Kohler 32EOZ, 27EFOZ Service Manual

Page 1
Service
Marine Generator Sets
Models:
32EOZ
27EFOZ
TP-5936 7/04d
Page 2
Page 3
Safety Precautions and Instructions I.........
Introduction i...............................
Service Assistance i.........................
Section 1 Specifications 1....................
1.1 General 1..................................
1.2 Engine 1...................................
1.3 Generator 2.................................
1.4 Service View 3..............................
Section 2 Scheduled Maintenance 5...........
2.1 General 5..................................
2.2 Lubrication System 6.........................
2.2.1 Oil Specifications 6..................
2.2.2 Oil Change 6........................
2.3 Generator Storage 6.........................
Section 3 Intake and Exhaust System 7........
3.1 Air Intake Silencer/Cleaner 7..................
3.2 Exhaust System 7...........................
3.3 Mixing Elbow 7..............................
Section 4 Fuel System 9.....................
4.1 General 9..................................
4.2 Fuel Specifications 9.........................
4.3 Fuel Filter 9.................................
4.4 Bleed the Fuel System 10......................
4.5 Fuel Solenoid 11.............................
4.6 Fuel Pump 12................................
4.7 Governor 12.................................
Section 5 Cooling System 13..................
5.1 General 13..................................
5.2 Water-Cooled Exhaust Manifold 14..............
5.3 Closed Heat Exchanger 14.....................
5.4 Check and Fill the Cooling System 14...........
5.5 Flush and Fill the Cooling System 14............
5.6 Siphon Break 15..............................
5.7 Impeller Inspection and Replacement 16.........
5.8 Anticorrosion Zinc Anode 17...................
Section 6 Controller Troubleshooting 19........
6.1 Controller 19.................................
6.2 Controller Sequence of Operation 19............
6.2.1 Start 19.............................
6.2.2 Run 20..............................
6.2.3 Stop 20..............................
6.3 Engine Safety Shutdown Switches 20...........
6.3.1 Low Oil Pressure (LOP) Shutdown 20...
6.3.2 High Water Temperature (HWT) and High Exhaust Temperature (HET) Shutdown
Switch 21............................
6.3.3 Controller Circuit Board 21.............
6.3.4 Troubleshooting 22...................
Section 7 Generator Troubleshooting 27........
7.1 General 27..................................
7.2 General Troubleshooting 27....................
7.3 Separate Excitation 28........................
7.4 PowerBoost V Voltage Regulators 28............
7.5 Voltage Regulator Adjustment 30...............
7.6 Exciter Field 31...............................
7.7 Exciter Armature 32...........................
7.8 Rectifier Module 33...........................
7.9 Rotor 33.....................................
7.10 Stator 34....................................
Section 8 Component Troubleshooting 37......
8.1 General 37..................................
8.2 Remote Panels (Optional) 39...................
Section 9 Generator Disassembly/
Reassembly 41...............................
9.1 Disassembly 41..............................
9.2 Reassembly 44...............................
Section 10 Voltage Reconnection and Wiring
Diagrams 45..................................
10.1 4-Lead Reconnection 45.......................
10.1.1 100--120-Volt Configurations 45.........
10.1.2 100--120-/200--240-Volt
Configurations 46.....................
10.1.3 200--240-Volt Configurations 46.........
10.2 12-Lead Reconnection 46.....................
10.3 Two and Three Wire Manual (Ship-to-Shore)
Transfer Switch 47............................
10.4 Four Wire Manual (Ship-to-Shore)
Transfer Switch 48............................
10.5 Generator Reconnection 48....................
10.6 Single-Phase Wiring Diagram—Schematic 50....
10.7 Single-Phase Wiring Diagram—Point-to-Point 51.
10.8 Three-Phase Wiring Diagram—Schematic 52.....
10.9 Three-Phase Wiring Diagram—Point-to-Point 53..
10.10 Remote Start Panel 54........................
10.11 Remote Start and Two-Meter Panel 54..........
10.12 Remote Start and Four-Meter Panel 55..........
Appendix A Abbreviations A-1................
Appendix B Common Hardware Application
Guidelines A-3...............................
Appendix C General Torque
Specifications A-4............................
Appendix D Common Hardware
Identification A-5.............................
Appendix E Common Hardware List A-6.......
TP-5936 7/04 Table of Contents
Page 4
Notes
TP-5936 7/04Table of Contents
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has severaltypesofsafety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury,death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury,death,or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
TP-5936 7/04 ISafety Precautions and Instructions
Page 6
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner/silencer removed.
Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the fuel system. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Wipe up spilled fuels and engine oil.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Copper tubing exhaust systems. Carbon monoxide can cause severe nausea, fainting, or death. Do not
use copper tubing in diesel exhaust systems. Sulfur in diesel exhaust causes rapid deterioration of copper tubing exhaust systems, resulting in exhaust/water leakage.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the
safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operating the generator set. Do not install the exhaust outlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft.
TP-5936 7/04II Safety Precautions and Instructions
Page 7
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels inawell-ventilatedareaawayfrom spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Donot operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Pipe sealant. Explosive fuel vapors can cause severe injury or death.
Fuel leakage can cause an explosion. Use pipe sealant on all threaded fittings to prevent fuel leakage. Use pipe sealant that resists gasoline, grease, lubrication oil, common bilge solvents, salt deposits, and water.
Ignition-protected equipment. Explosive fuel vapors can cause severe injury or death. Gasoline
vapors can cause an explosion. USCG Regulation 33CFR183 requires that all electrical devices (ship-to-shore transfer switch, remote start panel, etc.) must be ignition protected when used in a gasoline and gaseous-fueled environment. The electrical devices listed above are not ignition protected and are not certified to operate in a gasoline and gaseous-fueled environment such as an engine room or near fuel tanks. Acceptable locations are the wheelhouse and other living areas sheltered from rain and water splash.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving rotor.
TP-5936 7/04 IIISafety Precautions and Instructions
Page 8
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect
the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Welding the generator set. Can cause severe electrical equipment damage. Before welding the generator
set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage
is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only)
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death.
Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool.
Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
TP-5936 7/04IV Safety Precautions and Instructions
Page 9
Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
Moving rotor.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set
must be operating in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause
the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware.
246242
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
TP-5936 7/04 VSafety Precautions and Instructions
Page 10
Notes
TP-5936 7/04VI Safety Precautions and Instructions
Page 11
Introduction
This manual provides troubleshooting and repair instructions for 32EOZ and 27EFOZ model generator sets, controllers, and accessories.
Refer to the engine service manual for generator set engine service information.
x:in:001:001
This manual may be used for models not listed on the front cover.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
For professional advice on generator power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably-trained maintenance personnel familiar with generator set operation and service.
x:in:001:003
Service Assistance
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
D Visit the Kohler Power Systems website at
KohlerPowerSystems.com
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product
D Call toll free in the US and Canada 1-800-544-2444
D Outside the US and Canada, call the nearest regional
office
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems ZI Senia 122 12, rue des Hauts Flouviers 94517 Thiais Cedex France Phone: (33) 1 41 735500 Fax: (33) 1 41 735501
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-5936 7/04 iIntroduction
Page 12
Product Information
f
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Engine Identi
Record the product identification information from the engine nameplate.
Manufacturer
Model Number
Serial Number
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Number
Specification Number
Serial Number
Accessory Number Accessory Description
ication
TP-5936 7/04ii Introduction
Page 13
1.1 General
19(
0
)
6(3.0
)
The 32EOZ/27EFOZ units are powered by a Yanmar 4TNE98 four-cylinder, water-cooled, four-cycle diesel engine with heat exchanger.
Ratings: Kohler Co. develops all Kohler marine generator set ratings using accepted reference
1.2 Engine
Section 1 Specifications
conditions of 25_C(77_F) and pressure of 29.2 in. Hg dry barometer. ISO 3046 and ISO 8528-1 include reference conditions and output calculations. Obtain technical information bulletin (TIB-101) on ratings guidelines for complete ratings definitions.
Generator Model 32EOZ 27EFOZ
Engine Manufacturer Yanmar
Engine Model 4TNE98
Number of Cylinders 4
Cylinder Block Material Cast iron
Cylinder Head Material Cast iron
Piston Rings 2 compression/1 oil
Crankshaft Material Stamped forging
Connecting Rod Material Forged carbon steel
Governor Centrifugal, mechanical
Bore x Stroke, mm (in.) 98 x 110 (3.86 x 4.33)
Displacement, L (CID) 3.319 (202.5)
Compression Ratio 18.0:1
Horsepower, 60/50 Hz 55 46
RPM, 60/50 Hz (Full Load) 1800 1500
Direction of Rotation (as viewed from generator end)
Lubrication System Pressure, trochoid pump
Lube Oil Capacity, (w/filter) L(qts)
Oil Recommendation (API) CC or CD
Engine Firing Order (#1 cylinder nearest to flywheel)
Fuel Injection Timing (BTDC)
Fuel Injection Pressure, kPa (psi)
Combustion System Direct injection
Battery Voltage
Battery Charging (alternator)
Battery Recommendation, min.
Counterclockwise
4.7(5.0)
1-3-4-2
10--12_
1517--1586 (220--230)
12 volt (standard)
24 volt (optional)
50 amps
800 CCA, 100 amp hr
Generator Model 32EOZ 27EFOZ
ISO 8217 DMA, BS 2869
Fuel Recommendation
Fuel Shutoff Solenoid System
Fuel Feed Pump Electric, rotary vane
Fuel Pump Priming Electric
Max. Recommended Fuel Pump Lift, m (ft.)
Coolant Capacity, L (U.S. qts.) (approx.)
Coolant Recovery Tank, L(oz.)
Recommended Coolant
Thermostat 71°C (160°F)
Pressure Cap Rating, kPa (psi)
Starter Motor 2.3 kW
Intake/Exhaust Valve Clearance, mm (in.) (lash) (cold)
Belt Tension (force), @ 10 kg (22 lbs.), mm (in.)
Cylinder Head Torque
Final, Nm (ft. lbs.) (2-step intervals)
Initial, Nm (ft. lbs.) 49--58.8 (36--43)
Overbolt Torque (M10-1.5), Nm (ft. lbs.)
Inlet Water Line Hose ID, seawater pump inlet, mm (in.)
Outlet Water Line Hose ID, mixing elbowoutlet, mm (in.)
Fuel Inlet, (Fuel Pump Inlet)
Fuel Return Size, Type 1/4 NPT
Part 1, class 1
or Part 2, class 2
Electric
1.2 (4)
7.6 (8.0)
0.24 (8.0)
50% ethylene glycol; 50%
clean, softened water
97 (14)
0.15--0.25 (0.006--0.010 )
10--15 (0.4--0.6)
102.9--112.7 (76--83 )
38 (28)
.75
7
1/4 NPT
TP-5936 7/04 1Section 1 Specifications
Page 14
1.3 Generator
32EOZ/27EFOZ—4 Lead, 1 Phase Generator
Component Specification Value
Hot exciter field voltage/current readings at rated voltage*
No load (63 Hz) (volts/amps)
Full load (60 Hz) (volts/amps)
Cold exciter field resistance (ohms)
Cold exciter armature resistance (ohms)
Cold main field (rotor) resistance (ohms)
Stator output voltages with separately excited generator using 12-volt battery (60 Hz only)*
1--2, 3--4, 33--44 (volts) 84
55--66 (volts) 148
B1-B2 (volts) 10
Cold stator resistance
1--2, 3--4, 33--44 (ohms) 0.04
55--66 (ohms) 1.7
B1-B2 (ohms) 0.19
* Exciter field circuit includes resistor.
18.0/0.7
45.4/1.7
22.72.3
0.6ᐔ0.05
2.24
32EOZ/27EFOZ—12 Lead, 3 Phase Generator
Component Specification Value
Hot exciter field voltage/current readings at rated voltage*
No load (63 Hz) (volts/amps)
Full load (60 Hz) (volts/amps)
Cold exciter field resistance (ohms)
Cold exciter armature resistance (ohms)
Cold main field (rotor) resistance (ohms)
Stator output voltages with separately excited generator using 12-volt battery (60 Hz only)*
1--4, 2--5, 3--6, 7--10, 8--11, 9--12, 7--8 (volts)
55-66 (volts) 150
B1-B2 (volts) 6
Cold stator resistance
1--4, 2--5, 3--6, 7--10, 8--11, 9--12, 7--8 (ohms)
55--66 (ohms) 2.1
B1-B2 (ohms) 0.15
* Exciter field circuit includes resistor.
21.1/0.8
70.0/2.5
22.72.3
0.6ᐔ0.05
2.24
84
0.09
TP-5936 7/042 Section 1 Specifications
Page 15
1.4 Service View
1 2 3 4 5 6 8 9 10 11 12 13 14 15 16 17
7
2325
21222426
16 1227
28
33
18
12
19
20
29
32
31
1. Controller
2. Start/Stop switch
3. Hourmeter
4. DC circuit breaker
5. AC load lead connector (rear)
6. Nameplate (top)
7. Remote start connector (rear)
8. AC circuit breaker
9. Air intake silencer
10. Lifting eye
11. Fuel filter
12. Oil fill
13. Fuel return (or located behind valve cover and filter)
14. Governor
15. Fuel injection pump
16. Pressure cap
17. Overflow tube
30
GB-250000
18. High water temperature switch
19. Seawater pump (water inlet)
20. Coolant overflow bottle
21. Oil filter
22. Oil drain valve
23. Oil drain hose
24. Oil dipstick
25. Fuel inlet
26. Low oil pressure switch
27. Thermostat housing and thermostat
28. High temperature shutdown switch
29. Mixing elbow (water/exhaust outlet)
30. Engine starter motor
31. Heat exchanger
32. Water temperature sender (optional)
33. Battery charging alternator
Figure 1-1 Generator Set Service View
TP-5936 7/04 3Section 1 Specifications
Page 16
Notes
TP-5936 7/044 Section 1 Specifications
Page 17
Section 2 Scheduled Maintenance
2.1 General
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set must be operating
in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
Note: See the generator set operation manual for the
service schedule and other service not included in this manual.
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
TP-5936 7/04 5Section 2 Scheduled Maintenance
Page 18
2.2 Lubrication System
The following paragraphs describe the engine lubrication system.
2.2.1 Oil Specifications
Use oil that meets the American Petroleum Institute (API) classification of CC or CD. Using unsuitable oil or neglecting an oil change may result in engine damage and a shorter engine life.
2.2.2 Oil Change
4. Drain the seawater from the heat exchanger by removing the coolant drain plug.
5. Close the seacock and remove the hose at the seacock. Place the hose in a container having approximately 3.7--7.5 L (1--2 gal.) of marine antifreeze. Use an environmentally safe marine antifreeze with corrosion inhibitors.
6. With a container at the exhaust outlet, run the generator set until coolant discharges at the exhaust outlet or until depleting the coolant mixture. Do not allow the coolant mixture to flow into waterways.
Change the engine oil according to the service schedule. Change the oil more frequently under dirty, dusty conditions. Change the oil while the engine is still warm. See Section 1.2 for oil capacities. See Section 1.4 , Service View, for the oil fill, oil check, and oil filter locations.
2.3 Generator Storage
Perform the generator storage procedure while the craft is afloat. Follow the procedure below when storing your generator set for 3 months or more.
Storage Procedure
1. Start and run the generator set until it reaches operating temperature, about 30 minutes.
2. Stop the generator set.
3. Change the oil and oil filter. See the generator set operation manual.
7. Stop the generator set.
8. Connect the hose to the seacock. Leave the seacock closed.
9. Check the coolant level in the heat exchanger and add coolant if necessary.
Note: Use antifreeze with the lowest available
temperature rating.
10. Clean the exterior of the generator set and spread a light film of oil or silicon spray over any exposed surfaces which may be subject to rust or corrosion.
11. Disconnect and remove the battery. Place the battery in a dry location for the storage period. Recharge the battery once a month to maintain a full charge.
12. Cover the entire unit with a breathable dust cover.
TP-5936 7/046 Section 2 Scheduled Maintenance
Page 19
Section 3 Intake and Exhaust System
3.1 Air Intake Silencer/Cleaner
At the interval specified in the service schedule, clean or replace the air intake silencer. Clean more frequently in
dirty, dusty conditions.
3.2 Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system connections.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.
D Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional. and (3) energized whenever the generator set operates.
3.3 Mixing Elbow
The mixing elbow combines high-temperature exhaust and cool seawater. When exposed to engine vibration this mixture can cause rapid deterioration and failure in an incorrectly maintained exhaust system.
1. Check inside the mixing elbow for carbon accumulation and corrosion.
2. Remove carbon accumulation.
3. Inspect the exhaust manifold mounting surface for cracks and corrosion.
Inspect the exhaust system components (exhaust manifold, mixing elbow, exhaust line, hose clamps, silencer, and outlet flapper) for cracks, leaks, and
4. Replace a damaged mixing elbow or other components to prevent engine exhaust (carbon monoxide) leakage.
corrosion.
TP-5936 7/04 7Section 3 Intake and Exhaust System
Page 20
Notes
TP-5936 7/048 Section 3 Intake Exhaust System
Page 21
Section 4 Fuel System
4.1 General
In most installations, both the generator set and the propulsion engine operate from a common fuel tank with a dual dip tube arrangement. The generator set dip tube is shorter than the propulsion engine’s dip tube. With this arrangement fuel may not be available to the generator set when the fuel supply is low. See Figure 4-1 for a fuel system schematic.
To fuel pump
Propulsion Engine
1
2
4
3
Generator Set
4.2 Fuel Specifications
Use a clean, good quality diesel fuel oil with a cetane number of 45 or greater. Clean fuel prevents diesel fuel injectors and pumps from clogging.
Fuel Recommendation
United States ISO 8217 DMA, BS 2869 Part 1 Class A1
or Part 2 Class A2
United Kingdom BS 2869-1983, Part 2 Class A2
Germany DIN 51 601-1978
4.3 Fuel Filter
The quality and condition of the fuel largely determine the filter’s useful life. Replace the fuel filter according to the service schedule.
1. Fuel tank
2. Dual dip tubes
3. Fuel filter
4. Fuel feed pump
Figure 4-1 Fuel System Schematic, Typical
TP-5936 7/04 9Section 4 Fuel System
Page 22
4.4 Bleed the Fuel System
Bleed the air from the fuel system to prevent starting failures and/or erratic operation. One or more of the following causes air to collect in the fuel system.
D The generator set operates until the fuel supply is
emptied.
D Air is drawn into the suction side of the fuel system.
D Replacing the fuel filter.
Note: Connect the battery during the priming procedure
to allow engine cranking. Do not allow the engine/generator to start. To prevent starting, toggle the start/stop switch by momentarily placing the start/stop switch in the START position for a few seconds and then placing the switch in the STOP position. Close the seacock during bleeding.
Procedure to Bleed the Fuel System
5. Loosen vent screw C at the fuel filter. See Figure 4-2.
6. Toggle the start/stop switch until fuel, free of air bubbles, flows from vent screw C. Tighten vent screw C.
1234 5
1. Loosen vent screw A at the fuel filter. See Figure 4-2.
2. Toggle the start/stop switch until fuel, free of air bubbles, flows from vent screw A. Tighten vent screw A.
3. Loosen vent screw B at the fuel filter. See Figure 4-2.
4. Toggle the start/stop switch until fuel, free of air bubbles, flows from vent screw B. Tighten vent screw B.
GB-250000A-K
1. Vent screw A
2. Vent screw B
3. Fuel filter
4. Vent screw C
5. Fuel injection pump
Figure 4-2 Fuel System, Typical
TP-5936 7/0410 Section 4 Fuel System
Page 23
4.5 Fuel Solenoid
The fuel solenoid pulls the injector pump lever to the fuel on position when energized. The fuel solenoid is spring loaded to return the injector pump lever to the fuel off position when deenergized.
The generator set uses a three-lead fuel solenoid. This solenoid has a white lead (P) which energizes the pull-in coil only during cranking. During operation, the red lead energizes the hold coil and the black lead is the common ground.
Figure 4-3 shows the current (amps) and resistance readings. Disconnect the fuel solenoid from the engine wiring harness and take the resistance readings to determine if the solenoid windings are open or shorted.
In addition to the ohmmeter test, check for smooth, non-binding movement of the plunger. Be sure to adjust the linkage between the fuel solenoid and the fuel injection pump lever to allow the solenoid plunger to fully compress. Incorrect adjustment may cause burnout of the pull-in coil. If the fuel solenoid is removed, see Figure 4-4 and use the following procedure.
Fuel Solenoid Test Procedure
1. Remove the linkage to allow the fuel solenoid plunger to be manually compressed.
Reading
Fuel Solenoid
Pull-In 50 amps 22 amps
Hold 1.0 amps 0.37 amps
Black-white (P) leads 0.12--0.26 ohms
Black-red leads 11--13 ohms
12V System 24V System
Figure 4-3 Fuel Solenoid Readings
1
GB-250000A-K
1. Fuel solenoid
Figure 4-4 Fuel Solenoid
2. With the fuel solenoid fully compressed, align the linkage and check the injection pump lever for travel. The fuel solenoid should fully compress and the injection pump lever should be at 1.6 mm (0.06 in.) before the lever contacts (internal full open) stop.
Note: The fuel solenoid must compress (bottom)
fully or the fuel solenoid pull-in coil will burn out.
3. If alignment is not correct, check the linkage and mounting brackets. Loosen the locknuts and adjust the ball joint length in or out to attain the correct alignment. Tighten the locknuts.
TP-5936 7/04 11Section 4 Fuel System
Page 24
4.6 Fuel Pump
The fuel pump transfers fuel from a source to the fuel injection pump.
Fuel Pump Test Procedure
1. Remove the two leads from the terminals at the bottom of the fuel pump. The pump terminals are labeled (--) and (+). See Figure 4-5.
2. Connect the inlet side of the pump to a fuel source. Disconnect the outlet hose from the fuel filter and place the hose end in a container to catch the fuel.
60 Hz generator sets are designed to operate at 57--63 Hz, 1800 rpm under full load and 1890 rpm under no load.
50 Hz generator sets are designed to operate at 47--53 Hz, 1500 rpm under full load and 1590 rpm under no load.
Check the engine speed using a frequency meter connected to the load leads. Loosen the locking nut on the speed adjusting screw. Turn the screw clockwise to increase the speed and frequency. Turn the screw counterclockwise to decrease the speed. Tighten the locknut at the new setting. See Figure 4-6.
3. Connect the positive (+) terminal of the 12-volt battery to the positive terminal of the fuel pump. Connect the negative terminal of the fuel pump to the negative (--) terminal of the battery. You should hear the pump operate and see the fuel discharge from the pump outlet. Replace the pump if it does not operate.
1
23
1. Fuel inlet
2. Negative terminal
3. Positive terminal
4. Fuel outlet
4
I-940
Governor Adjustment Procedure
1. Loosen the locknut on the speed adjusting screw.
2. Turn the speed adjusting screw clockwise to increase the speed and frequency or counterclockwise to decrease the speed.
3. Tighten the locknut at the new setting. See Figure 4-6.
4. Adjust the voltage regulator. See Section 7.5, Voltage Regulator Adjustment.
12
3
Figure 4-5 Fuel Pump
4.7 Governor
The centrifugal, mechanical governor keeps the engine speed constant by automatically adjusting the amount of fuel supplied to the engine according to changes in the load. No regular service is required on the governor. The factory adjusts the governor during run-in, and further adjustment should not be needed unless poor governor control develops after extended generator usage.
GB-250000A-K
1. Governor
2. Locknut
3. Speed adjusting screw
Figure 4-6 Governor
TP-5936 7/0412 Section 4 Fuel System
Page 25
Section 5 Cooling System
5.1 General
The heat exchanger cooling system consists of a heat exchanger with a coolant recovery tank, a thermostat, a rubber impeller seawater pump, a centrifugal-type engine circulating pump, a water-cooled exhaust manifold, and an exhaust mixer. See Figure 5-1 for cooling system components.
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
1
2
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool. Release pressure
from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
Note: Do not add coolant to a hot engine. Adding
coolant to a hot engine can cause the cylinder block or cylinder head to crack. Wait until the engine has cooled.
1. Engine block
2. Exhaust manifold
3. Exhaust mixer elbow
4. Outlet flapper
5. Silencer
6. Thermostat
12
9
10
11
3
4
5
6
7
8
Seawater Coolant/Antifreeze
60531099
7. Heat exchanger
8. Engine seawater pump
9. Seawater strainer
10. Seacock
11. Intake strainer
12. Engine-driven water pump
Figure 5-1 Cooling System Components
TP-5936 7/04 13Section 5 Cooling System
Page 26
5.2 Water-Cooled Exhaust Manifold
5.4 Check and Fill the Cooling System
Each marine generator set has a water-cooled exhaust manifold. The coolant solution circulates through the manifold, reducing the amount of heat radiated from the exhaust into the surrounding area.
The engine thermostat is located in the water-cooled exhaust manifold. See Section 1 for the thermostat location. See Figure 5-2 and Figure 5-3 for exhaust manifold bolt tightening sequence and torques.
Model Bolt Torque
32EOZ/27EFOZ 19 Nm (14 ft. lbs. )
Figure 5-2 Water-Cooled Exhaust Manifold Bolt
Tightening Torques
54
1
8
7
23
6
Before filling the cooling system, close all the petcocks and tighten all of the hose clamps. Usea solution of 50% ethylene glycol and 50% fresh, softened water to inhibit rust/corrosion and prevent freezing. Add additional coolant, as necessary, to the coolant recovery tank. Maintain the level in the coolant recovery tank at approximately 1/4 full. Periodically check the coolant level on closed systems by removing the pressure cap. Do not rely solely on the level in the coolant recovery tank. Add fresh coolant until the level is just below the overflow tube opening.
5.5 Flush and Fill the Cooling System
For optimum protection drain, flush and refill the cooling system at the interval listed in the service schedule.
1. Open the petcocks located at the heat exchanger, engine block, and cooling system and let the system drain completely. The petcocks on some models are located behind the belt guard. Remove the pressure cap to simplify draining.
344848-E
Figure 5-3 Water-Cooled Exhaust Manifold Bolt
Tightening Sequence
5.3 Closed Heat Exchanger
In a closed cooling system, the seawater circulates through separate chambers within the heat exchanger to cool the engine coolant. The seawater then mixes with engine exhaust and ejects out the exhaust outlet. See Section 1.2 for the coolant capacities; include coolant recovery tank capacity of 0.24 L (8.0 oz.). See Section 1.2 for the thermostat and pressure cap ratings.
Note: Use antifreeze capable of withstanding the
lowest possible temperatures.
2. Drain, clean, and flush the coolant recovery tank.
3. Flush the cooling system with clean water.
4. Fill the cooling system with recommended coolant.
Note: Pay special attention to the coolant level. After
the coolant drains, allow time for complete refill of the engine water jacket. Check coolant level as prescribed in the prestart checklist in the operation manual.
TP-5936 7/0414 Section 5 Cooling System
Page 27
5.6 Siphon Break
A siphon break prevents seawater entry into the engine when the engine exhaust manifold outlet is less than 23 cm (9 in.) above the waterline of a fully-loaded craft. Check the siphon break at the interval listed in the service schedule. Use the following procedure and Figure 5-4 to inspect the siphon break.
Siphon Break Inspection Procedure
1. Place the generator set controller start/stop switch in the STOP position.
2. Remove the retaining cap to inspect the reed valve assembly.
2
3
3. Use a light detergent to clean the reed valve to remove the residue and oxidation.
4. Check that the reed valve opening is clear.
5. Replace the siphon break if it is cracked or if the reed valve material has hardened or deteriorated.
6. Install the reed valve into the mounting base with the valve downward.
7. Install the retaining cap and finger-tighten only. Do not overtighten.
7
8
9
1
6
5
4
16
21
Waterline
20
19
17
15
18
1. Mounting holes
2. Retaining cap
3. Reed valve assembly
4. Silencer vertical lift 1.2 m (4 ft.) max.
5. Exhaust mixer elbow distance above waterline. If less than 23 cm (9 in.), siphon break is required.
6. Siphon break distance above waterline 30.5 cm (1 ft.) min.
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank
NOTE: Consult the installation manual for complete explanation of dimensions and other installation considerations.
11. Coolant recovery tank
12. Seawater strainer
13. Seacock
14. Intake strainer
15. Engine-driven seawater pump
16. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
17. Water lock (optional)
18. Silencer distance from exhaust mixer elbow 3 m (10 ft.) max.
19. Silencer (customer-supplied)
20. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
21. Exhaust outlet distance above waterline 10 cm (4 in.) min.
14
10
11
12
13
TP-5586-3
Figure 5-4 Siphon Break, Plastic U Type
TP-5936 7/04 15Section 5 Cooling System
Page 28
5.7 Impeller Inspection and Replacement
The belt-driven seawater pump is located on the service side of the generator set. Check and change the seawater pump impeller at the interval specified in the service schedule. Follow instructions in the impeller kit. If the instructions are not included with the kit use the following procedure.
Impeller Inspection and Replacement Procedure:
1. Close the seacock.
2. Remove the seawater pump coverplate. See Figure 5-5.
3. Remove the impeller.
10
8
9
1. Seawater pump
2. Coverplate
3. Gasket
4. Impeller
5. Bearing
1
2
3
4
5
6
7
6. Housing
7. Pulley
8. Drive shaft
9. Washer
10. Nut
TP-5936-28
4. Inspect the impeller for damage, including visible cracks, missing pieces, or flat spots. Impeller vanes should be straight and flexible. See Figure 5-6.
5. Lubricate the impeller with soapy water before installation.
6. While installing the impeller, always rotate the drive shaft and the impeller together in the same direction as the engine rotates.
7. Inspect the coverplate and gasket for corrosion and/or damage. Replace components as necessary.
8. Lubricate the gasket with silicon grease and attach the gasket and coverplate to the seawater pump housing.
9. Open the seacock.
10. Start the generator set and check for leaks.
11. Stop the generator set and repair leaks or replace components as necessary.
Figure 5-5 Seawater Pump, Typical
1
1. Flat spot
2. Crack
3. Broken vane
Figure 5-6 Worn Impeller
2
3
TP-5936-57
TP-5936 7/0416 Section 5 Cooling System
Page 29
5.8 Anticorrosion Zinc Anode
The heat exchanger contains an anticorrosion zinc anode (plug) to prevent electrolyte corrosion by the seawater.
Check and replace the anticorrosion zinc anode at the intervals recommended in the service schedule. See Figure 5-7.
Inspection and Replacement Procedure
1. Place the generator set controller start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, negative (--) lead first.
3. With the generator set cooled, close the seacock, open the engine petcock, and drain the coolant into a suitable container.
4. Remove the anticorrosion zinc anode from the heat exchanger. See Figure 5-7.
5. Remove the loose corrosion on the anticorrosion zinc anode. Replace the anode according to Figure 5-8 and Figure 5-9.
6. Apply pipe sealant suitable for marine applications to the threads of the anticorrosion zinc anode (plug) and install the anode in the heat exchanger.
1
3
1. Anticorrosion zinc anode (seawater drain)
2. Heat exchanger
3. Coolant drain
2
GB-250000A-K
Figure 5-7 Anticorrosion Zinc Anode Location
Anticorrosion Zinc Anode Replacement
Replace When
Models
32EOZ/27EFOZ 9 (0.34) x 19 (0.75)
New Anode
Dimensions mm (in.)
Percent of Zinc
Remaining is:
<50% of
length/diameter
Figure 5-8 Anticorrosion Zinc Anode Measurements
1
7. Close the engine petcock and open the seacock.
8. Refill the cooling system.
9. Reconnect the generator set engine starting battery, negative (--) lead last.
10. Start the generator set and check for leaks at the anticorrosion zinc anode location. The pump is running if cooling water flows from the exhaust outlet. If water is not being discharged at the exhaust outlet, see the Prestart Checklist, Seawater Pump Priming, in the operation manual.
2
1. Diameter: 9 mm (0.34 in.)
2. Length: 19 mm (0.75 in.)
Figure 5-9 Anticorrosion Zinc Anode
TP-5936 7/04 17Section 5 Cooling System
TP-5586-3
Page 30
Notes
TP-5936 7/0418 Section 5 Cooling System
Page 31
Section 6 Controller Troubleshooting
6.1 Controller
This section covers the controller troubleshooting procedure for generator sets equipped with a relay controller and related engine components. Refer to Section 1.4 to identify the controller external components. Refer to Figure 6-1 to identify the controller internal components.
1
7
6
2
6.2 Controller Sequence of Operation
The following describes the controller sequence of operation during generator start, run, stop, and fault shutdown modes. Use the LEDs on the controller circuit board to assist in the troubleshooting process. An illuminated LED indicates that the respective relay is receiving power; the LED does not indicate whether that relay is energized. Refer to the wiring diagrams in Section 10, Voltage Reconnection and Wiring Diagrams.
6.2.1 Start
Close the start/stop switch between N and 47 (local or remote starting).
The K2 relay energizes. The normally open K2 contacts close to energize the K3 relay (LED3 lights), the K25 (fuel solenoid) relay, the controller hourmeter, and the generator armature exciter field.
The K25 normally open contacts close to energize the fuel solenoid.
45
4
5
3
1. Controller circuit board
2. K25 relay (fuel solenoid)
3. Hourmeter
4. DC circuit breaker
5. Start/stop switch
6. Voltage regulator circuit board
7. K20 relay (starter solenoid relay)
8. AC circuit breaker location
3
8
Figure 6-1 Controller Internal Components
The K3 relay normally open contacts close to energize the K20 (starter) relay. The K20 relay normally open contacts close to energize the S relay (starter solenoid). The S relay normally open contacts close to energize the starter motor.
The normally closed low oil pressure (LOP) contacts open.
A-359001-C
TP-5936 7/04 19Section 6 Controller Troubleshooting
Page 32
6.2.2 Run
6.2.3 Stop
The K1 relay energizes (LED1 lights) when the B1 and B2 windings receive AC output from the stator main field. After a 5--10 second time delay, the K5 relay energizes (LED5 lights).
Note: The bridge rectifier (BR1) and the voltage
regulator (VR1) provides 12 volts DC voltage to the K1 and K5 relays.
Stator winding V1--V4 provides voltage sensing source to the voltage regulator (PBV).
The normally open K1 (A) contacts close to maintain voltage to the K2 relay (LED2 remains lit).
The normally open K2 contacts remain closed to maintain voltage to the fuel solenoid and the controller hourmeter.
The normally open K1 (B) contacts close to energize the (optional) oil pressure, coolant temperature, battery voltmeter, hourmeter gauges, and generator ON light.
The normally open K5 contacts close to permit the high water temperature (HWT), high exhaust temperature (HET), and low oil pressure (LOP) switches to function.
Close the start/stop switch between N and 43 (local or remote).
The K4 relay is energized (LED4 lights).
The normally closed K4 contacts open to deenergize the K25 relay. The K25 normally open contacts open to deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground to the K4 relay.
As the generator set is shutting down, the K1 relay is deenergized (LED1 goes out). The normally open K1 (A) contacts open to deenergize the K2 relay (LED2 goes out).
6.3 Engine Safety Shutdown Switches
6.3.1 Low Oil Pressure (LOP) Shutdown
When low oil pressure occurs, the LOP shutdown switch contacts close and energize the K4 relay (LED4 lights).
Note: The LOP switch contacts open when the engine
develops oil pressure.
One set of normally closed K1 (C) contacts open to disconnect the circuit to (+) connection of the exciter fields (field flashing).
A set of normally closed K1 (E) contacts open to disconnect the circuit to (--) connection of the exciter field (field flashing). The normally closed K1 (D) contacts open to deenergize the K3 relay (LED3 goes out) and prevent accidental reenergizing of the starter motor. The K3 contacts open to deenergize the K20 relay. The K20 contacts open to deenergize the S relay. The S contacts open to deenergize the starter motor.
When the generator set is running, the start switch contacts N and 47 are opened by releasing the start/stop rocker switch.
Note: During cranking, the LOP shutdown switch is
deactivated until the K5 relay is energized. This delay allows the engine to reach normal operating oil pressure. The normally closed LOP contacts open when the generator set develops adequate oil pressure.
The normally closed K4 contacts open to deenergize the K25 relay. The normally open K25 contacts open to deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground to the K4 relay.
As the generator set shuts down, the K1 relay is deenergized (LED1 goes out). The normally open K1 (A) contacts open to deenergize the K2 relay (LED2 goes out). The normally closed K2 contacts close to ground circuit to the K4 relay until the generator set comes to a complete stop.
TP-5936 7/0420 Section 6 Controller Troubleshooting
Page 33
6.3.2 High Water Temperature (HWT) and High Exhaust Temperature (HET) Shutdown Switch
When a high temperature is encountered at one (or both) of these sources, the shutdown switch contacts close and energize the K4 relay (LED4 lights).
The normally closed K4 contacts open to deenergize the K25 relay. The K25 normally open contacts open to deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground to the K4 relay.
14
12
11
23
5
As the generator set shuts down, the K1 relay deenergizes (LED1 goes out). The normally open K1 (A) contacts open to deenergize the K2 relay (LED2 goes out). The normally closed K2 contacts close to ground circuit to the K4 relay until the generator set comes to a complete stop.
6.3.3 Controller Circuit Board
Some controller circuit board components can be tested without removing the component from the circuit board. Perform these checks prior to installing a new circuit board and attempting startup. Refer to Figure 6-3, troubleshooting flow chart.
The controller circuit board has light-emitting diodes (LEDs) which indicate relay coil power and aid in the circuit board and the generator fault detection. When any of relays K1--K5 receive power, the corresponding LED lights. See Figure 6-2. The LED does not indicate whether the relay coil is energized. Determine if the relay coil is energized by analyzing the generator faults by performing a continuity test on the relay coil.
Relay Schematic
1. Engine crank control relay (K3)
2. P1 connector
3. P2 connector
4. Time delay relay (K5)
5. LED5
6. LED2
7. Engine run relay (K2)
8. AC crank disconnect relay (K1)
9. LED1
10. Fault shutdown relay (K4)
11. LED4
12. LED3
Figure 6-2 Controller Circuit Board
678910
H-239563-
TP-5936 7/04 21Section 6 Controller Troubleshooting
Page 34
6.3.4 Troubleshooting
Use the following flow chart as an aid in troubleshooting the main circuit board and the entire generator set. If the
prescribed remedy does not correct the problem, the circuit board may have to be replaced.
Press the start switch (Local or remote)
No
--Check condition/ connections of the start/stop switch (N, 43, and 47).
--Check the battery
condition and connections.
--Check the connections
at P1--14.
Does the engine crank?
No
Is K2 relay LED lit?
No
Is K2 relay functioning?
No
Yes
Yes
Yes
Is K3 relay LED lit?
Is voltage present at K20 relay coil?
No
Is K3 relay functioning?
No
Go to A (next page)
Yes
Yes
Yes
Is 10-amp controller circuit breaker okay?
YesNo
Reset the circuit breaker
Replace the circuit board (D9 open)
Replace the circuit board
Replace the K20 relay
K3relayorK1 relay faulty. Replace the circuit board
No
Is the K20 relay functioning correctly?
Figure 6-3 Troubleshooting Relay Controller Circuit Board (1 of 4)
Replace the circuit board
Is voltage present at the S relay coil?
YesNo
Check P4--22 connection
Replace the S relay
Check the P1--4 connection
Yes
Is voltage present at the S relay contact (starter motor side)?
No
Yes
Replace the starter motor
TP-5936 7/0422 Section 6 Controller Troubleshooting
Page 35
A
Does the engine start?
Yes
Go to B (next page)
No
No
Is there continuity between P1-9 and P9-1?
No
No
No
Is there continuity between P9-2 and P1-8?
Is there continuity between P1-8 and P1-14?
Is the K4 relay LED lit?
No
Is 12 volts DC present at the (P9-2)?
Yes
Yes
Yes
Is there continuity across the P1, P4, and P9 connectors?
Yes
No
Is the fuel pump working?
Is there continuity between P2-8 and N?
Yes
Disconnect the P2 connector. Is there continuity between P2-5 and N?
No
Replace the remote start/stop switch
Is there continuity between P4-5 and N?
No
- Diagnose engine safety shutdown switches (LOP, LCS, HET).
- Engine fault (check the
fuel supply, carburetion, ignition, compression)
Yes
See engine service manual.
Yes
Check wiring for opens
Yes
Replace fuel pump
Figure 6-4 Troubleshooting the Run Relay Controller Circuit (2 of 4)
Replace the start/stop switch
TP-5936 7/04 23Section 6 Controller Troubleshooting
Page 36
B
to run after the start
Yes
switch is released?
Does the engine continue
Can the engine be stopped by using the stop switch?
Yes
No
Go to C (next page)
Did the K4 relay LED light?
No
Does the K1 relay LED light?
Yes
Does the K5 relay LED light after 5--10 seconds of running time?
Yes
Did the K4 relay LED light?
Do the local and remote start/ stop switches function?
No
Replace the circuit board (K5 relay inoperative)
No
No
No
Yes
Replace the circuit board (K4 relay inoperative)
Generator set checks out okay
Yes
Is the fuel solenoid functioning?
No
Yes
Replace the inoperative start/stop switch
Is the K25 relay functioning?
No
Replace the fuel solenoid
No
Do the local and remote start/stop
Yes
Yes
Replace the circuit board (inoperative K1 or K2 relay)
switches function?
Replace the inoperative start/stop switch
No
Does the low oil pressure (LOP) safety shutdown switch function?
Yes
Use a mechanical gauge to
No
Yes
Replace the LOP safety shutdown switch
Do the temperature safety shutdown switches function?
verify oil pressure. Does the engine have proper oil pressure?
No
Check the oil level. Repair/replace the oil pump
Figure 6-5 Troubleshooting Relay Controller Circuit Board (3 of 4)
No
Yes
Replace the circuit board (inoperative K4 relay)
Yes
Replace the inoperative temperature switch(es)
Replace the K25 relay
Replace the circuit board (inoperative K4 relay)
TP-5936 7/0424 Section 6 Controller Troubleshooting
Page 37
Is there AC output when the start button
C
is HELD and the unit
Yes
is running?
Is AC output at the correct voltage, e.g. 120 volts AC?
No
Is the voltage regulator fuse okay?
No
No
Is there 12VDC at the exciter field?
No
Replace the controller circuit board
Go to B at the beginning of the preceding page
(OPTIONAL)
Yes
Tes t th e stator and main field
Replace the controller circuit board
Yes
Is there 12VAC output at the B1/B2 stator winding?
Yes
No
Replace the fuse
Yes
Test the voltage regulator Refer to Section 7
Separately excite the generator set to determine if other components are inoperative.
Is AC output voltage at spec (See Section 7, Separate Excitation)?
No
Test the stator, main field (rotor), and exciter/armature. Refer to Section 7
Yes
Test the voltage regulator. Refer to Section 7
Figure 6-6 Troubleshooting Relay Controller Circuit Board (4 of 4)
TP-5936 7/04 25Section 6 Controller Troubleshooting
Page 38
Notes
TP-5936 7/0426 Section 6 Controller Troubleshooting
Page 39
Section 7 Generator Troubleshooting
7.1 General
Before beginning the troubleshooting procedures, read all the safety precautions at the beginning of this manual. The following tests include additional safety precautions; OBSERVE THESE PRECAUTIONS!
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving rotor.
7.2 General Troubleshooting
To determine the cause of no- or low-AC output , refer to the following steps and the troubleshooting flow chart (Figure 7-1).
1. Check the condition of the voltage regulator 8-amp fuse.
2. If the fuse is good, separately excite the generator. (See Section 7.3) The separate excitation test duplicates the role of the voltage regulator in providing the excitation current to the rotor.
Generator has no
output
Separately
excite
generator
Generator has no
output
Generator has
output
Test voltage
regulator &
wiring
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Exciter circuit & rectifier module
Test rotor
Figure 7-1 General Troubleshooting
Test stator
TP-593651
TP-5936 7/04 27Section 7 Generator Troubleshooting
Page 40
7.3 Separate Excitation
By separately exciting the generator to determine the presence of a faulty voltage regulator, it is possible to determine if a running fault exists in the rotor and/or stator. A generator component that appears good while static (stationary) may exhibit a running open or short circuit while dynamic (moving). Short circuits can be caused by centrifugal forces acting on the windings during rotation or insulation breakdown as temperatures increase.
1. Disconnect all of the leads from the voltage regulator.
2. Disconnect the P6 (F1, F2) connector.
3. Connect separate excitation circuit as shown in Figure 7-2. Connect an ammeter and a 10 amp fuse in series with F1. Note and record the ammeter reading.
4. The approximate ammeter reading should be battery voltage divided by the specified exciter resistances (cold). Disconnect the resistor leads and determine the exciter current value using an ohmmeter. See Section 1, Specifications, for the normal values.
Example:
Note: See Section 1, Specifications, for the stator
output voltages (with separately excited generator). These specifications are based on a battery voltage of 12. Should the battery voltage vary (11--14 volts), the resulting stator output values will also vary.
+—
8
P6
F1 F2
1. Voltage regulator
2. 10-amp fuse
3. DC ammeter
4. Battery
5. Ground to generator frame
6. Exciter armature
7. Exciter field
8. P6 connector
1
2
7
5
6
3
+
4
TP-593653
Figure 7-2 Separate Excitation Connections
12 Volts (Battery Voltage)
22.7 Ohms Exciter
Resistance
0.5-amps
=
Exciter Current
5. Start the engine and check that the ammeter remains stable. An increasing meter reading indicates a shorted exciter field or inoperative F1 resistor. A decreasing meter reading to zero, or unstable reading, suggests a running open in the exciter or F1 resistor. If the ammeter is stable, continue with step 6.
6. Check for AC output across the stator leads and compare it to the values in Section 1, Specifications. If the output varies considerably from those listed, a faulty stator, rotor, rectifier module, or armature is likely.
If the AC output is not within specifications, the voltage regulator is probably inoperative. If there is no generator output during normal operation, but output is available when the generator set is separately excited, the voltage regulator is probably inoperative.
7.4 PowerBoost V Voltage Regulators
The generator set is equipped with a PowerBoostt V voltage regulator. See Figure 7-3. The PowerBoostt V voltage regulator monitors output voltage magnitude to control the current to the generator exciter field. The voltage regulator has an underfrequency unloading feature that is referred to as volts-per-Hz (V/Hz). To determine if the voltage regulator is functioning, reduce the engine speed (Hz) and watch for a corresponding drop in the AC voltage. The AC voltage should remain constant until the engine speed drops below 57.5 Hz on 60 Hz models or 47.5 Hz on 50 Hz models.
When the frequency drops below either 57.5 or 47.5 Hz, the AC voltage should decline. Perform the following test to check the regulator output.
TP-5936 7/0428 Section 7 Generator Troubleshooting
Page 41
The following components will be needed to test the voltage regulator:
D Step-up transformer, 1:2, 120 volts to 240 volts
(1.0 amp min.)
D Variable transformer, 0--140 volts (1.0 amp min.)
D Lamp, 250-volt, 100-watt
D AC voltmeter, 250 volt minimum
3. Plug the power cord into the outlet.
4. Turn the power supply on. The AC voltmeter should indicate a power supply voltage of 200--240 volts. The lamp should be off. If lamp is lit, replace the voltage regulator.
5. Slowly turn the volts adjustment pot clockwise. The lamp should light. Replace the voltage regulator if the lamp does not light.
D Fuse, 1-amp
D Switch, 1 single-pole single-throw (SPST) 1 amp
(minimum)
D Plug, 120-volt AC (200--240 volt AC plug optional)
D Copper wire, #14 AWG (minimum)
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
Voltage Regulator Test Procedure
1. Connect the components as shown in Figure 7-3. If a 200--240 volt power source is available, the step-up transformer is not required.
2. Turn the volts potentiometer (pot) fully counterclockwise.
Moving rotor.
2
3
8
7
6
5
4
3
2
1
4
66
55
12
11
10
1
9
8
STAB
Input
Green
V/HZ VOLTS
Sensing
Yellow
7
Output
Red
13
6
11
13
8
TP-593655
14
1. LED1 (input)
2. PowerBoostt V voltage regulator
3. LED2 (output)
4. 250-volt, 100-watt lamp
5. AC voltmeter 250 volt (minimum)
6. 1:2 step-up transformer
7. Single-pole single-throw switch
8. 1-amp fuse
9. LED3 (sensing)
10. Volts potentiometer
11. Black wire
12. 100--120 VAC
13. White wire
14. 200--240 VAC (optional)
7
Figure 7-3 PowerBoostt V Voltage Regulator Test
5
TP-5936 7/04 29Section 7 Generator Troubleshooting
Page 42
7.5 Voltage Regulator Adjustment
The voltage regulator is factory set and, under normal circumstances, requires no further adjustment. However, if the voltage regulator has been replaced, or tampered with, or if voltage/frequency reconnection has been done, readjust the voltage regulator according to the following procedure. The voltage regulator components are identified and described in the following paragraphs.
Output
Stab
V/HZ
Input
Green
Sensing
Yellow
Volt s
6
8
Red
7
6
5
4
3
2
1
1
7
66 55 4
3
Note: The voltage regulator is located inside the
generator set controller.
Voltage Adjustment Pot. Pot adjusts the generator output.
Stability Pot. Pot fine tunes the regulator circuitry to reduce light flicker.
Volts/Hz Pot. Pot adjustment determines the engine speed (Hz) at which the generator output begins to drop.
Voltage Regulator Adjustment Procedure
1. Place the generator set controller start/stop switch in the STOP position.
2. Turn the Volts/Hz and the stability pots fully counterclockwise. Connect the voltmeter to the AC circuit or an electrical outlet.
3. Start the generator set and rotate the voltage adjustment pot clockwise (increase voltage) or counterclockwise (decrease voltage) until the desired output voltage is achieved.
F+
AC AC AC
F--
5
4
B1 B2
3
1
1. Sensing leads
2. Main field (rotor)
3. Stator windings
4. Rectifier
5. Armature
6. Exciter field
7. Voltage regulator power supply leads
Figure 7-4 PowerBoostt V Voltage Regulator
Connection
2
8
7
6
5
4
3
2
1
1
STAB
V/HZ VOLTS
6
5
1. LED1 (green input)
2. LED2 (red output)
3. Voltage potentiometer
Input
Green
Sensing
Yellow
Output
Red
4
3
4. LED3 (yellow sensing)
5. Volts/Hz potentiometer
6. Stability potentiometer
2
2
TP-593656
TP-593657
4. Rotate the stability pot clockwise until light flickers minimally.
5. Readjust the voltage adjustment pot until the desired output voltage is achieved.
6. Adjust the engine speed to the specified cut-in frequency as measured on the frequency meter. The factory setting is 57.5--58 Hz for 60 Hz models and 47.5--48 Hz for 50 Hz models.
7. Rotate the volts/Hz pot clockwise until the voltage level as measured on the voltmeter begins to drop. When the regulator is set to these specifications, the generator will attempt to maintain normal output until the engine speed drops below the frequency set in step 6 as load is applied.
8. Readjust the engine speed to 1800 rpm for 60 Hz models and 1500 rpm for 50 Hz models.
9. Readjust the voltage adjustment pot until the desired output is achieved.
10. Readjust the stability pot until light flickers minimally.
11. Place the generator set controller start/stop switch in the STOP position.
Figure 7-5 PowerBoostt V Voltage Regulator
TP-5936 7/0430 Section 7 Generator Troubleshooting
Page 43
7.6 Exciter Field
Direct current from the battery magnetizes the exciter field. When the exciter armature rotates within the magnetized exciter field windings, an electrical current develops within the exciter armature. Test the exciter field according to the following procedure.
Exciter Field Test Procedure
2
1
P6
F1 F2
3
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, negative (--) lead first.
3. Disconnect the P6 connector (F1/F2 leads).
4. Check the exciter field resistance by connecting an ohmmeter across exciter field F1 and F2 leads. See Section 1, Specifications, for the resistance reading for a cold exciter field. A low reading indicates an internal short and a high reading indicates an open winding. Repair or replace the exciter field if the ohmmeter readings indicate a inoperative exciter field (Refer to Section 9 for removal). If the resistance test is inconclusive, perform a megohmmeter test on the exciter field as described in the next step.
5. Check the exciter field for a short to ground condition. Use a megohmmeter to apply 500 volts DCtotheF1orF2leadandtheexciterfieldframe. Follow the megohmmeter manufacturer’s instructions for using the megohmmeter. A reading of approximately 500 kOhms (1/2 megohm) and higher indicates the field winding is good. A reading of less than approximately 500 kOhms indicates deterioration of the winding insulation and possible current flow to ground. Replace the exciter field.
4
1. Voltage regulator
2. Ohmmeter
3. Exciter field
4. Exciter armature
Figure 7-6 Exciter Field Resistance Test
1
5
F1 F2
1. Voltage regulator
2. Ohmmeter
3. Frame connection
2
P6
3
4
4. Exciter armature
5. Exciter field
Figure 7-7 Megohmmeter Connections on the
Exciter Field
TP-593658
TP-593659
TP-5936 7/04 31Section 7 Generator Troubleshooting
Page 44
7.7 Exciter Armature
AC AC AC
1
F+
F--
6
5
3
2
4
TP-5936510
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-8 Exciter Armature Ohmmeter Test
7
6
4
5
1. Main field rotor
2. Stator windings
3. Rectifier module
4. Megohmmeter
1
F+
AC AC AC
F--
3
5. Shaft connection
6. Armature
7. Exciter field
2
TP-5936511
Figure 7-9 Megohmmeter Connections on Exciter
Armature
The exciter armature supplies excitation current to the generator main field through the rectifier module. Test the exciter armature as described in the following steps.
Exciter Armature Test Procedure
1. Disassemble the alternator. Refer to Section 9.
2. With the alternator disassembled, disconnect the armature leads from the rectifier module AC terminals. Refer to Section 9.
3. With an ohmmeter on the R x 1 scale, check the resistance across the exciter armature leads. See Figure 7-8. See Section 1, Specifications, for the armature resistance. No continuity indicates an open armature winding. If the resistance test is inconclusive, perform a megohmmeter test on the exciter armature as described in the next step.
Note: Consider the exciter armature good if the
resistance reading (continuity) is low and there is no evidence of a shorted winding (heat discoloration).
4. Check the exciter armature winding for a short to ground condition. Use a megohmmeter to apply 500 volts DC to either armature lead and the armature frame. Follow the megohmmeter manufacturer’s instructions for using the megohmmeter. See Figure 7-9. A reading of approximately 500 kOhms (1/2 megohm) and higher indicates the exciter armature is good. A reading of less than approximately 500 kOhms indicates deterioration of the winding insulation and possible current flow to ground. Replace the exciter armature.
TP-5936 7/0432 Section 7 Generator Troubleshooting
Page 45
7.8 Rectifier Module
The rectifier module converts the AC from the exciter armature to DC, which magnetizes the generator main field. Test the rectifier module as described in the following steps.
Rectifier Module Test Procedure
1. Disconnect the exciter armature and the main field leads from the rectifier module.
2. Use an ohmmeter on the R x 100 scale to check the resistance between the rectifier diodes as shown in Figure 7-10. The ohmmeter should show a low resistance in one direction and, upon reversing the ohmmeter leads, a high resistance in the other direction. Replace the rectifier module if any of the diodes test differently than described.
7.9 Rotor
The generator rotor (magnetized by DC from the rectifier module) rotating within the stator windings induces AC in the stator windings. Test the generator rotor (main field) as described in the following steps. Disassemble the generator prior to performing this test. See Section 9.
Generator Rotor Test Procedure
1
+
AC
AC AC
2
--
3
1. Diode terminal
2. Diode terminal
3. Ohmmeter
Figure 7-10 Rectifier Module Test
6
F+
AC AC AC
F--
5
4
3
TP-5936512
1
2
1. With the generator disassembled, disconnect the generator rotor (main field) windings the rectifier module terminals F+ and F--.
2. Check the main field resistance by connecting an ohmmeter across the main field F+ and F-- leads. See Figure 7-11. See Section 1 for the resistance reading. A low reading indicates an internal short and a high reading indicates an open winding. Repair or replace the main field if the ohmmeter readings indicate the main field is inoperative. If the resistance test is inconclusive, perform a megohmmeter test on the main field as described in the next step.
3. Check the main field for a short to ground condition by using a megohmmeter. Apply 500 volts DC to either field lead and the main field frame. Follow the megohmmeter manufacturer’s instructions for using the megohmmeter. See Figure 7-12. A reading of 500 kOhms (1/2 megohm) and higher indicates the main field is good. A reading of less than 500 kOhms indicates deterioration of the winding insulation and possible current flow to ground. Replace the main field.
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-11 Ohmmeter Connections on Rotor
8
7
1. Main field (rotor)
2. Stator windings
3. Frame connection
4. Shaft connection
AC AC AC
1
F+
F--
5
2
3
6
5. Rectifier module
6. Megohmmeter
7. Armature
8. Exciter field
Figure 7-12 Megohmmeter Connections on
Main Field
TP-593613
4
TP-5936514
TP-5936 7/04 33Section 7 Generator Troubleshooting
Page 46
7.10 Stator
The stator consists of a series of coils of wire laid in a laminated steel frame. The stator leads supply voltage to the AC load and exciter regulator.
Before testing the stator, inspect it for heat discoloration and visible damage to the housing lead wires and exposed and varnished areas of the frame laminations. Be sure the stator is securely fastened in the stator housing.
The stator produces electrical output (AC) as the magnetized main field rotates within the stator windings. Test the condition of the stator according to the following procedure.
Leads 1, 2, 3, and 4 are the generator output leads. Leads 55 and 66 are the voltage regulator supply and sensing leads. The output of leads B1 and B2 is rectified by BR1 to supply the control voltage. BR1 is located on the controller circuit board. Refer to the schematic in Figure 7-13 when performing the following tests.
Stator Test Procedure
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, negative (--) lead first.
3. Check the generator output lead connections. See Section 10, Voltage Reconnection and Wiring Diagrams.
33 3
F1 F2
6
1
F+
AC AC AC
F--
5
3
55 44
12B1 B2
4
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-13 Stator Ohmmeter Connections
Between leads Continuity
1 and 2 3 and 4 55 and 66 B1 and B2
Yes Yes Yes
Yes 1 and 3, 4, 33, 44 1 and 55, B1, and B2 4 and B1 and B2 55 and B1 and B2 Any stator lead and ground
Figure 7-14 Stator Continuity, 1 Phase
4
2
TP-553615
No No No No No
4. Disconnect all the stator leads to isolate the windings. To check the stator continuity, set the ohmmeter on the R x 1 scale. Check the stator continuity by connecting the meter leads to the stator leads as shown in Figure 7-13 through Figure 7-15. Perform the stator tests on all the stator windings.
Between leads Continuity
1 and 4 2 and 5 3 and 6 7 and 10 8 and 11 9 and 12 55 and 66 B1 and B2 1 and 2, 5, 3, 6, 7, 10, 8, 11, 9, 12 1 and 55, 66, B1, and B2 Any stator lead and ground
Figure 7-15 Stator Continuity, 3 Phase
Yes Yes Yes Yes Yes Yes Yes Yes
No No No
TP-5936 7/0434 Section 7 Generator Troubleshooting
Page 47
5. Contact the ohmmeter leads and readjust the ohmmeter to zero ohms. Check the cold resistance of the stator windings by connecting the meter leads to the stator leads 1-2, 3-4, etc. See Section 1, Specifications, for the stator resistance values. If the stator resistance test is inconclusive, perform a megohmmeter test on the stator as described in the next step.
Note: Consider the stator good if the resistance
reading (continuity) is low and there is no evidence of shorted windings (heat discoloration).
F1 F2
8
1
1
66
9
F+
AC AC AC
F--
5
55
B1 B2
4
3
6
P8
V1
V4
3
4
4
12
2
3
Note: When taking an ohmmeter reading using
lead 55, make the connection prior to the in-line fuse.
Note: The stator resistance varies directly with
increased temperature.
6. If any of the stator readings vary during the previous checks, replace the stator.
7. Check the stator for a short to ground condition using a megohmmeter. See Figure 7-16 and Figure 7-17. Apply 500 volts DC to any stator lead from each winding and the stator frame. Follow the megohmmeter manufacturer’s instructions for using the megohmmeter. Repeat the test on the other leads until all the stator windings have been tested. A reading of 500 kOhms (1/2 megohm) and higher indicates the stator is good. A reading of less than 500 kOhms indicates deterioration of the winding insulation and possible current flow to ground. Repair or replace the stator.
7
1. Voltage regulator power supply leads
2. Sensing leads (208--240 volts nominal)
3. Stator windings
4. Main field (rotor)
5. Rectifier module
6. Frame connection
7. Megohmmeter
8. Armature
9. Exciter field
6
TP-5936517
Figure 7-16 Megohmmeter Connections on Stator,
1 Phase
1
2
F1 F2
9
3
4
TP-5936 7/04 35Section 7 Generator Troubleshooting
7
8
5
6
TP-5936518
1. Voltage regulator power supply leads
2. Sensing leads (208--240 volts nominal)
3. Stator windings
4. Main field (rotor)
5. Frame connection
6. Megohmmeter
7. Rectifier module
8. Armature
9. Exciter field
Figure 7-17 Megohmmeter Connections on Stator,
3 Phase
Page 48
Notes
TP-5936 7/0436 Section 7 Generator Troubleshooting
Page 49
Section 8 Component Troubleshooting
8.1 General
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Component Voltmeter Connections Procedure Results
Hourmeter and wiring Connect the red test lead to
Stator auxiliary winding B1 and B2
Moving rotor.
the hourmeter positive (+) terminal. Connect the black test lead to the hourmeter negative (--) terminal.
None (see Procedure) Disconnect the hourmeter
Connect the AC voltmeter leads to the B1 and B2 windings at connector P11.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
See Figure 8-1 through Figure 8-2 for component testing.
With the generator set battery connected, check the generator wiring harness and the components listed in the following tables. Check each component using a multimeter to verify that the switches function and that voltage is present at each component.
Set the voltmeter to 12 volts DC or greater. Start the generator set.
leads and apply 12 volts DC to the hourmeter. The hourmeter is polarity sensitive.
Stop the generator set. Connect a voltmeter to the B1 and B2 windings. Crank the generator set and allow the set to reach rated its speed.
A 12 volt DC reading indicates the wiring harness is functional.
If functional, hourmeter operates.
A reading of 12--15 volts AC indicates a functional B1/B2 winding.
Figure 8-1 Engine/Generator Component Testing, Relay Controller
TP-5936 7/04 37Section 8 Component Troubleshooting
Page 50
Note: Before performing ohmmeter checks, disconnect
the generator set battery to prevent damage to the ohmmeter.
To further check the generator set components,
plugs from the controller circuit board. Use an ohmmeter to check the continuity of the components and to isolate inoperative components. Refer to Figure 8-2.
disconnect the battery and remove the wiring harness
Component Ohmmeter Connections Procedure Results
Start/stop switch Connect the ohmmeter to the P2-6
K20 relay coil and wiring
Starter solenoid (S relay)
Controller 10-amp circuit breaker and wiring
Main field (rotor) Disconnect the P10 and P11
B1/B2 stator windings Connect the ohmmeter to the
P1 ground connection Connect the ohmmeter to the P1-9
High exhaust temperature (HET), low coolant (LCS) safety shutdown switches
Low oil pressure (LOP) safety shutdown switch
and P2-4 leads.
Connect the ohmmeter to the P2-6 and P2-5 leads.
Connect the ohmmeter to the P1-4 and P1-9 leads.
Connect the ohmmeter to the P4-22 lead and the battery positive (+) cable. Note: The J4 and P4 leads must be disconnected to perform this test.
Connect the ohmmeter to the battery positive (+) cable and the P1-14 lead. Note: The J4 and P4 leads must be connected to perform this test.
connectors and connect the ohmmeter to the P10-1 and P10-2 leads.
P11-1 and P11-2 leads. Note: Disconnect P11 and J11 to perform this test.
and ground.
Connect the ohmmeter to the P1-15 and engine block (ground). Note: Remove and isolate the LOP switch lead.
Connect the ohmmeter to the P13-1 and engine block (ground).
Place the ohmmeter on the R x 1000 scale. Place the rocker switch in the START position.
Place the ohmmeter on the R x 1000 scale. Place the rocker switch in the STOP position.
Place the ohmmeter on theRx1scale.
Place the ohmmeter on theRx1scale.
Place the ohmmeter on the R x 1000 scale.
Place the ohmmeter on theRx1scale.
Place the ohmmeter on theRx1scale.
Place the ohmmeter on theRx1scale.
Place the ohmmeter on the R x 1000 scale.
Place the ohmmeter on the R x 1000 scale. This test is not conclusive until the temperature shutdown switches are checked.
If the switch is functional, zero ohms continuity. Any resistance other than zero or very low ohms, replace the switch.
If the switch is functional, zero ohms continuity. Any resistance other than zero or very low ohms, replace the switch.
If functional, 85 ohms. Low resistance, shorted C relay coil and/or wiring. High resistance, open C relay and/or wiring. Replace the controller board.
If functional, approximately
0.5--0.6 ohms at 27°C(80°F).
If functional, zero or very low ohms. No reading (infinity), open circuit or circuit breaker tripped.
If the resistance readings match those specified in Section 1, Specifications, the rotor is functional. Low resistance, rotor windings shorted. High resistance, rotor windings open.
If the resistance readings match those specified in Section 1, Specifications, the B1/B2 windings are functional. Low resistance, B1/B2 windings shorted. High resistance, B1/B2 windings open.
If functional, zero ohms (continuity). Any other reading indicates a poor ground connection.
If functional, open circuit. Any continuity suggests an inoperative temperature switch(es). Replace the switch(es).
If functional, zero ohms (continuity). Then, disconnect the LOP switch lead and isolate the terminal. Meter reading should show an open circuit.
Figure 8-2 Engine/Generator Component Testing, Relay Controller
TP-5936 7/0438 Section 8 Component Troubleshooting
Page 51
8.2 Remote Panels (Optional)
open or shorted. Refer to Figure 8-3 and Figure 8-4 for resistance values. Refer to Figure 8-5 for
Kohler Co. offers three remote panels for connection to
troubleshooting information on the remote start panels.
the generator set:
D A panel with a start/stop switch
D A panel with a start/stop switch and two gauges
(engine oil pressure and water temperature)
D A panel with a start/stop switch and four gauges (DC
voltmeter, engine oil pressure, water temperature,
Figure 8-3 Water Temperature Sender Resistance
2-Meter and 4-Meter Panels
Temperature Resistance
60_C (140_F)
90_C (194_F)
100_C (212_F)
134 ± 10 ohms
51.5 ± 4 ohms
38 ± 3 ohms
and hourmeter)
If difficulty with the remote operation occurs, test the switch, gauges, and gauge senders using the following procedures. See Section 10, Voltage Reconnection and Wiring Diagrams.
345 kPa (50 psi)
690 kPa (100 psi)
2-Meter and 4-Meter Panels
Pressure Resistance
0 kPa (0 psi)
Generally, if the sender changes its resistance values as its respective pressure/temperature changes, it is
Figure 8-4 Oil Pressure Sender Resistance
working correctly. An inoperative sender will either be
Component Ohmmeter Connections Procedure Results
Remote start/stop switch
Generator set ON light, gauge lights, DC voltmeter, and hourmeter
Water temperature gauge
Oil pressure gauge
Note: Check continuity of gauge wiring and extension harness before replacing components.
Remote switch: yellow/red wire terminal and black wire terminal.
Remote switch: grey/black wire terminal and black wire terminal.
Connect the red test lead to P3-4 and black test lead to P3-1.
Connect the red test lead to P3-4 (socket side) and black test lead to P3-2 (socket side).
Connect the red test lead to P3-4 (socket side) and black test lead to P3-3 (socket side).
Place the ohmmeter on the R x 1 scale. Press the rocker switch to the START position.
Place the ohmmeter on the R x 1 scale. Press the rocker switch to the STOP position.
Place the controller rocker switch to the START position. Stop the generator set when the test is complete. Generator set does not need to be running, just cranking for this test. Note: If the hourmeter is not illuminated, test it by connecting it to a 12-volt battery. Note:The hourmeter is polarity sensitive.
Start the generator set for the test. If 0.5--12-volts DC is present and
Start the generator set for the test. If 0.5--12-volts DC is present and
Continuity, the switch is functional. Open, replace switch.
Continuity, the switch is functional.
If 12-volts DC is present and the component does not function after the J3 is connected to the controller P3, replace the component(s).
the gauge does not function after the J3 is connected to controller, replace the gauge.
the gauge does not function after the J3 is connected to the controller, replace the gauge.
10 ohms
80 ohms
135 ohms
Figure 8-5 Remote Start Panels Troubleshooting
TP-5936 7/04 39Section 8 Component Troubleshooting
Page 52
Notes
TP-5936 7/0440 Section 8 Component Troubleshooting
Page 53
Section 9 Generator Disassembly/Reassembly
9.1 Disassembly
In some installations, it is not possible to remove the generator set from the craft.
Disconnect the external connections—battery cables (negative lead first), AC-output leads in the controller, remote start panel at the controller P3 connector, water line at the seawater pump, fuel line at the fuel pump filter inlet, and exhaust line at the mixing elbow. Observe all of the safety precautions listed during the disassembly/ reassembly procedures.
Note: Because this manual covers several models, the
procedure for disassembly may vary because of product updates and the assembly variations.
Disassembly Procedure
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, the negative (--) lead first.
3. Loosen the 4 screws and lift off the controller cover.
4. Disconnect the P4 (22-pin) connector from J4. See Figure 9-1.
5. Remove the bolt and disconnect the ground strap. SeeFigure9-1.
Note: It is possible to connect the output leads in
various positions for different voltage configurations. Mark the leads for correct reconnection.
1
2
3
4
8
14
9 15
19
20
21
22
1. P4 (22-Pin) connector
2. Ground strap
Figure 9-1 22-Pin Connector
2
1
1. Controller mount locknut
2. Socket with extension
3. Neutral stud (L0)
Figure 9-2 Controller Removal
1
2
GB-250000B-G
3
558863
6. Disconnect the generator output leads 1, 2, 3, and 4 from the circuit breaker and the neutral stud (L0).
7. Remove the 4 controller mount locknuts. See Figure 9-2.
8. Lift the controller from the rubber mounts while guiding the leads through the bottom hole of the controller box.
9. Remove the tie wraps from the wire harness as necessary. Disconnect the F1 connectors from the resistor leads.
10. Disconnect the P7 (FP and FN) and P6 (F1 and F2) connectors.
TP-5936 7/04 41Section 9 Generator Disassembly/Reassembly
Page 54
2
1
3
4
5
2
1
3
1. 3/8 in. nut (4) and plain washer (4)
2. End bracket cover
3. Vibromount hardware
Figure 9-3 Alternator, End View
2
1
3
3
5936
1. Bolt (3/8 x 16 x 1.25)
558864
2. Plate 4” x 1/4” min.
3. Washers (4)
4. Alternator
5. Rotor
Figure 9-5 Securing the Rotor
11. Remove the vibromount mounting hardware. See Figure 9-3.
Note: Use a hoist with a capacity rating of one-half
ton or greater.
12. Remove the 4 nuts and washers securing the alternator end bracket cover to the alternator end. See Figure 9-3.
13. Raise the alternator end of the generator set and place a wood block under the oil pan/flywheel area. Lower the alternator. See Figure 9-4.
2
1. Alternator end bracket
2. Alternator end bracket mounting bolts
3. Alternator fan guard
4. Wood support block
4
Figure 9-4 Raising the Alternator
558865
14. Secure the rotor to the alternator with a bolt, plate, and 4 washers. The end of the rotor shaft is threaded for this purpose. See Figure 9-5.
15. Remove the 2 screws and clips securing the alternator fan guard to the alternator. See Figure 9-4.
TP-5936 7/0442 Section 9 Generator Disassembly/Reassembly
Page 55
16. Support the alternator assembly and remove the 8 bolts, washers, and spacers securing the rotor assembly to the engine flywheel. See Figure 9-6.
17. Remove the 12 bolts and washers securing the alternator side alternator adapter to the engine side alternator adapter and carefully remove the alternator assembly. See Figure 9-6.
18. Remove the 8 bolts and washers securing the armature drive discs to the rotor drive hub. See Figure 9-6.
19. Place the alternator assembly on the floor and remove the bolt, plate, and 4 washers.
20. Rotate the alternator assembly in a vertical position with the rotor hub facing upward. See Figure 9-7.
21. Connect the hoist securely to the rotor hub with an eyebolt or lifting plate.
22. Carefully lift the rotor out of the stator housing.
1
2
6
3
5
4
9
7
8
10
23. Remove the 4 alternator end bracket bolts. See Figure 9-8.
24. Carefully remove the end bracket with the exciter field and wires from the stator housing. See Figure 9-8.
558865
Figure 9-7 Alternator Position
16
15
1. Bolt (3/8-16 x 2.5 in.) and washer
2. Alternator side alternator adapter
3. Rotor
4. Rotor hub
5. Nut (10-32)
6. Alternator fan
7. Armature drive disc (alternator fan)
8. Armature drive disc (engine flywheel)
9. Engine side alternator adapter
10. Flywheel
11. Flywheel stud (8)
12. Bolt (M10-1.5) and washer
13. Bolt (3/8-16 x 1.25 in.) and washer (3/8 in.)
14. Spacers (16) 2 on each stud
15. Washer (8)
16. Nut (8) @39 ft. lbs.
13
14
Figure 9-6 Alternator Disassembly
12
11
558866
1
4
2
3
3
5
1. Alternator end bracket and exciter field
2. Stator
3. Stator mounting bolts (3/8-16 x 1.75 in.) and washers (6)
4. Alternator adapter mounting bolts (3/8-16 x 2.5 in.) and washers (12)
5. End bracket bolts
Figure 9-8 Alternator Disassembly
558865
TP-5936 7/04 43Section 9 Generator Disassembly/Reassembly
Page 56
9.2 Reassembly
1. Reinstall the alternator end bracket with the exciter field. Feed the exciter leads into the hole in the top of the stator housing. Torque the mounting bolts to
38.0 Nm (28 ft. lbs.). See Figure 9-9.
2. Gently insert the rotor into the stator housing. Be careful to avoid damaging the rotor assembly or the stator during installation. See Figure 9-10.
3. Secure the rotor to the alternator with a bolt, plate, and 4 washers. The end of the rotor shaft is threaded for this purpose. See Figure 9-5.
4. Using alignment pins, align the loose armature drive disk to the alternator fan and attach to the rotor drive hub with 8 bolts (3/8-16 x 1.25 in.) and washers. Torque the bolts to 61.0 Nm (45 ft. lbs.). SeeFigure9-6.
558865
Figure 9-10 Alternator Position
1
5
1. Alternator end bracket and exciter field
2. Stator
3. Stator mounting bolts (3/8-16 x 1.75 in.) and washers (6)
4. Alternator adapter mounting bolts (3/8-16 x 2.5 in.) and washers (12)
4
2
3
3
Figure 9-9 Exciter Reinstallation
558865
5. Secure the alternator assembly to the engine flywheel studs with washers, nuts, and spacers. Torque the mounting nuts to 52.9 Nm (39 ft. lbs).
6. Secure the alternator side adapter to the engine side alternator adapter with 12 bolts (3/8-16 x 2.5 in.) and washers. Torque the mounting bolts to 52.9 Nm (39 ft. lbs.).
7. Reinstall the alternator fan guard using two spring clips and screws.
8. Raise the alternator end of the generator set and remove the wood block under the oil pan/flywheel area. Lower the alternator.
9. Reinstall the vibromount mounting hardware (bolt, large washer, two small washers, and locknut in each vibromount). Tighten the mounting bolts to 28 Nm (20 ft. lbs.).
TP-5936 7/0444 Section 9 Generator Disassembly/Reassembly
Page 57
Section 10 Voltage Reconnection and Wiring Diagrams
10.1 4-Lead Reconnection
The following information illustrates the reconnection of 4-lead generator sets. In all cases, follow the National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
10.1.1 100--120-Volt Configurations
If the installation requires a factory two-pole circuit breaker, do not connect the load-side terminals of the circuit breaker together. See Figure 10-1. If the installation requires a 100--120-volt, 2-wire system, use a single-pole circuit breaker. See Figure 10-2. When connecting stator phase leads together, size the output lead (L1) accordingly to handle the amperage. Use a jumper lead on the line side of the circuit breaker to balance the load of the generator set.
L0 (Neutral)
Ground
Load Side
Line Side
4321
Stator Leads
60 Hz 50 Hz
L0--L1 100--120 Volt 100--120 Volt L0--L2 100--120 Volt 100--120 Volt
L0
GRD.
L1
Single-Pole Circuit Breaker
Figure 10-2 100--120-Volt, 2-Wire Configuration
L0 (Neutral)
Ground
Load Side
Line Side
4321
60 Hz 50 Hz
L0--L1 100--120 Volt 100--120 Volt L0--L2 100--120 Volt 100--120 Volt
L0
GRD.
L1 L2
Two-Pole Circuit Breaker
Jumper lead
Figure 10-1 100--120-Volt, 3-Wire Configuration
TP-5936 7/04 45Section 10 Voltage Reconnection and Wiring Diagrams
Page 58
L0 (Neutral)
Ground
Load Side
Line Side
4321
Stator Leads
60 Hz 50 Hz
L0--L1 100--120 Volt 100--120 Volt L0--L2 100--120 Volt 100--120 Volt L1--L2 200--240 Volt 200--240 Volt
L0
GRD.
L2
L1
Factory Two-Pole Circuit Breaker
Figure 10-3 100--120/200--240-Volt, 3-Wire
Configuration
L0 (Neutral)
Ground
Load Side
Line Side
4321
Stator Leads
60 Hz
L0--L1 200-240 Volt 200--220--240 Volt
Single-Pole Circuit Breaker
Tape to insulate from ground
L0
GRD.
L1
50 Hz
Figure 10-4 200--220--240-Volt 2-Wire Configuration
10.1.2 100--120-/200--240-Volt Configurations
The 100--120/200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3 wire, remove the jumper lead (see
Figure 10-1 for location). Select a two-pole circuit breaker. Application of two single-pole circuit breakers does not conform to NEC requirements for supplying a 200--240-volt load, even if the breakers are mechanically attached together. Leads L1 and L2 are for different phases; never connect them together.
10.1.3 200--240-Volt Configurations
The 200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3 wire, remove the jumper lead (see Figure 10-1 for location).
10.2 12-Lead Reconnection
The following reconnection procedure details voltage reconnections only. If the generator set requires frequency changes, adjust the governor and voltage regulator as described earlier in Section 7.5.
The following information illustrates the reconnection of 12-lead generator sets. In all cases, follow the National Electrical Code (NEC) guidelines.
Reconnect the stator leads of the generator set to change output phase or voltage. Refer to the following procedure and connection schematics. Follow all safety precautions at the front of this manual during reconnection procedure.
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
Reconnection Procedure
1. Move the generator set start/stop switch to STOP position.
2. Disconnect the engine starting battery, the negative (--) lead first. Disconnect the power to the battery charger, if equipped.
3. Use Figure 10-3 or Figure 10-4 to determine the generator set voltage configuration. Note the original voltage and reconnect as needed.
TP-5936 7/0446 Section 10 Voltage Reconnection and Wiring Diagrams
Page 59
10.3 Two and Three Wire Manual (Ship-to-Shore) Transfer Switch
Electro Switch
L1
To Generator Set
L2
L1
To Generator Set
L2
2-Wire Generator Sets
2134
6578
To Load
To Shore Power
Kraus Naimler/American Solenoid
(Early Rectangular Design)
2-Wire Generator Sets
1265
348 7
To Shore Power
L1
L2
To Generator Set
L0
L1
L2
To Generator Set
L0
3-Wire Generator Sets
2134
657 8
10 9 11 12
To Load
3-Wire Generator Sets
1265
348 7
91014 13
To Shore Power
To Shore Power
L1
To Generator Set
L2
To Load
Kraus Naimler/American Solenoid
(Newer Round Design)
2-Wire Generator Sets
3241
768 5
To Load
To Shore Power
L1
L2
To Generator Set
L0
To Load
3-Wire Generator Sets
3241
768 5
11 10 12 9
To Load
To Shore Power
TP-5399-5
TP-5936 7/04 47Section 10 Voltage Reconnection and Wiring Diagrams
Page 60
10.4 Four Wire Manual (Ship-to-Shore) Transfer Switch
Kraus Naimer/American Solenoid
4-Wire, 3-phase Generator Sets
To Generator Set To Shore Power
10.5 Generator Reconnection
Generator Connections
Single-Phase
Some sets not rated for single phase, see manuals
Not
Used
110/220 Volt 50 Hz 120/240 Volt 60 Hz
Remove V9 from terminal strip and tape
Single-Phase
(Marine Only)
Tape to insulate
from ground
Not
Used
To Load
3-Phase Delta
110/220 Volt 50 Hz 120/240 Volt 60 Hz
I-940
3-Phase WYE
190-208 Volt 50 Hz 208-240 Volt 60 Hz
3-Phase WYE
220 Volt 50 Hz 240 Volt 50 Hz
Remove V9 from terminal strip and tape
Notes:
CTs not used on all generator sets. Current transformers dot or “HI” toward generator.
380-416 Volt 50 Hz 416-480 Volt 60 Hz
EM-250000-
TP-5936 7/0448 Section 10 Voltage Reconnection and Wiring Diagrams
Page 61
Notes
TP-5936 7/04 49Section 10 Voltage Reconnection and Wiring Diagrams
Page 62
10.6 Single-Phase Wiring Diagram—Schematic
229937-G
TP-5936 7/0450 Section 10 Voltage Reconnection and Wiring Diagrams
Page 63
10.7 Single-Phase Wiring Diagram—Point-to-Point
TP-5936 7/04 51Section 10 Voltage Reconnection and Wiring Diagrams
229937-G
Page 64
10.8 Three-Phase Wiring Diagram—Schematic
229938-D
TP-5936 7/0452 Section 10 Voltage Reconnection and Wiring Diagrams
Page 65
10.9 Three-Phase Wiring Diagram—Point-to-Point
TP-5936 7/04 53Section 10 Voltage Reconnection and Wiring Diagrams
229938-D
Page 66
10.10Remote Start Panel
+--
P
P
P1-14
10-amp fuse
47
P2-4
Local switch
Start
Stop
43
P2-5 P2-6
N
N
P1-9
10.11 Remote Start and Two-Meter Panel
+--
P
10-amp fuse
P
P1-1447P2-4
Local switch
Start
Stop
43
P2-5 P2-6
N
N
P1-9
W.T. sender
O.P. sender
K2
K1
P2-3 P2-7 P2-8 P2-9
70
P3-4
J3-4 J3-5 J3-1J3-6
Violet
Yellow/ Red
Gen. ON light
Relay circuit board
47
Grey/
P3-5 P3-6 P3-1
Black
Stop
Start
43
Remote switch
N
Black
TP-5588-7
K2
K1
P2-3
70
P3-4
J3-4 J3-5
Violet
Yellow/ Red
Gen. ON light
Water temp. gauge
Oil pressure gauge
Relay circuit board
P2-7
47
P3-5 P3-6
Stop
Start
P2-8 P2-9
43 Grey/ Black
Remote switch
J3-6
N
P3-1
Black
P4-2 P4-3
5
P3-2
J3-1
J3-2
Tan
7C
P3-3
J3-3
L. Blue
TP-5588-7
TP-5936 7/0454 Section 10 Voltage Reconnection and Wiring Diagrams
Page 67
10.12Remote Start and Four-Meter Panel
+--
P
10-amp fuse
P
P1-14
K2
K1
P2-3
70
P3-4
J3-4 J3-5
Violet
Yellow/ Red
Gen. ON light
Water temp. gauge
47
P2-4
P2-7
47
P3-5
Local switch
Start
Relay circuit board
Grey/ Black
Stop
Start
Stop
P2-8 P2-9
P3-6
43
N
P2-5 P2-6
N
43
P3-1
J3-6
Remote switch
N
P1-9
W.T. sender
P4-2 P4-3
5
P3-2
J3-1 J3-2 J3-3
Tan
Black
O.P. sender
7C
P3-3
L. Blue
Oil pressure gauge
DC voltmeter
Hourmeter
TP-5588-7
TP-5936 7/04 55Section 10 Voltage Reconnection and Wiring Diagrams
Page 68
Notes
TP-5936 7/0456 Section 10 Voltage Reconnection and Wiring Diagrams
Page 69
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC analog to digital converter adj. adjust, adjustment ADV advertising dimensional
AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only API American Petroleum Institute approx. approximate, approximately AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary A/V audiovisual avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CARB California Air Resources Board CB circuit breaker cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
cogen. cogeneration com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards
CT current transformer Cu copper cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dBA decibel (A weighted) DC direct current DCR direct current resistance deg., ° degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth)
substrate (semiconductor)
Association
e. V. (also Deutsche Industrie Normenausschuss)
Association
Association
Agency
engineered special
exh. exhaust ext. external F Fahrenheit, female fglass. fiberglass FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temperature,
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP iron pipe ISO International Organization for
J joule JIS Japanese Industry Standard
ground
high engine temperature
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
TP-5936 7/04 Appendix A-1
Page 70
k kilo (1000) K kelvin kA kiloampere KB kilobyte (2 kg kilogram
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter
10
bytes)
kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
sound power level, A weighted LWL low water level LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
units), male
cubic meter
/min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCM one thousand circular mils MCCB molded-case circuit breaker meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, m
milliohm
MOhm, M
megohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard m/sec. meters per second
MTBF mean time between failure MTBO mean time between overhauls mtg. mounting MW megawatt mW milliwatt µF microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillips head crimptite (screw) PHH Phillips hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent-magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head
RHM round head machine (screw) rly. relay rms root mean square rnd. round ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTV room temperature vulcanization SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SN serial number SPDT single--pole, double--throw SPST single--pole, single--throw spec, specs
specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer
TP-5936 7/04A-2 Appendix
Page 71
Appendix B Common Hardware Application Guidelines
Use the information below and on the following pages to identify proper fastening techniques when no specific reference for reassembly is made.
Bolt/Screw Length: Whenbolt/screw length is not given, use Figure 1 as a guide. As a general rule, a minimum length of one thread beyond the nut and a maximum length of 1/2 the bolt/screw diameter beyond the nut is the preferred method.
Washers and Nuts: Use split lock washers as a bolt locking device where specified. Use SAE flat washers with whiz nuts, spiralock nuts, or standard nuts and preloading (torque) of the bolt in all other applications.
See Appendix C, General Torque Specifications, and other torque specifications in the service literature.
Preferred Nut/Bolt Clearance
1
2
Steps for common hardware application:
1. Determine entry hole type: round or slotted.
2. Determine exit hole type: fixed female thread (weld nut), round, or slotted.
For round and slotted exit holes, determine if hardware is greater than 1/2 inch in diameter, or 1/2 inch in diameter or less. Hardware that is greater than 1/2 inch in diameter takes a standard nut and SAE washer. Hardware 1/2 inch or less in diameter can take a properly torqued whiz nut or spiralock nut. See Figure 2.
3. Follow these SAE washer rules after determining exit hole type:
a. Always use a washer between hardware and a
slot.
b. Always use a washer under a nut (see 2 above
for exception).
c. Use a washer under a bolt when the female
thread is fixed (weld nut).
Unacceptable Nut/Bolt Clearance
3
1. 1/2 of bolt diameter
2. Min. 1 full thread beyond top of nut
3. Below top of nut
Figure 1 Acceptable Bolt Lengths
G-585
4. Refer to Figure 2, which depicts the preceding hardware configuration possibilities.
1
6
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
2
3
5
4
G-585
TP-5936 7/04 Appendix A-3
Figure 2 Acceptable Hardware Combinations
Page 72
Appendix C General Torque Specifications
T
A
lumi
A
Use the following torque specifications when service literature instructions give no specific torque values. The charts list values for new plated, zinc phosphate, or
American Standard Fasteners Torque Specifications
orque
Size
8-32 Nm (in. lb.) 1.8 (16) 2.3 (20) 1.8 (16)
10-24 Nm (in. lb.) 2.9 (26) 3.6 (32) 2.9 (26)
10-32 Nm (in. lb.) 2.9 (26) 3.6 (32) 2.9 (26)
1/4-20 Nm (in. lb.) 6.8 (60) 10.8 (96) 14.9 (132) 6.8 (60)
1/4-28 Nm (in. lb.) 8.1 (72) 12.2 (108) 16.3 (144) 8.1 (72)
5/16-18 Nm (in. lb.) 13.6 (120) 21.7 (192) 29.8 (264) 13.6 (120)
5/16-24 Nm (in. lb.) 14.9 (132) 23.1 (204) 32.5 (288) 14.9 (132)
3/8-16 Nm (ft. lb.) 24.0 (18) 38.0 (28) 53.0 (39) 24.0 (18)
3/8-24 Nm (ft. lb.) 27.0 (20) 42.0 (31) 60.0 (44) 27.0 (20)
7/16-14 Nm (ft. lb.) 39.0 (29) 60.0 (44) 85.0 (63)
7/16-20 Nm (ft. lb.) 43.0 (32) 68.0 (50) 95.0 (70)
1/2-13 Nm (ft. lb.) 60.0 (44) 92.0 (68) 130.0 (96)
1/2-20 Nm (ft. lb.) 66.0 (49) 103.0 (76) 146.0 (108)
9/16-12 Nm (ft. lb.) 81.0 (60) 133.0 (98) 187.0 (138)
9/16-18 Nm (ft. lb.) 91.0 (67) 148.0 (109) 209.0 (154)
5/8-11 Nm (ft. lb.) 113.0 (83) 183.0 (135) 259.0 (191)
5/8-18 Nm (ft. lb.) 128.0 (94) 208.0 (153) 293.0 (216)
3/4-10 Nm (ft. lb.) 199.0 (147) 325.0 (240) 458.0 (338)
3/4-16 Nm (ft. lb.) 222.0 (164) 363.0 (268) 513.0 (378)
1-8 Nm (ft. lb.) 259.0 (191) 721.0 (532) 1109.0 (818)
1-12 Nm (ft. lb.) 283.0 (209) 789.0 (582) 1214.0 (895)
Measurement
Assembled into Cast Iron or Steel
Grade 2 Grade 5 Grade 8
oiled threads. Increase values by 15% for nonplated threads. All torque values are +0%/--10%.
Assembled into
num
Grade2or5
Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.)
Size (mm)
M6 x 1.00 5.6 (4) 9.9 (7) 14.0 (10) 5.6 (4)
M8 x 1.25 13.6 (10) 25.0 (18) 35.0 (26) 13.6 (10)
M8 x 1.00 21.0 (16) 25.0 (18) 35.0 (26) 21.0 (16)
M10 x 1.50 27.0 (20) 49.0 (35) 68.0 (50) 27.0 (20)
M10 x 1.25 39.0 (29) 49.0 (35) 68.0 (50) 39.0 (29)
M12 x 1.75 47.0 (35) 83.0 (61) 117.0 (86)
M12 x 1.50 65.0 (48) 88.0 (65) 125.0 (92)
M14 x 2.00 74.0 (55) 132.0 (97) 185.0 (136)
M14 x 1.50 100.0 (74) 140.0 (103) 192.0 (142)
M16 x 2.00 115.0 (85) 200.0 (148) 285.0 (210)
M16 x 1.50 141.0 (104) 210.0 (155) 295.0 (218)
M18 x 2.50 155.0 (114) 275.0 (203) 390.0 (288)
M18 x 1.50 196.0 (145) 305.0 (225) 425.0 (315)
Assembled into Cast Iron or Steel
Grade 5.8 Grade 8.8 Grade 10.9
Assembled into
luminum
Grade 5.8 or 8.8
TP-5936 7/04A-4 Appendix
Page 73
Appendix D Common Hardware Identification
Screw/Bolts/Studs
Head Styles
Hex Head or Machine Head
Hex Head or Machine Head with Washer
Flat Head (FHM)
Round Head (RHM)
Pan Head
Hex Socket Head Cap or Allent Head Cap
Hex Socket Head or Allent Head Shoulder Bolt
Sheet Metal Screw
Stud
Drive Styles
Hex
Hex and Slotted
Phillipsr
Nuts
Nut Styles
Hex Head
Lock or Elastic
Square
Cap or Acorn
Wing
Washers
Washer Styles
Plain
Split Lock or Spring
Spring or Wave
External Tooth Lock
Internal Tooth Lock
Internal-External Tooth Lock
Hardness Grades
American Standard
Grade 2
Grade 5
Grade 8
Grade 8/9 (Hex Socket Head)
Metric
Number stamped on hardware; 5.8 shown
5.8
Slotted
Hex Socket
Allent head screw is a trademark of Holo-Krome Co.
Phillipsr screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20
Length In Inches (Screws and Bolts)
Threads Per Inch
Major Thread Diameter In Fractional Inches Or Screw Number Size
Length In Millimeters (Screws and Bolts)
Distance Between Threads In Millimeters
Major Thread Diameter In Millimeters
Plain Washers
9/32
x5/8x 1/16
Lock Washers
5/8
Thickness
External Dimension
Internal Dimension
Internal Dimension
TP-5936 7/04 Appendix A-5
Page 74
Appendix E Common Hardware List
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No. Dimensions Hex Head Bolts (Grade 5)
X-465-17 1/4-20 x .38 X-465-6 1/4-20 x .50 X-465-2 1/4-20 x .62 X-465-16 1/4-20 x .75 X-465-18 1/4-20 x .88 X-465-7 1/4-20 x 1.00 X-465-8 1/4-20 x 1.25 X-465-9 1/4-20 x 1.50 X-465-10 1/4-20 x 1.75 X-465-11 1/4-20 x 2.00 X-465-12 1/4-20 x 2.25 X-465-14 1/4-20 x 2.75 X-465-21 1/4-20 x 5.00 X-465-25 1/4-28 x .38 X-465-20 1/4-28 x 1.00
X-125-33 5/16-18 x .50 X-125-23 5/16-18 x .62 X-125-3 5/16-18 x .75 X-125-31 5/16-18 x .88 X-125-5 5/16-18 x 1.00 X-125-24 5/16-18 x 1.25 X-125-34 5/16-18 x 1.50 X-125-25 5/16-18 x 1.75 X-125-26 5/16-18 x 2.00 230578 5/16-18 x 2.25 X-125-29 5/16-18 x 2.50 X-125-27 5/16-18 x 2.75 X-125-28 5/16-18 x 3.00 X-125-22 5/16-18 x 4.50 X-125-32 5/16-18 x 5.00 X-125-35 5/16-18 x 5.50 X-125-36 5/16-18 x 6.00 X-125-40 5/16-18 x 6.50
X-125-43 5/16-24 x 1.75 X-125-44 5/16-24 x 2.50 X-125-30 5/16-24 x .75 X-125-39 5/16-24 x 2.00 X-125-38 5/16-24 x 2.75
X-6238-2 3/8-16 x .62 X-6238-10 3/8-16 x .75 X-6238-3 3/8-16 x .88 X-6238-11 3/8-16 x 1.00 X-6238-4 3/8-16 x 1.25 X-6238-5 3/8-16 x 1.50 X-6238-1 3/8-16 x 1.75 X-6238-6 3/8-16 x 2.00 X-6238-17 3/8-16 x 2.25 X-6238-7 3/8-16 x 2.50 X-6238-8 3/8-16 x 2.75 X-6238-9 3/8-16 x 3.00 X-6238-19 3/8-16 x 3.25 X-6238-12 3/8-16 x 3.50 X-6238-20 3/8-16 x 3.75 X-6238-13 3/8-16 x 4.50 X-6238-18 3/8-16 x 5.50 X-6238-25 3/8-16 x 6.50
Part No. Dimensions Hex Head Bolts, cont.
X-6238-14 3/8-24 x .75 X-6238-16 3/8-24 x 1.25 X-6238-21 3/8-24 x 4.00 X-6238-22 3/8-24 x 4.50
X-6024-5 7/16-14 x .75 X-6024-2 7/16-14 x 1.00 X-6024-8 7/16-14 x 1.25 X-6024-3 7/16-14 x 1.50 X-6024-4 7/16-14 x 2.00 X-6024-11 7/16-14 x 2.75 X-6024-12 7/16-14 x 6.50
X-129-15 1/2-13 x .75 X-129-17 1/2-13 x 1.00 X-129-18 1/2-13 x 1.25 X-129-19 1/2-13 x 1.50 X-129-20 1/2-13 x 1.75 X-129-21 1/2-13 x 2.00 X-129-22 1/2-13 x 2.25 X-129-23 1/2-13 x 2.50 X-129-24 1/2-13 x 2.75 X-129-25 1/2-13 x 3.00 X-129-27 1/2-13 x 3.50 X-129-29 1/2-13 x 4.00 X-129-30 1/2-13 x 4.50 X-463-9 1/2-13 x 5.50 X-129-44 1/2-13 x 6.00
X-129-51 1/2-20 x .75 X-129-45 1/2-20 x 1.25 X-129-52 1/2-20 x 1.50
X-6021-3 5/8-11 x 1.00 X-6021-4 5/8-11 x 1.25 X-6021-2 5/8-11 x 1.50 X-6021-1 5/8-11 x 1.75 273049 5/8-11 x 2.00 X-6021-5 5/8-11 x 2.25 X-6021-6 5/8-11 x 2.50 X-6021-7 5/8-11 x 2.75 X-6021-12 5/8-11 x 3.75 X-6021-11 5/8-11 x 4.50 X-6021-10 5/8-11 x 6.00
X-6021-9 5/8-18 x 2.50
X-6239-1 3/4-10 x 1.00 X-6239-8 3/4-10 x 1.25 X-6239-2 3/4-10 x 1.50 X-6239-3 3/4-10 x 2.00 X-6239-4 3/4-10 x 2.50 X-6239-5 3/4-10 x 3.00 X-6239-6 3/4-10 x 3.50
X-792-1 1-8 x 2.25 X-792-5 1-8 x 3.00 X-792-8 1-8 x 5.00
Part No. Dimensions Type
Hex Nuts
X-6009-1 1-8 Standard
X-6210-3 6-32 Whiz X-6210-4 8-32 Whiz X-6210-5 10-24 Whiz X-6210-1 10-32 Whiz
X-6210-2 1/4-20 Spiralock X-6210-6 1/4-28 Spiralock X-6210-7 5/16-18 Spiralock X-6210-8 5/16-24 Spiralock X-6210-9 3/8-16 Spiralock X-6210-10 3/8-24 Spiralock X-6210-11 7/16-14 Spiralock X-6210-12 1/2-13 Spiralock X-6210-15 7/16-20 Spiralock X-6210-14 1/2-20 Spiralock
X-85-3 5/8-11 Standard X-88-12 3/4-10 Standard X-89-2 1/2-20 Standard
Washers
Bolt/
Part No. ID OD Thick. Screw
X-25-46 .125 .250 .022 #4 X-25-9 .156 .375 .049 #6 X-25-48 .188 .438 .049 #8 X-25-36 .219 .500 .049 #10 X-25-40 .281 .625 .065 1/4 X-25-85 .344 .687 .065 5/16 X-25-37 .406 .812 .065 3/8 X-25-34 .469 .922 .065 7/16 X-25-26 .531 1.062 .095 1/2 X-25-15 .656 1.312 .095 5/8 X-25-29 .812 1.469 .134 3/4 X-25-127 1.062 2.000 .134 1
TP-5936 7/04A-6 Appendix
Page 75
Metric
Hex head bolts are hardness grade 8.8 unless noted.
Part No. Dimensions Hex Head Bolts (Partial Thread)
M931-05055-60 M5-0.80 x 55 M931-06040-60 M6-1.00 x 40 M931-06055-60 M6-1.00 x 55 M931-06060-60 M6-1.00 x 60 M931-06060-SS M6-1.00 x 60 M931-06070-60 M6-1.00 x 70 M931-06070-SS M6-1.00 x 70 M931-06075-60 M6-1.00 x 75 M931-06090-60 M6-1.00 x 90 M931-06145-60 M6-1.00 x 145 M931-06150-60 M6-1.00 x 150
M931-08035-60 M8-1.25 x 35 M931-08040-60 M8-1.25 x 40 M931-08045-60 M8-1.25 x 45 M931-08050-60 M8-1.25 x 50 M931-08055-60 M8-1.25 x 55 M931-08055-82 M8-1.25 x 55* M931-08060-60 M8-1.25 x 60 M931-08070-60 M8-1.25 x 70 M931-08070-82 M8-1.25 x 70* M931-08075-60 M8-1.25 x 75 M931-08080-60 M8-1.25 x 80 M931-08090-60 M8-1.25 x 90 M931-08095-60 M8-1.25 x 95 M931-08100-60 M8-1.25 x 100 M931-08110-60 M8-1.25 x 110 M931-08120-60 M8-1.25 x 120 M931-08130-60 M8-1.25 x 130 M931-08140-60 M8-1.25 x 140 M931-08150-60 M8-1.25 x 150 M931-08200-60 M8-1.25 x 200
M931-10040-82 M10-1.25 x 40* M931-10040-60 M10-1.50 x 40 M931-10045-60 M10-1.50 x 45 M931-10050-60 M10-1.50 x 50 M931-10050-82 M10-1.25 x 50* M931-10055-60 M10-1.50 x 55 M931-10060-60 M10-1.50 x 60 M931-10065-60 M10-1.50 x 65 M931-10070-60 M10-1.50 x 70 M931-10080-60 M10-1.50 x 80 M931-10080-82 M10-1.25 x 80* M931-10090-60 M10-1.50 x 90 M931-10090-82 M10-1.50 x 90* M931-10100-60 M10-1.50 x 100 M931-10110-60 M10-1.50 x 110 M931-10120-60 M10-1.50 x 120 M931-10130-60 M10-1.50 x 130 M931-10140-60 M10-1.50 x 140 M931-10180-60 M10-1.50 x 180 M931-10235-60 M10-1.50 x 235 M931-10260-60 M10-1.50 x 260 M960-10330-60 M10-1.25 x 330
M931-12045-60 M12-1.75 x 45 M960-12050-60 M12-1.25 x 50 M960-12050-82 M12-1.25 x 50* M931-12050-60 M12-1.75 x 50 M931-12050-82 M12-1.75 x 50* M931-12055-60 M12-1.75 x 55 M931-12060-60 M12-1.75 x 60 M931-12060-82 M12-1.75 x 60* M931-12065-60 M12-1.75 x 65 M931-12075-60 M12-1.75 x 75 M931-12080-60 M12-1.75 x 80 M931-12090-60 M12-1.75 x 90 M931-12100-60 M12-1.75 x 100 M931-12110-60 M12-1.75 x 110
Part No. Dimensions Hex Head Bolts (Partial Thread),
continued
M960-16090-60 M16-1.50 x 90 M931-16090-60 M16-2.00 x 90 M931-16100-60 M16-2.00 x 100 M931-16100-82 M16-2.00 x 100* M931-16120-60 M16-2.00 x 120 M931-16150-60 M16-2.00 x 150
M931-20065-60 M20-2.50 x 65 M931-20090-60 M20-2.50 x 90 M931-20100-60 M20-2.50 x 100 M931-20120-60 M20-2.50 x 120 M931-20140-60 M20-2.50 x 140 M931-20160-60 M20-2.50 x 160
M931-22090-60 M22-2.50 x 90 M931-22120-60 M22-2.50 x 120 M931-22160-60 M22-2.50 x 160
M931-24090-60 M24-3.00 x 90 M931-24120-60 M24-3.00 x 120 M931-24160-60 M24-3.00 x 160 M931-24200-60 M24-3.00 x 200
Hex Head Bolts (Full Thread)
M933-04006-60 M4-0.70 x 6
M933-05030-60 M5-0.80 x 30 M933-05035-60 M5-0.80 x 35 M933-05050-60 M5-0.80 x 50
M933-06010-60 M6-1.00 x 10 M933-06012-60 M6-1.00 x 12 M933-06014-60 M6-1.00 x 14 M933-06016-60 M6-1.00 x 16 M933-06020-60 M6-1.00 x 20 M933-06025-60 M6-1.00 x 25 M933-06030-60 M6-1.00 x 30 M933-06040-60 M6-1.00 x 40 M933-06050-60 M6-1.00 x 50
M933-07025-60 M7-1.00 x 25
M933-08010-60 M8-1.25 x 10 M933-08012-60 M8-1.25 x 12 M933-08016-60 M8-1.25 x 16 M933-08020-60 M8-1.25 x 20 M933-08025-60 M8-1.25 x 25 M933-08030-60 M8-1.25 x 30 M933-08030-82 M8-1.25 x 30*
M933-10012-60 M10-1.50 x 12 M961-10020-60 M10-1.25 x 20 M933-10020-60 M10-1.50 x 20 M933-10025-60 M10-1.50 x 25 M961-10025-60 M10-1.25 x 25 M933-10025-82 M10-1.50 x 25* M961-10030-60 M10-1.25 x 30 M933-10030-60 M10-1.50 x 30 M933-10030-82 M10-1.50 x 30* M961-10035-60 M10-1.25 x 35 M933-10035-60 M10-1.50 x 35 M933-10035-82 M10-1.50 x 35* M961-10040-60 M10-1.25 x 40
Part No. Dimensions Hex Head Bolts (Full Thread),
continued
M933-12016-60 M12-1.75 x 16 M933-12020-60 M12-1.75 x 20 M961-12020-60F M12-1.50 x 20 M933-12025-60 M12-1.75 x 25 M933-12025-82 M12-1.75 x 25* M961-12030-60 M12-1.25 x 30 M933-12030-82 M12-1.75 x 30* M961-12030-82F M12-1.50 x 30* M933-12030-60 M12-1.75 x 30 M933-12035-60 M12-1.75 x 35 M961-12040-82 M12-1.25 x 40* M933-12040-60 M12-1.75 x 40 M933-12040-82 M12-1.75 x 40*
M961-14025-60 M14-1.50 x 25 M933-14025-60 M14-2.00 x 25 M961-14050-82 M14-1.50 x 50*
M961-16025-60 M16-1.50 x 25 M933-16025-60 M16-2.00 x 25 M961-16030-82 M16-1.50 x 30* M933-16030-82 M16-2.00 x 30* M933-16035-60 M16-2.00 x 35 M961-16040-60 M16-1.50 x 40 M933-16040-60 M16-2.00 x 40 M961-16045-82 M16-1.50 x 45* M933-16045-82 M16-2.00 x 45* M933-16050-60 M16-2.00 x 50 M933-16050-82 M16-2.00 x 50* M933-16060-60 M16-2.00 x 60 M933-16070-60 M16-2.00 x 70
M933-18035-60 M18-2.50 x 35 M933-18050-60 M18-2.50 x 50 M933-18060-60 M18-2.50 x 60
M933-20050-60 M20-2.50 x 50 M933-20055-60 M20-2.50 x 55
M933-24060-60 M24-3.00 x 60 M933-24065-60 M24-3.00 x 65 M933-24070-60 M24-3.00 x 70
Pan Head Machine Screws
M7985A-03010-20 M3-0.50 x 10 M7985A-03012-20 M3-0.50 x 12
M7985A-04010-20 M4-0.70 x 10 M7985A-04016-20 M4-0.70 x 16 M7985A-04020-20 M4-0.70 x 20 M7985A-04050-20 M4-0.70 x 50 M7985A-04100-20 M4-0.70 x 100
M7985A-05010-20 M5-0.80 x 10 M7985A-05012-20 M5-0.80 x 12 M7985A-05016-20 M5-0.80 x 16 M7985A-05020-20 M5-0.80 x 20 M7985A-05025-20 M5-0.80 x 25 M7985A-05030-20 M5-0.80 x 30 M7985A-05080-20 M5-0.80 x 80 M7985A-05100-20 M5-0.80 x 100
M7985A-06100-20 M6-1.00 x 100
Flat Head Machine Screws
M965A-04012-SS M4-0.70 x 12
M965A-05012-SS M5-0.80 x 12 M965A-05016-20 M5-0.80 x 16 M965A-06012-20 M6-1.00 x 12
* This metric hex bolt’s hardness is grade 10.9.
TP-5936 7/04 Appendix A-7
Page 76
Metric, continued
Part No. Dimensions Type Hex Nuts
M934-03-50 M3-0.50 Standard
M934-04-50 M4-0.70 Standard M934-04-B M4-0.70 Brass
M934-05-50 M5-0.80 Standard
M934-06-60 M6-1.00 Standard M934-06-64 M6-1.00 Std. (green) M6923-06-80 M6-1.00 Spiralock M982-06-80 M6-1.00 Elastic Stop
M934-08-60 M8-1.25 Standard M6923-08-80 M8-1.25 Spiralock M982-08-80 M8-1.25 Elastic Stop
M934-10-60 M10-1.50 Standard M934-10-60F M10-1.25 Standard M6923-10-80 M10-1.50 Spiralock M6923-10-62 M10-1.50 Spiralock[ M982-10-80 M10-1.50 Elastic Stop
M934-12-60 M12-1.75 Standard M934-12-60F M12-1.25 Standard M6923-12-80 M12-1.75 Spiralock M982-12-80 M12-1.75 Elastic Stop
M982-14-60 M14-2.00 Elastic Stop
M6923-16-80 M16-2.00 Spiralock M982-16-80 M16-2.00 Elastic Stop
M934-18-80 M18-2.5 Standard M982-18-60 M18-2.50 Elastic Stop
M934-20-80 M20-2.50 Standard M982-20-80 M20-2.50 Elastic Stop
M934-22-60 M22-2.50 Standard
M934-24-80 M24-3.00 Standard M982-24-60 M24-3.00 Elastic Stop
M934-30-80 M30-3.50 Standard
Washers
Bolt/
Part No. ID OD Thick. Screw
M125A-03-80 3.2 7.0 0.5 M3 M125A-04-80 4.3 9.0 0.8 M4 M125A-05-80 5.3 10.0 1.0 M5 M125A-06-80 6.4 12.0 1.6 M6 M125A-08-80 8.4 16.0 1.6 M8 M125A-10-80 10.5 20.0 2.0 M10 M125A-12-80 13.0 24.0 2.5 M12 M125A-14-80 15.0 28.0 2.5 M14 M125A-16-80 17.0 30.0 3.0 M16 M125A-18-80 19.0 34.0 3.0 M18 M125A-20-80 21.0 37.0 3.0 M20 M125A-24-80 25.0 44.0 4.0 M24
[ This metric hex nut’s hardness is grade 8.
TP-5936 7/04A-8 Appendix
Page 77
Page 78
Page 79
Page 80
TP-5936 7/04d
E 2000, 2001, and 2004 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPowerSystems.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65)6264-6422, Fax (65)6264-6455
Loading...