Kidde HR230CT Owner's Manual

HEAT ALARM FEATURES
•This heat alarm is powered from a 230V AC supply, and has a DC battery back-up source. AC/DC heat alarms offer added protection in the event of a power failure.
• Unique power connector prevents interconnecting with incompatible heat alarms, smoke alarms, or security systems.
• Model HR230CT heat alarms can be interconnected with as many as 35 other Firex heat alarms or Firex 230V AC smoke alarms. Interconnectable Firex smoke alarms include: GC240, I240C, IAR230C, PG240, PAD240, PADC240 and PAR230. Interconnectable Firex heat alarms include: H230, H230CT and HR230CT.
•False Alarm Control quiets unwanted alarms for up to 10 minutes.
• Model HR230CT includes permanent rechargeable lithium batteries.
• Optional use tamper-resistant feature serves as a safeguard against tampering.
• The heat alarm will sound a short beep about once a minute if the battery is low.
• Multi-purpose green and red LEDs indicate that the heat alarm is connected to the AC supply, is working normally, or is in alarm.
• Loud alarm sounder – 85 decibels [dB(A)] at 3m – will sound to alert you to an emergency.
•Test button checks heat alarm operation.
SPECIFICATIONS
MODEL NUMBER HR230CT ELECTRICAL RATING 230V AC, 13 VOLT DC RECHARGEABLE LITHIUM BACK UP INTERCONNECTING FIREX UPTOANY COMBINATION OF 35 OTHER FIREX HEAT
SMOKE AND HEAT ALARMS ALARMS (MODEL H230CT, H230, HR230CT) OR FIREX (OR PATTRESS WITH RELAY)SMOKE ALARMS (MODELS GC240, I240C, IAR230C,
PG240, PAD240, PADC240
AND PAR230)
NOTE: THE ABOVE FIREX MODELS ALSO MAY BE INTERCONNECTED
WITH
FIREX P
ATTRESS WITH R
ELAY (MODEL PATR).
TEMPERATURE RATING 58°C M
AXIMUM AMBIENT 37.8°C
T
EMPERATURE RATING
OPERATING TEMPERATURE -30°C TO 70°C RECOMMENDED COVERAGE 50M
2
RECOMMENDED SPAC ING 5.3M M
AXIMUM DISTANCE FROM WALL 7.7M
M
AXIMUM CEILING
HEIGHT 6M
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE INSTRUCTIONS
!WARNING
• This heat alarm requires constant 230V AC power AND fully charged batteries to operate properly. It requires 2 full days under mains power to reach full back up capacity. The batteries are not replaceable. DO NOT connect this heat alarm to any other type of device except those listed in this manual.
• The TEST/FALSE ALARM CONTROL button accurately tests all heat alarm functions. DO NOT use any other test method for routine testing. Test heat alarm weekly to ensure proper operation.
• Higher ceilings will increase the time needed by the heat alarm to detect a fire. In most dwellings the ceiling height will keep this reaction time within acceptable limits. However, ceilings with a height of over 6m may delay the reaction time of the heat alarm significantly. Advice from your local distributor or Fire Brigade should be obtained when installing a heat alarm on a ceiling higher than 6m.
• This heat alarm should be installed only by a qualified electrician. The installation should comply with BS 7671 and all prevailing local, regional and national codes.
• This heat alarm is designed to be used only as part of the protection of a single family dwelling or a house in multiple occupation (HMO) of no more than two stories. It also may be used in conjunction with smoke alarms within individual flats or apartments in larger houses in multiple occupation, to provide an early warning to occupants of a fire in a room within the dwelling, but a communal fire alarm system also should be provided in such cases. DO NOT install this heat alarm in any other buildings, such as hotels, motels, dormitories, hospitals, nursing homes or group homes of any kind. In these occupancies, a complete automatic fire detection and alarm system, complying with BS 5839: Part 1, should be installed.
• Heat alarms should be used only in conjunction with smoke alarms, with which the heat alarms should be interconnected, in order to provide early warning of heat, smoke, or fire. Smoke alarms should be installed on every level of the dwelling.
• Interconnected heat alarms and smoke alarms offer maximum protection. By interconnecting heat alarms and smoke alarms, when one unit senses heat, smoke, or fire, and sounds its alarm, all others will sound as well. DO NOT connect this heat alarm to any other type of alarm except those stated in this manual or an approved auxiliary device.
• Heat alarms interconnected with smoke alarms may not alert every house­hold member every time. The alarm sounder of the heat alarm is loud in order to alert individuals of a potential danger. However, there may be limiting circumstances where an occupant may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, impaired hearing, etc.). Household members must hear the alarm’s warning sound and quickly respond to it to reduce the risk of damage, injury, or death that may result from fire.
• Check carefully that, when any one device operates, the alarm signal given by interconnected devices is clearly audible throughout the building, particularly in bedrooms, where it is essential that the alarm signal will wake sleeping occupants.
• This heat alarm can sound an alarm only when it detects temperatures of 58°C or above. Heat alarms do not sense smoke or gas. In some fires, hazardous levels of toxic chemicals and smoke can build up before a heat alarm will operate. Temperatures may not reach 58°C to activate the heat alarm QUICKLY ENOUGH to ensure safe escape.
• Some fires are slow smouldering, low heat-producing, or are in a different room to that in which the heat alarm is located, or the heat from the fire may bypass the alarm – the heat alarm may not give a warning under these circumstances.
HEAT ALARMS HAVE LIMITATIONS. This heat alarm is not guaranteed to pro- tect lives or property. Heat alarms are not a substitute for insurance. Householders should insure their lives and property. In addition, as with any electronic device, it is possible for the heat alarm to fail at any time.
• Never paint this heat alarm.
HEAT ALARM LOCATION
Heat alarms give an audible warning when the temperature at the alarm reaches 58°C. Heat alarms are ideal for kitchens, garages, cellars, boiler rooms, attics and other areas where there are normally high levels of fumes, smoke or dust which preclude the use of smoke alarms due to the risk of false alarms.
Guidance on fire detection in dwellings is contained in BS 5839: Part 6. For normal­sized bungalows, two-story houses, flats and maisonettes, the British Standard recommends that the minimum level of protection should comprise smoke alarms in the hallways and staircases. This minimum standard necessitates one smoke alarm in the hallway of a typical bungalow or one smoke alarm on each level of a two-story house. Heat alarms should not be used in these circulation areas. If there are, for example, long hallways, even the minimum standard may necessitate additional interconnected smoke alarms.
If, however, the design of the dwelling does not comply with modern fire safety standards, or if factors such as the presence of several young children, or elderly occupants or disabled people, or of smokers, the use of portable heaters or solid fuel fires during the night, or the use of electric blankets, particularly by the elderly, the British Standard advises that additional detection devices, installed within rooms, may be necessary.
The British Standard recommends that, if the risk justifies the provision of detectors in a kitchen, boiler room, or other area (except a circulation area) in which smoke alarms would be likely to give false alarms, heat alarms should be used. However, the Standard also advises that heat alarms may be installed in other rooms instead of smoke alarms, provided that the construction enclosing the room (including the door) can resist fire for a sufficient time after operation of a heat alarm to enable occupants to escape safely. However, a heat alarm is unlikely to operate early enough to save the life of anyone asleep in the room in which it is installed. Moreover, a heat alarm in the room of fire origin may not give sufficient warning for occupants to escape safely if the door to that room is open.
HEAT ALARM SITING
FOR BEST PROTECTION, IT IS RECOMMENDED THAT YOU INSTALL A SMOKE OR HEAT ALARM IN EVERY ROOM. In addition, it is recommended that all smoke and
heat alarms should be interconnected. Install heat alarm on a standard electrical box or surface mount pattress (Firex
Model PAT or PATR) as close to the centre of the ceiling as possible. If the centre is not practical, mount the heat alarm no closer than 300mm away from a wall or corner.
In rooms with open joists or beams, all ceiling-mounted alarms should be located on the bottom of such joists or beams and not up in joist channels. On sloped, peaked or gabled ceilings, install heat alarm 90cm from highest point. If only wall placement is possible, install no further than 150mm from ceiling.
DO NOT install heat alarms:
• Directly over the cooker, stove or oven.
• In areas with high humidity, like bathrooms or shower rooms, or areas near dishwashers or washing machines. Install heat alarms at least 3m away from these areas if possible.
• Adjacent to, or directly above, heaters, air-conditioning vents or ceiling fans.
• In an area where the temperature may fall below -30°C or rise above 37°C.
• Near fluorescent lights. Electrical noise and flickering may affect the operation of the heat alarm.
• Closer than 300mm to light fittings.
• In such a position that it is difficult or dangerous to reach for testing or maintenance.
• Do not site the alarm in area where water or other liquids may enter the alarm.
HOW TO INSTALL THIS HEAT ALARM
!DANGER: E
LECTRIC SHOCK HAZARD
. T
URN OFF POWER TO THE HEAT ALARM CIRCUIT AT THE MAIN DISTRIBUTION BOARD BY REMOVING THE FUSE OR SWITCHING THE CIRCUIT BREAKER TO THE
OFF
POSITION AND SECURING IT.
!WARNING: T
HIS HEAT ALARM SHOULD BE INSTALLED ONLY BY A QUALIFIED ELECTRICIAN IN ACCOR
-
DANCE WITH THE REGULATIONS FOR ELECTRICAL INSTALLATIONS PUBLISHED BY THE INSTITUTION OF
ELECTRICAL ENGINEERS (BS 7671) AND/OR ALL PRESIDING LOCAL, REGIONAL AND NATIONAL
CODES
.
!WARNING: H
EAT ALARMS SHOULD BE CONNECTED ON A SINGLE INDEPENDENT
, DEDICATED CIRCUIT
AT THE MAIN DISTRIBUTION BOARD
. NO OTHER ELECTRICAL EQUIPMENT, EXCEPT COMPATIBLE SMOKE
ALARMS
, SHOULD BE CONNECTED TO THIS CIRCUIT. IF YOUR HOME HAS RESIDUAL CURRENT DEVICE
PROTECTION ON THE ELECTRICAL INSTALLATION OR ON INDIVIDUAL CIRCUITS
, CHECK WITH A QUALIFIED
ELECTRICIAN TO MAKE SURE THAT FAULTS ON CIRCUITS SERVING SOCKET OUTLETS OR PORTABLE APPLI
-
ANCES CANNOT CAUSE INTERRUPTION TO THE SUPPLY TO THE HEAT ALARMS.
H
EAT ALARMS ALSO MAY BE CONNECTED TO A SEPARATE ELECTRICALLY PROTECTED
, REGULARLY USED
LOCAL LIGHTING CIRCUIT
. HOWEVER, THIS WILL MEAN THAT
, UNLESS A SEPARATE MEANS OF ISOLATION
IS PROVIDED FOR THE HEAT ALARMS
, IT WILL BE NECESSARY TO ISOLATE THE LIGHTING CIRCUIT EVERY
TIME THAT THERE IS A NEED TO ISOLATE THE SUPPLY TO THE HEAT ALARMS
; THIS MAY CAUSE
INCONVENIENCE OR HAZARDS
.
1. Route the household AC supply/interconnect cable into the electrical accessory box or surface Pattress (Firex Model PAT or PATR).
2. Using a suitably-rated connector (supplied with Firex Pattress models), connect the neutral supply to the blue lead of the connector plug.
3. Using a suitably-rated connector (supplied with Firex Pattress models), connect the line supply to the brown lead of the connector plug.
4. If interconnecting is desired, connect the orange of the connector plug to the designated interconnect conductor of the household cable. See note INTERCONNECTING HEAT ALARMS.
5. Insert the completed connector block onto the mounting pins of the Firex Pattress or recess into the electrical accessory box.
6. Pass the connector plug through the mounting plate of the heat alarm, align slots and fasten mounting plate securely to the Firex Pattress or electrical accessory box.
NOTE: If this is to be a single-station heat alarm, cover the orange wire with
electrical tape and tuck it into the electrical box or pattress.
7. Attach the connector plug to the pins on the back of the heat alarm. The plug will only fit one way, and will snap into place.
8. Gently tug the connector to be sure it is attached securely.
9. Position the heat alarm on the mounting plate and turn it clockwise to lock it into place.
10. Turn on the power to the heat alarm circuit at the main distribution board.
11. Test the heat alarm for AC operation. See TESTING THE HEAT ALARM.
©2003 Invensys Climate Controls Americas
111-278
58°C TEMPERATURE RATING
MODEL HR230CT
MODEL HR230CT 230V HEAT ALARM WITH RECHARGEABLE LITHIUM BATTERY AND FALSE ALARM CONTROL
PLEASE READ AND SAVE THIS MANUAL
Installer: Please leave this manual with the occupier (or, in the case of a house in multiple operation, with the owner).
CONTENTS
p.1 Heat Alarm Features p.1-2 Specifications p.2 Important Safety Information p.3 Heat Alarm Location p.3 Heat Alarm Siting p.4 How to Install This Heat Alarm p.5 Interconnecting Heat Alarms p.5 Red and Green LED Indicators p.5 False Alarm Control p.5-6 Testing the Heat Alarm p.6 Maintenance, Cleaning, and Repair p.6-7 Fire Safety Rules and Preventing Hazardous Situations p.7 Fire Procedure p.7 What to Do in Case of Fire p.8 Troubleshooting p.8 Guarantee
!WARNING: HEAT ALARMS ALONE ARE NOT SUFFICIENT FOR LIFE SAFETY AS THEY ARE NOT DESIGNED TO
DETECT SMOKE
. THEY ARE INTENDED TO DETECT TEMPERATURES OF 58°C AND ABOVE TO PROVIDE AN
ADDITIONAL SOURCE OF INFORMATION THAT IS SUPPLEMENTARY TO THAT PROVIDED BY SMOKE ALARMS TO INCREASE THE PROBABILITY THAT AN EARLY WARNING WILL BE PROVIDED AND SO ENHANCE LIFE SAFETY AND PROPERTY PROTECTION
. SEE HEAT ALARMS HAVE LIMITATIONS IN THE IMPORTANT SAFETY
INFORMATION
SECTION OF THIS MANUAL.
230V AC
with Rechargeable
Lithium Battery
FIREX MODEL HR230CT
®
Heat Alarm
HEAT ALARM
SMOKE ALARM
UNFINISHED ATTIC
BEDROOM
BOILER ROOM
BEDROOM
KITCHENLIVING ROOM
SMOKE ALARM WITH FALSE ALARM CONTROL
UTILITY/
LAUNDRY
GARAGE
STANDARD ELECTRICAL JUNCTION BOX OR
MODEL PAT OR PATR PATTRESS
INTERLINK
LINE
BROWN
ORANGE
CEILING
NEUTRAL
BLUE
INTERCONNECTING HEAT ALARMS
Use 1.5mm2minimum solid or stranded cable with a rating of 230V. When intercon­necting heat alarms and/or smoke alarms, the maximum cable length between any two should be 450m for 1.5mm2cable (20 ohm loop resistance.)
This heat alarm may be interconnected with as many as 35 other Firex Model H230, H230CT or HR230CT heat alarms or model GC240, I240C, IAR230C, PG240, PAD240, PADC240 or PAR230 smoke alarms. DO NOT connect to any other type or model of heat alarm or smoke alarm. If interconnecting to Firex Pattress with Relay (Model PATR) only 12 total Firex models may be interconnected.
Connect all interconnected heat and smoke alarms to a single final circuit. Wiring must conform to I.E.E. Regulations for Electrical Installations (BS 7671).
RED AND GREEN LED INDICATORS
This heat alarm features a red and green LED indicator that can be seen through the clear light pipe on the top of alarm. The LEDs indicate the following:
GREEN
ON – AC power is present. OFF – AC power is not present.
RED
BLINKS ONCE A MINUTE – DC power is present indicating normal operation. BLINKS SIX TIMES PER MINUTE – False Alarm Control activated. OFF – DC power is not present. BLINKS ONCE A SECOND and unit is sounding alarm – senses 58°C
temperature or greater. OFF and unit is sounding alarm – Another interconnected smoke/heat alarm
in the network has sensed smoke or 58°C and is signaling this alarm.
FALSE ALARM CONTROL
!WARNING: BEFORE USING THE ALARMS FALSE ALARM CONTROL FEATURE, FULLY IDENTIFY THE
SOURCE OF THE HEAT BUILD UP AND MAKE SURE THAT THE AREA IS SAFE
.
T
O ACTIVATE THE FALSE ALARM CONTROL PUSH AND RELEASE THE TEST/FALSE ALARM CON-
TROL
BUTTON IN THE CENTER OF THE ALARM. THE ALARM WILL SILENCE IMMEDIATELY AND THE RED
LIGHT
(LED) WILL BLINK APPROXIMATELY EVERY 10 SECONDS FOR THE NEXT 10 MINUTES. THIS FEA-
TURE IS TO BE USED ONLY WHEN A SAFE CONDITION IS KNOWN TO EXIST.
The False Alarm Control will silence the alarm for approximately 10 minutes. A rapid rise in temperature will override the False Alarm Control and cause the unit
to sound an alarm. After 10 minutes the heat alarm will beep twice. This signals the end of the False
Alarm Control period and the unit will revert to normal operation. If the unit still detects a dangerous situation the alarm will sound again.
If interconnected alarms are installed, the unit that detects the high temperature and sounds the alarm cannot be inadvertently silenced by the TEST/FALSE ALARM CON­TROL button of other units. In this case all of the alarms will continue to sound for as long as a dangerous situation is detected or until the TEST/FALSE ALARM CONTROL button of the initiating alarm is pressed.
If the alarm does not go into False Alarm Control and continues to sound its alarm, the heat in the area is too high and a dangerous situation may exist – take emer­gency action.
TESTING THE HEAT ALARM
!WARNING: TEST EACH HEAT ALARM AND SMOKE ALARM TO BE SURE THAT EACH IS INSTALLED
CORRECTLY AND IS OPERATING PROPERLY
.
S
TAND AT ARMS LENGTH FROM THE HEAT ALARM WHEN TESTING. THE ALARM SOUNDER IS LOUD TO
ALERT YOU TO AN EMERGENCY AND CAN BE HARMFUL TO HEARING
.
T
EST THE HEAT ALARM WEEKLY AND UPON RETURNING FROM HOLIDAY, OR WHEN THE HOUSE HAS
BEEN UNOCCUPIED FOR SEVERAL DAYS
.
Test all heat alarms weekly by doing the following:
1. Check the TEST/FALSE ALARM CONTROL button. If the green LED above the test button is ON, the heat alarm is receiving AC power.
2. Firmly depress the TEST/FALSE ALARM CONTROL button for at least five (5) seconds. The heat alarm will sound a loud beep for about four (4) times a sec­ond. The alarm may sound for up to ten (10) seconds after the TEST/FALSE ALARM CONTROL button is released. NOTE: If heat alarms are interconnect­ed, all heat and smoke alarms should sound an alarm within three (3) seconds after any test button is pushed and the tested heat alarm sounds.
3. If the heat alarm does not sound, turn off the power to the heat alarm circuit at the main distribution board and check the wiring. Retest the heat alarm.
!WARNING: I
F THE HEAT ALARM SOUNDS, AND THE HEAT ALARM IS NOT BEING TESTED, THE HEAT
ALARM IS SENSING A TEMPERATURE OF
58°C OR ABOVE. THE ALARM SOUND REQUIRES YOUR
IMMEDIATE ATTENTION AND ACTION. EVACUATE THE DWELLING IMMEDIATELY!
MAINTENANCE AND CLEANING
In addition to weekly testing, this heat alarm must be cleaned periodically to remove dust, dirt and debris.
!DANGER: ELECTRIC SHOCK HAZARD.
T
URN OFF THE
AC SUPPLY TO THE HEAT ALARM AT THE MAIN DISTRIBUTION BOARD BY REMOVING THE
FUSE OR SWITCHING THE APPROPRIATE CIRCUIT BREAKER TO THE
OFF POSITION BEFORE CLEANING THE
HEAT ALARM
.
!WARNING: H
EAT ALARMS ARE LIFE
-SAVING DEVICES AND SHOULD BE CARED FOR PERIODICALLY
.
!WARNING: BATTERIES NOT REPLACEABLE
.
Model HR230CT has permanently mounted rechargeable lithium batteries that are designed to outlast the useful life of the alarm.
CLEANING
Clean the heat alarm at least once annually to remove dust, dirt and debris. Always turn off the AC power to the heat alarm before cleaning it.
Using the soft brush or wand attachment to a vacuum cleaner, vacuum all sides and the cover of the heat alarm. Be sure that all vents are free from debris.
If necessary, turn off the AC power and use a cloth dampened with warm water to clean the heat alarm cover.
IMPORTANT: Do not attempt to remove the cover or clean inside the heat alarm. THIS WILL INVALIDATE YOUR GUARANTEE. Failure to properly clean and maintain this heat alarm may result in impaired operation and possible failure and will invali­date the guarantee.
REPAIR
!CAUTION: D
O NOT ATTEMPT TO REPAIR THIS HEAT ALARM
. DOING SO WILL INVALIDATE YOUR GUARANTEE.
If the heat alarm is not operating properly, see TROUBLESHOOTING. If necessary, and if the heat alarm is still under warranty, return it to your local distributor. Pack it in a well-padded carton and send it, postage prepaid, to the address given at the end of this manual.
If the heat alarm is no longer under guarantee, have a qualified electrician replace the heat alarm immediately with a comparable Firex brand heat alarm.
FIRE SAFETY RULES AND PREVENTING HAZARDOUS SITUATIONS
Siting, testing, and taking care of heat and smoke alarms is just one step in helping to protect your family and home from fires. You must also reduce the chance that fires will start in your home and increase your chances of escaping if a fire does start. At a minimum, your home fire safety program should include the following guidelines.
• Use smoking materials properly – never smoke in bed or when sleepy or under the influence of alcohol or other drugs.
• Keep matches and other sources of ignition away from children.
•Store flammable materials in proper containers and never store or use them near open flames or sparks.
• Keep electrical appliances and their leads in good working condition, and do not overload electrical circuits.
• Keep fireplaces, chimneys, and barbecue grills clean, and make sure they are properly sited away from combustible materials.
• Keep portable heaters and open flames such as candles away from com­bustible materials.
• Do not allow rubbish to accumulate.
• Have the electrical wiring in your house checked by a qualified electrician at least every 10 years (or more often as it ages).
• Never leave cooking unattended.
FIRE PROCEDURE
If you hear the heat or smoke alarm sounding, and you have not pushed the test but­ton, it is warning you of a dangerous situation. You will need to respond immediately. To prepare for such occurrences, develop family escape plans, discuss them with all household members, and practice them regularly. For your safety, as a minimum, you should do the following to have more effective fire safety.
• Draw a floor plan of your home and find all ways to escape if there is a fire. On the ground floor, consider whether windows can be used for escape. On upper floors, consider whether external rescue will be possible if escape routes are blocked by fire or smoke.
• Expose everyone to the sounds of the heat alarm and of the smoke alarm and explain what the sounds mean. Show them how to check to see if doors are hot before opening them, how to stay close to the floor and crawl along the floor to stay below dangerous smoke, fumes and gases, and how to use the alternative exit if a door is hot. Instruct them not to open the door if the door is hot.
• Decide on a meeting place a safe distance from your house and make sure all members of your household understand they should go and wait for you there if there is a fire. Explain to children that they must be ready to leave the house by themselves if necessary.
• Hold fire drills every six (6) months to make sure everyone, even small children, know what to do to escape safely.
• Know where to go to call the Fire Brigade from outside your house.
• Provide emergency equipment, such as fire extinguishers, and teach your family how and when to use this equipment.
WHAT TO DO IN CASE OF A FIRE
After you have prepared family escape plans and practiced them with your family, you have increased their chances of escaping safely. Review the following rules with your family when you have fire drills, so everyone will remember them in a real fire.
1. Don’t panic, stay calm. Your safe escape may depend on thinking clearly and remembering what you have practiced.
2. Get out of the house, following your planned escape route, as quickly as possible. Do not stop to collect anything or to get dressed.
3. Open doors carefully only after feeling to see if they are hot. Do not open a door if it is hot; use an alternative escape route. If your escape route is blocked, go to a window and shout for help. If necessary, stuff clothing or other materials in the gaps round the room door to stop smoke from entering until help arrives.
4. Stay close to the floor; smoke and hot gases rise toward the ceiling.
5. Keep doors and windows closed unless you open them to escape.
6. Meet at your pre-arranged meeting place after leaving the house.
7. Call the Fire Brigade as soon as possible from outside your house. Give your full address, including the name of the town or village.
8. Always call the Fire Brigade as soon as possible, even if a fire seems small.
9. Never re-enter a burning or smoke-filled building.
These guidelines will assist you in the event of a fire. However, to reduce the chance that fires will start, practice fire safety rules and prevent hazardous situations. Contact your local Fire Brigade for more information.
TROUBLESHOOTING
GUARANTEE
Climate Controls Americas (the “Company”) guarantees this product to be free from defects in material and workmanship under normal use and service (“Defects”) for a period of six (6) years from the date of purchase (the “Guarantee Period”). Should any Defects be discovered within the Guarantee Period, the Company will, at its option, repair or replace the defective product provided that: (a) it is returned during the Guarantee Period with postage prepaid and with proof of purchase date to the address shown below and (b) the Company verifies that the claim is proper. This Guarantee does not cover damage resulting from accident, improper installation, maintenance or repair, misuse, abuse or product modification. This Guarantee does not confer any rights other than those expressly set out above and does not cover any claims for consequential loss or damage. This Guarantee is offered as an extra benefit and does not affect your statutory rights as a consumer.
Return units, postage prepaid, to your local distributor. For information on your local distributor, contact:
SENSOTEC EUROPE LTD.
Unit 7, Enterprise Park
Bala, Gwynedd LL23 7NL
Wales, United Kingdom
Technical Services: Telephone +44 08700 730000
Fax +44 08700 740000
Sales: Telephone +44 08700 710000
Fax +44 08700 720000
Climate Controls Americas
191 E. North Avenue Carol Stream, IL 60188 United States of America
©2003 Invensys Climate Controls Americas
NOTE: Colors shown correspond to electrical codes in the United Kingdom. Colors may
vary in other countries.
PROBLEM SOLUTION Heat alarm does not 1. Check that AC power is
sound when tested. turned on.
2. Turn off power. Remove heat alarm from mounting
NOTE: PUSH TEST/FALSE plate and check that ALARM CONTROL BUTTON connector plug is for at least five (5) seconds securely attached. while testing! 3. Clean heat alarm.
Heat alarm beeps about 1. Verify that unit has been under once a minute. mains operation for a minimum
of 2 full days. If the beeping persists after required charging period, return the unit for service.
Heat alarm sounds 1. Hire an electrician to move unwanted alarms. heat alarm to a new location.
See the HEAT ALARM SITING section of this manual.
Interconnected heat alarms 1. Press and hold button for at do not sound when system least three seconds after the is tested. first unit sounds.
2. Turn off AC power or circuit breaker and check the interconnect wiring. See INTERCONNECTING HEAT ALARMS section of this manual.
BLUE BLUE ORANGE ORANGE BROWN BROWN
FOR INTERCONNECTING: USE A MINIMUM OF 1.5mm2 CABLE
NEUTRAL
LINE
Loading...