Kidde K-45-9049 User Manual

Kidde Engineered Fire Suppression System
Designed for use with 3M™ Novec 1230™ Fire Protection Fluid
Explosion Proof Solenoid, Electric Control Head Data Sheet
Explosion Proof: – UL Listed as Suitable for Hazardous Locations
Class I Div 1 Groups C and D Class II Div 1 Groups E, F and G
FM Approved
Compatible with UL Listed and FM Approved Suppression Systems:
®
– FM-200 – Carbon Dioxide Systems
–FE-13
Systems, Including the ADS
Systems
P/N: 81-100000-001
DESCRIPTION
The Explosion Proof Control Head is designed to operate FM-200 valves, stop valves and directional valves. The Explosion Proof Control Head can be operated electronically from the Detection and Control system, or by local manual operation via an affixed manual control head. The Explo­sion Proof Control Head has a continuous current draw, which must be accommodated for at the Control Panel. The actuating pin latches in the released position and must be mechanically reset prior to re-arming the sys­tem.
A suitable Control Panel, Listed and/or Approved for use with the Explosion Proof Control Head, shall be provided for supervision of the releasing circuit per NFPA require­ments.
®
, ADS, Carbon Dioxide and FE-13™ cylinder
•Operated By: – Control Panel – Mechanical Manual Actuator
Nominal 24 Vdc Operation
Low Current Consumption
Operates: – Cylinder Valves –Stop Valves – Directional Valves
Wide Operating Temperature Range
Rugged Brass Body
A UTC Fire & Security Company
Effective: April 2008
K-45-9049
The Explosion Proof Control Head is designed and rated for use in the following hazardous areas: Class I Division 1 Group C and D and Class II Division 1 Group E, F and G.
3.0 in.
(76 mm)
7.8 in. (198 mm)
Figure 1. Assembly Drawing
INSTALLATION
The Explosion Proof Control Head can be mounted directly on either the cylinder valve, stop/directional valve.
Care should be taken to ensure that the actuating pin is in the set position when attaching the control head to the cylinder or the stop/directional valve.
WARNING
Tighten the swivel nut securely in place.
Accidental system discharge could occur, which could cause property damage, personal injury and/or death.
When installing the Explosion Proof Control Head in haz­ardous locations, wiring connections must be terminated in explosion proof junction boxes.
The lead wires must be connected using the indicated polarity (red to positive, black to negative) in order to obtain correct operation.
MAINTENANCE
Regular scheduled maintenance should be performed on the Explosion Proof Control Head to ensure that the unit operates correctly if and when required.
MONTHLY
The Explosion Proof Control Head should be inspected for any signs of physical damage, deterioration, corro­sion, distortion, cracks, dirt ingress and loose couplings. Tighten any loose couplings. Replace damaged or miss­ing caps. Replace control head if damage is found. Ensure that all explosion proof control heads are in the “set” position.
SEMI-ANNUALLY
The Explosion Proof Control Head should be tested for proper operation.
All Explosion Proof Control Heads should be removed from agent cylin­ders (Carbon Dioxide, FM-200 or FE-
WARNING
Remove control heads from all master cylinders within the hazard area being tested. Let the Explosion Proof Control Head hang freely from the flexible electrical con­duit connections. Operate the Explosion Proof Control Head, either by actuation at the system control panel or via manual operation of an electric pull station. Ensure that the control head has operated. Observe that the actuating pin has moved to the fully released position. If any control heads have not operated, check circuit for electric continuity. Replace all damaged control heads. Repeat operation test if any control heads have been replaced. Replace any damaged control head, which fails to reset properly. Make certain that electric control heads are in the set position before reconnecting to agent cylin­ders. Reattach all control heads to threaded ports on cyl­inder valves and tighten swivel nuts securely.
13) to avoid accidental system dis­charge, which could cause property damage, personal injury and/or death.
SPECIFICATIONS
Part Number: 81-100000-001 Applications: FM-200, ADS, Carbon Dioxide
and FE-13 Suppression Sys­tems
Approval/Listing:
Releasing Device– UL, FM HazLoc– UL, FM
HazLoc Ratings: Class I Division 1 Group C
and D Class II Division 1 Group E, F and G
Operating Voltage: 18 Vdc @ 0.20 A to
30 Vdc @ 0.50 A Current Draw: At 24 Vdc– 270 mA continuous
At 30 Vdc– 500 mA continuous
Wiring Connections:
Wire Size– 18 AWG
Lead Length– 36 in. (914 mm)
Ambient Temperature: -40°F to 130°F (-40°C to 55°C) Construction:
Material– Brass body
Weight– 8.1 lb. (3.7 kg) Dimensions: 3 in. D x 7.8 in. L
(76 mm D x 198 mm L)
ORDERING INFORMATION
Part Number Description
81-100000-001
870652 Mechanical Manual Actuator
81-129958-001 Reset Tool Assembly
Explosion Proof Solenoid
(Electric Control Head)
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or ques­tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-45-9049 Rev AC © 2008 Kidde-Fenwal Inc. Printed in USA
A UTC Fire & Security Company
400 Main Street Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920
www.kiddefiresystems.com
Loading...