KitchenAid KEYS750LT2, KEYS850LQ2, KEYS850LT2, KEYS850LE2, KEYS750LQ2 Installation Guide

2Y'(73.7CM)ELECTRICDRYER
INSTAIIATION INSTRUCTIONS
INSTRUCTIONSPOURL'INSTAILATIONDELASECHEUSE
/
ELECTRIQUEDE2Y'(73,7CM)
Table of Contents /Table des mati_res
DRYER SAFETY ............................................... 1 Sg:CURITE DE I.A Sg:CREUSE ............................. 16
INSTALLATION INSTRUCTIONS.. .................. 2
Venting Requirements ................................. 11
Plan Vent System ........................................ 12
Install Vent System ..................................... 13
Install Leveling Legs .................................... 13
Connect Vent.. ............................................ 14
Level Dryer .................................................. 14
Reverse Door Swing (Optional) ................... 14
Complete Installation ....................... 15
DRYERSAFETY
INSTRUCTIONS D'INSTALLATION ...................... 16
Outillage et pieces ................................ 16
Exigences d'emplacement ................................. 17
Specifications _lectriques ................................... 18
Exigences concernant I'_vacuation ............... 19
Planification du systeme d'_vacuation ............... 20
Installation du systeme d'_vacuation ................. 21
Installation des pieds de nivellement. ................. 22
Raccordement du conduit d'_vacuation ......... 22
Mise h niveau de la s_cheuse ..................... 22
Inversion de I'ouverture de la porte (facultatif) ... 22
Achever I'installation ........................................... 23
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
8577189
INSTALLATIONINSTRUCTIONS
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed
here.
Flat-blade screwdriver #2 Phillips screwdriver Adjustable wrench that
opens to 1" (2.54 cm) or hex-head socket wrench
(for adjusting dryer feet) Vent clamps
Parts supplied:
Remove parts package from dryer drum. Check that all parts were included.
4 leveling legs
Parts needed:
Check local codes, check existing electrical supply and venting and see "Electrical Requirements" and "Venting Requirements"
before purchasing parts. Mobile home installations require metal exhaust system hardware
available for purchase from the dealer from whom you purchased
your dryer. For further information, please reference the front page
of the Dryer User Instructions.
Tin snips(new vent installations)
Caulking gun and compound (for installing new exhaust vent)
Wire stripper (for U.S. only, direct wire installations)
Level
Explosion Hazard
Keep flammable materials and vapors, such as
gasoline, away from dryer. Place dryer at least 18 inches (46 cm) above the
floor for a garage installation. Failure to do so can result in death, explosion,
or fire.
You will need
A location that allows for proper exhaust installation. See "Venting Requirements."
Aseparate30-amp circuit.
If using a power supply cord, a grounded electrical outlet located within 2 ft (61 cm) of either side of the dryer. See "Electrical Requirements - U.S.A." or "Electrical Requirements - Canada."
A sturdy floor to support the total weight (dryer and load) of 200 Ibs (90.7 kg). The combined weight of a companion appliance should also be considered.
A level floor with a maximum slope of 1" (2.5 cm) under entire dryer. (If slope is greater than 1" [2.5 cm], install Extended Dryer Feet Kit, Part Number 279810.) Clothes may not tumble properly and models with automatic sensor cycles may not
operate correctly if dryer is not level.
Do not operate your dryer at temperatures below 45°F (7°C). At lower temperatures, the dryer might not shut off at the end of an automatic cycle. Drying times can be extended.
The dryer must not be installed or stored in an area where it will be exposed to water and/or weather.
Check code requirements. Some codes limit, or do not permit, installation of the dryer in garages, closets, mobile homes or
sleeping quarters. Contact your local building inspector.
Installation Clearances
The location must be large enough to allow the dryer door to
open fully.
Dryer Dimensions
_/8,,_- ........... _ I
Additional clearances might be required for wall, door and floor moldings.
For closet installation, with a door, minimum ventilation openings in the top and bottom of the door are required. Louvered doors with equivalent ventilation openings are
acceptable.
Companion appliance spacing should also be considered.
(66cm)_ (70.5cm) _
A
22 _/4" 0_! I
J_ _ 13_/4"
(70.5cm) (70.5cm)
(73.e6cm) \_---_3.6_cm)
C D
A. Small opening side-swing door
B.Large opening side-swing door C.Wide opening side-swing door
D.Wide opening hamper door
*Most installations require a minimum 51/2'' (14 cm) clearance
behind the dryer for the exhaust vent with elbow. See "Venting Requirements."
Minimum installation spacing for recessed area or closet installation
The dimensions shown following are for the minimum spacing
allowed.
Additional spacing should be considered for ease of installation and servicing.
_.6 cm)
1 3,,
(7.6cm)
(45.7
__H LI_I 1_ max.
48in?
(310crn2)
24in.2
(155cm2]
o"*-_t_ 2g"_ _o"* _o"*F 2_4"Hs,/2"<--
(0cm) (73,66crn) (0cm) (0crn) (70,5crn) (14cm)
A B
A. Recessed area B. Side view - closet or confined area C. Closet door with vents
*Additional spacing recommended
Mobile Home - Additional Installation Requirements This dryer is suitable for mobile home installations.
The installation must conform to the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD Part 280) or the Canadian Manufactured Home Standard, CAN/CSA-Z240 MH.
Mobile home installations require:
Metal exhaust system hardware, which is available for purchase from your dealer.
Special provisions must be made in mobile homes to introduce outside air into the dryer. The opening (such as a
nearby window) should be at least twice as large as the dryer exhaust opening.
It is your responsibility
[] Tocontact a qualified electrical installer.
[] To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSl/NFPA 70-latest edition and all local codes and ordinances.
The National Electric Code requires a 4-wire supply connection for homes built after 1996, dryer circuits involved in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from: National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269.
To supply the required 3 or 4 wire, single phase, 120/240 volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt electrical supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect
to an individual branch circuit. Do not have a fuse in the neutral or grounding circuit.
[] Do not use an extension cord. [] If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions provided for it here.
[] If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see "Optional 3-wire connection" section.
This dryer is manufactured ready to install with a 3-wire electrical supply connection. The neutral ground wire is permanently connected to the neutral conductor (white wire) within the dryer. Ifthe dryer is installed with a 4-wire electrical supply connection, the neutral ground wire must be removed from the external ground conductor screw (green screw), and secured under the neutral terminal (center or white wire) of the terminal block. When the neutral ground wire is secured under the neutral terminal (center or white wire) of the terminal block, the dryer cabinet is isolated from the neutral
conductor. A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through the neutral conductor is prohibited. Grounding through the neutral is prohibited for (1) new branch-circuit installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local codes prohibit grounding through the neutral
conductors.
If using a power supply cord: Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain: [] A UL listed 30-amp power supply cord, rated
120/240 volt minimum. The cord should be type SRD or SRDT and be at least 4 ft (1.22 m) long. The wires that
connect to the dryer must end in ring terminals or spade terminals with upturned ends.
[] A UL listed strain relief.
If your outlet looks like this:
4-wire receptacle (14-30t:?)
Then choose a 4-wire power supply cord with ring or spade terminals and UL listed strain relief. The 4-wire power supply
cord, at least 4 ft (1.22 m) long, must have four 10-gauge copper wires and match a 4-wire receptacle of NEMA Type 14-30R. The
ground wire (ground conductor) may be either green or bare. The neutral conductor must be identified by a white cover.
If your outlet looks like this:
3-wire receptacle (10-30t:?)
Then choose a 3-wire power supply cord with ring or spade terminals and UL listed strain relief. The 3-wire power supply cord, at least 4 ft (1.22 m) long, must have three 10-gauge copper wires and match a 3-wire receptacle of NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire) and be:
[] Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), protected with flexible metallic conduit. All current-carrying wires must be insulated.
[] 10-gauge solid copper wire (do not use aluminum). [] At least 5 ft (1.52 m) long.
GROUNDING INSTRUCTIONS
[] For a grounded, cord-connected dryer: This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
[] For a permanently connected dryer: This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead on the dryer.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is properly grounded. Do not modify the plug on the power supply cord: if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.
SAVE THESE INSTRUCTIONS
Electrical Shock Hazard
Plug into a grounded 4 prong outlet. Failure to do so can result in death or electrical shock.
It is your responsibility
To contact a qualified electrical installer.
To be sure that the electrical connection is adequate and in conformance with the Canadian Electrical Code, C22.1-1atest edition and all local codes. A copy of the above codes standard may be obtained from: Canadian Standards
Association, 178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.
To supply the required 4 wire, single phase, 115/230 volt, 60 Hz., AC only electrical supply on a separate 30-amp circuit,
fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch
circuit. This dryer is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-30R wall receptacle. The cord is 5 ft (1.52 m) in length. Be sure wall receptacle is within reach of dryer's final location.
If you are using a replacement power supply cord, it is recommended that you use Power Supply Cord Replacement Part Number 3394208. For further information, please reference
the service numbers located in the Dryer User Instructions.
GROUNDING iNSTRUCTiONS
For a grounded, cord-connected dryer: This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for electric current. This dryer is equipped with a cord having an equipment- grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with the dryer: if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
SAVE THESE INSTRUCTIONS
4-wire receptacle 14-30R
Do not use an extension cord.
PowerSupply Cord Direct Wire
Fire Hazard
Use a new UL listed 30 amp power supply cord. Use a UL listed strain relief.
Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections. Failure to de so can result in death, fire, or
electrical shock.
1. Disconnect power.
2. Remove the hold-down screw and terminal block cover.
A B C D
Fire Hazard
Use t0 gauge solid copper wire. Use a UL listed strain relief.
Disconnect power before making electrical connections. Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections. Failure to do so can result in death, fire, or
electrical shock.
3. Install strain relief.
Style 1: Power supply cord strain relief
Remove the screws from a 3/4"(1.9 cm) UL listed strain relief (UL marking on strain relief), Put the tabs of the two clamp sections into the hole below the terminal block opening so that one tab is pointing up and the other is pointing down, and hold in place. Tighten strain relief screws just enough to hold the two clamp sections together.
A.Terminalblock cover B.Externalground conductor screw
C.Center,silver-colored terminal block screw D.Hold-down screw location
E.Neutral ground wire F.Hole below terminal block opening
A. Strain relief tab pointing up
B. Hole below terminal block opening C. Clamp section D. Strain relief tab pointing down
Put power supply cord through the strain relief. Be sure that the wire insulation on the power supply cord is inside the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Do not further tighten strain relief screws at this point.
Style 2: Direct wire strain relief
Unscrew the removable conduit connector and any screws from a 3/4"(1.9 cm) UL listed strain relief (UL marking on strain relief). Put the threaded section of the strain relief through the hole below the terminal block opening. Reaching inside the terminal block opening,
screw the removable conduit connector onto the strain relief threads.
Electrical Connection Options
If your home has: And you will be Go to Section
connecting to:
4-wire receptacle A UL listed, 4-wire connection: (NEMA Type 14-30R) 120/240-volt Power supply cord
30-amp, dryer
_.._ minimum,
4-wire direct A fused 4-wire connection:
(12.7 ore)
3-wire receptacle A UL listed, (NEMA type 10-30R) 120/240-volt
3-wire direct A fused 3-wire connection:
power supply cord*
disconnect or Direct Wire circuit breaker
box*
3-wire connection:
Power supply cord
30-amp, dryer power supply
minimum,
cord*
disconnect or Direct Wire box*
circuit breaker
.......................................................g
t
A. Removable conduit connector B. Hole below terminal block opening
C. Strain relief threads
Put direct wire cable through the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against
the direct wire cable.
*If local codes do not permit the connection of a frame-grounding
conductor to the neutral wire, go to "Optional 3-wire connection" section.
4-wire connection: Power Supply Cord
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit the use of 3-wire connections.
B F
C D E G
A. 4-wire receptacle (NEMA type 14-30R) B. 4-prong plug C. Ground prong D. Neutral prong
E.Spade terminals with upturned ends F. 3_,,(1.9 cm) UL listed strain relief
G. Ring terminals
4=
Now complete installation following instructions for your type of electrical connection:
4-wire (recommended) 3-wire (if 4-wire is not available)
1=
Remove center silver-colored terminal block screw.
2.
Remove neutral ground wire from external ground conductor screw. Connect neutral ground wire and the neutral wire (white
or center wire) of power supply cord under center, silver- colored terminal block screw. Tighten screw.
A B C
s
J
D
A. External ground conductor screw - Dotted line shows
position of NEUTRAL ground wire before being moved to center silver-colored terminal block screw
B. Center silver-colored terminal block screw C. Neutral wire (white or center wire)
D. 3_,, (1.9 cm) UL listed strain relief
E.Neutral ground wire
3=
Connect ground wire (green or bare) of power supply cord to external ground conductor screw. Tighten screw.
A B C
4-wire connection: Direct Wire
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit the use of 3-wire connections.
Direct wire cable must have 5 ft (1.52 m) of extra length so dryer can be moved if needed.
Strip 5" (12.7 cm) of outer covering from end of cable, leaving bare ground wire at 5" (12.7 cm). Cut 11/2'' (3.8 cm) from 3 remaining wires. Strip insulation back 1" (2.5 cm). Shape ends of wires into a hook shape.
When connecting to the terminal block, place the hooked end of the wire under the screw of the terminal block (hook facing right), squeeze hooked end together and tighten screw, as shown.
1=
Remove center silver-colored terminal block screw.
2.
Remove neutral ground wire from external ground conductor screw. Connect neutral ground wire and place the hooked end
(hook facing right) of the neutral wire (white or center wire) of direct wire cable under the center screw of the terminal block.
Squeeze hooked ends together. Tighten screw.
E
A. External ground conductor screw B. Center silver-colored terminal block screw
C. Neutral wire (white or center wire) D. 3_, (1.9 cm) UL listed strain relief E. Neutral ground wire
F. Ground wire (green or bare) of power supply cord
4. Connect the other wires to outer terminal block screws. Tighten screws.
5. Tighten strain relief screws.
6. Insert tab of terminal block cover into slot of dryer rear panel. Secure cover with hold-down screw.
7. You have completed your electrical connections. Now go to "Venting Requirements."
A B C
,/
D// _
A. External ground conductor screw - Dotted line shows
position of NEUTRAL ground wire before being moved to
center silver-colored terminal block screw B. Center silver-colored terminal block screw C. Neutral wire (white or center wire)
D. 3_,, (1.9 cm) UL listed strain relief
E.Neutral ground wire