Kidde HD 200 Owner's Manual

Effective November, 2001
Heat Detectors Series 600
The Heat Detectors Series 600 are supplied with the following standard features:
• Rate-of-Rise and Fixed Temperature
• One or Two-Circuit, Normally Open
• Easy Installation
Description
The Series 600 Heat Detector is attractive, durable and features combination rate-of-rise and fixed temperature operation. Heat detectors are available in 135°F and 200°F temperature ratings.
Rate-of-rise detects heat by quickly responding to a rapid temperature increase. Rate-of-rise units have a wide spacing allowance of 50-foot centers. See specification table for details.
Fixed temperature reacts to heat by responding to a specific temperature setting.
Series 600 Detectors use the same reliable pneumatic rate-of­rise element of former models, but offer added aesthetic appeal.
The pneumatic rate-of-rise element responds to a rapid rise in temperature, approximately 15°F. (8°C) per minute, by expansion of air within the sealed chamber faster than it can escape through a calibrated vent. The resultant increase in pressure depresses the diaphragm, causing the electrical contact to close the circuit.
The fixed temperature element uses a fusible alloy. When activated, the external heat collector drops away to provide quick visual confirmation that the element has operated.
The units protrude only 1-3/8 inch from the ceiling surface with a junction box mounting. They have pleasing contours and an all-white finish that conforms to ceiling aesthetics.
Installation
Each detector includes a patented reversible mounting plate. In one position, it easily attaches to 3.25" or 4" octagonal box, or plaster ring.
In reverse, the plate can be used for open wiring without a junction box. A 1/4" space between detector and mounting surface allows for wire connections. All mounting screws are concealed.
The detector attaches easily to the mounting plate with a push and twist motion. No tools are required.
• Low Profile
• Visual Indication
• Operation Testing
3-1/4" or 4" Octagonal Box
Mounting plate is molded of white self-extinguishing thermo­plastic rated at 221°F (105°C). The plate is extremely strong yet adapts to uneven mounting surfaces.
Series 600 Testing Methods
Models 601/621 and 602/622 can be tested by the quick application of heat from any convenient source. A portable hair dryer is recommended. However, do not apply heat that exceeds the fixed temperature rating of the detector.
Models 603/623 and 604/624 cannot be tested. However, the fusible alloy element used is considered so reliable that testing is not necessary.
All rights reserved (11/01).
Effective: November, 2001
Model 601 and 621
No Marking Model 601 (1 circuit) Model 621 (dua circuit)
Rate-of-Rise and Fixed Temperature, 135°F (57°C)
Applications: Normal temperature fluctuations and ceiling temperatures not exceeding 100°F (38°C)
Maximum Spacing Allowance* ­50 x 50 ft. - UL 30 x 30 ft. - FM
*Refer to National Fire Alarm Code Standard NFPA 72 for application requirements
Model 602 and 622
Gray Ring Model 602 (1 circuit) Model 622 (dual circuit)
Rate-of-Rise and Fixed Temperature, 200°F (94°C)
Applications: Normal tempe­rature fluctuations and ceiling temperatures exceeding 100°F (38°C) but not 150°F (66°C)
Maximum Spacing Allowance* ­50 x 50 ft. - UL 30 x 30 ft. - FM
Screw Terminals
Model 603 and 623
Gray Spot Model 603 (1 circuit) Model 623 (dual circuit)
Fixed T emperature only, 135°F (57°C)
Applications: Unusually violent temperature fluctuations and ceiling temperatures not exceeding 100°F (38°C)
Maximum Spacing Allowance* ­25 x 25 ft. - UL 20 x20 ft. - FM
Model 604 and 624
Gray Ring and Dot Model 604 (1 circuit) Model 624 (dual circuit)
Fixed T emperature only, 200°F (94°C)
Applications: Unusually violent temperature fluctuations and ceiling temperatures exceeding 100°F (38°C) but not 150°F (66°C)
Maximum Spacing Allowance* ­15 x 15 ft. - UL
Important Special Notes
Application: Heat detectors should be used for property protection. Reliance should not be placed on heat detectors for Life Safety .
CAUTION: When life safety is involved, smoke detectors MUST also be used. Detectors must not be painted.
Battery Back-Up: Heat detectors should be electronically supervised with battery back-up at the panel.
The rate-of-rise mechanism may be subject to reduced sensitivity over time. Annual testing of the rate-of-rise mecha­nism is recommended.
Electrical Ratings
6-125 Volts A.C., 3.0 Amps. 6-28 Volts D.C., 1.0 Amps. 125 Volts D.C., 0.3 Amps. 250 Volts D.C., 0.1 Amps.
Listings/Approvals
• Listed by Underwriters Laboratories (UL)
• Factory Mutual Approved (FM)
• California State Fire Marshal Approval (CSFM)
• City of New York (MEA) Listing No. 188-94-E
• Listed by Underwriters’ Laboratories of Canada (ULC)
This literature is provided for informational purposes only. CHEMETRONICS assumes no responsibility for the product’s suitability for a particular application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem or question, contact CHEMETRONICS, Ashland, MA; Telephone (800) 496-8383.