Kidde HD135F Owner's Manual

HD135F
For model: HD135F
Heat Alarm User’s Guide
AC Wire-in Single and/or Multiple Station (up to 24 Devices) Heat Alarm with 9 Volt Battery Back Up, 135ºF fixed temperature.
Thank you for purchasing this heat alarm. It is an important part of your family’s home safety plan. You can trust this product to provide the highest quality safe­ty protection. We know you expect nothing less when the lives of your family are at stake. Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models of interconnect compatible alarms. Connection of Kidde products to a non-speci­fied manufacturer’s interconnect system, or connection with non-specified equipment from another manufacturer into an existing Kidde system could result in nuisance alarming, failure to alarm, or damage to one or all of the devices in the interconnect system. Refer to the User’s Guide supplied with each Kidde product for interconnect compatible models, brands, and devices. Refer to the wiring instructions in section 3 for NFPA initiating device limits
For your convenience, write down the following information. If you call
our Consumer Hotline, these are the first questions you will be asked.
Heat Alarm Model Number (located on back of alarm):
Date Code (located on back of alarm): The National Fire Protection Association (NFPA) and the manufacturer recommend replacing this alarm ten years from the date code.
Date of Purchase:
Where Purchased:
820-0917 Rev. B
11/2006
WARNING! BATTERY DOOR WILL NOT CLOSE UNLESS A BATTERY IS PRE­SENT. REMOVAL OF THE HEAT ALARM BATTERY AND DISCONNECTING OR LOSS OF AC POWER WILL RENDER THE HEAT ALARM INOPERATIVE.
ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm (maximum 80mA for originating unit with 24 devices interconnected).
IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND KEEP THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE.
WARNING! THIS HEAT ALARM IS NOT DESIGNED TO PROTECT LIFE SAFE­TY AGAINST FIRE AND SMOKE.
SEE LIMITATIONS OF ALARMS IN SECTION 8 FOR DETAILS.
CONTENTS OF THIS MANUAL
1 SPECIFICATIONS 2 RECOMMENDED LOCATIONS OF ALARMS 3 LOCATIONS TO AVOID 4 INSTALLATION INSTRUCTIONS 5 OPERATION AND TESTING 6 FALSE ALARMS 7 MAINTENANCE 8 LIMITATIONS OF HEAT ALARMS
9 GOOD SAFETY HABITS 10 NFPA PROTECTION STANDARD 72 11 SERVICE AND WARRANTY
Do not try to repair this heat alarm yourself. Refer to the instructions in Section 11 for service.
1. SPECIFICATIONS
Model Number . . . . . . . . . . . . . . . . . . . . . . . . . .HD135˚F
AC 120 VAC, 60HZ, 80 mA max, 9 V battery backup, Multiple station (up to
24), compatible with Kidde/Lifesaver smoke alarms (see section 3 for a complete list of compatible devices).
U.L. Temperature rating . . . . . . . . . . . . . . . . . . .135ºF Fixed temperature only
U.L. Maximum ambient temperature at ceiling . .100ºF
U.L. Recommended coverage . . . . . . . . . . . . . . .2500 Square Feet (Note "A")
U.L. recommended spacing . . . . . . . . . . . . . . . . .50 Feet
Maximum distance from wall . . . . . . . . . . . . . . .25 Feet (Note"B")
Note A: Maximum coverage established by U.L. is based on providing equal
(10 cm)
4"
MINIMUM
(10 cm)
4"
CEILING
DEAD AIR
SPACE
SIDE WALL
MINIMUM
(30.5 cm)
12"
MAXIMUM
BEST HERE
NEVER
HERE
ACCEPTABLE
HERE
response time as sprinkler devices spaced at 10-Ft intervals (100 Sq/Ft) on a smooth ceiling approximately 15 feet high. Higher ceilings may adversely affect response time and earlier response time may be obtained by reducing the spac­ing between alarms.
Note B: Maximum distance is from any wall or ceiling projection extending down more than 12 inches.
2. RECOMMENDED LOCATION OF ALARMS
• The most favorable mounting location for a heat alarm is on the ceiling in the center of the room. At this location the alarm is closest to all areas of the room (see figure 3).
EXCEPTION: When the mounting surface might become considerably warmer or cooler than the room, such as a poorly insulated ceiling, below an unfinished attic, or an exterior wall. In these cases the alarm should be mounted on an inside wall.
• If the alarm cannot be located in the center of the room, an off-center location can be used on the ceiling. When off cen-
FIGURE 1
ter mounting an alarm on the ceiling, locate it at a minimum of 4" (10 cm) from the side wall (see figure 3).
• If a ceiling mounting location is not fea­sible the next logical location for mounting heat alarms is on the side wall. When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a minimum of 4" (10 cm) and a maxi­mum of 12" (30.5 cm) below the ceiling (see figure 1).
• Install Heat Alarms on sloped, peaked or cathedral ceilings at or within 3 ft (0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4m) hori-
FIGURE 2
zontally shall be located on the high side of the room.” NFPA 72 states: “A row
of alarms shall be spaced and located within 3 ft (0.9m) of the peak of the ceiling measured horizontally” (see figure 3).
• In rooms with open joists or beams, all ceiling mounted alarms shall be located on the bottom of such beams (see figure 2).
• Alarms installed on an open-joisted ceiling shall have their smooth ceiling spacing reduced to no more than half of the listed spacing when measured at right angles to the solid joist (See figure 2).
MOBILE HOME INSTALLATION
Modern mobile homes have been
FIGURE 3
designed and built to be energy effi­cient. Install heat alarms as recom­mended above (refer to RECOMMENDED LOCATIONS and FIGURE 1).
In older mobile homes that are not well insulated compared to present stan­dards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the heat from reaching an alarm mounted on the ceiling. In such units, install the heat alarm on an inside wall with the top edge of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see figure 1).
If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall.
WARNING: TEST YOUR HEAT ALARM OPERATION AFTER RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.
3. LOCATIONS TO AVOID
• In front of forced air supply ducts used for heating and air conditioning, near
ceiling fans, or other high air flow areas.
• In an area where the temperature may fall below -20ºF or rise above 100ºF.
• Near fluorescent lights – electronic "noise" may cause nuisance alarms.
• Heat alarms are not to be used with detector guards unless the combination
(alarm and guard) have been evaluated and found suitable for that purpose.
4. INSTALLATION INSTRUCTIONS
WIRING REQUIREMENTS
• This smoke alarm should be installed on a U.L. listed or recognized junction
box. All connections should be made by a qualified electrician and all wiring used shall be in accordance with articles 210 and 300.3(B) of the U.S. National Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic­tion in your area. The multiple station interconnect wiring to the alarms must be run in the same raceway or cable as the AC power wiring. In addition, the resistance of the interconnect wiring shall be a maximum of 10 ohms.
• The appropriate power source is 120 Volt AC Single Phase supplied from a
non-switchable circuit which is not protected by a ground fault interrupter.
• WARNING:This alarm cannot be operated from power derived from a square
wave or modified square wave inverter. These type of inverters are sometimes used to supply power to the structure in off grid installations, such as solar or wind derived power sources. These power sources produce high peak voltages that will damage the alarm.
WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.
• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE
TO ANYTHING. Leave the red wire insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box.
• When alarms are interconnected, all interconnected units must be powered
from a single circuit.
• A maximum of 24 Kidde/Lifesaver devices may be interconnected in a multiple
station arrangement. The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, heat, carbon monoxide, etc.). With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 remote signaling devices and/or relay modules.
Loading...
+ 11 hidden pages