Kidde TM0098 User Manual

HOT WIRE TEST BOX
USER GUIDE
TM0098
WARNING
Please read this guide fully before attempting to operate the unit.
1.0 Introduction
This Guide describes the use of the Kidde Fire Protection Hot Wire Test Box (part number 1-53836­K237) to test aspirating smoke detection systems. The unit provides 6V AC output from 220-240V AC mains supply. High current at low voltage is passed through a cable in order to heat it, which causes its insulation to burn giving off smoke. A timer is incorporated to provide a selectable burn period of up to 3 minutes. The timer also helps to prevent the unit being inadvertently left on for an extended period. The unit must never be left on unattended.
The unit must be operated for no more than three (3) minutes continuously and must be left off immediately after operating for a period of at least six (6) minutes to allow it to cool.
The unit is protected against over-temperatures by a thermal switch. Once tripped, the thermal switch will not allow operation for an extended period (up to an hour) regardless of power being present or not. The thermal switch cannot be by-passed or reset manually.
TM0098 Page 1 of 4 Issue 1.00
2.0 Preparation and Precautions
When performing a hot wire test, ensure that all local standards, practices and regulations are understood and have been adhered to where applicable. Also, ensure that the detection equipment being proved/tested is isolated from both the local fire authority notification alerts and any suppressant actioning devices. The hot wire test is intended to trigger a response from the High
Sensitivity Smoke Detectors under test. Ensure that the consequences of this activation are understood and under control.
Precautions must also be taken to ensure that all personnel present are aware that the test is being conducted and that those who are required to remain in the immediate vicinity of the test are suitably attired for the smoke levels about to be created. Avoid inhaling the smoke plume as it contains
small quantities of hydrogen chloride.
The wire burn tests, particularly the 1m and 2 x 1m tests, produce sufficiently high temperatures to generate small quantities of hydrogen chloride. However, test personnel are unlikely to be exposed to concentrations of hydrogen chloride that exceed the Occupational Exposure Standard (OES) of 5ppm in a 15 minute period unless they are directly exposed to the smoke plume.
It is strongly recommended that personnel wear appropriate protective equipment such as an E1 respirator conforming to EN140 and goggles, without ventilation, conforming to EN166 in the following situations:
Multiple tests are required
Personnel are within the immediate vicinity (e.g. 2m) of the smoke source
Due to the nature of hot wire tests there is a minor fire hazard. It is essential that an appropriate type of fire extinguisher (e.g. C0
It is the responsibility of the person carrying out the tests to ensure that the electrical equipment used is maintained at all times for safety. In particular the correct fuse is fitted and that a power cord with suitable local approvals is used. If in doubt, please seek guidance from a qualified electrician.
2 or Dry Powder) is available during the test.
3.0 Equipment Set-Up
Ensure that the fuse fitted has the correct rating. If the fuse is not the correct rating for the supply
voltage in use then it must be replaced as follows:
1. Turn the unit off and disconnect the power supply cord
2. Eject the fuse drawer
3. Remove the existing fuse and replace with one of the correct rating (See section 8)
4. Re-insert the fuse drawer
The timer must be in mode “C” with the scale set to “min” (minutes) and the scale showing from “0 to 3” (maximum of three minutes operation). The timer should appear like this:
TM0098 Page 2 of 4 Issue 1.00
Loading...
+ 2 hidden pages