Kidde LHS User Manual

LHS™ Linear Heat Sensor
Installation Instructions 73-202
DESCRIPTION
The LHS™ Linear Heat Sensor cable is a flexible, durable and cost-effective fixed-temperature fire detector, suitable for protecting a wide range of commercial and industrial fire applications.
LHS is a small diameter cable capable of detecting heat from a fire over its entire length. The sensor cable consists of a twisted pair of 19 AWG copper coated steel conductors covered by a temperature sensitive insulation, and protected by either a plastic braid or jacket for various environmental applications (see Figure 1).
LHS is designed for open area as well as proximity detec­tion. A wide range of jackets and operating temperatures (see Table 1) are available for proper system design, in­cluding confined areas or harsh environments which pro­hibit the use of other forms of detection. LHS cable is compatible with any Fire Control Panel that is capable of accepting contact closure type initiating devices.
The LHS linear heat detector is Factory Mutual Approved. An FM Approved installation requires the LHS cable to be connected to an FM Approved Fire Control Panel.
Effective: June 2006
OPERATION
The heat from a fire causes the LHS cable’s special insula­tion to melt at a specific temperature, allowing the two con­ductors to short together, thus creating an alarm condition on the Fire Control Panel. The LHS cable may also be used as a stand-alone contact device. The LHS normal operat­ing state is an open circuit.
Conductor
Tinned copper-covered steel
Insulation
Temperature-sensitive thermoplastic or fluoropolymer
Figure 1. Cable Construction
Jacket
Thermoplastic strip braid, PVC, nylon, or fluoropolymer
Table 1. LHS Sensor Cable Specification
Part Number: 656 ft (200 m) length roll 3,280 ft (1000 m) length roll
Alarm Temperature Ambient Storage Te mp. * Min. Installatio n Temp. Min. Operating Temp. ** Application Approved Spacing Flame Detection Outer Jacket Materia l
Outer Jacket Color
Conductor Insulation
Conductor Color
External Diameter Electrical Rating Conductor Resistance
Conductor Capacitance
Insu la tio n Rat in g
Weight
* Do not store in direct sunlight. ** When not subjected to vibration.
73-200000-001 73-201000-001
155°F (68° C) 155°F (68° C) 185°F (8 5°C) 185°F (85 °C ) 220°F (105° C) 350°F (17 6° C) 465° F (24 0° C)
Up to 113°F (45° C) Up to 113°F (45° C) Up to 113° F (45° C) Up to 113°F (45° C) Up to 158° F (70° C) Up to 221° F (105° C) Up to 39 2° F (200° C)
5°F (-15° C) 5°F (-15° C) 5°F (-15°C) 5°F (-15° C) 32°F (0° C) 32°F (0° C) -4°F (-2 0°C)
-40°F (-40° C) -40°F (-40°C) -40°F (-40°C) -40°F (-40° C) -22°F (-30° C) -40°F (-40° C) -58° F (-50° C) Indoor Only Indoor/Outdoor Indoor Only Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor
20 ft. (6 m) maximum 20 ft. (6 m) maximum 20 ft. (6 m) maximum 20 ft. (6 m) maximum 20 ft. (6 m) maximum Proximity Detection Proximity Detectio n
5 seconds (max) 5 seconds (max) 5 seconds (max) 5 seconds (max ) 12 seconds (max) 20 seconds (max) 20 seconds (max)
Polypropylene Braid Nylon Polypropylene Braid Nylon PVC PVC FEP
Red/Green Tracer
EVA EVA EVA EVA Polythene Polypropylene FEP
1 Black
1 Red
0.146 in ch (3. 7 mm) 0.132 inc h (3. 35 mm) 0.146 inc h (3.7 m m) 0.132 inch (3. 35 mm) 0.1 67 inc h (4.25 m m) 0. 171 inc h (4. 35 mm) 0.138 in ch (3.5 mm)
20.2 1 pF/ft.
(66.32 pF/m)
11.29 lb./1000 ft. (16.8 kg/km)
73-200000-011 73-201000-011
Black
Marke d H804 0N
1 Black
1 Red
20.21 pF/ft.
(66.32 pF/m)
10.65 lb./1000 ft. (15.85 kg/km)
1000 megohm per 3280 ft. (1000 m) afte r 1 minute @ 500 Vdc Minimum
73-200000-002 73-201000-002
Red /B lac k Trace r
1 Blac k
1 Red
30.48 ohms/1000 ft. @ 68°F (1 0 0 o hms/1 0 0 0 m) @ 2 0 °C
25.42 pF/ft.
(83.41 pF/m)
11.29 lb./1000 ft. (16.8 kg/km)
73-200000-012 73-201000-012
Black
Marke d H8045N
1 Blac k
1 Red
1 Amp maximum, 110 Vdc maximum
25.4 2 p F /ft.
(83.41 pF/m)
10.65 lb./10 00 ft. (15.85 kg/km)
73-200000-003 73-201000-003
19.9 6 pF/ft.
(65.48 pF/m)
15.25 lb./1 000 ft. (22.7 kg/km)
Black Red White
1 Blac k
1 Red
73-200000-004 73-201000-004
1 Black
1 Blac k /Whi te
17.52 pF/ft.
(57.48 pF/m)
12.67 lb./1000 ft. (18.85 kg/km)
73-200000-005 73-201000-005
1 Black 1 White
19.22 pF/ft.
(63.07 pF/m)
14.65 lb./1000 ft. (21.8 kg/km)
DESIGN CONSIDERATIONS
The system design and installation must follow accepted principles of fire protection engineering, as well as comply with applicable codes and standards:
NFPA-72, National Fire Alarm Code
NEC 760, National Electric Code
Any local installation requirements
Requirements of the Authority Having Jurisdiction (AHJ)
1. Selection of the appropriate part number for a specific application must take into consideration the tempera­ture of the hazard, the ambient temperature, and the environment where the sensor is installed.
2. For open area protection, LHS must be mounted at the ceiling, using the FM Approved spacing between p aral­lel runs. Distances from walls are half the spacing shown. The thermal path to the LHS sensor must not be obstructed. Maintain a 1” (25 mm) distance from the ceiling for fastest detection.
3. For proximity detection, the LHS sensor must be tight against the object being protected, to insure good ther­mal transfer. Exercise care to insure that vibration and sharp edges do not cause abrasions to the cable, which could result in a false activation.
4. Outdoor applications may need to be shielded from di­rect sunlight to prevent the LHS sensor’s operating tem­perature and/or maximum ambient temperature from being exceeded, which may cause a false activation.
5. To use LHS sensor in hazardous locations (Class 1 Groups A,B,C,D; and Class 2 Groups E,F,G), FM Ap­proved intrinsic safety barriers must be used to isolate the sensor from the control panel.
INITIA TING CIRCUIT WIRING
The LHS sensor connects to any Fire Control Panel (FCP) as a dry-contact initiating device. Follow the installation in­structions of the FCP for specific electrical requirements of the initiating circuit (see figure 2).
1. The LHS sensor can be run as a Class B or Class A circuit loop, with no T -t ap s.
2. The maximum LHS sensor zone length is determined by the electrical characteristics of the FCP initiating cir­cuit. Use the LHS resistance and capacitance as shown in Table 1 to calculate the maximum length. For ex­ample, a FCP with input loop resistance of 50 ohms will allow 820 feet (=50/(2 x 0.03048)) of LHS sensor.
3. If the FCP is some distance away from the protected space, install LHS sensor only in the protected space, and use lead-in cable to connect the LHS sensor to the FCP. The lead-in cable can be any copper wiring ap­proved for fire alarm use.
4. The LHS sensor in the protected space does not need to be contiguous. Copper wiring approved for fire alarm
use may be used to connect the separate lengths of LHS sensor.
5. If the initiating circuit is run as Class B (2 wire), then an end-of-line device compatible with the FCP must be installed at the end of the LHS sensor cable.
6. If allowed by the AHJ, other initiating devices (smoke detectors, manual stations, etc.) may be installed on the same zone as the LHS sensor. The LHS sensor cable can be wired directly between these other devices.
Fire Control Panel
Initiating
Circuit
Lead-In Cable
LHS Sensor Cable
Junction Box
End-of-Line Device
Junction Box
Figure 2. FCP with LHS Sensor Cable
SENSOR CABLE MOUNTING
The LHS sensor cable must be mounted in a professional manner, in accordance with any applicable codes and re­quirements. The recommended mounting techniques de­scribed below do not preclude the use of alternate means that are more suitable for a specific installation so long as such means are acceptable to the local AHJ.
CAUTION
!
Where subject to mechanical damage, the sensor cable should be protected to prevent damage which could result in false activation.
> When designing the LHS layout, sensor cables should be located where they will not be subject to physical damage.
> If metal fasteners are used, non-metallic bushings must be used to prevent chafing or crushing of the sensor cables.
1. The cable should be adequately supported to prevent sagging. It is not necessary to tension the cable, how­ever on straight runs it is recommended that the cable is supported every 3 feet (1 m). Reduced spacing may be employed to suit local codes or conditions such as around corners and transition points. Tension on the sensor cable cannot exceed 50 Newtons. The sensor cable can be bent around a radius no smaller than 2” (50 mm)
2. Wherever possible, the sensor cable should be installed in a continuous run with as few splices as possible.
3. The sensor cable should be the last item installed on a project. If not installed last, it should be temporarily sup­ported by cable ties to minimize the risk of damage. Care should be taken to prevent damage due to foot traffic, mechanical impact, kinking or any external heat sources.
2
Loading...
+ 2 hidden pages