Kidde G6 Owner's Manual

120V AC Ionization Smoke Alarm
110-427K
MODEL G-6, H, GC PG40 and FXW-R
T
I
N
S
I
G
A
C
L
L
I
F
F
O
O
R
E
N
T
I
A
A
T
S
S
L
T
A
A
H
T
E
S
R
F
A
I
S
R
M
E
E
E
C
R
I
V
PLEASE READ AND SAVE THIS MANUAL
Installer: Please leave this manual with the occupier (or, in the case of a house in multiple operation, with the owner)
The ionization type alarms are generally more effective at detecting fast, flaming fires which consume combustible materials rapidly and spread quickly. Sources of these fires may include flammable liquids or paper burning in a waste container. The photoelectric type alarms are generally more effective at detecting slow, smoldering fires which smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. However, both types of alarms are designed to provide adequate detection of both types of fires. If you desire the benefits of both systems, you should install smoke alarms that combine in one alarm both photoelectric and ionization sensing technologies.
SMOKE ALARM FEATURES
Model PG40 and GC smoke alarms can be interconnected with as many
as 11 other specific model smoke alarms (Model G-6, as many as 5). Model GC features False Alarm Control that temporarily
silences nuisance alarms. Multi-purpose LED indicates that the smoke alarm is receiving
AC power, working under normal operation, or in alarm. Loud alarm horn—85 decibels at 10 feet—sounds to alert you
to a fire emergency. This alarm incorporates the internationally recognized horn sig-
nal for evacuation. During alarm mode, the horn produces three short beeps followed by a 2 second pause and then repeats. This pattern is somewhat different than the previous alarm sound, which continually beeped.
Model FXW-R is a direct replacement for Firex models FX1014,
FX1020, FX1106, and FXW-1A. Model FXW-R cannot be inter­connected with any other smoke alarm.
Test button checks smoke alarm operation.
IMPORTANT SAFETY INFORMATION PLEASE
READ AND SAVE THESE INSTRUCTIONS
!
This smoke alarm requires constant 120-volt, AC power to operate. It
will not work if AC power is not connected or has failed or been interrupted for any reason. DO NOT turn off AC power to quiet false alarms. Open win­dows or fan the air around smoke alarm to silence it.The Push-to-Test but­ton accurately tests all smoke alarm functions. DO NOT use any other test method. Test smoke alarm weekly.We recommend you install smoke alarms that operate from both battery and AC power.Having smoke alarms that work from two different power sources can give extra protection in case of a dead battery or an AC power failure.If you have repeated false alarms, move the smoke alarm to a different location, or install specialized smoke alarms with a False Alarm Control or a photoelectric sensor.
This smoke alarm should be installed only by a licensed, quali-
fied electrician. Observe and follow all local and national electrical and building codes for installation.
This smoke alarm is designed to be used INSIDE a single family
household only. In multi-family buildings, each individual living unit should have its own smoke alarms. It is not designed for use in common areas, stairwells, or common hallways in multi-family buildings.
This smoke alarm IS NOT designed to be the PRIMARY protec-
tion for buildings that require complete fire alarm systems.
Buildings of this type include hotels, motels, dormitories, hospitals, nursing homes, and group homes. This is true even if they were once single family homes. However, this smoke alarm MAY be used
inside individual rooms as SUPPLEMENTAL protection.
WARNING
1
DO NOT connect this smoke alarm to any other smoke alarm or
devices except as specifically listed in this manual. Model PG40, GC and FXW-R smoke alarms can be interconnected with up to 11 other spe­cific model smoke alarms (Model G-6, as many as 5). DO NOT use exter-
nal bug screens or alarm guards. This may cause improper operation.
Smoke alarms must not be used with detector guards unless
the combination of alarm and guard has been evaluated and found suitable for that purpose.
Smoke alarms sound their alarm horns when they detect smoke.
They do not detect heat, flame, or gas.They will not operate if smoke does not reach the smoke alarm.
We recommend that you install a smoke alarm in every room and
on every level of the home. Smoke may not reach the smoke alarm for many reasons. For example, if a fire starts in a remote part of the home, on another level, in a chimney, wall, roof, or on the other side of a closed door, smoke may not reach the smoke alarm in time to alert household members. A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed.
Model G-6, PG40, GC and FXW-R smoke alarms meet all NFPA
requirements for new and existing homes. Per the National Fire Protection Association (NFPA) Standard 72, Chapter 2, this type of smoke alarm can be used to meet the minimum requirements for new and existing residential dwellings.The standard requires that smoke alarms for new residential dwellings be AC powered and interconnect­ed. Therefore, Model G-6, PG40, and GC can be used to meet the mini­mum requirements for new construction residential dwellings.
Smoke alarms may not alert every household member every
time. There may be limiting circumstances where a household member may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, the hard of hearing, etc.). If you suspect that this smoke alarm may not alert a household member, install and maintain specialty smoke alarms. Current studies have shown smoke alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.
This smoke alarm will not provide adequate escape or rescue
time in extremely fast moving fires. Fast fires include gas fires, flammable liquid fires, or fires set on purpose. The smoke alarm will not give adequate escape time to people very close to the fire. Such examples might be, children playing with matches or smokers who fall asleep and drop a cigarette into their bed.
Smoke alarms have limitations. This smoke alarm is not foolproof
and is not warranted to protect lives or property from fire. Smoke alarms are not a substitute for insurance. Homeowners and renters should insure their lives and property. In addition, it is possible for the smoke alarm to fail at any time. For this reason, you must test
the smoke alarm weekly and replace it every 10 years.
SMOKE ALARM PLACEMENT
Invensys Controls Americas recommends complete coverage pro­tection achieved by installing a smoke alarm in every room of your home. The National Fire Protection Association’s (NFPA) MINIMUM requirement for locating smoke alarms in family living units is detailed in NFPA Standard 72, Chapter 2. It reads as follows:
“2-2.1.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each addi­tional story of the family living unit including basements and excluding crawl spaces and unfinished attics. In new construction a smoke detector also shall be installed in each sleeping room."
Further, section 2-2.2.1 states that: “In new construction, where more than one smoke detector is required by
2-2.1, they shall be so arranged that operation of any smoke detector shall cause the alarm in all smoke detectors within the dwelling to sound."
The NFPA, 1993 Edition, Appendix A, however, clearly points out that: “The required number of smoke detectors [as defined in the paragraphs
above] may not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke detectors. For this reason, it is recommended that the householder con­sider the use of additional smoke detectors for those areas for increased protection. The additional areas include: basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke detectors.”
Further, the California State Fire Marshal states that the minimum number of required smoke alarms is not enough to give the earliest warning under all conditions.The California State Fire Marshal states that:
“Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed in each separate sleeping area (in the vicinity, but outside the bedrooms), and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.”
It is clear from the above abstracts that the earliest warning of a developing fire is best achieved by the installation of smoke alarms in all rooms and areas of the residence. Accordingly, Invensys Controls Americas recommends that you install smoke alarms in every room of your residence, even though this is not required by the typical code or standard.
2
FOR MAXIMUM COVERAGE, WE RECOMMEND THAT YOU INSTALL A SMOKE ALARM IN EVERY ROOM OF THE HOME, INCLUDING BASEMENTS AND FINISHED ATTICS. In addition, we recommend interconnecting all smoke alarms capable of being interconnected.
Invensys Controls Americas recommends a minimum of two smoke alarms in every home, no matter how small the home (including effi­ciency apartments). Invensys Controls Americas also recommends maximum coverage by installing smoke alarms in both required and recommended locations as illustrated and described.
SMOKE ALARM PLACEMENT (Cont’d)
Existing Homes:
The NFPA requires a smoke alarm on
every level and outside each sleeping area in existing construction. An existing household with one level and one sleep­ing area is required to have one smoke alarm.
O
Bedroom
Bedroom
Bedroom
O
O
Kitchen
Δ
Living Room
Bedroom
O
SINGLE STORY RESIDENCE/APARTMENT
New Construction Homes:
Bedroom Bedroom
Living Room
Utility Room
TWO STORY RESIDENCE
Bedroom
O
O
Hall
O
O
Hall
Δ
Kitchen
Basement
The NFPA requires AC-powered, inter-
connected smoke alarms to be installed inside each bedroom, outside each bedroom area, and on
Bedroom
every level of the home. They also require a minimum of two AC-powered, interconnected smoke alarms in any
Bedroom Bedroom
Hall
new construction home.
Bedroom
Bedroom
Bedroom
Kitchen
Δ
Living Room
Bedroom
SINGLE STORY RESIDENCE/APARTMENT
O
Living Room
O
Utility Room
TWO STORY RESIDENCE
Hall
Kitchen
Basement
Δ
Key
NFPA minimum REQUIRED smoke alarm locations
O Additional Smoke Alarm RECOMMENDED by
Invensys Controls Americas, NFPA, and California State Fire Marshal
Δ RECOMMENDED type with False Alarm Control
--- Denotes interconnection
Mobile Home Installation:
For minimum protection, smoke alarms should be installed in compli-
ance with H.U.D. Manufactured Home Construction Safety Standards Title 24 CFR, Section 3280.208 and Section 3282.
For additional protection, see single story residence smoke alarm
requirements/recommendations for existing homes and new construc­tion above.
ADDITIONAL SMOKE ALARM
If a bedroom area hallway is more than 30 feet long, install a smoke
alarm at each end. In basements, install a smoke alarm on
the ceiling at the bottom of the stairwell. Install a smoke alarm at the top of a
first-to-second floor stairwell. Install a smoke alarm as close to the
center of the ceiling as possible. If this is not practical, mount no closer than 4 inches from a wall or corner. Also, if local codes allow wall mounting, you may install smoke alarms on walls between 4 and 12 inches from ceiling/wall intersections.
Install a smoke alarm in each room that
is divided by a partial wall (either coming down from the ceiling at least 24 inches, or coming up from the floor).
Install smoke alarms on peaked, cathedral, or
gabled ceilings 3 feet from the highest point (measured horizontally).
Install a smoke alarm in lived-in or
finished attics.
NOTE: For mobile homes built before 1978, install smoke alarms on
PLACEMENT INFORMATION:
4 IN
NEVER HERE
TOP OF DETECTOR ACCEPTABLE HERE
STUB WALL
(0.1m )
SOFFIT
ACCEPTABLE IN
THIS AREA
4 IN
(0.1m )
MINIMUM
12 IN
(0.3 m )
MAXIMUM
SIDE
WALL
8"
PEAKED CEILING
3 feet
CEILING
ACCEPTABLE HERE
inside walls between 4 and 12 inches from the ceiling. (Older mobile homes have little or no insulation in the ceiling.) This is especially important if the ceiling is unusually hot or cold.
3
Loading...
+ 5 hidden pages