Appendix A Abbreviations41..................................................................
Appendix B Electrical Lead Entry Template43...................................................
TP-6733 8/11Table of Contents 3
Page 4
Notes
TP-6733 8/114
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanicalequipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
connected equipment, disable the
generator set as follows: (1) Move the
generator set master switch to the OFF
position. (2) Disconnect the power to
the battery charger. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent starting of
the generator set by an automatic
transfer switch, remotestart/stop
switch, or engine start command from a
remote computer.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
containerwith4L(1gal.)ofwaterand
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
TP-6733 8/115Safety Precautions and Instructions
Page 6
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
cause severe injuryor death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaust systemmustbe
leakproof and routinely inspected.
Generator set operation.Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a potentially
occupied building through windows, air
intake vents, or other openings.
Carbonmonoxidedetectors.
Carbon monoxide can cause severe
nausea, fainting, or death. Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequatelywarnthebuilding’s
occupants of the presence of carbon
monoxide.Keepthe detectors
operational at all times. Periodically
test and replace the carbon monoxide
detectorsaccordingtothe
manufacturer’s instructions.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
TP-6733 8/116Safety Precautions and Instructions
Page 7
Fuel System
Hazardous Noise
CAUTION
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
inawell-ventilatedareaawayfrom
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Gas fuel leaks.Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ouncespersquareinch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage/
Moving Parts
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection ofstandby and
normal sources of supply.
Moving parts.
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodes andstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turnoff the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Welding on the generator set. Can
cause severe electrical equipment
damage.Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnectthebatterycorrectly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).Haveaqualified
electrician install the battery(ies).
TP-6733 8/117Safety Precautions and Instructions
Page 8
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeedinto a utility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
Hot Parts
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
Servicing the engine heater. Hot
parts can cause minor personal
injury or property damage. Install the
heater before connecting it to power.
Operating the heater before installation
can cause burns and component
damage.Disconnect power to the
heater and allow it to cool before
servicing the heater or nearby parts.
TP-6733 8/118Safety Precautions and Instructions
Page 9
This manual provides installation instructions for
Residential/Commercialmodel14/20RESor
14/20RESL generator sets. See Figure 1. Refer to
TP-6734, Operation Manual, for generator set operation
and maintenance instructions.
The generator set is approved for use in stationary
applications in locations served by a reliable utility
power source.
Have an authorized distributor/dealer install the
generator set outdoors according to the instructions in
this manual. The generator set installation must comply
with the National Electrical Code (NEC) and local code
requirements. Do not install this generator set indoors.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual.
Introduction
zaa28533
Figure 114/20RES/RESL Generator Set
Startup and Registration
When the generator set is installed, complete the
startup and installation checklists supplied with the
startup notification form. Complete and sign the startup
notification form and register the unit using the Kohler
online Warranty Processing System.
TP-6733 8/119
Page 10
Service Assistance
For professional advice on generator set power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D VisittheKohlerPower Systemswebsiteat
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax:(33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6733 8/1110
Page 11
Section 1 Installation
1.1General
Have an authorized distributor/dealer install the
generator set outdoors according to the instructions in
this manual. Do not install this generator set indoors.
Use the specifications provided here only in the initial
planning. Use the generator set and transfer switch
dimension drawings and wiring diagrams for installation.
1.2Lifting
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
ModelWeight, kg (lb.)
14RES/RESL186 (410)
20RES/RESL227 (500)
Figure 1-1Approximate Weights
Approximate generator set weights are shown in
Figure 1-1. Use lifting bars inserted through the holes in
the skid to lift the unit. See the dimension drawings on
the following pages for lifting hole locations.
1.3Generator Set Inspection
Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil.Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.See TP-6734,
Operation Manual, for additional information.
1.4Location and Mounting
See the dimension drawings on the following pages for
the generator set dimensions and fuel and electric inlet
locations.The drawing dimensions are shown in
millimeters, with inches in brackets.
Install the generator set outdoors. Provide the minimum
clearance around the generator set shown in the
clearance drawings on the following pages. Locate the
generator set so that the hot exhaust does not blow on
plants or other combustible materials. Do not install the
generator set where exhaust gas could accumulate and
seep inside or be drawn into a potentially occupied
building.
1.4.1Exhaust Requirements
WARNING
TP-6733 8/1111Section 1 Installation
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaust systemmustbe
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
Page 12
The exhaust system is complete for generator sets
installed outdoors.Do not install this generator set
indoors.
Figure 1-2 gives the exhaust temperature at rated load.
The engine exhaust mixes with the generator set
cooling air at the exhaust end of the enclosure. Mount
the generator set so that the hot exhaust does not blow
on plants or other combustible materials. Maintain the
clearances shown in Figure 1-7 in Section 1.5.
Temperature,
Exhaust
Exhaust gas exiting the enclosure
at rated kW, _C(_F)
_C(_F)
260 (500)
Figure 1-2Exhaust Flow and Temperature
The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-3 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.
1
REAR VIEW
1. Air intake
2. Exhaust outlet
1
2
tp6733
Figure 1-3Cooling Air Intake and Exhaust
1.4.2Mounting Area
The generator set is shipped on a plastic mounting pad.
Prepare a flat, level mounting area covered with a weed
barrier and gravel or a concrete mounting pad. Set the
plastic mounting pad directly on the gravel or concrete.
Do not install the mounting pad directly on grass, wood,
or other combustible materials.See Figure 1-7 in
Section 1.5.
The generator set is designed to operate with all
enclosure panels and internal baffling in place. If during
installation, maintenance or repair the unit must be
operated without the complete enclosure and baffling as
shipped from the factory make sure the exhaust panel is
removed as well.
1.5Dimension Drawings
The generator set dimension drawings are shown on the
following pages.
TP-6733 8/1112 Section 1 Installation
Page 13
Figure 1-4Dimension Drawing ADV-8423, Sheet 1
TP-6733 8/1113Section 1 Installation
Page 14
Figure 1-5Dimension Drawing ADV-8423, Sheet 2
TP-6733 8/1114 Section 1 Installation
Page 15
Figure 1-6Dimension Drawing ADV-8423, Sheet 3
TP-6733 8/1115Section 1 Installation
Page 16
Figure 1-7Dimension Drawing ADV-8423, Sheet 4
TP-6733 8/1116 Section 1 Installation
Page 17
1.6Fuel Requirements
The generator set operates using natural gas or LP
vapor fuel. The generator set is EPA-certified for both
natural gas and LP vapor fuels.
The fuel system installation must comply with the NEC
and local codes.
1.6.1Fuel Supply
Because ofvariable climatesandgeographical
considerations, contact the local fuel supplier for fuel
system planning and installation. Figure 1-8 lists the
recommended fuel ratings and other fuel supply
information for natural gas and LP vapor fuels.
Natural
Fuel type
Gas
Fuel supply inlet1/2 NPT
Fuel supply pressure,
kPa (in. H
2
O),
1.3--2.7
(5--11)
Fuel flow rate, maximum, Btu/hr.:
14RES/RESL193,000203,000
20RES/RESL281,000340,000
Nominal Fuel Rating, Btu/ft.
3
Natural gas1000
LP vapor2500
Figure 1-8Fuel Supply
Verify that the output pressure from the primary gas
utility (or LP tank) pressure regulator is 1.7--2.7 kPa
(7--11 in. water column) and that the utility gas meter
flow rate is sufficient to supply the generator set at rated
load plus all other gas-consuming appliances.See
LP
Vapor
1.7--2.7
(7--11)
Figure 1-10 for fuel consumption.Contact the fuel
supplier for flow rate information or a gas meter
upgrade.
The dimension drawing in Section 1.5 shows the
location of the fuel inlet connection.Use flexible
sections to prevent fuel line breakage caused by
vibration. Hold the fuel solenoid valve with a wrench
when tightening the fuel connections. Protect all fuel
lines from machinery or equipment contact, adverse
weather conditions, and environmental damage.
1.6.2Fuel Pipe Size
Ensure that the fuel pipe size and length meet the
specifications in Figure 1-9. Measure the pipe length
from the primary gas pressure regulator to the pipe
connection on the generator set fuel inlet. Add 2.4 m
(8 ft.) to the measured length for each 90 degree elbow.
Compare the total pipe length with the chart in
Figure 1-9 to find the required pipe size.
Contact local LP provider for LP installation information.
Minimum Gas Pipe Size Recommendation, in. NPT
14RES/RESL20RES/RESL
Pipe
Length,
m (ft.)
8(25)3/43/413/4
15(50)13/411
30 (100)1111/41
46 (150)11/4111/411/4
61 (200)11/4111/411/4
Natural
Gas
(193,000
Btu/hr.)
LP Vapor
(203,000
Btu/hr.)
Figure 1-9Fuel Pipe Size Recommendations
Natural
Gas
(281,000
Btu/hr.)
LP Vapor
(340,000
Btu/hr.)
Fuel Type% Load
100%
Natural Gas
LP Vapor
LP vapor conversion factors:
8.58 ft.
0.535 m
36.39 ft.
3
=1lb.
3
=1kg
3
= 1 gal.
75%
50%
25%
100%
75%
50%
25%
Figure 1-10 Fuel Consumption
TP-6733 8/1117Section 1 Installation
Fuel Consumption, m3/hr. (cfh)
14RES/RESL20RES/RESL
60 Hz50 Hz60 Hz50 Hz
5.4(193)4.9(175)8.0(281)6.4(225)
4.7(163)4.2(148)6.9(243)5.4(189)
3.5(124)3.1(108)4.6(161)3.9(139)
2.6(93)2.4(84)3.6(127)2.9(103)
2.3(81)2.1(74)3.9(136)2.9(102)
2.1(75)1.9(68)3.1(109)2.4(85)
1.8(60)1.5(53)2.3(82)1.8(63)
1.2(45)1.1(40)1.7(59)1.3(47)
Nominal fuel rating:
Natural gas:37 MJ/m
LP vapor:93 MJ/m
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
Page 18
1.7Fuel Conversion
The multi-fuel system allows conversion from natural
gas to LP vapor (or vice-versa) in the field while
maintaining emissions-standard compliance. A trained
technician or an authorized distributor/dealer can
convert the fuel system.
Figure 1-11 shows the fuel system components.
Figure 1-12 shows the revised fuel system.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
TP-6733 8/1118 Section 1 Installation
Page 19
1
2
(Enlarged to
show detail)
3
4
1. Regulator
2. Fuel block (not shown; see Figure 1-13) or LP orifice location
(see Figure 1-15)
3. Regulator vent hose (20RES/RESL only)
Figure 1-11 Original Fuel System
2
5
GM66563
4. Fuel solenoid valve and digital spark advance ignition (DSAI)
leads
5. Fuel inlet, 1/2 in. NPT female
DSAI Lead Connection
1
GM80110
1. Regulator
2. Fuel block (not shown; see Figure 1-13) or LP orifice location
(see Figure 1-15)
3
4
3. Fuel solenoid valve and digital spark advance ignition (DSAI)
leads
4. Fuel inlet, 1/2 in. NPT female
DSAI Lead Connection
Figure 1-12 Revised Fuel System
TP-6733 8/1119Section 1 Installation
Page 20
1.7.1Fuel Conversion, 14RES/RESL
Two fuel connections on the fuel block allow fieldconversion between natural gas and LP vapor. The fuel
metering valves are factory-set and sealed to comply
with applicable emission standards and to provide the
best possible hot and cold starting.
Note: Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block. Changing the fuelmetering adjustments may violate federal or state
laws.
Use the following procedure to convert from natural gas
(NG) to LP vapor. The procedure includes moving the
fuel connection from the natural gas to the LP port,
plugging the natural gas port, and disconnecting the
leads for the digital spark advance ignition (DSAI). See
Figure 1-11 or Figure 1-12for the fuelsystem
component locations.
Procedure to convert from NG to LP, 14RES/RESL
1. Press the OFF button on the generator set
controller and remove the F3 fuse (located in the
service access area).
2. Disconnect the power to the battery charger.
1
5
4
2
Natural gas
setup shown
3
GM66563
1. Fuel block
2. Fuel metering valves—factory-sealed, do not adjust
3. Fuel inlet, 1/2 in. NPT
4. Hose fitting
5. Plug
Figure 1-13 Fuel Block, 14RES/RESL
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting in the fuel block. See Figure 1-13.
6. Remove the hose fitting from the natural gas outlet
port in the fuel block. See Figure 1-13.
7. Remove the plug from the LP port in the fuel block.
See Figure 1-13.
8. Clean the plug with a dry cloth or brush, apply fresh
pipe sealant, and install the plug into the natural
gas outlet port.
9. Clean the hose fitting with a dry cloth or brush,
apply fresh pipe sealant to the threads, and install
the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
10. Slide the hose onto the hose fitting and secure it
with the clamp.
14. Reconnect power to the battery charger.
15. Install the F3 fuse and start the generator set by
pressing the RUN button on the generator set
controller.
16. Check for leaks using a gas leak detector.
17. Run the generator set and check the operation.
Use the controller to adjust the output and stability if
necessary. See Section 1.15 for instructions.
18. Press the OFF button to to shut down the generator
set.
Conversion from LP to Natural Gas
To convert from LP vapor to natural gas, follow the fuel
conversion procedure above, moving the hose fitting to
the natural gas port and plugging the LP port. Connect
the DSAI leads for natural gas. See Figure 1-14.
FuelDSAI Leads 65 and N
Natural GasConnect lead 65 to N
LPDisconnect
11. Disconnect the DSAI leads for LP. The DSAI leads
are located near the fuel solenoid valve.See
Figure 1-11 or Figure 1-12.
12. Connect and turn on the new fuel supply.
Figure 1-14 DSAI Connection
TP-6733 8/1120 Section 1 Installation
Page 21
1.7.2Fuel Conversion, 20RES/RESL
For LP vapor fuel, an orifice is used in the fuel line. The
unit is typically shipped set up for natural gas, with the
loose orifice tied near the fuel solenoid valve. To convert
to LP vapor, install the orifice and disconnect the spark
advance leads as described below. See Figure 1-15 for
the fuel system component locations.
Procedure to Convert from NG to LP, 20RES/RESL
Note: LP setup
shown
1
2
3
1. Press the OFF button on the generator set
controller and remove the F3 fuse (located in the
service access area).
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-15.
6. Insert the orifice into the hose fitting.See
Figure 1-15.
7. Slide the hose onto the hose fitting and secure it
with the clamp.
8. Disconnect digital spark-advance module (DSAI)
leads 65 and N5 for LP. The DSAI leads are located
near the fuel solenoid valve. See Figure 1-11 or
Figure 1-12.
9. Connect and turn on the new fuel supply.
10. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
11. Reconnect power to the battery charger.
12. Reinstall fuse F3 and start the generator set by
pressing the RUN button on the generator set
controller.
4
GM66563
5
1. LP orifice
2. Hose fitting
3. Regulator
4. Fuel inlet, 1/2 in. NPT female
5. Vent hose
Figure 1-15 Fuel Regulator and LP Orifice,
20RES/RESL
13. Check for leaks using a gas leak detector.
14. Run the generator set and check the operation.
Use the controller to adjust the output and stability if
necessary. See Section 1.15 for instructions.
15. Press the OFF button to shut down the generator
set.
Conversion from LP to Natural Gas
To convert from LP vapor to natural gas, remove the fuel
orifice and connect the DSAI leads together.
FuelDSAI Leads 65 and N
Natural GasConnect lead 65 to N
LPDisconnect
Figure 1-16 DSAI Connections
TP-6733 8/1121Section 1 Installation
Page 22
1.8Electrical Connections
1.8.1Electrical Lead Entry
WARNING
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection ofstandby and
normal sources of supply.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection
of standby and other sources of power. Electrical backfeed
into a utility electrical system can cause severe injury or death
to utility personnel working on power lines.
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer
switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed
electrician make the following electrical connections.
The electrical installation must comply with the National
Electrical Code (NEC) class 1 wire designation and all
applicable local codes.Canadian installations must
comply with the Canadian Electrical Code (CEC) and
applicable local codes.
Ground the generator set from the GRD terminal inside
controller compartment according to applicable codes.
Drill or punch holes in the enclosure for the electrical
conduit in the locations shown in Figure 1-17.A
full-scale dimensioned template for the hole locations is
printed in Appendix B. See page 43.
1
2
3
ADV--7876
Note: See Appendix B for a full-scale template
with dimensions.
1. 1/2 NPT female fuel inlet
2. ATS signal electrical lead entry point
3. Utility voltage electrical lead entry point
Figure 1-17 Electrical Lead Entry Locations
1.8.2Power Supply
Power must be supplied to the generator set location for
the battery charger and the optional accessories shown
in Figure 1-18.The power source must be GFCI
protected.The power to the accessories must be
available at all times, i.e. the circuit must be powered by
the utility source and backed up by the generator.
Connect power to the utility power connection points on
the terminal block. See Section 1.8.3 and the wiring
diagrams in Section 2 for connection details.See
Figure 1-18 for the power requirements for the battery
charger and accessories.
Power Requirement, Max.
Equipment
Battery charger (standard)1921.6
Carburetor heater (optional)
Battery heater (optional)1100.92
WattsAmpsVol t s
370.33
Figure 1-18 Power Requirements
120
TP-6733 8/1122 Section 1 Installation
Page 23
1.8.3Field-Connection Terminal Block
Procedure
The generator set is equipped with a field-connection
terminal block located in the air inlet area near the
junction box. Leads have been factory-installed from
the junction box to the terminal block for easy field
wiring.
See the dimension drawing in Section 1.5 for the
terminal block location. See Figure 1-19 or Figure 1-20
for terminal block details. Refer to the terminal block
decal for connections and cable sizes. Also see
Section 2, Wiring Diagrams.
Note: The connections on the revised terminal block
are arranged in a different order than the original.
Be sure to follow the connections shown on the
decal on the generator set.
Route AC leads through flexible conduit. Ensure that
the leads and conduit do not interfere with the operation
of the generator set or obstruct the service areas. Route
low-voltage communication leads through separate
conduit.
1. Drill holes for the conduit fittings.See the
Figure 1-17 and Appendix B for the recommended
electrical inlet locations. Feed the cables through
the openings.
2. Connect the leads from the transfer switch
emergency source lugs to the L1 and L2
connections on the generator set terminal block.
3. Connect the neutral (L0) and ground (GRD) leads
from the ATS and the main panel to the
corresponding connection points on the terminal
block. See Section 1.8.4, Grounding.
1
2
GM66565
GM80177
1
2
1. Terminal block
2. Decal
Figure 1-20 Revised Terminal Block
1. Field-connection terminal block
2. Decal
Figure 1-19 Original Field-Connection Terminal Block
TP-6733 8/1123Section 1 Installation
Page 24
4. Connect the ATS or remote start/stop switch.
Route low-voltage communication leads through
separate conduit.
a. For a Model RRT transfer switch: Connect
the Model RRT transfer switch interface panel
to connections ATS1--ATS4. See Figure 1-21.
b. For a remote start/stop switch or Model RDT
or RSB transfer switch: Connect the engine
start leads from the transfer switch or remote
start switch to terminals 3 and 4 on the terminal
block. Route the engine start leads through
separate conduit from the AC power and load
leads.
Note: To ensure that the controller recognizes the
Model RRT transfer switch, connect leads
ATS1 through ATS4 to the terminal block
before connecting the engine starting
battery.
Generator
Set
1
GM66565
5. Connect utility power to the terminal block
connections labelled Utility. Connect to a circuit
that is supplied by the utility source and backed up
by the generator. The power source must be GFCI
protected. See Section 1.8.2 for more information
about the utility power requirement.
ATS
2
ADV-7598
Customer
connections
12--24 AWG
3
4
1. 14/20RES/RESL generator set field-connection terminal block
2. Controller interface module location on the ATS, typical
3. Interface module connector P14
4. ATS1 through ATS4 on generator set field-connection terminal block
Figure 1-21 Model RRT Transfer Switch Connection to Generator Set Terminal Block
GM63552
TP-6733 8/1124 Section 1 Installation
Page 25
1.8.4Grounding
1.9Controller Fuse F3
Ground the generator set. The grounding method must
comply with NEC and local codes.Connect the
grounding strap to the generator set ground lug,
terminal GND inside the controller compartment.
Generator sets are shipped with the generator neutral
bonded (connected) to the generator ground in the
junction box. The requirement for having a bonded
(grounded) neutral or ungrounded neutral is determined
by the type of installation. At installation, the neutral can
be grounded at the generator set or lifted from the
ground stud and isolated if the installation requires an
ungrounded neutral connection at the generator. The
generator set will operate properly with the neutral either
bonded to ground or isolated from ground at the
generator.
Various regulations and site configurations including the
National Electrical Code (NEC), local codes, and the
type of transfer switch used in the application determine
the grounding of the neutral at the generator. NEC
Section 250 is one example that has a very good
explanation of the neutral grounding requirements for
generators.
To prevent controller reset during installation, remove
controller fuse F3 before connecting or disconnecting
the battery cables. See Figure 1-22 for the F3 fuse
location in the controller’s service access area.
1
Service Access Area
2
1.8.5Battery Charger
A battery charger is factory-installed in the battery
compartment to keep the starting battery fully charged.
The battery charger’s DC leads are factory-connected
to the battery. Supply power to the generator set for the
battery charger and carburetor heater as described in
Sections 1.8.2 and 1.8.3. Plug the battery charger’s
power cord into the receptacle on the bottom of the
controller junction box.
Refer to the generator set operation manual for battery
charger operation information.
1. Controller’s service access area (remove cover)
2. Controller fuse F3
Figure 1-22 F3 Fuse Location
TP-6733 8/1125Section 1 Installation
Page 26
1.10 Battery
WARNING
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with 4 L (1 gal.) of water and mix the
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury
or death.Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery.Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--)
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting
the terminals together.
Connecting the battery and the battery charger.
Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and
negative to negative, to avoid electrical shock and damage to
the battery charger and battery(ies).Have a qualified
electrician install the battery(ies).
TP-6733 8/1126 Section 1 Installation
Page 27
Use a 12-volt group 51 battery with a minimum rating of
500 cold cranking amps at 0_F. The generator set uses
a negative ground with a 12-volt engine electrical
system. See Figure 1-23 for battery connections. Make
sure that the battery is correctly connected and the
terminals are tight.
Note: The generator set will not start and circuit board
damage may occur if the battery is connected in
reverse.
Use the following procedure to install and connect the
battery.
Battery Installation Procedure
1. Remove controller fuse F3. The fuse is located in
thecontrollerserviceaccessarea.See
Figure 1-22.
2. Ensure that the starting battery is fully charged
before placing the battery in service.
1
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
2
EZ-273000-J
Figure 1-23 Typical Battery Connection
See the dimension drawing in Section 1.5 for the engine
starting battery location on the air intake side of the
generator set. Standard battery cables provide easy
connection to the battery.
To prevent controller reset during installation, remove
controller fuse F3 before connecting or disconnecting
the battery cables. See Figure 1-22 in Section 1.9 for
the F3 fuse location in the controller’s service access
area.
3. Clean the battery posts and/or adapters if
necessary.
4. Install the battery post adapters, if needed.
5. Place the battery in the housing.
6. Connect the positive (+) lead to the engine starting
battery.
7. Connect the negative (--) lead to the engine starting
battery.
8. Install controller fuse F3.
Refer to the generator set operation manual and the
batterymanufacturer’sinstructionsforbattery
maintenance instructions.
If the battery is disconnected for service or replacement,
the exercise settings on the RDC/DC controller are lost.
Set the exerciser after installing and connecting the
battery. See Section 1.13, Set Exerciser.
TP-6733 8/1127Section 1 Installation
Page 28
1.11 Accessories
Have accessories installed by an authorized distributor/
dealer or a licensed electrician. Follow the installation
instructions provided with each kit. Use separate conduit
for AC and DC leads to reduce the possibility of electrical
interference. Verify that the leads and conduit do not
interfere with the operation of the generator set or
obstruct the service areas. Verify that the electrical
installation complies with the National Electrical Code
(NEC) and all applicable local codes. See Section 2,
Wiring Diagrams, for more information regarding
generator set electrical connections.
1.11.1Regulator Heater
The regulator heater kit is designed for Model 20RES
and 20RESL generator sets. The regulator heater kit is
recommended in addition to the carburetor heater for
reliable engine starting in temperatures below --18_C
(0_F). See Figure 1-24 for heater specifications.
Regulator Heater
Heater rating120 VAC, 60 W
Thermostat
Pad diameter127 mm (5 in.)
Cord length610 mm (24 in.)
4_C/13_C (40_F/55_F) Snap action
Figure 1-24 Regulator Heater Specifications
The regulator heater requires a source of 120 VAC
power. The generator set is equipped with two 120 VAC
receptacles, one of which is used for the battery charger.
If another accessory such as the carburetor heater or
battery heater is also used, the installer will need to
provide another receptacle for the regulator heater. The
circuit should be ground fault protected.
To install the regulator heater kit, follow the instructions
in TT-1569, provided with the kit. Figure 1-25 shows the
installed regulator heater kit.
An optional carburetor heater is recommended for
improved cold starting in locations where the ambient
temperature drops below 0_C (32_F). The carburetor
heater prevents condensation and carburetor icing. The
heater turns on when the temperature at the thermostat
falls below approximately 4_C(40_F) and turns off when
the temperature rises above approximately 16_C
(60_F).The carburetor heaters are shown in
Figure 1-26.
To install the carburetor heater, follow the instructions
provided with the kit. Figure 1-27 shows the installed
carburetor heater kit installed for a 14 kW generator set.
Figure 1-28 shows the location for the carburetor heater
kit on a 20 kW generator set.
The heater thermostat is installed in the cord.
Figure 1-26 shows the location of the thermostat on the
power cord. The heater power cord and thermostat are
located in the generator set housing air intake area/
battery compartment.
Note: Do not place the heater thermostat inside the
generator setengine compartment.The
thermostat must be exposed to the ambient air.
1
1. Carburetor heater (air cleaner removed to show heater)
2. Carburetor heater power cord
2
Figure 1-27 14RES/RESL Carburetor Heater
tp6195
The heater requires a continuous source of power. Plug
the carburetor heater into one of the 120 VAC
receptacles provided.
1
2
3
14RES/RESL Carburetor Heater
GM19463
1
2
3
20RES/RESL Carburetor Heater
GM57968
1. Power plug
2. Thermostat
3. Heater
1
tp6514
1. Carburetor heater location
Figure 1-28 20RES/RESL Carburetor Heater
Location on Engine (bulkhead removed
to show heater location)
Figure 1-26 Carburetor Heaters
TP-6733 8/1129Section 1 Installation
Page 30
1.12 Prestart Installation Check
1.13 Set Exerciser
Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is ready
for operation. Check all items in the following Prestart
Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Enclosure.Check that all enclosure panels and
internal baffling are in place.
Exhaust System.Check for exhaust leaks and
blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed.
Set the exerciser to automatically run the generator set
on the desired day and time every week. See TP-6734,
Operation Manual, for detailed descriptions of the
unloaded and loaded exercise operation.
Procedure to Set the Exerciser
1. Press the AUTO button on the controller.
2. Press the down arrow button (RDC) or the exercise
button (DC) to start an unloaded exercise. The
engine starts and runs a 20-minute unloaded
variable-speed exercise with system diagnostics.
EnLd is displayed.
3. If the generator set is connected to a Kohlerr Model
RRT transfer switch, the exercise can be changed
to a loaded exercise by pressing the down arrow
button (RDC) or the exercise button (DC) again
after the engine has started. ELdis displayed.
4. After 20 minutes, verify that the exercise ends and
the engine shuts down automatically.After a
loaded exercise, the engine runs for 5 minutes or
until cool, and then shuts down.
The exercise will run every seven days at the same time
that the exercise was started.
Other transfer switches: For a loaded exercise with a
transfer switch other than a Kohlerr Model RRT, refer to
the transfer switch operation manual for instructions.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
TP-6733 8/1130 Section 1 Installation
Page 31
1.14 Controller Configuration
1.14.1 Firmware Version Number
The controller configuration for each generator model is
set at the factory and should not normally require
changes.
An authorized Kohler distributor/dealer can adjust the
RDC controllerconfiguration andgenerator set
performance using the RDC controller keypad. Use the
select and arrow buttons to change settings or adjust
performance as described in the following sections.
Note: The DC controller cannot be adjusted from the
controller keypad.
An authorized Kohler distributor/dealer can adjust the
controller configuration and generator set performance
on both the RDC and DC controllers using Kohlerr
SiteTecht software and a personal computer. Contact
an authorized Kohler distributor/dealer for service.
Adjust the controller configuration with the generator set
off.Adjust the generator set performance with the
generator set running.
1
To check the firmware version number on the RDC
controller, hold the select button and the up arrow button
for about 5 seconds, until the firmware version number
appears on the display. See Figure 1-31. On the DC
controller, the firmware version number is displayed
during the first 2 seconds of the engine start cycle.
The manufacturer may release new versions of
controller firmware. An authorized Kohlerr distributor or
dealer can update the controller firmware in the field.
Kohlerr SiteTecht software and a personal computer
are required.See TP-6701, SiteTech Software
Operation maunal, for instructions.
1.14.2 System Parameters
The controller configuration for each generator model is
set at the factory and should not normally require
changes. The controller will display fault code NoEC (no
engine configuration setting) if the configuration is not
set.
The controller’s configuration mode allows adjustment
of the system parameters listed in this section. Use the
instructions in this section to check the configuration
after installation and change it to match the settings
shown in Figure 1-30 for your application, if necessary.
8
7
6
1. LED display
2. Up button
3. Select button
4. Down/Exercise button
2
3
4
5
5. Service access
6. RUN button and LED
7. AUTO button and LED
8. OFF button and LED
An authorized distributor or dealer can use a personal
computer running Kohlerr SiteTecht software to set
the system parameters, if desired. The controller will
display Uu---- if the voltage and frequency are not set to
one of the standard combinations shown in Figure 1-30.
Definition
ParameterSetting
System voltage
and frequency *
Engine
Configuration *
* Factory-set for each model.
Uu01160120/240
Uu06150115/230
Uu07DO NOT USE
Uu11DO NOT USE
Uu15DO NOT USE
Uu16DO NOT USE
Uu19DO NOT USE
Uu21DO NOT USE
Uu22DO NOT USE
Ec1314RES/RESL
Ec1420RES/RESL
PhasesHzVA C
Figure 1-30 Controller Configuration Parameters
Figure 1-29 RDC Residential Digital Control
TP-6733 8/1131Section 1 Installation
Page 32
1.14.3 RDC Controller Configuration
In order to prevent inadvertent changes, a code is
required to enter configuration mode.With the
controller in OFF, hold the select button and press the up
arrow button for 5 seconds. The controller display will
show the software version. Press the arrow buttons in
the following order to enter configuration mode: down,
up, down, up, down, up.
Follow the instructions in Figure 1-31 to enter the
configuration mode while the engine is not running and
then step through the following parameters. Use the up
(∧) and down (∨) arrow buttons to select the appropriate
settings for the application.
1.15 Voltage and Frequency
Adjustments, RDC Controller
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Moving parts.
If no buttons are pressed for one minute, the controller
will automatically exit the configuration mode without
saving any changes. Start the configuration procedure
over again from the beginning if the controller exits the
configuration mode before the settings have been
saved.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the OFF button is
pressed.
System voltage/frequency setting (Uu). Select the
system voltage and frequency from the table in
Figure 1-30.
Note: The Uu parameter sets the system’s rated
voltage and frequency.To adjust the output
(measured) voltage and frequency, see Section
1.15, Voltage and Frequency Adjustments.
Engine configuration (Ec). The engine configuration
must match the generator set engine type.See
Figure 1-30.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
The generator output voltage and frequency can be
adjusted, if necessary. Have adjustments performed by
an authorized distributor/ dealer or service technician.
The generator set must be running during performance
adjustments.
Note: A digital multimeter that measures voltage and
frequency is required for these adjustments.
Use a digital multimeter to check the output voltage and
frequency. If output voltage or frequency is not within
specifications, use the controller keypad to adjust the
output voltage and engine speed (frequency) while the
generator set is running.See Figure 1-29.The
flowchart in Figure 1-31 outlines the adjustment
procedures.
Note: Be sure to save your changes as instructed in
Figure 1-31 before exiting configuration mode.
Changes in voltage and speed adjustments are lost if
not saved before the generator set shuts down. The
generator set continues to run with the new settings until
it shuts down but then reverts to the previous settings at
the next startup if the changes have not been saved.
Note: The DC controller cannot be adjusted from the
controller keypad.
An authorized Kohler distributor/dealer can adjust the
voltage and frequency on both the RDC and DC
controllers using Kohlerr SiteTecht software and a
personal computer.Contact an authorized Kohler
distributor/dealer for service.
TP-6733 8/1132 Section 1 Installation
Page 33
Hold select and up
buttons for 5 seconds
Softwareversion
Software version
numberdisplayed
number displayed
u1.0
u2.0
Enter pass code
SAUE
Generator Set
Running?
Yes
RUN mode
Coarse Voltage Adjust
1P33
Press
Fine Voltage Adjust
1P36
Coarse Gain Adjust
2P14
Fine Gain Adjust
2P17
OFF mode
No
Adjust
Adjust
Adjust
Adjust
System Voltage Setting
1uU
Engine Configuration
Adjust Setting
Ec 1 4
Adjust
Adjust
Engine Governor
Speed Adjust
4P 1
Engine Governor
Gain Adjust
P
5
5
Figure 1-31 Controller Configuration and Performance Adjustments, RDC controller
TP-6733 8/1133Section 1 Installation
Adjust
YES
Save Changes
Save Changes?
SAUE
n0
Discard Changes
Exit Setup
Page 34
1.15.1 Voltage Adjustment
1.15.2 Frequency Adjustment
Note: Refer to the flowchart in Figure 1-31 during the
following procedure.
Voltage Adjustment Procedure
1. With the generator set off, connect a digital
multimeter to the output leads or an electrical outlet
on the load side of the generator set. Set the meter
to measure AC voltage.
2. Start the generator set by pressing the RUN button
on the RDC controller.
3. Use the RDC controller to adjust the voltage
(parameter 1P) until the output voltage reaches the
desired value. Refer to the flowchart in Figure 1-31
for instructions to adjust the output voltage. See
Figure 1-32 for the approximate change in voltage
per step.
Voltage Change per
Measured
Voltage, VAC
85--1801P00--9950.5
180--3601P00--9970.7
ADC
Display
Step, VAC
CoarseFine
Figure 1-32 Voltage Adjustment (approximate)
4. Adjust the voltage stability (gain, parameter 2P) to
minimize light flicker.
The engine speed determines the generator output
frequency; 60 Hz units operate at 3600 rpm and 50 Hz
units run at 3000 rpm.Adjust the engine governor
speed and gain to set the output frequency and stability
using the following procedure.
Note: Refer to the flowchart in Figure 1-31 during the
following procedure.
Frequency Adjustment Procedure
Note: Refer to the flowchart in Figure 1-31 during the
following procedure.
1. Attach a frequency meter to the AC output leads or
an electrical outlet on the load side of the generator
set.
2. Start and run the generator set until it reaches
normal operating temperature (at least 10 minutes).
3. Adjust engine governor speed (parameter 4P) to
obtain a frequency reading of 60 Hz (or 50 Hz if
appropriate). See Figure 1-33.
4. Check stability with the generator set running and
with no load applied. If the generator set speed is
unstable, hunts, or surges, adjust the engine
governor gain, parameter 5P, until the generator
set becomes stable with no hunting or surging.
(Increasing the gain slows the governor response.)
5. Readjust the voltage, if necessary.
6. Save settings. See Figure 1-31.
7. Stop the generator set.
Note: Volts-per-hertz parameter 3P can be adjusted
only by a Kohlerr authorized distributor/dealer
usingapersonalcomputerandKohlerr
SiteTecht software.
5. Check the frequency reading. Repeat steps 3 and
4 if necessary to obtain the rated frequency and
stable operation.
6. Save settings. See Figure 1-31.
50 Hz
4P
Setting
00342057285047.5
50360060300050
99377663315052.5
RPM
60 Hz
FrequencyRPMFrequency
Figure 1-33 Engine Speed Settings
TP-6733 8/1134 Section 1 Installation
Page 35
Section 2 Wiring Diagrams
Figure 2-1 lists the wiring diagram numbers and page
numbers.
Note: The revised design uses the revised fuel system
and the revised field-connection terminal block
layout shown in Figure 1-20.
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
APUAuxiliary Power Unit
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CAT5Category 5 (network cable)
CBcircuit breaker
CCcrank cycle
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., °degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
exh.exhaust
ext.external
FFahrenheit, female
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
IBCInternational Building Code
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPinternet protocol
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
KBusKohler communication protocol
kgkilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6733 8/11Appendix 41
Page 42
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, kΩ kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
3
m
3
m
3
m
units), male
cubic meter
/hr.cubic meters per hour
/min.cubic meters per minute
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mΩ milliohm
MOhm, MΩmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
μFmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
Manufacturers Association
NFPANational Fire Protection
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROread only
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTDsResistance Temperature
Detectors
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SMTPsimple mail transfer protocol
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SMSshort message service
SSstainless steel
std.standard
stl.steel
tach.tachometer
TBterminal block
TCPtransmission control protocol
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
UIFuser interface
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
URLuniform resource locator
(web address)
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
WOwrite only
w/owithout
wt.weight
xfmrtransformer
TP-6733 8/1142 Appendix
Page 43
Appendix B Electrical Lead Entry Template
Use the full-scale drawing in Figure 2 to mark the openings for the electrical conduit, if desired. See Section 1.8.1 for
more information.
SCALE: FULLNote: Dimensions are in mm.
Figure 2Template, Electrical
TP-6733 8/11Appendix 43
GM78090
Page 44
Notes
TP-6733 8/1144 Appendix
Page 45
Notes
TP-6733 8/1145
Page 46
Notes
TP-6733 8/1146
Page 47
Page 48
TP-67338/11a
E 2010, 2011 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.