To automatically switch the showroom lights, store window lighting,
and external advertising display for a retail store on or off. The on/off
function must take into account the day of the week, the time, and
a daylight control switch. The connection times for the store window
lighting can be set as required. It must also be possible to switch
all the lights on and off manually. The showroom and store window
lighting must turn on in the event of an alarm.
Overview drawing
Showroom lighting
Mon–Fri 8:55 a.m. to 1:05 p.m.
Time switch 3
1:55 a.m. to 6:35 p.m.
Sat 8:55 a.m. to 2:05 p.m.
The flush-mounted switches S1, S2, and S3 can be used to activate
the showroom lighting outside the programmed times.
In the event of an alarm, the showroom and store window lights are
turned on by contact S6.
Control circuit
F1
L1
N
S5
S2
S1
S3
S4
I1 I2 I3 I4 I5 I6 I7 I8
L
NN
S6
ALT
DEL
Figure 1. Overview
Operating description
External advertising display
Mon–Sun 6:00 a.m. to 11:00 p.m.
Time switch 1
The daylight control switch causes the advertising display to turn off
as the light level rises and to turn on at dusk.
It must also be possible to manually turn the advertising display on
and off at any time. The P2 (Up arrow) and P4 (Down arrow) function
buttons on the easyRelay are used for this purpose.
ote:NThe P buttons are activated in the Special system menu. Press ALT
and DEL simultaneously to change to the Special menu. See also the User
Manual MN05013003E.
Store window lighting
Mon–Fri 8:00 a.m. to 10:00 p.m.
Time switch 2
Sat 8:00 a.m. to 11:00 p.m.
Sun 10:00 a.m. to 10:00 p.m.
The store window lighting is also controlled by the daylight control
switch. It is turned off as the light level rises and is turned on when
it starts to get dark.
The S5 button is used to turn the store window lighting on and off
manually outside the programmed times.
In the event of an alarm, potential-free contact S6 in the alarm
system turns the store window lighting on.
Once time switch 2 has been enabled, it can be used to change
the on/off times, even if a password was activated up in the Special
menu. The time switch is enabled by programming the “+” symbol.
OK
EASY512-AC-RC
12 12 12 12
Q1Q2Q3Q4
H1
S1–S3 Light switches for showroom lighting
S4 Connection contact for daylight control switch
S5 Light switch for store window lighting
S6 Connection contact for alarm system
H1 External advertising display
H2 Store window lighting
H3 Showroom lighting
F1 16A char. B miniature circuit breaker
ESC
H3
H2
Figure 2. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL,® AND CSA®
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
2
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
List of operands
I1 Input, light switch 1, showroom lighting
I2 Input, light switch 2, showroom lighting
I3 Input, light switch 3, showroom lighting
I4 Input, connection contact, daytime control switch
P2 Up arrow cursor key = external advertising display ON
P4 Down arrow cursor key = external advertising display OFF
Q1 Output relay, external advertising display
Q2 Output relay, store window lighting
Q3 Output relay, showroom lighting
1 Connection contact, time 1 = time switching,
external advertising display
2 Connection contact, time 2 = time switching,
store window lighting
3 Connection contact, time 3 = time switching,
showroom lighting
Benefits
t
Implemented functions:
t 3 x single-channel time switches with weekly
and daily programs
t 3 x impulse changeover relays
t
Less wiring required
t
Takes up less space than conventional systems
t
Password function protects against unauthorized access
Examples
Art Deco
Customer:Program:
1/4/13
Date:Page:
Comment:
I
I2
I3
P2
P4
I5
M1
M2
I6
M3
I6
1
1
I4
2
I4
3
M3
Flush-mounted switch S1, S2, S3
for showroom lighting
M1S
Set external advertising display switch
M1R
Reset external advertising display switch
M2
Switch for store window lighting
Q1
External advertising display which is dependent
on daytime control switch I4
Q2
Store window lighting which is dependent
on daytime control switch I4, switch
and alarms
Q3
Showroom lighting which is dependent on
flush-mounted switch
and alarms
Figure 3. easyRelay Display Diagram
Customer:Program:
Date:Page:
Art Deco
1/4/13
Lighting, example 1
1
Lighting, example 1
2
Time switches
MO S
06 00 A
ON
OFF
23 00
Time switches
MOS AS UFR
08 00
ON
OFF
22 00
Time switches
MO F R
08 55
ON
OFF
13 05
U
-
1
:
:
-
:
:
-
:
:
ON
–
OFF
222
A
ON
+
OFF
3
A
ON
OFF
–
-
:
:
-
08 00
:
23 00
:
MO F R
-
13 55
:
18 35
:
Figure 4. easyRelay Display Parameters
EATON CORPORATION
-
ON
OFF
B
ON
+
OFF
3
B
ON
OFF
–
:
:
-
10 00
:
22 00
:
SA
-
08 55
:
14 05
:
C
+
3
C
–
3
Product Application AP05013001E
Effective February 2013
easyRelay applications
Floor lighting
Task
To enable the corridor lights on each floor of a multi-story building
to be switched on and off at various flush-mounted switches. In
parallel, there should also be a central switch from which all the
lights can be turned on and off. In the event of a fire, it must be
possible to turn on all the corridor lights. To save energy, the corridor
lights should be turned off altogether at certain times.
Overview drawing
Figure 5. Overview
Control circuit
F1
L1
N
S2
S1
S3
S4
S5
S6
L
NN
EASY512-AC-RC
12 12 12 12
Q1Q2Q3Q4
H1
F1 16 A, char. B miniature circuit breaker
H1–H4 Lights on 1st–4th floors
S1–S3 Light switches, 1st floor
S4–S6 Light switches, 2nd floor
S7–S9 Light switches, 3rd floor
S10–S12 Light switches, 4th floor
S13 Central ON switch
S14 Central OFF switch
K1 Contact, fire alarm system
S7
S8
S9
S10
I1 I2 I3 I4 I5 I6 I7 I8
ALT
DEL
OK
ESC
H2
H3
S12
S11
H4
S13
S14
K1
Operating description
On each of the four floors, the corridor lights can be turned on
andoff (three-wire control) at three flush-mounted switches
(S1through S12).
If necessary, for example, for cleaning, the corridor lights on every
floor can be turned on at switch S13 and turned off at switch
S14 in the maintenance personnel’s quarters or the building
superintendent’s room.
In the event of a fire, contact K1 in the fire alarm system turns on all
the corridor lights.
To save energy, all corridor lights are turned off at 6:30 p.m. Monday
through Friday and at 2:30 p.m. Saturday.
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
Figure 6. Control Wiring Diagram
List of operands
I1 Input, light switches on 1st floor
I2 Input, light switches on 2nd floor
I3 Input, light switches on 3rd floor
I4 Input, light switches on 4th floor
I5 Input, central ON switch
I6 Input, central OFF switch
I7 Input, contact in fire alarm system
M1 Marker relay, buffer memory light on 1st floor ON/OFF
M2 Marker relay, buffer memory light on 2nd floor ON/OFF
M3 Marker relay, buffer memory light on 3rd floor ON/OFF
M4 Marker relay, buffer memory light on 4th floor ON/OFF
M5 Marker relay, buffer memory light ON/OFF at central switch
M6 Marker relay, buffer memory light ON/OFF at central switch
or via fire alarm system
Q1 Output relay, lights on 1st floor
Q2 Output relay, lights on 2nd floor
Q3 Output relay, lights on 3rd floor
Q4 Output relay, lights on 4th floor
T1 Timing relay, control pulse, central light OFF switch
1 Contact switch, Time 1 Current switch,
Mon–Fri 6:30 p.m./Sat 2:30 p.m.
4
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Benefits
t
Implemented functions:
t 1 x single-channel time switch with weekly and daily programs
t 4 x impulse changeover relays with central circuit
t
Less wiring required
t
Takes up less space than conventional systems
t
Increased flexibility facilitates modification and extension
t
Password function protects against unauthorized access
Examples
I
1
I2
I3
I4
I5
Floor Lighting
1/4/13
M1
M2
M3
M
4
M5S
Customer:Program:
Date:Page:
Example 2
1
Comment:
Turn on 1st floor—press (51–53)
Turn on 2nd floor—press (54–56)
Turn on 3rd floor—press (57–59)
Turn on 4th floor—press (510–512)
Central corridor lighting ON switch S13
M
4
M6
1
T1
M5
TI1
6
Floor Lighting
1/4/13
Comment:
Q4
Lights on 4th floor ON (H4)
central switch or in the event of a fire
TT1
Press to turn off all lights together
MR
1
1st floor lights OFF from central switch
M2R
2nd floor lights OFF from central switch
MR3
3rd floor lights OFF from central switch
MR4
4th floor lights OFF from central switch
MR5
Reset from central ON switch
Central corridor lighting OFF switch S14
Customer:Program:
Date:Page:
Example 2
2
MI5
7
M1
6
MM2
MM6
3
M6
M6
Central lighting ON switch (S13) or
in the event of a fire (K1)
Q1
Lights on 1st floor ON (HI)
central switch or in the event of a fire
Q2
Lights on 2nd floor ON (H2)
central switch or in the event of a fire
Q3
Lights on 3rd floor ON (H3)
central switch or in the event of a fire
Figure 7. easyRelay Display Diagram
Figure 8. easyRelay Display Diagram
MO F R
18 30
ON
OFF
18 31
Floor Lighting
1/4/13
01S
00
TRGT
RES
-
:
:
::::::
ON
OFF
S
14 30
14 31
TRGT
RES
A
-
:
:
1
+
I
A
+
Customer:Program:
Date:Page:
Timing relays
Time switches
Example 2
3
I
B
+
ON
OFF
TRGT
RES
-
:
:
Figure 9. easyRelay Display Parameters
EATON CORPORATION
5
Product Application AP05013001E
Effective February 2013
easyRelay applications
Belt sequence control for three conveyor
belts with motor monitoring
Task
To start up and shut down three conveyor belts at different times.
There are to be three operating modes “Staggered start-up”,
“Staggered shut-down”, and “Fast stop”. The motor-protective circuit
breakers in the belt drives should be monitored; if a circuit breaker
trips, the conveyor system should stop in a controlled manner.
Thefault should also be signaled by a flashing light.
Overview drawing
Belt 1
Belt 2
10
Motor failure
If a drive motor fails, the trip-indicating auxiliary contact (PKZ) opens.
The fault is signaled via the flashing light and automatically triggers
the STOP function. This means that in the event of a fault, any belts
downstream of the defective drive run at no-load for 5 seconds
before they are turned off. Any belts upstream of the defective drive
are turned off immediately.
Control circuit
F1
L1
N
S0
S1
S2
S3
I1 I2 I3 I4 I5 I6 I7 I8
L
NN
DEL
EASY512-AC-R
12 12 12 12
Q1Q2Q3Q4
K1
ESC
K2
Q1
ALT
OK
K3
Q3
Q2
H1
Belt 3
Figure 10. Overview
Operating description
The three conveyor belts in a bulk material handling installation have
to be started up and shut down at different times in order to ensure
that the materials are transported safely and without interruption.
Startup
When START button S1 is pressed, the belts start up at 5-second
intervals (this interval is permanently programmed and cannot be
changed). Belt 3 starts up first.
Shutdown
When STOP button S2 is pressed, the belts stop in reverse order,
i.e., starting from belt 1. This guarantees that the belts are running
at no-load when they are restarted, thus avoiding heavy starting with
a loaded belt.
When the button is pressed, 5 seconds elapse before belt 1 is shut
down. The subsequent belts turn off again after a 5-second delay. It
must be possible to change the time via the easyRelay. To do this,
the “+” must be set when the function block is programmed.
“Fast stop” button S3 turns off all three belts without a timedelay.
S0 Emergency stop
S1 START button
S2 STOP button
S3 Fast stop button
Q1–Q3 Trip-indicating auxiliary contact for motor 1–3
K1–K3 Motor, belt 1–3
H1 Indicator light
F1 16 A, char B miniature circuit breaker
Figure 11. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
Load circuit
L1
L2
L3
N
PE
Q1
K1
3 ~
M1
4.43
Q2
4.44
K2
M
3 ~
M2
4.43
Q3
4.44
K3
M
3 ~
M3
4.43
4.44
M
Figure 12. Load Circuit Diagram
6
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
List of operands
I1 Input, START button
I2 Input, STOP button
I3 Input, Fast stop button
I4 Input, trip-indicating auxiliary contact for motor 1
I5 Input, trip-indicating auxiliary contact for motor 2
I6 Input, trip-indicating auxiliary contact for motor 3
T1 Timing relay with 5-second ON delay —> Start belt 2
T2 Timing relay with 5-second ON delay —> Start belt 1
T3 Timing relay with 5-second OFF delay —> Stop belt 1
T4 Timing relay with 5-second OFF delay —> Stop belt 2
T5 Timing relay with 5-second OFF delay —> Stop belt 3
T6 Timing relay flashing for 1 second to indicate fault
Benefits
t
Implemented functions:
t 2 x ON-delayed timing relays
t 2 x OFF-delayed timing relays
t 1 x flash/blink relay
t 2 x auxiliary contactors
t
Less wiring required
t
Takes up less space than conventional systems
t
Password function protects against unauthorized access
Examples
Customer:Program:
Date:Page:
Belt control
1/4/13
I
4I5I6
I1 M1
Q3
T1 M1
Q2
2
MT1
I2
2
TM3
M3
1
M
3
I
Q1
Comment:
M1
Motor-protective circuit breaker 1, 2, 3 not tripped
Q3S
START button-> motor for belt 3 on
M3S
START button pressed
T1T
ON-delay for belt 2
Q2S
Motor for belt 2 on
TT2
ON-delay for belt 1
Q1
S
Motor for belt 1 on
M2
S
STOP button pressed
TT3
OFF-delay for belt 1
QR1
Motor for belt 1 off
Q3
TT4
OFF-delay for belt 2
Figure 13. easyRelay Display Diagram
Example 3
1
EATON CORPORATION
7
Product Application AP05013001E
Effective February 2013
easyRelay applications
Customer:Program:
Date:Page:
Belt control
1/4/13
T
43
M
5
I
6I
I
3
2
Q
M3
T5
6
I
I3
I4
I
5
I
6
6
T
Q2
R
T5T
QR3
TT6
Q4
Comment:
Motor for belt 2 off
OFF-delay for belt 3
Motor for belt 3 off
A motor has failed
Indicator light
Example 3
2
Customer:Program:
Date:Page:
Belt control
1/4/13
T
53
M
1
M
3I
I
2
1
M
3I
R
R
Comment:
M2
Reset buffer memory for STOP
M3
Reset buffer memory for START
Example 3
3
Figure 14. easyRelay Display Diagram
Figure 15. easyRelay Display Diagram
X
X
Belt control
1/4/13
X
05S
0005 0005 00
TRGT
RES
05S
0005 0001 00
TRGT
RES
S
::::::
1
+
4
+
TRGT
RES
X
SS
::::::
TRGT
RES
Customer:Program:
Date:Page:
Timing relays
Timing relays
Figure 16. easyRelay Display Parameters
Example 3
4
2
+
5
+
X
S
TRGT
RES
TRGT
RES
3
+
6
+
8
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Greenhouse temperature and
ventilationcontrol
Task
To automatically open and close the roof lights of a greenhouse in
order to adjust the ventilation and temperature. Warm air should
beblown in via the heating system when the temperature drops
below a certain level. The drive motors for the fans and the roof
lights must be monitored for faults, which should also be signaled
bya flashing light.
Overview drawing
Warm air supply
When the temperature in the greenhouse falls below a certain level,
the fan motor M2 is automatically activated to blow in warm air. The
motor is switched off again when the temperature returns to the
desired level.
Motor failure
If M1 or M2 fails, the contact of the corresponding trip-indicating
auxiliary contact Q1 or Q2 opens. The fault is signaled via the
flashing light H1 for both motors.
Continuous ventilation
Key switch S1 is used to turn off the automatic temperature control
and select “Continuous ventilation”. It may be necessary to first
close the roof lights and then open them again in order to use
thisfunction.
It should be possible to enter the motor run time T2, which
determines how far the roof light is opened, directly on the
easyRelay.
The roof lights can be opened as far as the end position. The default
for T2 is 4 seconds.
Manual operation
For maintenance and repairs, the windows can be opened via the
P2button (Up arrow) and closed via the P4 button (Down arrow).
ote:NThe P buttons are activated in the Special menu. Press ALT and DEL
simultaneously to change to the Special menu. See also the User Manual
MN05013003E.
Figure 17. Overview
Operating description
The greenhouse is also used as a display and sales area. The roof
lights are opened for ventilation and are closed again depending
on the temperature. The “Open window” and “Close window”
switching points are programmed via the easyRelay. The voltage
output of temperature sensor B1 supplies the necessary comparison
value. The following example demonstrates how the switching points
are determined or calculated.
Ventilation control
All the roof lights are activated by a three-phase AC motor M1 with
a reversing contactor circuit. The end positions are detected by limit
switch S2 (open) and S3 (closed). The motor switches off when the
limit switch is reached.
EATON CORPORATION
9
Product Application AP05013001E
Effective February 2013
easyRelay applications
Control circuit
L1
N
PE
F1
G1
~
S0
+24V
B1 Temperature sensor
F1 16 A char. B miniature circuit breaker
F2 Miniature circuit breaker (optional)
G1 Power supply unit 230 Vac/24 Vdc
H1 Motor fault indicator light
K1 Contactor for Open window drive motor
K2 Contactor for Close window drive motor
K3 Contactor for fan motor
Q1 Window drive motor tripping indicator
Q2 Fan motor tripping indicator
S0 Emergency stop
S1 Key switch
S2 Open limit switch
S3 Closed limit switch
F2
-
0V
S2
S1
24V
0V 0V
EASY512-DC-R
12 12 12 12
Q2Q3Q4
Q1
K2
K1
K2
K1
S3
I1 I2 I3 I4 I5 I6 I7 I8
DEL
ESC
K3
Q2
Q1
ALT
OK
H1
Figure 18. Control Wiring Diagram
ote:NThe electrical interlock may be omitted when using a reversing
contactor combination with a mechanical interlock.
Load circuit
L1
L2
L3
N
PE
Q1
K1
M
3 ~
M1
4.43
4.44
Q2
K2
K3
M
3 ~
M2
Figure 19. Load Circuit Diagram
T
0-10V
4.43
4.44
Sample switching points
t
Temperature sensor measuring range: –35°C to +55°C
t
Output signal from temperature sensor: 0 to 10 Vdc
t
Selected switching point—Open: 25°C
t
Selected switching point—Close: 23°C
t
B1
Selected switching point—Heat: 20°C
General formula for the comparison value:
10V
×=
UL + LL
(Switchpoint + LL)
UL = Upper limit of measured value
LL = Lower limit of measured value
Set point value for Open comparator:
10V
55ºC + 35ºC
×=(25ºC + 35ºC)6, 4V
Set point value for Close comparator:
10V
55ºC + 35ºC
×=(23ºC + 35ºC)6, 4V
Set point value for Heat comparator:
10V
55ºC + 35ºC
×=(20ºC + 35ºC)6, 1V
A switching range (± 0.1V) must be defined for each comparison
value to avoid having to repeatedly turn ON and OFF when the
comparison value is reached.
t
This gives the following switching points
in the comparator blocks:
t Open window
ON = 6.8V
OFF = 6.6V
t Close window
ON = 6.3V
OFF = 6.5V
t Heat
ON = 6.0V
OFF = 6.2V
List of operands
A1 Comparator, Open window ON
A2 Comparator, Open window OFF
A3 Comparator, Close window ON
A4 Comparator, Close window OFF
A5 Comparator, Heat ON
A6 Comparator, Heat OFF
I1 Input, key switch for continuous ventilation
I2 Input, Open limit switch
I3 Input, Closed limit switch
I4 Input, window drive motor trip-indicating auxiliary contact.
Input, fan motor trip-indicating auxiliary contact
I8 Input, comparative voltage of temperature sensor
10
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
M1 Marker relay, buffer memory, Open window
M2 Marker relay, buffer memory, Close window
M3 Marker relay, buffer memory, Open window comparator
M4 Marker relay, buffer memory, Close window comparator
M5 Marker relay, buffer memory, Heat comparator
M6 Open marker via T2
P2 Up arrow cursor button = Open window
P4 Down arrow cursor button = Close window
Q1 Output, contactor for Open window drive motor
Q2 Output, contactor for Close window drive motor
Q3 Output, contactor for fan motor
Q4 Output, motor fault indicator light
T1 Timing relay, flashing, for fault message
T2 Timing relay, single-pulse, 4 seconds = opening time
for continuous ventilation
Benefits
t
Implemented:
t 1 x ON-delayed timing relay
t 1 x flash/blink relay
t
Temperature values can be processed (analog values)
t
Less wiring required
t
More flexible if modifications are required
Customer:Program:
Date:Page:
Greenhouse
1/4/13
M
5I5
I1 I3
4
I
I5
T1
1
I
R
Q3
T2T
M6S
T1T
Q
4
M6
Comment:
20C, motor 2, ->warm air
degree of opening via T2
Marker Open via T2
Motor 1 or 2 defective
Indicator light H1 flashes
Reset marker Open via T2
Example 4
2
Examples
A
1
A2
A3
A4
A5
A6
M
3
1
M
P
2
T2
MM4
2
P4
I1
Greenhouse
1/4/13
2
I
12I
Q
I2
I2
I3
Q
I1
I3
I3 M6
I4
1
MS3
MR3
MS4
M4R
M5S
MR5
MI41
Q1
M2
Q2
Customer:Program:
Date:Page:
Example 4
1
Comment:
Open window ON
Open window OFF
Close window ON
Close window OFF
Heat ON
Heat OFF
25C, do not open window, motor 1
Motor 1 opens
23C, do not close window, motor 1
Motor 1 closes
Figure 21. easyRelay Display Diagram
Customer:Program:
Date:Page:
Timing relays
Analog comparators
Analog comparators
Greenhouse
1/4/13
01S
00
TRGT
RES
ANALOGANALOGANALOG
I8
68
.
ANALOGANALOGANALOG
I8
65
.
1
+
AA
1
+
AA
4
+
S
:::
I8
66
.
I8
60
.
04 00
:::
TRGT
RES
Example 4
3
2
+
2
+
5
+
I8
63
.
I8
62
.
TRGT
RES
A
3
+
A
6
+
Figure 20. easyRelay Display Diagram
Figure 22. easyRelay Display Parameters
EATON CORPORATION
11
Product Application AP05013001E
Effective February 2013
easyRelay applications
Lighting control in a production room
Task
To automatically turn on the lighting fixtures in a production room
during production hours. The lights should turn on and off gradually
in response to changes in the daylight level. It must be possible to
turn the switch for the individual lighting stages on and off manually
at any time. Faults in the lighting system should be signaled by a
flashing light.
Overview drawing
Connection to the busbar system
Phase 1:
Every 1st, 4th, 7th, and 10th neon light.
Activated via contactor K1.
Enabled via daylight control switch B1.
Phase 2:
Every 2nd, 5th, 8th, and 11th neon light.
Activated via contactor K2.
Enabled via daylight control switch B2.
Phase 3:
Every 3rd, 6th, 9th, and 12th neon light.
Activated via contactor K3.
Enabled via daylight control switch B3.
Lighting stages
Stage 0:
All the lights are off.
Stage 1:
Every third light is on. Contact B1 is closed.
Stage 2:
Every third light is off. Contacts B1 and B2 are closed.
Stage 3:
All the lights are on. Contacts B1, B2, and B3 are closed.
Manual operation
It must be possible to switch the individual lighting stages
atlightswitches S1 through S3.
Use of the manual function is signaled by indicator lights
H1throughH3.
Figure 23. Overview
Operating description
Three light fixtures, each with 12 fluorescent lights, are suspended
from a busbar system. The lighting is on from 6:00 a.m. to 5:30 p.m.
Monday through Friday and is varied according to the daylight level.
The switch-on times and the ON duration must be variable to suit
requirements.
Lighting stages
The use of three different switching stages guarantees the
necessary brightness, saves energy, and places a uniform load
onthe mains supply.
Failure of a busbar
The busbars are protected via miniature circuit breakers Q1 through
Q3 and are monitored by trip indicating auxiliary contacts. Faults are
signaled in the form of a group alarm via flashing indicator lightH4.
ote:NIf the daylight control switches already have an ON-delay or OFF-delay,
these times should be set as low as possible (of the order of 1 second).
Alternatively, the ON-delayed timers T1 through T6 programmed in the
easyRelay (default value 60 seconds) can be changed to obtain the required
overall delay.
12
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Control circuit
F1
L1
N
B1
S1
S2
S3
L
NN
EASY512-AC-RC
12 12 12 12
Q1Q2Q3Q4
K1
B2
I1 I2 I3 I4 I5 I6 I7 I8
DEL
ESC
K2
K3
Q1
B3
ALT
OK
S1
S2
S3
Q2
Q3
H3
H2
H1
H4
B1–B3 Contact, daylight control switch 1–3
F1 16 A, char B miniature circuit breaker
H1–H3 Indicator light, stage 1–3
H4 Fault indicator light
K1–K3 Cont actor, lighting stage 1–3
Q1–Q3 Miniature circuit breaker 1–3
S1–S3 Light switch, stage 1–3
Figure 24. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
Load circuit
Switching points of the daylight control switch
On <- B2-> Off
LightDark
On <- B3-> Off
On <- B1-> Off
Figure 26. Switching Points of the Daylight Programmable
Switch
List of operands
I1 Input, light switch, stage 1
I2 Input, light switch, stage 2
I3 Input, light switch, stage 3
I4 Input, contact of daylight control switch 1
I5 Input, contact of daylight control switch 2
I6 Input, contact of daylight control switch 3
I7 Input, circuit breaker messages
M1 Marker relay, buffer memory, stage 1
M2 Marker relay, buffer memory, stage 2
M3 Marker relay, buffer memory, stage 3
Q1 Output, contactor for stage 1
Q2 Output, contactor for stage 2
Q3 Output, contactor for stage 3
Q4 Output, fault indicator light
T1 Timing relay with 60-second ON delay —> Stage 1 ON
T2 Timing relay with 60-second ON delay —> Stage 1 OFF
T3 Timing relay with 60-second ON delay —> Stage 2 ON
T4 Timing relay with 60-second ON delay —> Stage 2 OFF
T5 Timing relay with 60-second ON delay —> Stage 3 ON
T6 Timing relay with 60-second ON delay —> Stage OFF
T7 Timing relay, flashing for 1 second to indicate fault
L1
L2
L3
N
PE
Q1
K1
4.43
4.44
Q2
K2
Figure 25. Load Circuit Diagram
4.43
4.44
Benefits
t
Implemented functions:
t 1 x flash/blink relay
Q3
K3
4.43
4.44
1L1
1L2
1L3
N
PE
2L1
2L2
2L3
N
PE
3L1
3L2
3L3
N
PE
t 1 x single-channel time switch with weekly and daily programs
t
Functional overall solution
t
Less wiring required
t
Takes up less space than conventional systems
EATON CORPORATION
13
Product Application AP05013001E
Effective February 2013
Examples
I
4
T1
I
4
T2
I5
TI3
I
5
T4
6
Light fixtures
1/4/13
TT1
MS1
TT2
M1R
T3T
S
M2
T
T4
R
M2
T
T5
Customer:Program:
Date:Page:
Example 5
1
Comment:
Daytime control switch 1 ON, B1
Stage 1 ON
Daytime control switch 1 OFF, B1
Stage 1 OFF
Daytime control switch 2 ON, B2
Stage 2 ON
Daytime control switch 2 OFF, B2
Stage 2 OFF
Daytime control switch 3 ON, B3
I
1
M1
I
2
M2
I3
M3
Light fixtures
1/4/13
Comment:
Q1
Stage 1 ON (B1)
Q2
Stage 2 ON (B1 + B2)
Q3
Stage 3 ON (B1 + B2 + B3)
Customer:Program:
Date:Page:
easyRelay applications
Example 5
2
S
T
R
T
M3
Stage 3 ON
T6
Daytime control switch 3 OFF, B3
M3
Stage 3 OFF
T7
Fault in busbar 1, 2 or 3
Q4
Fault indicator light, Is,
TT5
6
I
6
I
7
T7
Figure 27. easyRelay Display Diagram
Figure 28. easyRelay Display Diagram
X
Light fixtures
1/4/13
60S
00
TRGT
RES
60S
00
TRGT
RES
X
60 0060 00
S
:::
1
+
X
S
:::
4
+
:::
TRGT
RES
60 0060 00
:::
TRGT
RES
Customer:Program:
Date:Page:
Timing relays
Timing relays
Example 5
3
2
+
5
+
X
S
XX
S
TRGT
RES
TRGT
RES
3
+
6
+
14
EATON CORPORATION
Timing relays
01S
00
TRGT
RES
:::
7
+
:::
TRGT
RES
Figure 29. easyRelay Display Parameters
TRGT
RES
easyRelay applications
Product Application AP05013001E
Effective February 2013
Booster pumps
Task
Two pumps provide the water supply for an installation. Their
operation is to be monitored. The two pumps are to be operated
alternately to prevent excessive wear. The operating status and
the faults within the installation are to be signaled by two indicator
lights. It must be possible to select the pressure-related switching
points for activating the pumps as required.
Overview drawing
Faults
Electrical failure of a pump motor is detected by the trip-indicating
auxiliary contacts for the motor-protective circuit breaker Q1 and Q2.
The pump that is still in working order will be activated. If one of
the pumps is mechanically defective, the resulting drop in pressure
will be detected, and the other pump will be activated after time T4
has elapsed. Both fault types are signaled by the flashing indicator
light H1 or H2. When both pumps are electrically defective, indicator
lights H1 and H2 will flash simultaneously.
Low pressure
The system is monitored for low pressure, which is signaled
by indicator lights H1 and H2 that flash alternately after time T5
has elapsed. It must be possible to set the low pressure limit on
the easyRelay.
Acknowledgement
All fault messages are retained until they have been acknowledged
by pressing the S3 button.
Maintenance
It must be possible to directly switch pump P1 using key switch S1
and pump P2 using key switch S2.
Figure 30. Overview
Operating description
Pumping operation
The pumping station provides the water supply for an installation. It
must also ensure that the pressure does not fall below a specified
minimum level. There are two booster pumps—P1 and P2. If the
pressure is too low, one of the pumps is activated via pressure
sensor B1. To ensure that the two pumps are subject to equal use
and wear, they are run alternately for 48-hour periods. Two indicator
lights, H1 and H2, signal which of the two pumps is in use. If the
easyRelay is disconnected from the power supply, the operating
hours count will start again, and pump 1 will be activated first.
To enable the pumps to change over after a shorter or longer
operating period, counters C1 and C2 should be set to new
comparison values using the following formula:
Desired changeover time in hours x 60 = comparison value.
Default: 48 hours x 60 = 2880.
EATON CORPORATION
15
Product Application AP05013001E
Effective February 2013
easyRelay applications
Control circuit
L1
N
PE
F1
G1
~
S0
+24V
B1 Pressure sensor
F1 16 A char. B miniature circuit breaker
F2 Miniature circuit breaker (optional)
G1 Power supply unit 230 Vac/24 Vdc
H1 Indicator light for pump 1
H2 Indicator light for pump 2
K1 Contactor for pump P1
K2 Contactor for pump P2
Q1 Trip-indicating auxiliary contact for pump 1
Q2 Trip-indicating auxiliary contact for pump 2
S0 Emergency stop
S1 Key switch for pump 1
S2 Key switch for pump 2
S3 Acknowledgement button
F2
-
0V
S1
0V
+24V
EASY512-DC-R
12 12 12 12
Q1
K1
Figure 31. Control Wiring Diagram
Load circuit
L1
L2
L3
N
PE
Q1
K1
M
3 ~
M1
4.43
4.44
Figure 32. Load Circuit Diagram
Q2
Q1
S2
I1 I2 I3 I4 I5 I6 I7 I8
0V
Q2Q3
K2
ALT
DEL
OK
ESC
H1
Q2
K2
Pressure diagram
S3
P
0-10V
B1
0 bar
Figure 33. Pressure Diagram
A1A2A3
Pressure
Switching points
A1 Pump 1 or pump 2 is activated; H1 or H2 lights up
A2 Low pressure After time T4 (10 sec), changeover to the
inactive pump, the fault is indicated by flashing signal
at H1 or H2. After time T5, a total failure is signaled by
H1 and H2 flashing alternately
Q4
A3 Pump 1 or pump 2 is switched off; H1 or H2 goes out
See example 4 for determining the pressure switching points.
H2
List of operands
A1 Comparator for minimum pressure monitoring, lower threshold
A2 Comparator for low pressure monitoring due to electrical or
mechanical fault
A3 Comparator for minimum pressure monitoring, upper threshold
C1 Counter with 30-second pulse for operating hours of pump 1
C2 Counter with 30-second pulse for operating hours of pump 2
I1 Input, key switch for directly activating pump 1
I2 Input, key switch for directly activating pump 2
I3 Input, motor-protective circuit breaker for pump 1
I4 Input, motor-protective circuit breaker for pump 2
M2 Marker relay for low pressure/mechanical fault, pump 1
M3 Marker relay for low pressure/mechanical fault, pump 2
M4 Marker relay for electrical fault, pump 1
M5 Marker relay for electrical fault, pump 2
M6 Marker relay for total failure of pumping system
4.43
M7 Marker relay for minimum pressure switching point,
switch pump on/off
4.44
M8 Marker relay, buffer memory, indicator light for pump 1
M9 Marker relay, buffer memory, indicator light for pump 2
Q1 Output, contactor for pump 1
Q2 Output, contactor for pump 2
M
3 ~
M2
Q3 Output, indicator light for pump 1
Q4 Output, indicator light for pump 2
T1 30-second cycle for recording operating time, pump 1
T2 30-second cycle for recording operating time, pump 2
T3 1-second cycle for flashing signal from indicator light
T4 Time delay for low pressure message/mechanical fault,
pump 1, 2
T5 Time delay for low pressure message, total failure
16
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Benefits
t
Implemented functions:
t 1 x flash/blink relay
t 2 x ON-delayed timing relays
t 1 x operating hour counters
t
Processing of pressure values (analog values)
t
Variable switching points and operating hour changeover
t
Less wiring required
t
Takes up less space than conventional systems
Examples
Pumping station
Customer:Program:
1/4/13
Date:Page:
A
1
A3
I1
M7 M1 I 3
M1 I 4
I2
1Q
T
1
C1
Q2
T2
C2
M
S7
MR7
M8
Q1
Q2
M9
TT1
CRC2
C1
S
M1
TTR2
C1
C
C2
R
M1
Example 6
1
Comment:
Lower threshold for minimum pressure
Upper threshold for minimum pressure
Pump 1 ON indicator light
Pump 1 active
Pump 2 active
Pump 2 ON indicator light
Pump 1 run time clock
Reset counter 2
Pulse counter 1-48 hours
Change over to pump 2
Pump 2 run time clock
Reset counter 1
Pulse counter 2-48 hours
Change over to pump 1
Figure 34. easyRelay Display Diagram
Pumping station
Customer:Program:
1/4/13
Date:Page:
Comment:
T
I3
I4
A2
I5
5T
T
Q
4
I
M2
T
M2
M4
M8
M6 T3
T3
S
R
S
T
M
3
1
4
36
S
M
Clock for flashing signal from indicator light
1
MS
Electrical fault in pump 1
M4
Active pump 2
M1
Electrical fault in pump 2
M5
Active pump 1
T4
Low pressure monitoring
TT5
MSS6
Low pressure signal, total failure
M2
Mechanical fault in pump 1
M1
Active pump 2
Q3
Fault in pump 1 -> Indicator light
H1 flashes
Pump 1 in use
Total failure ->Lights flash alternately
Figure 35. easyRelay Display Diagram
Pumping station
Customer:Program:
1/4/13
Date:Page:
Comment:
M
S22Q4T3
M3 I 3
M5
M9
M6
T3
5I
M
M
6
Mechanical fault in pump 2
MR
1
Active pump 1
Q4T3M3
Fault in pump 2 -> Indicator light
H2 flashes
Pump 2 in use
Total failure -> Lights flash alternately
MR2
Acknowledge fault messages
MRR3
Example 6
2
Example 6
3
M4
R
M5
M6
R
Figure 36. easyRelay Display Diagram
EATON CORPORATION
17
Product Application AP05013001E
Effective February 2013
easyRelay applications
Customer:Program:
Date:Page:
Timing relays
Timing relays
Analog comparators
Up and down counters
Pumping station
1/4/13
30S
00
TRGT
RES
X
10S
00
TRGT
RES
ANALOGANALOGANALOG
I8
29
.
28 8028 80
DIR
CNT
RES
SS
30 0001 00
:::
1
+
X
S
:::
4
+
I8
AA
1
+
20
.
C
1
+
:::
TRGT
RES
25 00
:::
TRGT
RES
DIR
CNT
RES
Figure 37. easyRelay Display Parameters
Example 6
4
2
+
5
+
2
+
C
2
+
I8
31
.
TRGT
RES
TRGT
RES
DIR
CNT
RES
Tank installation level indicator
Task
To monitor the fill level of three tanks. When the maximum level is
reached, this should be indicated by a visual and audible signal.
Overview drawing
3
+
A
3
+
Figure 38. Overview
Operating description
The fill level of three fat tanks in an animal feed plant is monitored.
If one tank is full, the corresponding indicator light H1, H2, or H3
C
flashes in the control room to signal that a “new value” is being
formed. After a set time has elapsed (default 3 seconds), an alarm
starts as well. Acknowledgement button S4 can be used for all
three tanks; it acknowledges the audible signal from the alarm and
changes the flashing light to a continuous light.
18
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Control circuit
F1
L1
N
S1
S2
L
EASY512-AC-R
12 12 12 12
Q1Q2Q3Q4
H1
F1 16 A, char. B miniature circuit breaker
H1 Indicator light for tank 1
H2 Indicator light for tank 2
H3 Indicator light for tank 3
H4 Alarm
S1 Level indicator for tank 1
S2 Level indicator for tank 2
S3 Level indicator for tank 3
S4 Acknowledgement button
Figure 39. Control Wiring Diagram
S3
NN
S4
I1 I2 I3 I4 I5 I6 I7 I8
DEL
ESC
H2
List of operands
I1 Input, float switch for tank 1
I2 Input, float switch for tank 2
I3 Input, float switch for tank 3
I4 Input, acknowledgement button
M1 Marker relay, acknowledged full message from tank 1
M2 Marker relay, acknowledged full message from tank 2
M3 Marker relay, acknowledged full message from tank 3
Q1 Output, indicator light for tank 1
Q2 Output, indicator light for tank 2
ALT
Q3 Output, indicator light for tank 3
Q4 Output, Alarm
T1 Timing relay with 3-second ON delay —> delay after tank 1
OK
full message
T2 Timing relay with 3-second ON delay —> delay after tank 2
full message
T3 Timing relay with 3-second ON delay —> delay after tank 3
full message
H4
H3
T4 Single-pulse timing relay —> Alarm ON set pulse
T5 Single-pulse timing relay —> Alarm ON set pulse
T6 Single-pulse timing relay —> Alarm ON set pulse
T7 Timing relay flashing for 0.5 second —> New value signal
Benefits
t
Implemented functions:
t 3 x ON-delayed timing relays
t 1 x flash/blink relay
t 3 x auxiliary contactors
t
Less wiring required
t
Takes up less space than conventional systems
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
EATON CORPORATION
19
Product Application AP05013001E
Effective February 2013
easyRelay applications
Examples
Customer:Program:
Date:Page:
Tank installation
1/4/13
M
I
11
M
1
M
1
I4
M
I22
M
2
M2
I4
T
7
Q1
M1
T1T
T
7
Q2
M2
T2T
Example 7
1
Comment:
Tank 1 full (S1), H1 flashes
H1 maintained light
by acknowledgement button
Timing relay for alarm
Tank 2 full (S2), H2 flashes
H2 maintained light
by acknowledgement button
Timing relay for alarm
Tank installation
Customer:Program:
1/4/13
Date:Page:
Comment:
M3
I
3
1
T
T
2
T3
T
4
T5
T6
4
I
T7
M3
M3
I4
Q3
Tank 3 full (S3), H3 flashes
M3
H3 maintained light
by acknowledgement button
T3T
Timing relay for hooter
T4T
Pulse for alarm from tank 1
T5T
Pulse for alarm from tank 2
T6T
Pulse for alarm from tank 3
QSR4
Alarm ON for tank 1 after 3 seconds
Alarm ON for tank 2 after 3 seconds
Alarm ON for tank 3 after 3 seconds
Q4
Alarm OFF with acknowledgement button S4
T7T
Clock for flashing signal
Example 7
2
Figure 40. easyRelay Display Diagram
Figure 41. easyRelay Display Diagram
Tank installation
Customer:Program:
1/4/13
Date:Page:
Timing relays
XX X
03S
TRGT
RES
Timing relays
00S
TRGT
RES
Timing relays
00S
TRGT
RES
00
1
+
00
4
+
50
7
+
03 0003 00
SS
:::
TRGT
RES
SS
00 0000 00
:::
TRGT
RES
:::
TRGT
RES
Example 7
3
:::
TRGT
2
RES
+
:::
TRGT
5
RES
+
:::
TRGT
RES
3
+
6
+
20
Figure 42. easyRelay Display Parameters
ote:NThe specified time of 0 seconds in the timing relay produces a pulsing
signal of the same length as one easyRelay cycle time.
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Access monitoring for a parking garage
Task
To monitor the occupancy of a company parking garage. Cars can
enter the garage provided that there are still some spaces available.
Access is controlled by a barrier system. The occupancy of the
garage is signaled by a “Full/Empty” display.
Overview drawing
Faults
A fault in the barrier system, which is signaled via make contact S1,
is displayed by flashing indicator light H1 in the garage attendant’s
booth.
Maintenance
The barrier can be opened by pressing the P2 function button
(Uparrow) on the easyRelay.
Control circuit
F1
L1
N
S1
S2
S3
S4
S5
I1 I2 I3 I4 I5 I6 I7 I8
L
NN
ALT
DEL
OK
EASY512-AC-R
12 12 12 12
Q1Q2Q3Q4
ESC
Figure 43. Overview
Operating description
Entry and exit
Access to the garage is monitored by a swipe card reader. If the
card is valid, contact S3 is closed briefly. When a vehicle leaves
the garage, contact S2 is closed via an induction loop embedded
in the ground. A display panel with the message “Full” or “Spaces
free” at the point of entry should indicate whether there are still
parking spaces available. If voltage is present at signal input K2, the
display panel should read “Full”, otherwise it should read “Spaces
free”. The barrier opens when a voltage pulse is applied to K1 for
2 seconds, and it closes automatically when a vehicle has passed
through or after a set time has elapsed.
Counting the vehicles
Incoming and outgoing vehicles should be counted by the easyRelay.
The maximum number of vehicles that can be parked can be set
on the easyRelay. Vehicles may enter if there are parking spaces
available. The counter can be reset to zero via the key switch S5 in
order to establish a baseline.
K1
F1 16 A, char. B miniature circuit breaker
H1 Fault flashing indicator light
K1 Barrier driving circuit
K2 Display panel driving circuit
S1 Barrier fault indicator
S2 Contact for induction loop
S3 Contact for swipe card reader
S4 Open barrier button
S5 Reset counter key switch
K2
H1
Figure 44. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
Manual operation
The garage attendant should be able to open the barrier at any time
using button S4, regardless of whether the garage is full or not.
EATON CORPORATION
21
Product Application AP05013001E
Effective February 2013
easyRelay applications
List of operands
C1 Vehicle counter
I1 Input, fault barrier
I2 Input, contact for induction loop
I3 Input, contact for swipe card reader
I4 Input, open barrier button
I5 Input, reset counter key switch
P2 Up arrow cursor button = open barrier
Q1 Output, open barrier
Q2 Output, display panel
Q3 Output, fault indicator light
T1 Single 2-second single-pulse timing relay =
open barrier pulse
To activate the lighting in rarely visited rooms in a library only
whenturned on by the user in order to save energy. The user
mayselect how long he/she wants the lights to remain on. It should
alsobe possible to switch the lights on and off permanently at a
central switch.
Overview drawing
Figure 47. Overview
Operating description
The four groups of lights (H1 through H4) in a library should only
beswitched on at a reader’s request. Two flush-mounted buttons
(S1through S8) are provided for this purpose at the end of a
shelving area. Ifthe reader presses the button briefly, the light will
come on for just 5 minutes. More pressure on the button will light
the area for a half-hour period. All the lights can be turned on and off
for cleaning via the central flush-mounted S9 button.
Control circuit
F1
L1
N
S3
S2
S1
F1 16 A, char. B miniature circuit breaker
H1 Lights in area A
H2 Lights in area B
H3 Lights in area C
H4 Lights in area D
S1–S2 Light switch in area A
S3–S4 Light switch in area B
S5–S6 Light switch in area C
S7–S8 Light switch in area D
S9 Central ON/OFF light switch
S4
L
NN
EASY512-AC-R
12 12 12 12
Q1Q2Q3Q4
H1
S5
S6
I1 I2 I3 I4 I5 I6 I7 I8
DEL
ESC
H2
H3
S8
S7
ALT
OK
S9
H4
Figure 48. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
EATON CORPORATION
23
Product Application AP05013001E
Effective February 2013
easyRelay applications
List of operands
C1 Counter, ON duration 5 min., area A
C2 Counter, ON duration 30 min., area A
C3 Counter, ON duration 5 min., area B
C4 Counter, ON duration 30 min., area B
C5 Counter, ON duration 5 min., area C
C6 Counter, ON duration 30 min., area C
C7 Counter, ON duration 5 min., area D
C8 Counter, ON duration 30 min., area D
I1 Input, light switch S1/S2, area A
I2 Input, light switch S3/S4, area B
I3 Input, light switch S5/S6, area C
I4 Input, light switch S7/S8, area D
I5 Input, central ON/OFF light switch
M1 Marker relay, buffer memory, light in area A ON for 5 min.
M2 Marker relay, buffer memory, light in area A ON for 30 min.
M3 Marker relay, buffer memory, light in area B ON for 5 min.
M4 Marker relay, buffer memory, light in area B ON for 30 min.
M5 Marker relay, buffer memory, light in area C ON for 5 min.
M6 Marker relay, buffer memory, light in area C ON for 30 min.
M7 Marker relay, buffer memory, light in area D ON for 5 min.
M8 Marker relay, buffer memory, light in area D ON for 30 min.
M9 Marker relay, buffer memory, light ON/OFF at central switch
Q1 Output relay, light area A
Q2 Output relay, light area B
Q3 Output relay, light area C
Q4 Output relay, light area D
T1 Timing relay with 2-second ON delay = short/long
ON duration, area A
T2 Timing relay with 2-second ON delay = short/long
ON duration, area B
T3 Timing relay with 2-second ON delay = short/long
ON duration, area C
T4 Timing relay with 2-second ON delay = short/long
ON duration, area D
T8 Flashing 20-second cycle for short/long ON duration
Benefits
t
Implemented functions:
t 12 x ON-delayed timing relays
t 1 x impulse changeover relay
t
Less wiring required
t
Takes up less space than conventional systems
Examples
Library lighting
Customer:Program:
1/4/13
Date:Page:
Comment:
T8
R
M9
Central light ON/OFF switch
TTT1
M1
Switch S1/S2 short pressure
M2
Switch S1/S2 long pressure
C1C
Counter 1 Duration: 5 minutes
C2C
Counter 2 Duration: 30 minutes
5 min.
Q1
Light at output 1 ON 30 min.
C1R
via central ON switch
C2
Reset counter 1 and 2
I5
I1
M1
I1
M
M
M2
C
C2
M9
I
Q1
T1
Q1
2
T8
1
T8
M1
1
M2
1
Figure 49. easyRelay Display Diagram
Library lighting
Customer:Program:
1/4/13
Date:Page:
Comment:
T
R
T2
M3
Switch S3/S4 short pressure
M4
Switch S3/S4 long pressure
C3C
Counter 3 Duration: 5 minutes
C4C
Counter 4 Duration: 30 minutes
5 min.
Q2
Light at output 2 ON 30 min.
C3R
via central ON switch
C4
Reset counter 3 and 4
T3T
I2
M3
I2
M4
M3
M
C
C4
M
I2
I3
Q2
T2
Q2
T8
T8
4
M3
3
M4
9
Example 9
1
Example 9
2
24
EATON CORPORATION
5
M
Q3
M5
Switch S5/S6 short pressure
Figure 50. easyRelay Display Diagram
easyRelay applications
Product Application AP05013001E
Effective February 2013
Library lighting
Customer:Program:
1/4/13
Date:Page:
Comment:
I3 T3
Q3
M6
M5
M6
C
5
C
6
M
9
I3
I
4
M7
I4
8
M
7
M
T8
T8
M5
M6
Q4
T4
Q4
T8
M6
Switch S5/S6 long pressure
C5C
Counter 5 Duration: 5 minutes
C6C
Counter 6 Duration: 30 minutes
5 min.
Q3
Light at output 3 ON 30 min.
C5R
via central ON switch
C6R
Reset counter 5 and 6
T4T
M7
Switch S7/S8 short pressure
M8
Switch S7/S8 long pressure
CC7
Counter 7 Duration: 5 minutes
Figure 51. easyRelay Display Diagram
Example 9
3
Customer:Program:
Date:Page:
Timing relays
Timing relays
Library lighting
1/4/13
XX X
02S
X
00
TRGT
RES
02S
00
TRGT
RES
1
+
4
+
02 0002 00
SS
:::
TRGT
RES
30 00
S
:::
TRGT
RES
Example 9
5
:::
2
+
:::
8
+
TRGT
RES
TRGT
RES
Figure 53. easyRelay Display Parameters
Customer:Program:
Date:Page:
Up and down counters
Library lighting
1/4/13
00 05
DIR
CNT
RES
00 3000 05
DIR
C
1
+
CNT
RES
Example 9
6
C
2
+
DIR
CNT
RES
3
+
C
3
+
Library lighting
Customer:Program:
1/4/13
Date:Page:
Comment:
C
M8 T8
M7
C
7
M8
C
8
I4
C8
Counter 8 Duration: 30 minutes
Q4
5 min.
C7R
Light at output 4 ON 30 min.
C8R
Reset counter 7 and 8
Example 9
4
Up and down counters
00 3000 0500 30
DIR
C
CNT
RES
Up and down counters
00 0500 30
DIR
CNT
RES
4
+
C
7
+
DIR
CNT
RES
DIR
CNT
RES
Figure 54. easyRelay Display Parameters
DIR
C
5
+
C
8
+
CNT
RES
DIR
CNT
RES
C
6
+
C
Figure 52. easyRelay Display Diagram
EATON CORPORATION
25
Product Application AP05013001E
Effective February 2013
easyRelay applications
Refrigeration control system
Task
To turn the compressors of the refrigeration system in a hotel on
and off in response to the system pressure. The system pressure
is supplied by the easyRelay via analog input I8. The value at I8 is
compared with set point values and the switching points are derived
from the comparison value.
Overview drawing
Control circuit
L1
N
PE
F1
G1
~
F2
+24V
-
0V
S0
B1 Pressure sensor
F1 16 A, char. B miniature circuit breaker
F2 Miniature circuit breaker (optional)
G1 Power supply unit 230 Vac/24 Vdc
K1–K4 Compressor 1–4
S0 Emergency stop
S1 ON/OFF key switch
S1
I1 I2 I3 I4 I5 I6 I7 I8
24V
0V 0V
EASY512-DC-R
12 12 12 12
Q1Q2Q3Q4
K1
ALT
DEL
OK
ESC
K2
K4
K3
P
0-10V
B1
Figure 55. Overview
Operating description
The pressure of the refrigeration system is compared with set
point values. Timers are connected upstream of the outputs so that
pressure fluctuations in the system do not cause the compressors
to turn on immediately.
Set point values
Output Q1:
Set: A1 ≥ 1.8 bar
Time T1 = 5 sec
Reset: A5 ≤ 1.7 bar
Output Q2:
Set: A2 ≥ 2.0 bar
Time T2 = 20 sec
Reset: A6 ≤ 1.9 bar
Output Q3:
Set: A3 ≥ 2.2 bar
Time T3 = 20 sec
Reset: A7 ≤ 2.1 bar
Output Q4:
Set: A4 ≥ 2.4 bar
Time T4 = 20 sec
Reset: A8 ≤ 2.3 bar
Figure 56. Control Wiring Diagram
Load circuit
L1
L2
L3
N
PE
Q1
K1
4.43
Q2
4.44
K2
M
3 ~
M1
4.43
Q3
4.44
K3
M
3 ~
M2
4.43
Q4
4.44
K4
M
3 ~
M3
Figure 57. Load Circuit Diagram
List of operands
A1 Comparator, motor 1 ON after T1 has elapsed
A2 Comparator, motor 2 ON after T2 has elapsed
A3 Comparator, motor 3 ON after T3 has elapsed
A4 Comparator, motor 4 ON after T4 has elapsed
A5 Comparator, motor 1 OFF
A6 Comparator, motor 2 OFF
A7 Comparator, motor 3 OFF
A8 Comparator, motor 4 OFFI1 Input, system ON/OFF
I8 Input, comparison voltage from pressure sensor
4.43
4.44
M
3 ~
M4
26
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Q1 Output, motor 1
Q2 Output, motor 2
Q3 Output, motor 3
Q4 Output, motor 4
T1 Timing relay, ON delay, motor 1
T2 Timing relay, ON delay, motor 2
T3 Timing relay, ON delay, motor 3
T4 Timing relay, ON delay, motor 4
Benefits
t
Implemented functions:
t 4 x ON-delayed timing relays
t
Processing of pressure values (analog values)
t
Password function protects against unauthorized access
Examples
Customer:Program:
Date:Page:
Refrigeration system
1/4/13
I
1
T
1
T
2
T3
T
4
A
5
A6
A7
8
A
A1
A2
A3
A4
T1
T
T2T
T3T
T4T
Q1S
Q2S
Q3S
Q4S
QRR1
QR2
QR3
Q4
Example 10
1
Comment:
System switched on and pressure > 1.8 bar
Pressure > 2.0 bar
Pressure > 2.2 bar
Pressure > 2.4 bar
Compressor 1 (M1) ON after 5 sec.
Compressor 2 (M2) ON after 20 sec.
Compressor 3 (M3) ON after 20 sec.
Compressor 4 (M4) ON after 20 sec.
Pressure < 1.7 bar, compressor 1 OFF
Pressure < 1.9 bar, compressor 2 OFF
Pressure < 2.1 bar, compressor 3 OFF
Pressure < 2.3 bar, compressor 4 OFF
Customer:Program:
Date:Page:
Timing relays
Timing relays
Refrigeration system
1/4/13
XX X
05S
X
00
TRGT
RES
20S
00
TRGT
RES
1
+
4
+
20 0020 00
SS
:::
TRGT
RES
:::
TRGT
RES
Example 10
2
:::
2
+
:::
TRGT
RES
TRGT
RES
Figure 59. easyRelay Display Parameters
Customer:Program:
Date:Page:
Analog comparators
Analog comparators
Analog comparators
Refrigeration system
1/4/133
ANALOGANALOGANALOG
I8
18
.
ANALOGANALOGANALOG
I8
24
.
ANALOGANALOGANALOG
I8
21
.
I8
AA
12
20
.
I8
AA
45
17
.
I8
AA
78
23
.
Example 10
I8
22
.
I8
19
.
3
+
A
3
A
6
A
Figure 58. easyRelay Display Diagram
Figure 60. easyRelay Display Parameters
EATON CORPORATION
27
Product Application AP05013001E
Effective February 2013
easyRelay applications
Perimeter advertising in a stadium
Task
The time-dependent control of four advertising panels, each with
three sides. Each side is to be visible for 30 seconds, after which
thenext side is to be turned to the front.
Overview drawing
Figure 61. Overview
Operating description
Start
Start/Stop button S5 is used to start the procedure for all four panel
fixture electrical strips. The visible advertising panel is on view for a
variable time (controlled via T1 through T4). It should be possible to
stop the entire procedure by pressing the S5 button again.
Rotation
Once the set time has elapsed, the motor (M1 through M4)
associated with the strip must start automatically. The strip rotates
to display the next advertising panel. Once the advertising panel
is in the correct position, this is signaled via the corresponding
limit switch (S1 through S4) and the motor is turned off. To enable
the strip to leave the limit switch position, disconnection must be
bypassed, again fora variable time (controlled via T5 through T8),
when the rotation procedure starts.
Testing and maintenance
It must be possible to activate the rotation procedure manually in
order to be able to test the individual strips during installation and
assembly and to replace the advertising panels. The cursor buttons
P1 through P4 on the easyRelay are used to activate a single turn for
each individual strip, and button S6 activates a single turn ofall the
strips together.
ote:NThe P buttons are activated in the Special menu. Press ALT and DEL
simultaneously to change to the Special menu.
Circuit diagram
F1
L1
N
F1 16 A, char.B miniature circuit breaker
M1 Motor for strip 1
M2 Motor for strip 2
M3 Motor for strip 3
M4 Motor for strip 4
S1 Limit switch for strip 1
S2 Limit switch for strip 2
S3 Limit switch for strip 3
S4 Limit switch for strip 4
S5 Start/Stop button
S6 Turn button
S7–S10 Emergency stop
S10
S1
S2
S3
S4
S7
S8
S9
M1
L
EASY512-AC-R
12 12 12 12
Q1Q2Q3Q4
M
1~
M2
S5
I1 I2 I3 I4 I5 I6 I7 I8
NN
DEL
ESC
M
1~
M3
S6
ALT
OK
M4
M
1~
M
1~
Figure 62. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
List of operands
I1 Input, limit switch for strip 1
I2 Input, limit switch for strip 2
I3 Input, limit switch for strip 3
I4 Input, limit switch for strip 4
I5 Input, Start/Stop button
I6 Input, Turn button
M1 Marker relay, buffer memory, Start/Stop
P1 Cursor button 1 x Turn strip 1
P2 Cursor button 1 x Turn strip 2
P3 Cursor button 1 x Turn strip 3
P4 Cursor button 1 x Turn strip 4
Q1 Output, motor for strip 1
Q2 Output, motor for strip 2
28
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Q3 Output, motor for strip 3
Q4 Output, motor for strip 4
T1 Timing relay with 30-second ON delay => Advert viewing time,
strip 1
T2 Timing relay with 30-second ON delay => Advert viewing time,
strip 2
T3 Timing relay with 30-second ON delay => Advert viewing time,
strip 3
T4 Timing relay with 30-second ON delay => Advert viewing time,
strip 4
T5 Single 1-second pulse timing relay => Block limit switch for
starting strip 1
T6 Single 1-second pulse timing relay => Block limit switch for
starting strip 2
T7 Single 1-second pulse timing relay => Block limit switch for
starting strip 3
T8 Single 1-second pulse timing relay => Block limit switch for
starting strip 4
Benefits
t
Implemented functions:
t 8 x ON-delayed timing relays
t 1 x impulse changeover relay
t
Less wiring required
t
Takes up less space than conventional systems
t
Dwell-time of each strip can be individually selected
Stadium perimeter advertising
Customer:Program:
1/4/13
Date:Page:
Comment:
T
3
P3TT7
I6
I
3
T7
T4
PI4
6
I4
T8
Q3
S
QR3
Q4S
T8T
QR4
Start turning strip 3
Bypass disconnection of strip 3
Stop turning strip 3
Stop turning strip 4
Bypass disconnection of strip 4
Stop turning strip 4
Example 11
2
Examples
Stadium perimeter advertising
Customer:Program:
1/4/13
Date:Page:
I
5
M1Q1TT1
Q2
Q3
Q4
1
T
P
1
I6
I
1
T5
T2
P2
6
I
I
2
T6
M1
TT2
TT3
T4T
Q1S
T5T
QR1
Q2S
T6T
Q2
R
Example 11
1
Comment:
Start/Stop turning
Time for strip 1
Time for strip 2
Time for strip 3
Time for strip 4
Start turning strip 1
Bypass disconnection of strip 1
Stop turning strip 1
Stop turning strip 2
Bypass disconnection of strip 2
Stop turning strip 2
Figure 64. easyRelay Display Diagram
Customer:Program:
Date:Page:
Timing relays
Timing relays
Timing relays
Stadium perimeter advertising
1/4/13
XX X
30S
X
00
TRGT
RES
30S
00
TRGT
RES
01S
00
TRGT
RES
1
+
4
+
7
+
30 0030 00
SS
:::
TRGT
RES
01 0001 00
SS
:::
TRGT
RES
S
01 00
:::
TRGT
RES
Example 11
3
:::
2
+
:::
5
+
:::
8
+
TRGT
RES
TRGT
RES
TRGT
RES
3
+
6
+
Figure 63. easyRelay Display Diagram
Figure 65. easyRelay Display Parameters
EATON CORPORATION
29
Product Application AP05013001E
Effective February 2013
easyRelay applications
Rolling door control
Task
To automatically control the roll-up security door at the entrance
to an underground garage. The door should open on request and
then close automatically after a set time. It should also be possible
to close the door upon request. The door is locked at certain times
of the day and certain days of the week. The limit switches and
mechanical operation of the door should be constantly monitored.
Overview drawing
Figure 66. Overview
Operating description
Opening the rolling door
The rolling door can be opened from outside via a swipe card reader
and/or key switch S6. Contact K1 closes briefly once the swipe
card has been checked. It should be possible to lock the entrance
atcertain, variable times of the day and on certain days of the week
1); although it should always be possible to open the door using
(
key switch S5.
The door must be opened using pull switch S7 in order to leave
the garage.
Security
Door closing should be indicated by a brief audible signal (H3).
At the same time, red warning lights H1 and H2 light up at the
entrance and the exit. If there is a person, a vehicle, or another
object under the door while it is closing, the procedure will be
stopped or prevented via the contact in the safety bar (K2) and/or
the light barrier (K3). The door will either immediately open fully or
will remain open. If the safety bar is triggered, there is an audible
signal, and warning lights H1 and H2 light up.
The “Open door” function is disabled by the safety bar when the
door is closed (limit switches actuated) in order to prevent break-in
and vandalism.
The contact bar can be tested by triggering the alarm while the door
is open.
Pressing the emergency stop button stops all movement of the door.
Warning lights H1 and H2 will start to flash, and the audible signal
will start.
If the door is closed, the alarm cannot be triggered via the
emergency stop button. The “Open door” command must be given
to start the flashing lights and the audible signal in order to indicate
that the emergency stop button has been pressed.
Break contacts should be used for the emergency stop, safety bar,
and limit switch functions. The emergency stop button and the
safety bar must be wired as shown in Figure 67. This will guarantee
that the opening and closing procedure during an emergency stop,
and the door closing procedure when the safety bar is tripped, work
independently of the electronic circuit.
The following standards must be observed:
DIN EN 60 335-1 (VDE 0700 part 1)
DIN 57 700-238 (VDE 0700 part 238)
German Workplace Directive ASR 11/1-5ZH1/494
and ZH1/580.1 Safety Rules
Faults
Defective limit switches S1 and S2 (door closed S1/door openedS2)
and mechanical faults in the door must be detected. If a limit switch
is not working correctly, the drive should be shut down after a
variable time (T1 and T2) and warning lights H1 and H2 should start
to flash. The message can be cleared by pressing and resetting
emergency stop button S8. If emergency stop button S8 is pressed,
the warning lights should light up and a continuous audible signal
should start.
Closing the rolling door
Once a car has driven into the garage, the driver can close the door
manually via pull switch S7. If the driver does not use the pull switch,
the door will automatically close after a set time (T3). The door can
be opened and closed manually using the S4 and S5 buttons in the
control room.
30
EATON CORPORATION
easyRelay applications
Product Application AP05013001E
Effective February 2013
Control circuit
F1
L1
N
S1
S2
S3
K1
S6
I1 I2 I3 I4 I5 I6 I7 I8
L
NN
DEL
EASY512-AC-RC
12 12 12 12
Q1Q2Q3Q4
K5
K4
F1 16 A, char. B miniature circuit breaker
H1 Internal warning light
H2 External warning light
H3 Audible signal
K1 Contact for swipe card reader
K2 Contact for safety bar
K3 Contact for light barrier
K4 Close door contactor
K5 Open door contactor
S1 Door closed limit switch
S2 Door opened limit switch
S3 Close door button
S4 Open door button
S5 Open door key switch
S6 Open door key switch
S7 Pull switch
S8 Emergency stop button
S9 Emergency stop button
ESC
K4
K5
S5
S4
K3
ALT
OK
H2
H1
S8
S7
S9
K2
H3
Figure 67. Control Wiring Diagram
CAUTION
THE SAFETY REQUIREMENTS OF THE APPLICABLE VDE, IEC, UL, AND CSA
STANDARDS REQUIRE THE PHASE THAT IS USED FOR THE POWER SUPPLY
TO BE USED FOR THE INPUTS AS WELL. IF THIS IS NOT THE CASE, THE
easyRELAYS WILL NOT DETECT THE CONNECTION LEVEL AND CAN BE
DAMAGED BYOVERVOLTAGES.
Load circuit
L1
L2
L3
N
PE
Q1
K4
M
3 ~
M1
K5
Figure 68. Load Circuit Diagram
ote:NThe electrical interlock may be omitted if a reversing contactor with
amechanical interlock is used.
List of operands
I1 Input, door closed limit switch
I2 Input, door opened limit switch
I3 Input, close door button
I4 Input, open door key switch/contact swipe card reader
I5 Input, open door button/open door key switch
I6 Input, pull switch
I7 Input, safety bar/light barrier triggered signal
I8 Input, emergency stop triggered signal
M1 Marker relay, buffer memory, close door
M2 Marker relay, buffer memory, open door
M3 Marker relay, buffer memory, close
M4 Marker relay, buffer memory, open
M5 Marker relay, buffer memory, pull switch
M6 Marker relay, buffer memory, time monitoring of limit switch
Q1 Output relay, close door
Q2 Output relay, open door
Q3 Output relay, warning lights
Q4 Output relay, audible signal
T1 ON-delayed timing relay, monitoring of door closed limit switch
T2 ON-delayed timing relay, monitoring of door opened limit switch
T3 Single-pulse timing relay, warning time before door closes
T4 ON-delayed timing relay, time until door closes automatically