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
URLuniform resource locator
(web address)
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
WOwrite only
w/owithout
wt.weight
xfmrtransformer