![](/html/0f/0f45/0f455fc27dc8e8f708bfa3d77913928a1a7f358388bd3ee6154630dd39fe3ab1/bg2.png)
Cabinet opening dimensions
25” (63.5 cm) countertop
upper cabinet depth
18” (45.7 cm)
4” (10 2 cm) min
clearance to side will A
or other combustible
material
of range. wall receptacle -
Important: Observe
all governing codes
and ordinances.
Grounded electrical
outlet
“Electrical requirements,”
is required. See
Panel B.
Cabinet opening
dimensions
shown must be used.
that are
I
I
I
1 718” (2:2%)
e
H min. required
\ between
cutout and
cabinet door
or hinge.
Y
\
-H 3
1
\
w
8” (20.3 cm) to
22” (55.9 cm) from
either cabinet,
7” (17.8 cm) max.
from floor.
36” (91.4 cm)
countertop
height
I
Countertop preparation
The cooktop sides of the slide-in range fit over
the cutout edge of your countertop.
If you have a square finish (flat) countertop
and the opening width is 30-3/8” (77.2 cm),
countertop preparation is required.
Formed front-edged countertops:
molded edge shaved flat l/4” (0.64 cm) from
each front corner of opening.
Tile countertops
l/4” (0.64 cm) from each front corner and/or
rounded edge flattened.
may need trim cut back
Formed or tiled countertop
trimmed l/4” (0.64 cm)
back at front corners of
countertop opening.
Must have
no
If countertop opening width is greater than
30-318” (77.2
dimension.
Countertop must be level.
countertop, first side to side; then front to back. If
countertop is not level, range will not be level.
Oven must be level for satisfactory baking
conditions.
Product dimensions
30” 176.2 cm)
range width ’
Yl7
-4
Panel A
When installed in a 24” (61 cm)
base cabinet with 25” (63.5 cm)
countertop - front of oven door
protrudes l-7/8” (4.8 cm) beyond
24” (61 cm) base cabinet.
For minimum
clearance to the top
of the cooktop,
*** Note: 24” (61 cm) min. when bottom of
wood or metal cabinet is protected by
not less than l/4” (0.64 cm) flame
retardant millboard covered with not
less than No. 28 MSG sheet steel, 0.015”
(0.4 mm) stainless steel, 0.024” (0.6 mm)
aluminum or 0.020” (0.5 mm) copper.
30” (76.2 cm) min. clearance between
the top of the cooking platform and
the bottom of an unprotected wood or
metal cabinet.
cm),
adjust the l/4” (0.64 cm)
countertoo
see
Do Not pinch the
ower supply cord
E
etween the range
and the wall.
Do Not seal range
to side cabinets.
Place level on
I I
Anti-tip
bracket:
MUST be installed.To install
the anti-tip bracket shipped
with the range, see Panels D
and E and the anti-tip
bracket template.
Before you start...
Read electrical and carpentry instructions.
Proper installation
qualified technician must install this range. Make
sure you have everything necessary for correct
installation. It is the customer’s responsibility to
make sure that the countertop has been properly
prepared and that the installation clearances
specified on the serial/rating plate are met. The
serial/rating plate is located on the frame behind
the drawer.
Check location
The range should be located for convenient use
in the kitchen. Recessed installations must
provide complete enclosure of the sides and rear
of range.
ALL OPENINGS IN THE WALL OR FLOOR
WHERE RANGE IS TO BE INSTALLED MUST
BE SEALED.
Cutout shown
countertop with a 24-inch (61 cm) base cabinet
and no backsplash. If countertop has a
backsplash, see “Countertop preparation.”
Cabinet construction:
designed for use in a base cabinet with a depth
of 24 inches (61 cm). The maximum depth for
overhead cabinets is 13” inches
(33 cm). For the minimum vertical clearance
between the cooking surface and the overhead
cabinets, see Note.*** Overhead cabinets
installed at either side of the appliance must be
a minimum of 18 inches (45.7 cm) above the
cooking surface. The minimum horizontal
distance between the overhead cabinets is 30
inches
(76.2 cm).
Personal Injury Hazard
To eliminate the risk of burns or fire, avoid
installing cabinet storage above the cooking
surface. If cabinets are already installed,
reduce the hazard of reaching over a heated
cooking surface by installing a range hood.
The range hood should extend a minimum of
5 inches out from the bottom front of the
cabinets.
Reaching over a heated cooking surface
could result in a serious burn or other
personal injury.
Electrical Shock Hazard
lt is the customer’s responsibility:
.To contact a qualified electrical installer.
*To assure that the electrical installation is
adequate and in conformance with National
Electrical Code, ANWNFPA
70 - latest edition’, or CSA Standard C22.1,
Canadian Electrical Code, Part 1 -latest
edition”, and all local codes and ordinances.
Failure to do so could result in fire, electrical
shock or other personal injury.
Mobile home installation
The installation of this range must conform to the
Manufactured Home Construction and Safety
Standards, Tile 24 CFR, Part 3280 (formerly the
Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD, Part 280); or when such
standard is not applicable, the Standard for
Manufactured Homes Installations (Manufactured
Home Sites, Communities and Setups), ANSI
A2251/NFPA 501A, or with local codes’. In
Canada, the installation of this range must conform
with the current standards CANKSA - 2240 latest edition** or with local codes.
In Canada, the installation of this range must
conform with the current standards CAN/CSA-Z240
- latest edition***,
When this range is installed in a mobile home, it
must be secured to the floor during transit. Any
method of securing the range is adequate as long
as it conforms to the standards listed above.
Four-wire power supply cable must be used in a
mobile home installation. The appliance wiring will
need to be revised. See four-wire electrical
connection, Panels C and D.
Note:
The metal chassis of the range MUST be
earth- grounded in order for the control panel to
work. If the metal chassis of the range is not earthgrounded, NO keypads will operate. Check with a
qualified electrician if you are in doubt as to whether
the metal chassis of range is earth-grounded.
Copies of the standards listed may be obtained from:
* National Fire Protection Association
Batterymarch park
Guincy, Massachusetts 02269
** Canadian Standard Association
178 Rexdale Boulevard
Rexdale (Toronto), Ontario M9W 1 R3
is your responsibility. A
where range will be installed.
is for a 25inch (63.5 cm)
This appliance is
or with local codes.
![](/html/0f/0f45/0f455fc27dc8e8f708bfa3d77913928a1a7f358388bd3ee6154630dd39fe3ab1/bg3.png)
Tools needed for
installation:
flat-blade screwdriver
or-5116” (0.8 cm) nut
Power supply cord
Use a new 40-amp power supply cord.
Local codes may permit the use of a U.L.-listed,
250~volt, 40-ampere range power supply cord
(pigtail). Power supply cord should be Type SRD
or SRDT and be at least four feet long. The wires
that connect to the range must end with ring
terminals. A 3/4” (1.9 cm), U.L.-listed strain relief
must be installed where the power supply cord
connects to the range. (See Figures 1 and 2.)
ring
This blade connected
to this conduc
terminals
Electrical
connections
NOTE:
earth-grounded in order for the control panel to work.
If the metal chassis of the range is not earth-
grounded, NO keypads will operate. Check with a
qualified electrician if you are in doubt as to whether
the metal chassis of range is earth-grounded.
Where local codes permit connecting the
frame-grounding conductor to the neutral
(white) junction box wire:
This appliance is manufactured with the
neutral terminal connected to the cabinet. If
local codes Do Not permit connecting
cabinet-grounding conductor to neutral wire,
use “Four-wire connection” instructions.
The metal chassis of the range MUST be
hand or electric drill wood
floor: l/8” (0.3 cm) drill bit
concrete/ceramic floor:
3/16” (0.48 cm) carbidetipped masonry drill bit
Parts supplied for
installation:
(Bracket must be securely mounted to subfloor. Thickness of flooring may require longer
screws to anchor the bracket to sub-floor.)
Electrical
requirements
Save Installation Instructions for the local
electrical inspector’s use.
Power supply cord is not provided and is
available through your local electrical
supply houses.
Electrical Shock Hazard
l
Electrical ground is required on this
appliance.
. Use only a new power supply cord kit ratec
at 250 volts, 40 amperes and investigated
for use with ranges. Do Not reuse an old
power supply cord.
l
Do Not modify the power supply cord plug
If it does not fit the outlet, have a proper
outlet installed by a qualified electrician.
l
Do Not use an extension cord with this
appliance.
l
Do Not ground to a gas pipe.
l
Do Not have a fuse in the neutral or
grounding circuit. A fuse in the neutral or
grounding circuit could result in an
electrical shock.
l
Check with a qualified electrician if you arc
in doubt as to whether the appliance is
properly grounded.
Failure to follow these instructions could
result in serious injury or death.
If codes permit and a separate grounding wire
is used, it is recommended that a qualified
electrician determine that the grounding path
is adequate.
A three-wire or four-wire, single-phase, 120/240volt, 60-Hz, AC-only, electrical supply (or threewire or four-wire 120/208-volt if specified on the
serial/rating plate) is required on a separate
40-ampere circuit, fused on both sides of the line. A
time-delay fuse or circuit breaker is recommended.
THE RANGE MUST BE CONNECTED WITH
COPPER WIRE ONLY.
Wire sizes (COPPER WIRE ONLY) and
connections must conform with the rating of the
appliance (40 amperes).
A wiring diagram is located on back of range.
Panel B
strain relief
Three-wire power supply cord
NEMA lo-50P
Figure 1
314” 1.9 cm)
I U.L.- isted
strain relief
grounding prong
Four-wire power supply cord
(Mobile home or other four-wire
installations)
NEMA lo-5OP
The power supply cord must have three No.-10
copper wires to match a three-wire receptacle of
NEMA Type 1 O-50R. (See Figure 3.)
For mobile home or other four-wire installations:
This appliance is manufactured with ground
connected to cabinet.
revised
wire power cord is connected to the cabinet. See
four-wire electrical connection section, Panels C
and D.
When a four-wire receptacle of NEMA Type
14-50R is used (See Figure 4.), a matching
U.L.-listed, four-wire, 250~volt, 40-ampere, range
power supply cord (pigtail) must be used. This
cord contains four copper conductors with ring
terminals on the appliance end, terminating in a
NEMA Type 14-50P plug on the supply end. The
fourth (grounding) conductor must be identified
by a green or green/yellow cover and the neutral
conductor by a white cover. Cord should be Type
SRD or SRDT with a U.L.-listed strain relief and
be at least four feet long.
The
4-wire power supply cord are:
For use where
local codes
ermit use of
P
lexible power
supply cord.
so the green grounding wire of the four-
MINIMUM
40-ampere circuit
2, No.-8 conductors
1, No.-1 0 white neutral
1, No.-8 green grounding
conductor sizes for the copper
\.
Figure 2
The ground must be
(white or center)
NEUTRAL
P
UG
ny$l
3
three-wire wall
receptacle
(16SOR)
Figure 3
Direct wire
The range can be connected directly to fused
disconnect or circuit breaker box through flexible,
armored or non-metallic sheathed, copper cable
(with grounding wire). Do Not use two-wire with
bare grounding wire. All current-carrying wires
must be insulated.
A U.L.-listed conduit connector must be provided
at each end of the power supply cord (at the
appliance and at the junction box). USE ONLY
lo-GAUGE SOLID COPPER WIRE. DO NOT
USE ALUMINUM. Allow two or three feet of slack
in the line so the range can be moved if servicing
is ever necessary.
four-wire wall
receptacle
(14~SOR)
Figure 4
(white)
1
Electrical Shock/Fire Hazard
Check that wiring you are using matches
colors shown in illustrations and specified
in instruction steps. If wiring does Not
match, it is your responsibility to have a
qualified electrician install correct wiring.
Failure to follow these instructions could
result in fire, electrical shock or death.
Figure 5
Remove the terminal block cover located on
2.
back of range. Remove the 3/8” (0.95 cm) brass
terminal nuts attached to the knockout.
Remove the knockout for the 40-ampere
3.
power supply cord.
silver-colored
n U.L.-listed ’
Figure 7
Attach a 314” (1.9 cm) U.L.-listed strain
on strain relief) to the
rain relief firmly to cabinet.
Place power supply cord through strain relief.
Using the 3/8” (0.95 cm) brass nuts,
ch the neutral (white) wire of power supply
to the center, silver-colored screw of the
her two wires to the outer
rews. (See Figure 7.)
e factory-installed nuts on
g nuts are installed tight.
Tighten strain relief screws
6.
.-:-..: :..
:::.::.:::.
Iv
. Reattach terminal block cover.
..-.-.-.-.
’ ’
-
\\\\\\ 1
strain relief i
cover