Kohler 20-3250 kW User Manual

Operation
Industrial Generator Sets
Models:
20-3250 kW
Controllers:
Decision-Makerr 550
Software (Code) Version 2.10 or higher
TP-6200 10/12i
California Proposition 65
WARNING
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice. Record the Controller Serial Number from the controller nameplate.
Controller Description
Controller Serial Number
Decision-Makerr 550
Firmware/Software Version Numbers
Record the version and reference numbers as shipped from the manufacturer. Determine the Application Program Version Number as shown in Menu 20. Determine the Personality Profile Reference Number from the disk supplied with the literature packet.
Application Program Version Number
Personality Profile Reference Number
User Parameter File Reference Number
Version Number Upgrades/Updates
Record the version number upgrade/updates when installed.
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Version No./Date Installed
Software Options
Record the software options.
Number and Description
Number and Description
Number and Description
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 7........................................................
Introduction 13...............................................................................
Abbreviations 13..............................................................
List of Related Materials 13.....................................................
Service Assistance 14........................................................................
Section 1 Specifications and Features 15......................................................
1.1 Introduction 15..........................................................
1.2 Controller Features 15....................................................
1.2.1 Annunciator Lamps 16............................................
1.2.2 Digital Display and Keypad 18.....................................
1.2.3 Switches and Controls 20.........................................
1.2.4 Controller Circuit Boards 21.......................................
1.2.5 Fuses 21.......................................................
1.2.6 Terminal Strips and Connectors 21.................................
1.2.7 Circuit Board Interconnections for Calibration Procedure 22............
1.2.8 Communication Ports 23..........................................
1.3 Controller Logic Specifications 23..........................................
1.3.1 Status Event and Fault Specifications 23............................
1.3.2 Voltage Regulator and Calibration Specifications 30..................
1.3.3 Voltage Regulator Adjustments 30..................................
Section 2 Operation 33.......................................................................
2.1 Prestart Checklist 33.....................................................
2.2 Exercising Generator Set 33...............................................
2.3 Controller Operation 33...................................................
2.3.1 Starting 33......................................................
2.3.2 Stopping (User Stopping and Fault Shutdown) 35....................
2.3.3 Emergency Stop Switch Resetting 35...............................
2.3.4 Status Lamps 35.................................................
2.3.5 System Warning Lamp 35.........................................
2.3.6 System Shutdown Lamp 38.......................................
2.3.7 Controller Resetting (Following System Shutdown or Warning) 41......
2.4 Menu List Summary 41...................................................
2.5 Reviewing Digital Display 47..............................................
2.5.1 Keypad Operation 47.............................................
2.5.2 Auto-Scroll Function 48...........................................
2.5.3 Request and Error Messages 48...................................
2.6 Monitoring and Programming Setup 49......................................
2.6.1 PC Communications 50...........................................
2.6.2 Modbus Communications 51.......................................
2.7 Reviewing Menu Displays 52..............................................
2.7.1 Menu 1—Generator Monitoring 53..................................
2.7.2 Menu 2—Engine Monitoring 55....................................
2.7.3 Menu 3—Analog Monitoring 57....................................
2.7.4 Menu 4—Operational Records 58..................................
2.7.5 Menu 5—Event History 59.........................................
2.7.6 Menu 6—Time and Date 59.......................................
2.7.7 Menu 7—Generator System 59....................................
2.7.8 Menu 8—Time Delays 61
2.7.9 Menu 9—Input Setup 62..........................................
2.7.10 Menu 10—Output Setup 64........................................
2.7.11 Menu 11—Voltage Regulator 66....................................
2.7.12 Menu 12—Calibration 67..........................................
.........................................
TP-6200 10/12 Table of Contents 3
Table of Contents, continued
2.7.13 Menu 13—Communications 68....................................
2.7.14 Menu 14—Programming Mode 69..................................
2.7.15 Menu 15—Protective Relays (PR) 70...............................
2.7.16 Menu 20—Factory Setup (Version 2.10) 71..........................
2.7.17 Menu 20—Factory Setup (Version 2.21) 72..........................
2.8 Local Programming Mode On 74...........................................
2.8.1 Menu 1—Generator Monitoring 75..................................
2.8.2 Menu 2—Engine Monitoring 79....................................
2.8.3 Menu 3—Analog Monitoring 83....................................
2.8.4 Menu 4—Operational Records 86..................................
2.8.5 Menu 5—Event History 88.........................................
2.8.6 Menu 6—Time and Date 89.......................................
2.8.7 Menu 7—Generator System 90....................................
2.8.8 Menu 8—Time Delays 96.........................................
2.8.9 Menu 9—Input Setup 98..........................................
2.8.10 Menu 10—Output Setup 104........................................
2.8.11 Menu 11—Voltage Regulator 114....................................
2.8.12 Menu 12—Calibration 120..........................................
2.8.13 Menu 13—Communications 125....................................
2.8.14 Menu 14—Programming Mode 129..................................
2.8.15 Menu 15—Protective Relays (PR) 131...............................
2.8.16 Menu 20—Factory Setup 135.......................................
Section 3 Scheduled Maintenance 137..........................................................
3.1 Alternator Service 137.....................................................
3.2 Engine Service 137.......................................................
3.3 Service Schedule 138.....................................................
3.4 Alternator Bearing Service 140..............................................
3.4.1 20--300 kW Models 140............................................
3.4.2 300--2250 kW Models with Single-Bearing Alternator 140...............
3.4.3 1250 kW and Larger Models with Two-Bearing Alternator 140...........
3.5 Diesel Fuel Systems 140...................................................
3.5.1 Bleeding Air from Fuel System 140..................................
3.5.2 Subbase Fuel Day Tank Electronic Control Module (ECM) 141..........
3.5.3 Subbase Inner Fuel Tank Alarm 142.................................
3.6 Gas Fuel Systems (REZG_ and REZX_/RZX_ models) 142.....................
3.6.1 Gas Fuel System Concept (Single Fuel) 142..........................
3.6.2 LPG Liquid Withdrawal Fuel System Concept 142.....................
3.6.3 Natural Gas and LPG Conversion 143...............................
3.6.4 Fuel System Changeover Kits (Dual Fuel) 143........................
3.6.5 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1
(125/150REZG models) 145........................................
3.7 Cooling System 145.......................................................
3.7.1 Coolant Level Check 145...........................................
3.7.2 Cooling System Component Inspection 146...........................
3.7.3 Procedure to Drain Cooling System 146..............................
3.7.4 Procedure to Flush and Clean Cooling System 146....................
3.7.5 Procedure to Refill Cooling System 146..............................
3.8 Radiator Fan Bolt Retorque 147.............................................
3.9 Radiator Expansion Joint Loosening—Initial Setup Only 148....................
3.10 Radiator Fan Bearing Lubrication 148........................................
3.11 Battery 149
3.11.1 Clean Battery 149.................................................
3.11.2 Electrolyte Level Inspection 150.....................................
3.11.3 Specific Gravity Check 151.........................................
3.11.4 Charge Battery 151................................................
...............................................................
TP-6200 10/12Table of Contents4
Table of Contents, continued
3.12 Detroit Diesel Engine Control Systems 152...................................
3.12.1 Features 152.....................................................
3.12.2 DDEC Engine Diagnostics 152......................................
3.13 Engine Control Systems 153................................................
3.14 Storage Procedure 153....................................................
3.14.1 Lubricating System 153............................................
3.14.2 Cooling System 153...............................................
3.14.3 Fuel System 154..................................................
3.14.4 Internal Engine Components (Gas-Fueled Engines) 154................
3.14.5 Exterior 154......................................................
3.14.6 Battery 154.......................................................
Section 4 General Troubleshooting 155.........................................................
4.1 General Troubleshooting Chart 156..........................................
4.2 Controller Display and Voltage Regulation Troubleshooting Chart 159............
Section 5 Generator Set Reconnection 161.....................................................
5.1 Introduction 161..........................................................
5.2 Voltage Reconnection Procedure 162........................................
Section 6 Accessories 167.....................................................................
6.1 Accessories and Connections 167...........................................
6.1.1 Audiovisual Alarm Kit 167..........................................
6.1.2 Common Failure Relay Kit 168......................................
6.1.3 Controller (Customer) Connection Kit 168............................
6.1.4 Float/Equalize Battery Charger Kit with Alarm Option 168...............
6.1.5 Ground Fault Annunciation 170.....................................
6.1.6 Idle (Speed) Mode Feature 171.....................................
6.1.7 Low Fuel (Level/Pressure) Switch 172...............................
6.1.8 Prime Power Switch Kit 172........................................
6.1.9 Remote Emergency Stop Kit 173....................................
6.1.10 Remote Reset Feature 173.........................................
6.1.11 Remote Serial Annunciator 174.....................................
6.1.12 Remote Speed Adjustment Potentiometer Kit (Non-ECM Models) 181....
6.1.13 Run Relay Kit 181.................................................
6.1.14 Shunt-Trip Line Circuit Breaker 181..................................
6.1.15 Single-Relay Dry Contact Kit 182....................................
6.1.16 Ten-Relay Dry Contact Kit 182......................................
6.1.17 Twenty-Relay Dry Contact Kit 184...................................
6.1.18 Wireless Monitor 185..............................................
6.2 Accessory Connections 186................................................
Appendix A Abbreviations 193................................................................
Appendix B User-Defined Settings 195........................................................
Appendix C Voltage Regulator Definitions and Adjustments 202.................................
Appendix D Alternator Protection 208.........................................................
Appendix E Inputs and System Events by Application 209......................................
TP-6200 10/12 Table of Contents 5
Notes
6 TP-6200 10/12
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery
acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
7Safety Precautions and InstructionsTP-6200 10/12
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
8 Safety Precautions and Instructions TP-6200 10/12
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building unless the exhaust gas is piped safely outside. Never operate the generator set where exhaust gas could accumulate and seep back inside a potentially occupied building.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels inawell-ventilatedareaawayfrom spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Explosive fuel vapors can cause severe injury or death. Ta k e
additional precautions when using the following fuels:
Gasoline—Store gasoline only in approved red containers clearly marked GASOLINE.
Propane (LP)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
Fuel tanks. Explosive fuel vapors can cause severe injury or death.
Gasoline and other volatile fuels stored in day tanks or subbase fuel tanks can cause an explosion. Store only diesel fuel in tanks.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
LP liquid withdrawal fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage
can cause an explosion. Check the LP liquid withdrawal gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to at least 90 psi (621 kPa). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving parts.
9Safety Precautions and InstructionsTP-6200 10/12
High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the
test equipment manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
Testing the photo transistor circuit board. Hazardous voltage can cause severe injury or death. When
the end cover is removed, do not expose the photo transistor circuit board mounted on the generator set end bracket to any external light source, as exposure to light causes high voltage. Keep foreign sources of light away from the photo transistor circuit board during testing. Place black electrical tape over the LED on the circuit board before starting the generator set.
Installing the photo transistor circuit board. Hazardous voltage can cause severe injury or death.
Ensure that the foil side of the photo transistor circuit board, the end of the shaft, and the threaded holes are clean and free of metal particles and chips. Metal debris may short-circuit the photo transistor circuit board and cause hazardous voltage in the generator set. Do not reconnect the generator set to the load until the AC voltmeter shows the correct output.
Installing the battery charger. Hazardous voltage can cause severe injury or death. An
ungrounded battery charger may cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead on the battery charger. Install the battery charger as prescribed in the equipment manual. Install the battery charger in compliance with local codes and ordinances.
Servicing the day tank. Hazardous voltage can cause severe injury or death. Service the day tank electrical
control module (ECM) as prescribed in the equipment manual. Disconnect the power to the day tank before servicing. Press the day tank ECM OFF pushbutton to disconnect the power. Notice that line voltage is still present within the ECM when the POWER ON light is lit. Ensure that the generator set and day tank are electrically grounded. Do not operate the day tank when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Engine block heater. Hazardous voltage can cause severe injury or death. The engine block heater can
cause electrical shock. Remove the engine block heater plug from the electrical outlet before working on the block heater electrical connections.
Handling the capacitor. Hazardous voltage can cause severe injury or death. Electrical shock results from
touching the charged capacitor terminals. Discharge the capacitor by shorting the terminals together.
(Capacitor-excited models only)
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Heavy Equipment
WARNING
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
10 Safety Precautions and Instructions TP-6200 10/12
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Hot Parts
Notice
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the alternator. Hot parts can cause severe injury or death.
Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
NOTICE
This generator set has been rewired from its nameplate voltage to
246242
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Canadian installations only.For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
11Safety Precautions and InstructionsTP-6200 10/12
Notes
12 Safety Precautions and Instructions TP-6200 10/12
Introduction
This manual provides operation instructions for 20 kW and larger generator sets equipped with the following controller:
D Decisionr 550, Software (Code) Version 2.10 or
higher
Version2.10 refers to the controller application software. To determine the generator set controller software version, go to Menu 20—Factory Setup and scroll down to Code Version. The code version is the controller software version.
Wiring diagram manuals are available separately. Refer to the engine operation manual for generator set engine scheduled maintenance information.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably trained maintenance personnel familiar with generator set operation and service.
The disk supplied with this generator set is a backup copy of the generator set personality program containing data specific to the engine and alternator. The engine and alternator data was preprogrammed in the controller at the factory and no further use of the disk should be necessary. Typically, your authorized distributor stores this disk for possible future use such as controller replacement or other circumstances requiring a backup.
Abbreviations
This publication makes use of numerous abbreviations. Typically, the word(s) are spelled out along with the abbreviation in parentheses when shown for the first time in a section. Appendix A, Abbreviations, also includes many abbreviation definitions.
List of Related Materials
Separate literature contains communication and software information not provided in this manual. Figure 1 lists the available literature part numbers.
Communication and Software Manual Description
550 Controller Spec Sheet
Generator Set/Controller Wiring Diagram Manual
550 Communications Spec Sheet
Monitor III Converters, Connections, and Controller Setup
Monitor III Software Spec Sheet G6-76
Monitor III Converter, Modbusr/Ethernet Spec Sheet
Monitor III Software Operation Manual TP-6347
Modbusr Communications Protocol Operation Manual
Setup and Application Manual TP-6140
Service Parts Controllers TP-6780
Program Loader Software Installation TT-1285
SiteTecht Software Operation Manual
Remote Serial Annunciator (RSA) TT-1377
Remote Serial Annunciator (RSA II) TT-1485
Controller Service Replacement TT-1310
Figure 1 Related Literature
Literature Part No.
G6-46
Multiple Part Numbers
Contact your
Distributor/Dealer
G6-50
TT-1405
G6-79
TP-6113
TP-6701
Modbusr is a registered trademark of Schneider Electric.
13IntroductionTP-6200 10/12
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
14 Service Assistance TP-6200 10/12
Section 1 Specifications and Features
1.1 Introduction
The spec sheets for each generator set provide model­specific generator and engine information. The controller spec sheet provides specifications for this controller. Refer to the respective spec sheet for data not supplied in this manual. Consult the generator set service manual, installation manual, engine operation manual, and engine service manual for additional specifications.
1.2 Controller Features
The controller features include the annunciator lamps, digital display and keypad, switches and controls, and fuses and terminal strip. The following paragraphs detail the features by general topics.
124 5
3
The controller features, accessories, and menu displays depend upon the engine electronic control module (ECM) setup and features. Controller features apply to generator set models with ECM and non-ECM engines unless otherwise noted.
Note: Press any key on the keypad to turn on the
controller lights and display. The lights and display turn off 5 minutes after the last keypad entry.
Note: Measurements display in metric or English. Use
Menu 7—Generator System to change the measurement display.
See Figure 1-1 for an illustration of the controller front panel. See Figure 1-2 for an illustration of the controller with the keyswitch option.
6
8
1. Emergency stop switch
2. Alarm horn (see keypad for alarm silence)
3. Annunciator lamps (see keypad for lamp test)
4. Generator set master switch, run/off-reset/auto positions
5. Digital display
6. Keypad
7. Operating guide
8. Controller terminal strips (on circuit board)
7
Figure 1-1 550 Controller with Three-Position Selector Switch
TP-6200 10/12 15Section 1 Specifications and Features
TP-6083-2
12 4 5
3
6
8
1. Generator set master switch, run/off-reset/auto positions (keyswitch option)
2. Emergency stop switch
3. Alarm horn (see keypad for alarm silence)
4. Annunciator lamps (see keypad for lamp test)
Figure 1-2 550 Controller with Keyswitch Option
1.2.1 Annunciator Lamps
Five annunciator lamps provide visual generator set status. See Figure 1-3.
TP-6083-2
Figure 1-3 Annunciator Lamps
System Ready. Green lamp illuminates when the
generator set master switch is in the AUTO (automatic start) position and the system senses no faults. The unit is ready to start.
TP-6083-2
7
5. Digital display
6. Keypad
7. Operating guide
8. Controller terminal strips (on circuit board)
Programming Mode. Yellow programming lamp indicates the user selected programming mode. See Figure 1-4.
Programming Lamp Programming Mode Selection
Lamp Flashing Local Programming
Lamp Steady On Remote Programming
Lamp Off Programming Disabled
Figure 1-4 Programming Lamp Mode
Note: Find additional information for the programming
mode lamp function and access to the local or remote programming modes in Section 2.8, Local Programming Mode On, Menu 14—Programming Mode.
Not in Auto (NIA). Yellow lamp illuminates when the generator set master switch is not in the AUTO (automatic start) position.
TP-6200 10/1216 Section 1 Specifications and Features
System Warning. Yellow lamp identifies an existing fault condition that does not shut down the generator set. A continuing system warning fault condition may cause a system shutdown. Correct all system warnings as soon as practical.
System Shutdown. Red lamp indicates that the generator set has shut down because of a fault condition. The unit will not start without resetting the controller, see Section 2.3.7, Controller Reset Procedure.
See Section 2.3.5, System Warning Lamp, for definitions of the items listed.
The following conditions cause a system warning:
D Engine functions:
d ECM yellow alarm
(DDC/MTU engine with MDEC/ADEC)
d High battery voltage d High coolant temperature d Low battery voltage d Low coolant temperature d Low fuel (level or pressure)* d Low oil pressure d Speed sensor fault d Starting aid (system status) d Weak battery
D General functions:
d Auxiliary—Analog up to 7 user-selectable inputs
each with a high and low programmable warning level
d Auxiliary—Digital up to 21 user-selectable
warnings
d Battery charger fault* d Emergency power system (EPS) supplying load d Engine cooldown delay d Engine start delay d Load shed kW overload d Load shed underfrequency d Master switch not in AUTO (automatic start)
position
d NFPA 110 fault (National Fire Protection
Association)
d System ready (system status)
D Alternator functions:
d AC sensing loss d Ground fault* d Overcurrent
* Requires optional input sensors.
Note: See Figure 2-8 in User Inputs for factory-
reserved analog and digital inputs that are not user-selectable.
See Section 2.3.6, System Shutdown Lamp, for definitions of the items listed.
The following conditions cause a system shutdown:
D Engine functions:
d Air damper closed (status), if equipped d Coolant temperature signal loss d ECM red alarm
(DDC/MTU engine with MDEC/ADEC)
d Engine stalled (ECM only) d High coolant temperature d High oil temperature d Low coolant level d Low oil pressure d Oil pressure signal loss d Overcrank d Overspeed
D General functions:
d Auxiliary—Analog up to 7 user-selectable inputs
each with a high and low programmable shutdown level
d Auxiliary—Digital up to 21 user-selectable
shutdowns
d ECM communications loss (ECM models only) d Emergency stop d Internal fault d Master switch in OFF/RESET position d Master switch error d Master switch open d NFPA 110 fault
D Alternator functions:
d AC output overvoltage d AC output undervoltage d Alternator protection against overload and short
circuits
d Field overvoltage
(M4, M5, M7, or M10 alternator only)
d Locked rotor (failed to crank) d Overfrequency d Underfrequency
Note: See Figure 2-8 in User Inputs for factory-
reserved analog and digital inputs which are not user-selectable.
TP-6200 10/12 17Section 1 Specifications and Features
1.2.2 Digital Display and Keypad
Figure 1-5 illustrates the digital display and keypad.
Note: Press any key on the keypad to turn on the
controller lights and display. The lights and display turn off 5 minutes after the last keypad entry.
The 2-line vacuum fluorescent display provides generator set and engine condition information.
The 16-button keypad gives the user information access and local programming capability.
Keypad Functions
Alarm (Horn) Off key silences the alarm horn at the operator’s discretion. Place the generator set master switch in the AUTO position before silencing the alarm horn. See Section 2.3.7, Controller Reset Procedure, and Section 1.2.3, Switches and Controls.
TP-5829-2
Figure 1-5 Digital Display and Keypad
AM/PM key provides time of day data entries when
programming.
Enter key provides confirmation entry when selecting menu or programming.
Lamp Test key tests the controller indicator lamps, horn, and digital display. See Section 1.2.3, Switches and Controls.
Menu down key provides navigation within menus when necessary.
Menu right key provides navigation within menus when necessary.
Numeric 0--9 keys provide numeric data entries when selecting menus or programming.
Reset Menu key exits a menu, clears incorrect entries, and cancels the auto-scroll feature.
Stop Prog (Program) Run key allowstheusertostop any previously programmed generator set run sequence. See Section 1.2.3, Switches and Controls.
Yes/No keys provides data answer entries when programming.
Alternator Output Displays (Menu 1)
AC Amps displays the alternator output current. The display shows each line of 3-phase models.
AC Volts displays the alternator output voltages. The display shows all line-to-neutral and line-to-line voltage combinations.
Alternator Duty Level displays the actual load kW divided by the nameplate kW rating as a percentage.
Frequency displays the frequency (Hz) of alternator output voltage.
Hourmeter displays the generator set operating hours loaded and unloaded for reference in scheduling maintenance.
KVA displays the total and individual L1, L2, and L3 kVA.
KVAR displays the total and individual L1, L2, and L3
kVAR.
Power Factor displays the kW/kVA and the individual line power factor values.
Watts displays the total and individual L1, L2, and L3 kilowatts.
TP-6200 10/1218 Section 1 Specifications and Features
Engine Displays (Menu 2)
Some engine displays are available with selected generator set engines using engine ECMs only. The controller display shows N/A (not available) for items that are unavailable. See the controller spec sheet for applicable generator set models.
Ambient Temperature displays the generator set area ambient temperature.
Charge Air Pressure displays the engine turbocharger boost air pressure.
Charge Air Temperature displays the engine turbocharger boost air temperature.
Coolant Level displays the engine coolant level.
Coolant Pressure displays the engine coolant
pressure.
Coolant Temperature displays the engine coolant temperature.
Event History displays up to 100 stored system events including status, warnings, and shutdowns.
Last Start Date displays the date when the generator set last operated.
Number of Starts displays the total number of generator set startup events.
Number of Starts (Since) Last Maintenance displays the total number of generator set startup events since the last maintenance date.
Operating Days (Since) Last Maintenance displays the total number of days of operation since the last maintenance date. A counted day of operation can be 1--24 hours.
Run Time displays the total loaded hours, total unloaded hours, and total kW hours.
Run Time Since Maintenance displays the total loaded hours, total unloaded hours, and total kW hours.
Crankcase Pressure displays the engine crankcase pressure.
DC Volts displays the voltage of starting battery(ies).
Fuel Pressure displays the fuel supply pressure.
Fuel Rate displays the calculated fuel consumption rate
based on fuel injector outputs.
Fuel Temperature displays the fuel supply temperature.
Oil Level displays the engine oil level as a percent of full capacity.
Oil Pressure displays the engine oil pressure.
Oil Temperature displays the engine oil temperature.
RPM (Tachometer) displays the engine speed.
Used Last Run displays the accumulated amount of
fuel used since last reset by the engine DDEC reader.
Operational Record Displays (Menus 4 and 5)
The operational record displays events since last reset. See Section 2.8.4, Menu 4—Operational Records, for resetting procedure.
Time Delay Displays (Menu 8)
The time delays are user adjustable. See Section 2.8.8, Menu 8—TIme Delays, for time delay adjustments. See Section 1.3.1, Status Event and Fault Specifications, for range and default settings.
Crank On/Crank Pause displays the time allocated for generator set crank on and crank pause in minutes:seconds.
Engine Cooldown displays the time delay for engine cooldown while the master switch is in the AUTO or RUN positions and not in the idle mode.
Engine Start displays the time delay before the generator set starts while the master switch is in AUTO or RUN positions.
Overcrank Shutdown (Number of) Crank Cycles
displays the number of unsuccessful crank cycles (crank on/crank pause) before the generator set shuts down on an overcrank fault.
Overvoltage displays the time delay before the generator set shuts down because of an overvoltage condition.
Starting Aid displays the engine starting aid activation time.
Engine Start Countdown displays the time remaining before the next generator set startup.
TP-6200 10/12 19Section 1 Specifications and Features
Undervoltage displays the time delay before the generator set shuts down because of an undervoltage condition.
1.2.3 Switches and Controls
See Figure 1-6 and Figure 1-8 for switches and controls.
123
TP-6083-2
1. Emergency stop switch
2. Alarm horn
3. Generator set master switch
Figure 1-6 Switches and Alarm Horn
Note: Find additional switches and controls in
Section 2.5.1, Keypad Operation.
Alarm Horn. The alarm horn alerts the operator or other attendants that a shutdown or warning condition exists. See Section 1.3, Controller Logic Specifications, for conditions. Place the generator set master switch in the AUTO position before silencing the alarm horn. The alarm horn cannot be silenced unless the generator set master switch is in the AUTO position. See Section 2.3.7, Controller Reset Procedure.
The generator set master switch with the keyswitch option (Figure 1-7) is available to meet appropriate local code requirements. The key is removable in the AUTO position only.
TP-6083-2
Figure 1-7 Generator Set Master Switch with
Keyswitch Option
Lamp Test. The keypad switch tests the controller indicator lamps, horn, and digital display. Press the reset menu key before pressing the lamp test key.
Stop Prog (Program) Run. Keypad switch allows the user to stop any previously programmed generator set run sequence.
Alarm (Horn) Off. The keypad switch silences the alarm horn at the operator’s discretion. Place the generator set master switch in the AUTO position before silencing the alarm horn. Restore alarm horn switches at all locations including those on remote annunciator and audiovisual alarm kits to the normal position after correcting the fault shutdown to avoid reactivating the alarm horn. See Section 2.3.7, Controller Reset Procedure.
AM/PM. This keypad switch provides time of day data entries when programming.
Emergency Stop. The operator-activated pushbutton immediately shuts down the generator set in emergency situations. Reset the emergency stop switch after shutdown by pulling the switch knob outward. Use the
emergency stop switch for emergency shutdowns only.
Use the generator set master switch for normal shutdowns.
Generator Set Master Switch (Run/Off-Reset/Auto). This switch resets the controller fault lamps and start/stops the generator set. Refer to Section 2.3.1, Starting, Section 2.3.2, Stopping, and Section 2.3.3, Emergency Stop Switch Reset Procedure.
1
2
3
1. Lamp test
2. Alarm horn silence
3. Stop program run
Figure 1-8 Keypad Switches
TP-5829-2
TP-6200 10/1220 Section 1 Specifications and Features
1.2.4 Controller Circuit Boards
1.2.5 Fuses
The controller has five circuit boards—indicator, interconnection, keypad, digital display, and main logic/ communication. See Figure 1-9 for circuit board locations.
12
5
1. AC fuse block (TB5)
2. Interconnection circuit board TB1, TB2, TB3, and TB4 terminal strips and F1, F2, and F3 fuses
3. Main logic (microprocessor)/communication circuit board
4. Keypad and digital display circuit boards
5. Indicator circuit board (LED and alarm horn)
34
GM10193B-A
Figure 1-9 Controller Circuit Boards and Fuses
(Controller Top View)
Indicator (Status) Circuit Board includes the LED status lamps, alarm horn, and generator set master switch.
Interconnection Circuit Board provides the terminal strips to connect the controller (customer) connection board and/or dry contact kits and three DC fuses (F1, F2, and F3). See 6.1.3 for more information.
Keypad (Switch Membrane) Circuit Board provides the keypad to navigate the generator set displays and enter data.
Digital Display Circuit Board provides the vacuum fluorescent display (VFD) for monitoring the generator set functions and output values.
Main Logic (Microprocessor)/Communication Circuit Board provides the controller operation logic
and provides PC communication locally (direct) or remotely (via modem) using RS-232 or RS-485 connectors.
AC Circuit Fuses (TB5). Fuses are located inside the controller. See Figure 1-9.
D 1.5-Amp (V7) fuse protects L1 sensing input to
interconnection circuit board.
D 1.5-Amp (V8) fuse protects L2 sensing input to
interconnection circuit board.
D 1.5-Amp (V9) fuse protects L3 sensing input to
interconnection circuit board.
DC Circuit Fuses fuses are located on the controller interconnection circuit board.
D 5-Amp Remote Annunciator (F1) fuse protects the
dry contact kit if equipped and the controller panel lamps.
D 5-Amp Controller (F2) fuse protects the controller
circuitry.
D 15-Amp Engine and Accessories (F3) fuse protects
the engine/starting circuitry and accessories.
1.2.6 Terminal Strips and Connectors
Terminal strips and connectors for inputs and outputs are located on the interconnection circuit board. See Section 6, Accessories.
TB1 Input Connection Terminal Strip provides input connections for remote start and emergency stop (E-Stop).
TB2 Analog Input Connection Terminal Strip
provides analog input connections, including non-ECM sensor connections.
TB3 Accessory Power Output Connection Terminal Strips provides a generator set power supply for factory
use.
TB4 Digital Input Connection Terminal Strips
connect external devices (engine ECM and user supplied) to the generator set digital inputs.
P23 Connector connects the interconnection circuit board to the controller (customer) connection terminal strip (connector P25) inside the junction box. See 6.1.3 for more information.
TP-6200 10/12 21Section 1 Specifications and Features
Figure 1-10 shows locations of the terminal strips on the controller interconnection circuit board. See Section 6.2, Accessory and Connections, for specific terminal identification information. Refer to the wiring diagrams for additional information on connecting accessories to the terminal strips.
2
1
3
4
56
ADV-6533-A
1.2.7 Circuit Board Interconnections for Calibration Procedure
The interconnection circuit board shown in Figure 1-11 contains a ribbon connector that requires disconnection during the calibration procedure in Menu 12— Calibration. Disconnect ribbon connector P2 prior to zeroing out (resetting) the auxiliary analog inputs.
1
2
1. TB1 terminal strip
2. TB2 terminal strip
3. P1 Connector
4. P23 Connector
5. TB3 terminal strip
6. TB4 terminal strip
Figure 1-10 Interconnection Circuit Board Terminal
Strips and Connectors
4
4
ADV-6533-A
1. Interconnection circuit board
2. P2 ribbon connector
3. P12 ribbon connector
4. Main logic circuit board
Figure 1-11 Interconnection Circuit Board Ribbon
Connector P2 (Top View of Circuit Board)
TP-6200 10/1222 Section 1 Specifications and Features
1.2.8 Communication Ports
1.3 Controller Logic Specifications
The main logic circuit board contains several communication ports for Modbusr and KBUS connections. See Figure 1-12. Refer to the List of Related Materials in the Introduction for corresponding communication installation information.
12 34 5
The controller logic specifications section is an overview of the various features and functions of the controller. Certain features function only when optional accessories are connected. See Section 2, Operation, for details.
The default selection time delays and relay driver outputs (RDOs) are factory set and adjustable with the programming mode on (Menu 14). Some data entries require using a PC in the Remote Programming mode. See the monitor software operation manual for details.
Inhibit Time Delay. The inhibit time delay is the time period following crank disconnect during which the generator set stabilizes and the controller does not detect a fault or status event. Select the desired inhibit time delay from 0 to 60 seconds.
TIme Delay (Shutdown or Warning). The time delay follows the inhibit time delay. The time delay is the time period between when the controller first detects a fault or status event and the controller warning or shutdown lamp illuminates. The delay prevents any nuisance alarms. Select the desired time delay from 0 to 60 seconds.
6
ADV-6533-A
1. P19—unused isolated connection (ISO2), RS-485 port
2. P21—KBUS isolated connection (ISO1), RS-485 port
3. P18—KBUS or Modbusr, RS-232 port
(Monitor III connection)
4. P20—Modbus, RS-485 port (Monitor III connection)
5. P22—ECM connector
6. Main logic circuit board
Figure 1-12 Main Logic Circuit Board Communication
Ports (Top View of Circuit Board)
1.3.1 Status Event and Fault Specifications
The table starting on the next page contains all status events and faults with ranges and time delays including items that do not have adjustments.
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.
Modbusr is a registered trademark of Schneider Electric.
TP-6200 10/12 23Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Access Code (password)
AC Sensing Loss 10 AC SENSING
Air Damper Control (if used) **
Air Damper Indicator (if used), see D20 **
Air/Fuel Module (AFM) Engine Start Delay ]
Air/Fuel Module (AFM) Remote Start]
Air/Fuel Module (AFM) Shutdown (see D11) ]
Alternator Protection Shutdown
Analog Aux. Input 0 9 LOCAL BATT
Analog Aux. Inputs A01--A07
Analog Aux. Input A01 (non-ECM only)
Analog Aux. Input A02 (non-ECM only)
Analog Aux. Input A03 ]
Analog Aux. Input A04 *
Analog Aux. Input A04 ]
Analog Aux. Input A06 VSG (Volvo, GM, Doosan only)
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
14 User-Selectable 0(zero)
LOSS
10
10 AFM ENG
START DELAY
10 AFM REMOTE
10 ALTERNATOR
9 USER-DEFINED
9 A01
9 A02
9 A03
9 A04
9 A04
9, 12 A06 ANALOG
START
PROTECTION
VDC
A01--A07
COOLANT
TEMP
OIL
PRESSURE
INTAKE AIR
TEMP
FUEL LEVEL
OIL TEMP
AUXILIARY IN
Relay
Driver
Output
(RDO)
RDO-25 * On Warning
RDO-25 ]
Alarm
Horn
Off
On Shutdown
On Shutdown
On Shutdown
On Shutdown
On Warning Default Values with
Off Vol vo:
Lamp Range Setting
or
Warning
or
Warning
or
Warning
Shutdown
or
Warning
Fixed
Fixed
Default Values with
Warning Enabled:
HI warning 90%
LO warning 10%
HI shutdown 100%
LO shutdown 1%
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
(255 psi max.)
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
Default Values with
Warning Enabled:
HI/LO warning are
engine dependent
Warning Enabled:
HI/LO warning are
engine dependent
Default
Selection
30 sec.
inhibit,
5 sec. delay
30 sec.
inhibit,
0 sec. delay
warning,
5 sec. delay
shutdown
30 sec.
inhibit,
0 sec. delay
warning,
5 sec. delay
shutdown
30 sec.
inhibit,
0 sec. delay
warning
30 sec.
inhibit,
0 sec. delay
warning
30 sec.
inhibit,
0 sec. delay
warning
0.5V=1250
4.5V=8750
GM/Doosan
60 Hz:
0.5V=2375
4.5V=2625 50 Hz:
0.5V=2327
4.5V=2624
Inhibit
Time
Delay
(sec.)
0--60 0--60
Time Delay (sec.)
TP-6200 10/1224 Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Analog Aux. Input A07
Battery Charger Fault (see D01) **
Battle Switch (Fault Shutdown Override Switch)
Block Heater Control [[
Breaker Trip w
Common Protective Relay Output w
Critical Overvoltage Shutdown
Cyclic Cranking 8 Off 1--6 crank cycles
Defined Common Faults (each input value is set separately)
Detonation Shutdown (see D13) ]
Detonation Warning (see D12) ]
Digital Aux. Input D01--D21
Digital Aux. Input D01 Battery Charger Fault **
Digital Aux. Input D02 Low Fuel Warning **
Digital Aux. Input D03 Low Coolant Temperature **
Digital Aux. Input D04 Field Overvoltage (M4, M5, M7, or M10 alt. only)
Digital Aux. Input D05 Breaker Closed w
Digital Aux. Input D06 w
Digital Aux. Input D09 Low Fuel Pressure Shutdown (125RZG only)
Digital Aux. Input D11 Air/Fuel Module (AFM) Shutdown ]
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
9 A07
ANALOG VOLT
ADJUST
9 BATTLE
10 BLOCK HEATER
10 BREAKER
10 COMMON PR
10 CRITICAL
10 DEFINED
9, 10 USER-DEFINED
9, 10 D01 BATTERY
9, 10 D02
9, 10 D03 LOW
9, 10 D04
9, 10 D05
9, 10 D06 ENABLE
9, 10 D09
9, 10 D11
SWITCH
CONTROL
TRIP
OUTPUT
OVERVOLTAGE
COMMON
FAULT
D01--D21
CHARGER
FAULT
LOW FUEL
WARNING
COOLANT
TEMP
FIELD
OVERVOLTAGE
BREAKER
CLOSED
SYNCH
LOW FUEL
SHUTDOWN
AFM
SHUTDOWN
Relay Driver
Output
(RDO)
RDO only
RDO-30 Off Warning
RDO-31 w
RDO-18
(lead 32A)
RDO-11
(lead 61)
RDO-08 (lead 63)
RDO-05 (lead 35)
Alarm
Horn
Off Warning Fixed
Off Warning
On Shutdown Fixed 275 volts
On Shutdown
On Shutdown
On Warning Fixed 0 sec.
On Warning Fixed 0 sec.
On Warning Fixed 0 sec.
On Shutdown Fixed 1 sec.
Off Warning Fixed 0 sec.
On Shutdown Fixed 5 sec.
On Shutdown Fixed 0 sec.
or
Warning
or
Warning
Range SettingLamp
±10% of system
voltage over the range
of 0.5--4.5 VDC
10--30 sec. crank on
1--60 sec. pause
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
Default
Selection
(L1--L2)
15 sec. 15 sec.
30 sec.
inhibit,
5 sec. delay
30 sec.
inhibit,
5 sec. delay
inhibit,
0 sec. delay
inhibit,
0 sec. delay
inhibit,
0 sec. delay
inhibit,
15 sec.
delay
inhibit,
0 sec. delay
20 sec.
inhibit, 0
sec. delay
inhibit,
0 sec. delay
inhibit,
0 sec. delay
Inhibit
Time Delay (sec.)
3
0--60 0--60
0--60 0--60
Time Delay (sec.)
TP-6200 10/12 25Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Digital Aux. Input D12 Detonation Warning ]
Digital Aux. Input D13 Detonation Sensing Module (DSM) Shutdown ]
Digital Aux. Input D13 Knock Detection Module (KDM) Shutdown ]
Digital Aux. Input D14 Low Coolant Level, (with LCL switch) **
Digital Aux. Input D15 Remote Shutdown
Digital Aux. Input D16 Remote Reset
Digital Aux. Input D17 VAR/PF mode
Digital Aux. Input D18 Voltage Lower
Digital Aux. Input D19 Voltage Raise
Digital Aux. Input D20 Air Damper Indicator (if used) **
Digital Aux. Input D21 Idle (speed) Mode Function
ECM Red Alarm (was MDEC Red Alarm) [[
ECM Yellow Alarm (was MDEC Yellow Alarm) [[
EEPROM Write Failure
Emergency Stop Shutdown
Engine Cooldown (see Time Delay--)
Engine Derate Active 10 ENGINE
(Engine) J1939 CAN Shutdown (ECM only)
Engine Stalled (ECM only)
Engine Start (see Time Delay--)
EPS (Emergency Power System) Supplying Load
Field Overvoltage (see D04)
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
9, 10 D12
9, 10 D13
9, 10 D13
9, 10 D14 LOW
9, 10 D15 REMOTE
9, 10
9, 10
9, 10
9, 10
9, 10 D20
9, 10 D21
10 ECM RED
10 ECM YELLOW
10 EEPROM WRITE
10 EMERGENCY
10 J1939 CAN
10 ENGINE
10 EPS
DETON
WARNING
DETON
SHUTDOWN
KNOCK
SHUTDOWN
COOLANT LVL
SHUTDOWN
AIR DAMPER
IDLE MODE
ACTIVE
ALARM
ALARM
FAILURE
STOP
DERATE
ACTIVE
SHUTDOWN
STALLED
SUPPLYING
LOAD
Relay Driver
Output
(RDO)
RDO-19 On Shutdown Fixed 30 sec.
RDO-23 *
(lead 56)
RDO-21 Off Warning Fixed inhibit time 0 sec.
RDO-14 (lead 48)
RDO-22 Off Warning Fixed 1% of rated
Alarm
Horn
On Warning Fixed 2 sec.
On Shutdown Fixed 0 sec.
On Shutdown Fixed 0 sec.
On Shutdown 0 sec.
On Shutdown Fixed 0 sec.
On Shutdown
On Warning
On Shutdown
On Shutdown
On Shutdown
On Shutdown
Range SettingLamp
Default
Selection
inhibit,
0 sec. delay
inhibit,
0 sec. delay
inhibit,
0 sec. delay
inhibit,
5 sec. delay
inhibit,
0 sec. delay
inhibit,
0 sec. delay
inhibit,
60 sec.
delay
line current
Inhibit
Time Delay (sec.)
Time Delay (sec.)
0--600
or 9:99
for
infinity
TP-6200 10/1226 Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Fuel Level (see A04)
Fuel Valve Relay ]
Generator Set Running
Ground Fault Detected
High Battery Voltage 10 HIGH
High Coolant Temperature Shutdown
High Coolant Temperature Warning
High Oil Temperature Shutdown
High Oil Temperature Warning ][[
Idle (speed) Mode Function (see D21)
In Synch w
Intake Air Temperature Shutdown [[
Intake Air Temperature Warning
[[
Intake Air Temp Warning(seeA03)]
Intake Air Temp Shutdown (see A03)]
Internal Fault Shutdown
J1939 CAN Shutdown (see Engine J1939 CAN Shutdown)
Knock Shutdown (see D13) ]
kW Overload (see Load Shed)
Load Shed kW Overload ]]
Load Shed Over Temperature [[ (Activated by a High Coolant Temp. shutdown)
Load Shed Underfrequency [
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
10 FUEL VALVE
10 RDO-15
10 GROUND
10 HI COOL
10 HI COOL
10 HI OIL TEMP
10 HI OIL TEMP
10 IN SYNCH RDO-29 *
10 INTAKE AIR
10 INTAKE AIR
10 INTERNAL
10 LOAD SHED
10 LOAD SHED
10 LOAD SHED
RELAY
FAULT
BATTERY VOLTAGE
TEMP
SHUTDOWN
TEMP
WARNING
SHUTDOWN
WARNING
TEMP SDWN
TEMP WARN
FAULT
KW OVER
OVER
TEMPERATURE
UNDER
FREQUENCY
Relay Driver
Output
(RDO)
RDO-23 ]
(lead 70R)
RDO-13 Off Warning 14.5--16.5 V (12 V)
RDO-03 (lead 36)
RDO-06 (lead 40)
RDO-30 ]]
RDO only
RDO-31 [
Alarm
Horn
Off
On Warning
On Shutdown 30 5
On Warning 30
On Shutdown 30 5
On Warning 30
On Shutdown 30
On Warning 30
On Shutdown
Off Warning 80%--120% 100% of
Off Warning 59 Hz
Range SettingLamp
29--33 V (24 V)
Default
Selection
16 V (12 V) 32 V (24 V)
kW rating
with5sec.
delay
(60 Hz)
49 Hz
(50 Hz)
Inhibit
Time Delay (sec.)
Time
Delay
(sec.)
10
2--10
5
TP-6200 10/12 27Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Locked Rotor Shutdown
Loss of ECM Communication (ECM only)
Loss of Field Shutdown w
Low Battery Voltage 10 LOW BATTERY
Low Coolant Level (see D14) (with LCL switch) **
Low Coolant Temperature (see D03) **
Low Coolant Temperature Shutdown [[
Low Fuel (Level or Pressure) Warning (see D02) **
Low Fuel Pressure Shutdown (see D09) (125RZG only)
(Low) Oil Pressure Shutdown
(Low) Oil Pressure Warning
Maintenance Due 10 MAINTENANCE
Master Not In Auto (Generator Set Switch)
Master Switch Error 10 MASTER
Master Switch to Off 10 MASTER
Master Switch Open 10 MASTER
NFPA 110 Fault ** 10 NFPA 110
No Air Temperature Signal Warning ]
No Coolant Temperature Signal
No Oil Pressure Signal
No Oil Temperature Signal Warning ]
Overcrank Shutdown 8, 10 OVER CRANK RDO-02
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
10 LOCKED
10 LOSS OF ECM
10 SD LOSS OF
10 LOW COOLANT
10 OIL
10 OIL
10 MASTER NOT
10 NO AIR TEMP
10 NO COOL
10 NO OIL
10 NO OIL TEMP
ROTOR
COMM
FIELD
VOLTAGE
TEMP
SHUTDOWN
PRESSURE
SHUTDOWN
PRESSURE
WARNING
DUE
IN AUTO
SWITCH
ERROR
SWITCH TO
OFF
SWITCH OPEN
FAULT
SIGNAL
TEMP SIGNAL
PRESSURE
SIGNAL
SIGNAL
Relay Driver
Output
(RDO)
RDO-26 * On Shutdown 4
RDO-12 (lead 62)
RDO-04 (lead 38)
RDO-07 (lead 41)
RDO-09 (lead 80)
RDO-10 (lead 32)
(lead 12)
Alarm
Horn
On Shutdown
On Shutdown
Off Warning 10--12.5 V (12 V)
On Shutdown
On Shutdown 30 5
On Warning 30
On Warning
and Not
In Auto
On Shutdown
On Shutdown
and Not
in Auto
On Shutdown
On Shutdown
On Warning 30 4
On Shutdown 30 4
On Shutdown 30 4
On Warning 30 4
On Shutdown 0--6 Cycles 3 Cycles
or
Warning
Range SettingLamp
20--25 V (24 V)
Default
Selection
12 V (12 V) 24 V (24 V)
Inhibit
Time Delay (sec.)
0 10
Time
Delay
(sec.)
TP-6200 10/1228 Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Overcurrent 10 OVER
Over Current PR Shutdown w
Overfrequency Shutdown
Over Power Shutdown w
Overspeed Shutdown
Overvoltage Shutdown
Password (see Access Code)
Pre Lube Relay ]
Remote Reset (see D16)
Remote Shutdown (see D15)
Reverse Power Shutdown w
Speed Sensor Fault 10 SPEED
Starting Aid (see Time Delay Starting Aid)
System Ready 10 RDO-17
Time Delay Engine Cooldown (TDEC)
Time Delay Engine Start (TDES)
Time Delay Starting Aid
Underfrequency 7, 10 UNDER
Undervoltage Shutdown
Variable Speed Governor (VSG) (see A06)
VAR/PF Mode (see D17)
Voltage Lower (see D18)
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Refer
to
Menu
Digital Display
CURRENT
10 SD OVER
CURRENT PR
7, 10 OVER
7, 10 OVER SPEED RDO-01
8, 10 DELAY ENG
8, 10 DELAY ENG
8, 10 Off 0--10 sec.
FREQUENCY
10 SD OVER
7, 8,
10
10 PRE LUBE
10 SD REVERSE
7, 8,
10
POWER
OVER
VOLTAGE
RELAY
POWER
SENSOR
FAULT
COOLDOWN
START
FREQUENCY
UNDER
VOLTAGE
Relay Driver
Output
(RDO)
RDO-28 On Shutdown 102%-- 140% 110% Std.
(lead 39)
RDO-20 (lead 26)
RDO-26 ]
RDO-24 On Warning
(lead 60)
RDO-16
(lead 70C)
RDO-29 ]
RDO-27 On Shutdown 70%-- 95% 85%
Alarm
Horn
On Warning 110% 10
On Shutdown
On Shutdown 102%
On Shutdown 65--70 Hz (60 Hz)
On Shutdown 105%--135%
On Shutdown
Off System
Ready
Off 00:00--10:00
Off 00:00--5:00
On Shutdown 80%--97% 97% FAA
Range SettingLamp
55--70 Hz (50 Hz)
of nominal
min:sec
min:sec
Default
Selection
103% FAA
Stdby
112% Prime
70 (60 Hz) 70 (50 Hz)
115%
2-sec time
delay[
135%
10-sec time
delayw
5:00
00:01
90%[ 80%w
10-sec time
delay[
70%
30-sec time
delayw
Inhibit
Time Delay (sec.)
Time
Delay
(sec.)
10
0.25
2--10
4
10
5--30
TP-6200 10/12 29Section 1 Specifications and Features
Factory-Defined Settings
Status Event or Fault
Voltage Raise (see D19)
Weak Battery 10 WEAK
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC ] Waukesha-powered models ]] FAA only w Paralleling applications
Calibration
Voltage Adjustment 11 VOLT ADJ ±10% of system voltage—
Underfrequency Unload Frequency Setpoint
Underfrequency Unload Slope
Reactive Droop 11 VOLTAGE
VAR Control 11 KVAR ADJ 0 to rated kVAR generating
Power Factor (PF) Adjust Control
Controller Gain 11 REGULATOR
VAR/PF Gain or Utility Stability
Refer
to
Menu
Digital Display
BATTERY
Refer to
Menu
11 FREQUENCY
11 SLOPE 0--10% of rated voltage
11 PF ADJ 0.7 to 1.0 leading
11 VAR/PF GAIN 1--10000 100
Digital Display Range Setting Default Selection
Relay Driver
Output
(RDO)
SETPOINT
DROOP
GAIN
Alarm
Horn
Off Warning 60% of
Ver sio n 2.10
±20% of system voltage—
Version 2.11 or higher
40 to 70 Hz 1 Hz below system frequency (ECM)
volts per cycle
0--10% of system voltage 4% of system voltage
0 to 35% of rated kVAR absorbing
0.6 to 1.0 lagging
1--10000 100
Range SettingLamp
2 Hz below system frequency (non-ECM)
Default
Selection
nominal
System voltage
3.1% of system voltage
0
0.8 lagging
Inhibit
Time Delay (sec.)
Time
Delay
(sec.)
2
Figure 1-13 Settings for Controller Internal Voltage Regulation
1.3.2 Voltage Regulator and Calibration Specifications
Voltage Adjustment. The voltage adjustment allows theusertoenter the desired generator set output level.
This regulated level setting is the average of the three The 550 controller has a voltage regulation function that is internal to the processor. This means that no external
line-to-line voltages in three-phase configurations or
L1-to-L2 in single phase configurations. voltage regulator is necessary. The voltage regulation of the controller uses root mean square (rms) sensing for fast response to changes in indicated and regulated voltages resulting in excellent regulation accuracy.
Submenus display the individual line-to-line voltages.
These voltages are for reference only and are relevant in
unbalanced load conditions. The voltage adjust setpoint
can be changed to accommodate an important phase in RMS voltage regulation is available for both paralleling
an unbalanced system. and utility application to control changes in the reactive loads due to load changes, prime mover speed variation, thermal drift, and other variations. See Figure 1-13 for data on the 550 controller voltage regulation. Refer to Appendix C to customize adjustments for specific applications.
Underfrequency Unload Frequency Setpoint. This
adjustment affects the voltage droop (volts per Hz) when
load is applied and underfrequency occurs. The
underfrequency unload setting defines the setpoint
where underfrequency starts. Any frequency below the
setpoint causes the voltage to drop thus reducing the
load allowing the engine speed to recover according to
1.3.3 Voltage Regulator Adjustments
the underfrequency unload slope setting.
The descriptions of the voltage regulator adjustments and features follow. See Appendix C, Voltage Regulator Definitions and Adjustments, for additional information.
TP-6200 10/1230 Section 1 Specifications and Features
Loading...
+ 186 hidden pages