DATASHEET - EASY819-DC-RC
Control relay, 24 V DC, 12DI(4AI), 6DO relays, display, time, expandable, easyNet
Part no. |
EASY819-DC-RC |
Catalog No. |
256269 |
EL-Nummer |
4520956 |
(Norway) |
|
|
|
Delivery program |
|
|
|
Product range |
|
|
Control relay easyRelay |
Basic function |
|
|
easy800 (expandable, easyNet) |
Description |
|
|
Expandable: Digital/analog inputs/outputs and AS-Interface, PROFIBUS-DP, |
|
|
|
CANopen®, DeviceNet bus systems |
|
|
|
Bus system easyNet on board |
|
|
|
customized laser inscription or delivery with user program possible with EASY- |
|
|
|
COMBINATION-* product (article No. 2010781) |
Inputs |
|
|
|
Digital input count |
|
|
digital: 12 |
|
|
|
digital: 12; of which can be used as analog: 4 |
Digital |
|
|
12 |
of which can be used as analog |
|
|
4 |
Outputs |
|
|
|
Type |
|
|
Relay |
Quantity of outputs |
|
|
Relays: 6 |
Outputs |
|
Number |
6 |
Relay 10 A (UL) |
|
|
6 |
Additional features |
|
|
|
Display |
|
|
with display, with keypad |
Real time clock |
|
|
# |
Display & keypad |
|
|
# |
Expansions |
|
|
Expandable |
|
|
|
Networkable (easyNet) |
Supply voltage |
|
|
24 V DC |
Software |
|
|
EASY-SOFT-PRO |
|
|
|
|
Technical data |
|
|
|
General |
|
|
|
Standards |
|
|
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27 |
Dimensions (W x H x D) |
|
mm |
107.5 x 90 x 72 (6 PE) |
Weight |
|
kg |
0.3 |
Mounting |
|
|
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 |
|
|
|
(accessories) |
Terminal capacities |
|
|
|
Solid |
|
mm2 |
0.2/4 (AWG 22 - 12) |
Flexible with ferrule |
|
mm2 |
0.2/2.5 (AWG 22 - 12) |
Standard screwdriver |
|
mm |
3.5 x 0.8 |
Max. tightening torque |
|
Nm |
0.6 |
Climatic environmental conditions |
|
|
|
Operating ambient temperature |
|
°C |
In accordance with IEC 60068-2-1, -25 - +55 |
Condensation |
|
|
Take appropriate measures to prevent condensation |
LCD display (clearly legible) |
|
°C |
0 - 55 |
Storage |
ϑ |
°C |
In accordance with IEC 60068-2-1, -2, -14 |
|
|
|
-40 - +70 |
relative humidity |
|
% |
in accordance with IEC 60068-2-30, IEC 60068-2-78 |
|
|
|
5 - 95 |
Air pressure (operation) |
|
hPa |
795 - 1080 |
Ambient conditions, mechanical |
|
|
|
Protection type (IEC/EN 60529, EN50178, VBG 4) |
|
|
IP20 |
04/16/2018 |
Eaton 256269 ED2018 V43.0 EN |
1 / 7 |
|
Vibrations |
3,5 mm / 1 g |
|
Hz |
In accordance with IEC 60068-2-6 |
|
|
|
|
|
constant amplitude 0.15 mm: 10 - 57 |
|
|
|
|
|
constant acceleration 2 g: 57 - 150 |
|
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms |
|
|
Impacts |
18 |
|
Drop to IEC/EN 60068-2-31 |
Drop height |
|
mm |
50 |
|
Free fall, packaged (IEC/EN 60068-2-32) |
|
|
m |
1 |
|
Mounting position |
|
|
|
Vertical or horizontal |
|
Electromagnetic compatibility (EMC) |
|
|
|
|
|
Overvoltage category/pollution degree |
|
|
|
III/2 |
|
Electrostatic discharge (ESD) |
|
|
|
|
|
applied standard |
|
|
|
according to IEC EN 61000-4-2 |
|
Air discharge |
|
|
kV |
8 |
|
Contact discharge |
|
|
kV |
6 |
|
Electromagnetic fields (RFI) to IEC EN 61000-4-3 |
|
|
V/m |
0.8 - 1.0 GHz: 10 |
|
|
|
|
|
1.4 - 2 GHz: 3 |
|
|
|
|
|
2.0 - 2.7 GHz: 1 |
|
Radio interference suppression |
|
|
|
EN 55011 Class B |
|
Burst |
|
|
kV |
according to IEC/EN 61000-4-4 |
|
power pulses (Surge) |
|
|
|
according to IEC/EN 61000-4-5 |
|
|
|
|
|
1 kV (supply cables, symmetrical) |
|
Immunity to line-conducted interference to (IEC/EN 61000-4-6) |
|
|
V |
10 |
|
Insulation resistance |
|
|
|
|
|
Clearance in air and creepage distances |
|
|
|
EN 50178, UL 508, CSA C22.2, No. 142 |
|
Insulation resistance |
|
|
|
EN 50178 |
|
Back-up of real-time clock |
|
|
|
|
|
Back-up of real-time clock |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Backup time (hours) with fully charged double layer capacitor |
|
|
|
|
|
Service life (years) |
|
Accuracy of real-time clock to inputs |
|
|
s/day |
typ. ± 2 (± 0.2 h⁄Year) |
|
|
|
|
|
depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year) |
|
|
|
|
|
are possible |
|
Repetition accuracy of timing relays |
|
|
|
|
|
Accuracy of timing relays (of values) |
|
% |
± 0.02 |
|
|
Resolution |
|
|
|
|
|
Range “S” |
|
|
ms |
5 |
|
Range “M:S” |
|
|
s |
1 |
|
Range “H:M” |
|
|
min |
1 |
|
Retentive memory |
|
|
|
|
|
Write cycles of the retentive memory |
|
|
|
1012 (read⁄write cycles) |
|
Power supply |
|
|
|
|
|
Rated operational voltage |
Ue |
|
V |
24 DC (-15/+20%) |
|
Permissible range |
Ue |
|
|
20.4 - 28.8 V DC |
|
Residual ripple |
|
% |
5 |
|
|
Siemens MPI, (optional) |
|
|
|
yes |
|
Input current |
|
|
|
140 mA at Ue |
|
Voltage dips |
|
|
ms |
≤ In accordance with IEC 61131-2 |
|
|
|
|
|
≤ 20 |
|
Fuse |
|
|
A |
1A (T) |
|
Power loss |
P |
|
W |
Normally 3.4 |
|
Digital inputs 24 V DC |
|
|
|
|
|
Number |
|
|
|
12 |
|
Inputs can be used as analog inputs |
|
|
|
4 (I7, I8, I11, I12) |
|
Status Display |
|
|
|
LCD-Display |
|
Potential isolation |
|
|
|
from power supply: no |
|
|
|
|
|
between digital inputs: no |
|
|
|
|
|
from the outputs: yes |
|
|
|
|
|
to interface/memory card: no |
|
|
|
|
|
to easyLink: no |
|
|
|
|
|
to easyNet: yes |
|
Rated operational voltage |
Ue |
|
V DC |
24 |
04/16/2018 |
Eaton 256269 ED2018 V43.0 EN |
2 / 7 |
|
Input voltage |
|
V DC |
Signal 0: 5 (I1 - I6, I9, I10, 8 (I7, I8, I11, I12) |
|
|
|
|
Signal 1: 15 (I1 - I6, I9, I10), 8 (I7, I8, I11, I12) |
|
Input current at signal 1 |
|
mA |
I1 - I6, I9, I10: 3.3 (at 24 V DC) |
|
|
|
|
I7, I8, I11, I12: 2.2 (at 24 V DC) |
|
Deceleration time |
|
ms |
20 (0 -> 1/1 -> 0, Debounce ON) |
|
|
|
|
normally 0.025 (0 -> 1/1 -> 0, Debounce OFF, I1 - I4) |
|
|
|
|
normally 0.25 (0 -> 1/1 -> 0, Debounce OFF, I5, I6, I9, I10) |
|
|
|
|
normally 0.15 (0 -> 1/1 -> 0, Debounce OFF, I7, I8, I11, I12) |
|
Cable length |
|
m |
100 (unshielded) |
|
Frequency counter |
|
|
|
|
Number |
|
|
4 (I1, I2, I3, I4) |
|
Counter frequency |
|
kHz |
5 |
|
Pulse shape |
|
|
Square |
|
Pulse pause ratio |
|
|
1:1 |
|
Cable length |
|
m |
20 (screened) |
|
Incremental counter |
|
|
|
|
Number of counter inputs |
|
|
2 (I1 + I2, I3 + I4) |
|
Counter frequency |
|
kHz |
3 |
|
Pulse shape |
|
|
Square |
|
Signal o set |
|
|
90° |
|
Pulse pause ratio |
|
|
1:1 |
|
Rapid counter inputs |
|
|
|
|
Number |
|
|
4 (I1, I2, I3, I4) |
|
Cable length |
|
m |
20 (screened) |
|
Counter frequency |
|
kHz |
< 5 |
|
Pulse shape |
|
|
Square |
|
Pulse pause ratio |
|
|
1:1 |
|
Digital inputs 24 V DC |
|
|
|
|
Status Display |
|
|
LCD-Display |
|
Analog inputs |
|
|
|
|
Number |
|
|
4 (I7, I8, I11, I12) |
|
Potential isolation |
|
|
from power supply: no |
|
|
|
|
between digital inputs: no |
|
|
|
|
from the outputs: yes |
|
|
|
|
to interface/memory card: no |
|
|
|
|
to easyLink: no |
|
|
|
|
to easyNet: yes |
|
Input type |
|
|
DC voltage |
|
Signal range |
|
|
0-10 V DC |
|
Resolution |
|
|
0.01 V analog |
|
|
|
|
0.01 V digital |
|
|
|
|
10 Bit (value 0 - 1023) |
|
Input impedance |
|
kΩ |
11.2 |
|
Accuracy of actual value |
|
|
|
|
Two EASY devices |
|
% |
± 3 |
|
Within a single device |
|
% |
± 2, (I7, I8, I11, I12) ± 0.12 V |
|
Conversion time, analog/digital |
|
ms |
each CPU cycle |
|
Input current |
|
mA |
< 1 |
|
Cable length |
|
m |
30, screened |
|
Relay outputs |
|
|
|
|
Number |
|
|
6 |
|
Outputs in groups of |
|
|
1 |
|
Parallel switching of outputs for increased output |
|
|
Not permissible |
|
Protection of an output relay |
|
|
Miniature circuit-breaker B16 or fuse 8 A (slow) |
|
Potential isolation |
|
|
from power supply: yes |
|
|
|
|
From the inputs: yes |
|
|
|
|
between digital inputs: yes |
|
|
|
|
to the interface: yes |
|
|
|
|
to easyLink: yes |
|
|
|
|
to easyNet: yes |
|
|
|
|
Safe isolation according to EN 50178: 300 V AC |
|
|
|
|
Basic isolation: 600 V AC |
|
Lifespan, mechanical |
Operations |
x 106 |
10 |
|
Contacts |
|
|
|
|
|
|
|
|
04/16/2018 |
Eaton 256269 ED2018 V43.0 EN |
3 / 7 |