Kidde G6 Owner's Manual

Page 1
120V AC Ionization Smoke Alarm
110-427K
MODEL G-6, H, GC PG40 and FXW-R
T
I
N
S
I
G
A
C
L
L
I
F
F
O
O
R
E
N
T
I
A
A
T
S
S
L
T
A
A
H
T
E
S
R
F
A
I
S
R
M
E
E
E
C
R
I
V
PLEASE READ AND SAVE THIS MANUAL
Installer: Please leave this manual with the occupier (or, in the case of a house in multiple operation, with the owner)
The ionization type alarms are generally more effective at detecting fast, flaming fires which consume combustible materials rapidly and spread quickly. Sources of these fires may include flammable liquids or paper burning in a waste container. The photoelectric type alarms are generally more effective at detecting slow, smoldering fires which smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. However, both types of alarms are designed to provide adequate detection of both types of fires. If you desire the benefits of both systems, you should install smoke alarms that combine in one alarm both photoelectric and ionization sensing technologies.
SMOKE ALARM FEATURES
Model PG40 and GC smoke alarms can be interconnected with as many
as 11 other specific model smoke alarms (Model G-6, as many as 5). Model GC features False Alarm Control that temporarily
silences nuisance alarms. Multi-purpose LED indicates that the smoke alarm is receiving
AC power, working under normal operation, or in alarm. Loud alarm horn—85 decibels at 10 feet—sounds to alert you
to a fire emergency. This alarm incorporates the internationally recognized horn sig-
nal for evacuation. During alarm mode, the horn produces three short beeps followed by a 2 second pause and then repeats. This pattern is somewhat different than the previous alarm sound, which continually beeped.
Model FXW-R is a direct replacement for Firex models FX1014,
FX1020, FX1106, and FXW-1A. Model FXW-R cannot be inter­connected with any other smoke alarm.
Test button checks smoke alarm operation.
IMPORTANT SAFETY INFORMATION PLEASE
READ AND SAVE THESE INSTRUCTIONS
!
This smoke alarm requires constant 120-volt, AC power to operate. It
will not work if AC power is not connected or has failed or been interrupted for any reason. DO NOT turn off AC power to quiet false alarms. Open win­dows or fan the air around smoke alarm to silence it.The Push-to-Test but­ton accurately tests all smoke alarm functions. DO NOT use any other test method. Test smoke alarm weekly.We recommend you install smoke alarms that operate from both battery and AC power.Having smoke alarms that work from two different power sources can give extra protection in case of a dead battery or an AC power failure.If you have repeated false alarms, move the smoke alarm to a different location, or install specialized smoke alarms with a False Alarm Control or a photoelectric sensor.
This smoke alarm should be installed only by a licensed, quali-
fied electrician. Observe and follow all local and national electrical and building codes for installation.
This smoke alarm is designed to be used INSIDE a single family
household only. In multi-family buildings, each individual living unit should have its own smoke alarms. It is not designed for use in common areas, stairwells, or common hallways in multi-family buildings.
This smoke alarm IS NOT designed to be the PRIMARY protec-
tion for buildings that require complete fire alarm systems.
Buildings of this type include hotels, motels, dormitories, hospitals, nursing homes, and group homes. This is true even if they were once single family homes. However, this smoke alarm MAY be used
inside individual rooms as SUPPLEMENTAL protection.
WARNING
1
Page 2
DO NOT connect this smoke alarm to any other smoke alarm or
devices except as specifically listed in this manual. Model PG40, GC and FXW-R smoke alarms can be interconnected with up to 11 other spe­cific model smoke alarms (Model G-6, as many as 5). DO NOT use exter-
nal bug screens or alarm guards. This may cause improper operation.
Smoke alarms must not be used with detector guards unless
the combination of alarm and guard has been evaluated and found suitable for that purpose.
Smoke alarms sound their alarm horns when they detect smoke.
They do not detect heat, flame, or gas.They will not operate if smoke does not reach the smoke alarm.
We recommend that you install a smoke alarm in every room and
on every level of the home. Smoke may not reach the smoke alarm for many reasons. For example, if a fire starts in a remote part of the home, on another level, in a chimney, wall, roof, or on the other side of a closed door, smoke may not reach the smoke alarm in time to alert household members. A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed.
Model G-6, PG40, GC and FXW-R smoke alarms meet all NFPA
requirements for new and existing homes. Per the National Fire Protection Association (NFPA) Standard 72, Chapter 2, this type of smoke alarm can be used to meet the minimum requirements for new and existing residential dwellings.The standard requires that smoke alarms for new residential dwellings be AC powered and interconnect­ed. Therefore, Model G-6, PG40, and GC can be used to meet the mini­mum requirements for new construction residential dwellings.
Smoke alarms may not alert every household member every
time. There may be limiting circumstances where a household member may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, the hard of hearing, etc.). If you suspect that this smoke alarm may not alert a household member, install and maintain specialty smoke alarms. Current studies have shown smoke alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.
This smoke alarm will not provide adequate escape or rescue
time in extremely fast moving fires. Fast fires include gas fires, flammable liquid fires, or fires set on purpose. The smoke alarm will not give adequate escape time to people very close to the fire. Such examples might be, children playing with matches or smokers who fall asleep and drop a cigarette into their bed.
Smoke alarms have limitations. This smoke alarm is not foolproof
and is not warranted to protect lives or property from fire. Smoke alarms are not a substitute for insurance. Homeowners and renters should insure their lives and property. In addition, it is possible for the smoke alarm to fail at any time. For this reason, you must test
the smoke alarm weekly and replace it every 10 years.
SMOKE ALARM PLACEMENT
Invensys Controls Americas recommends complete coverage pro­tection achieved by installing a smoke alarm in every room of your home. The National Fire Protection Association’s (NFPA) MINIMUM requirement for locating smoke alarms in family living units is detailed in NFPA Standard 72, Chapter 2. It reads as follows:
“2-2.1.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each addi­tional story of the family living unit including basements and excluding crawl spaces and unfinished attics. In new construction a smoke detector also shall be installed in each sleeping room."
Further, section 2-2.2.1 states that: “In new construction, where more than one smoke detector is required by
2-2.1, they shall be so arranged that operation of any smoke detector shall cause the alarm in all smoke detectors within the dwelling to sound."
The NFPA, 1993 Edition, Appendix A, however, clearly points out that: “The required number of smoke detectors [as defined in the paragraphs
above] may not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke detectors. For this reason, it is recommended that the householder con­sider the use of additional smoke detectors for those areas for increased protection. The additional areas include: basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke detectors.”
Further, the California State Fire Marshal states that the minimum number of required smoke alarms is not enough to give the earliest warning under all conditions.The California State Fire Marshal states that:
“Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed in each separate sleeping area (in the vicinity, but outside the bedrooms), and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.”
It is clear from the above abstracts that the earliest warning of a developing fire is best achieved by the installation of smoke alarms in all rooms and areas of the residence. Accordingly, Invensys Controls Americas recommends that you install smoke alarms in every room of your residence, even though this is not required by the typical code or standard.
2
Page 3
FOR MAXIMUM COVERAGE, WE RECOMMEND THAT YOU INSTALL A SMOKE ALARM IN EVERY ROOM OF THE HOME, INCLUDING BASEMENTS AND FINISHED ATTICS. In addition, we recommend interconnecting all smoke alarms capable of being interconnected.
Invensys Controls Americas recommends a minimum of two smoke alarms in every home, no matter how small the home (including effi­ciency apartments). Invensys Controls Americas also recommends maximum coverage by installing smoke alarms in both required and recommended locations as illustrated and described.
SMOKE ALARM PLACEMENT (Cont’d)
Existing Homes:
The NFPA requires a smoke alarm on
every level and outside each sleeping area in existing construction. An existing household with one level and one sleep­ing area is required to have one smoke alarm.
O
Bedroom
Bedroom
Bedroom
O
O
Kitchen
Δ
Living Room
Bedroom
O
SINGLE STORY RESIDENCE/APARTMENT
New Construction Homes:
Bedroom Bedroom
Living Room
Utility Room
TWO STORY RESIDENCE
Bedroom
O
O
Hall
O
O
Hall
Δ
Kitchen
Basement
The NFPA requires AC-powered, inter-
connected smoke alarms to be installed inside each bedroom, outside each bedroom area, and on
Bedroom
every level of the home. They also require a minimum of two AC-powered, interconnected smoke alarms in any
Bedroom Bedroom
Hall
new construction home.
Bedroom
Bedroom
Bedroom
Kitchen
Δ
Living Room
Bedroom
SINGLE STORY RESIDENCE/APARTMENT
O
Living Room
O
Utility Room
TWO STORY RESIDENCE
Hall
Kitchen
Basement
Δ
Key
NFPA minimum REQUIRED smoke alarm locations
O Additional Smoke Alarm RECOMMENDED by
Invensys Controls Americas, NFPA, and California State Fire Marshal
Δ RECOMMENDED type with False Alarm Control
--- Denotes interconnection
Mobile Home Installation:
For minimum protection, smoke alarms should be installed in compli-
ance with H.U.D. Manufactured Home Construction Safety Standards Title 24 CFR, Section 3280.208 and Section 3282.
For additional protection, see single story residence smoke alarm
requirements/recommendations for existing homes and new construc­tion above.
ADDITIONAL SMOKE ALARM
If a bedroom area hallway is more than 30 feet long, install a smoke
alarm at each end. In basements, install a smoke alarm on
the ceiling at the bottom of the stairwell. Install a smoke alarm at the top of a
first-to-second floor stairwell. Install a smoke alarm as close to the
center of the ceiling as possible. If this is not practical, mount no closer than 4 inches from a wall or corner. Also, if local codes allow wall mounting, you may install smoke alarms on walls between 4 and 12 inches from ceiling/wall intersections.
Install a smoke alarm in each room that
is divided by a partial wall (either coming down from the ceiling at least 24 inches, or coming up from the floor).
Install smoke alarms on peaked, cathedral, or
gabled ceilings 3 feet from the highest point (measured horizontally).
Install a smoke alarm in lived-in or
finished attics.
NOTE: For mobile homes built before 1978, install smoke alarms on
PLACEMENT INFORMATION:
4 IN
NEVER HERE
TOP OF DETECTOR ACCEPTABLE HERE
STUB WALL
(0.1m )
SOFFIT
ACCEPTABLE IN
THIS AREA
4 IN
(0.1m )
MINIMUM
12 IN
(0.3 m )
MAXIMUM
SIDE
WALL
8"
PEAKED CEILING
3 feet
CEILING
ACCEPTABLE HERE
inside walls between 4 and 12 inches from the ceiling. (Older mobile homes have little or no insulation in the ceiling.) This is especially important if the ceiling is unusually hot or cold.
3
Page 4
DO NOT install smoke alarms:
In areas where combustion particles are present. (Combustion particles are the by-products of something that is burning.) Areas to avoid include poorly ventilated kitchens, garages, near furnaces, or near hot water heaters. Place smoke alarm as far from the source of combustion particles as possible to prevent nuisance alarms.
In damp or very humid areas—such as bathrooms with showers—where the normal humidity may rise above 93% relative humidity. Areas above this humidity level can cause a false alarm.
In direct air flow nor within 3 feet of heating and cooling supply vents. Install at least 3 feet (0.9 meters) away from these areas. The air could blow smoke away from the detector, interrupting its alarm.
In rooms where temperatures may fall below 40˚F (4˚C) or rise above 100˚F (38˚C).
In extremely dusty, dirty, or insect-infested areas. Loose particles interfere with smoke alarm operation and may cause a nuisance alarm.
Within 3 feet of fluorescent lighting. Electrical noise may cause nuisance alarms.
HOW TO INSTALL THIS SMOKE ALARM
!
DANGER: ELECTRICAL SHOCK HAZARD. Turn off
power at the main fuse box or circuit breaker by removing the fuse or switching the circuit breaker to the OFF position.
!
WARNING: This smoke alarm should be installed only
by a qualified electrician. Smoke alarm wiring to be used shall be in accordance with the provisions of Article 210 and 760 of the National Electrical Code, ANSI/NFPA 70, and any local codes that may apply. Interconnect wire location shall be in accordance with NEC Article 300.3b.
THIS SMOKE ALARM SHOULD BE INSTALLED IN ACCOR­DANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIA­TION’S STANDARD 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
Connect smoke alarms to a dedicated AC branch circuit. If local codes do not permit, be sure the neutral wire is common to both phases.
Install smoke alarm on a 4-inch
octagon or single gang junction box only.
1. From back of smoke alarm,
BLACK
unlock and remove mounting plate by turning plate counter­clockwise.
BLACK
2. Align plate with mounting holes of a 4-inch octagon or single gang junction box.
3. Gently pull household wires through center hole of plate.
4. Secure plate to junction box.
5. With a small wire connector, connect white wire from connector plug to white household wire.
6. Connect black wire from connector plug to black household wire.
7. If interconnection is desired, connect yellow wire (orange on model FXW-R) from connector to interconnect wire between smoke alarms. See INTERCONNECTING SMOKE ALARMS.
INTERCONNECT
WIRE CONNECTOR
YELLOW (ORANGE ON MODEL FXW-R)
WHITE
!
WARNING: Do not interconnect Firex smoke alarms
with yellow interconnect leads to Firex smoke alarms with orange interconnect leads. Violating this warning will result in damage to the smoke alarm.
NOTE: If this will be a single-station smoke alarm, cover yellow
wire (orange on model FXW-R) with electrical tape and tuck into junction box.
8. Attach connector plug to pins on back of smoke alarm. Plug
will fit only one way.
9. Gently tug connector to be sure it is attached securely.
10. Position smoke alarm to mounting plate and turn clockwise to
lock into place.
4
Page 5
11. Turn on power at main fuse box or circuit breaker.
12. Test smoke alarm. See TESTING THE SMOKE ALARM.
INTERCONNECTING
SMOKE ALARMS
!
WARNING:This smoke alarm should be installed only
IMPORTANT: The model FXW-R is a direct replacement
IMPORTANT: Do not interconnect Firex smoke alarms
IMPORTANT: Do not attempt to interconnect with any
As many as 12 Model GC & PG40 (6 for Model G-6) smoke alarms may be interconnected.
As many as 12 Model FXW-R smoke alarms may be interconnected.
Connect smoke alarms to a dedicated AC branch circuit. If local codes do not permit, be sure the neutral wire is common to both phases.
by a qualified electrician. Smoke alarm wiring to be used shall be in accordance with the provisions of Article 210 and 760 of the National Electrical Code, ANSI/NFPA 70, and any local codes that may apply. Interconnect wire location shall be in accordance with NEC Article 300.3b.
for Firex models FX1014, FX1020, FX1106 and FXW-1A. Model FXW-R cannot be inter­connected with any other smoke alarm.
with yellow interconnect wires to Firex smoke alarms with orange interconnect wires.
other type of device or manufacturer’s brand.
WHITE WHITE WHITE
YELLOW* YELLOW*
BLACK BLACK BLACK
*(Orange on Model FXW-R)
TO NEUTRAL
TO 120 VAC
LED INDICATORS
This smoke alarm features an LED indicator which can be seen through the Push-to-Test button.The LED indicates the following:
Blinks once a minute — indicating normal operation. Blinks once a second — smoke alarm senses smoke and
Blinks once approximately — False Alarm Control (FAC) every 10 seconds feature activated (model GC only).
OFF — another smoke alarm in the (Interconnected system only): network has sensed smoke and
simultaneously sounds an audi­ble alarm.
is signalling this alarm.
FALSE ALARM CONTROL
Model GC features a False Alarm Control that, when activated, quiets unwanted alarms for up to 15 minutes.
To use the False Alarm Control: Press and release the test button during an unwanted alarm. The alarm
should stop within ten seconds.This means the smoke alarm is in False Alarm Control.
If the smoke alarm does not go into False Alarm Control and continues to sound its loud alarm horn, or if it initially goes into False Alarm Control then resounds the alarm, the smoke is too heavy and a dangerous situation could exist—take emergency action.
NOTE: In an interconnected circuit, False Alarm Control must be activated on the initiating unit.
5
Page 6
TESTING THE
SMOKE ALARM
!
DANGER: If alarm horn sounds, and smoke alarm is not
Test each smoke alarm weekly to be sure it is installed cor-
rectly and operating properly. Test smoke alarms upon returning from vacation. Also test
when no one has been in the household for several days.
Stand at arm’s length from the smoke alarm when testing.
The alarm horn is loud to alert you to an emergency.The alarm horn may be harmful to your hearing.
The Push-to-Test button accurately tests all functions. NEVER use
an open flame from a match or lighter to test this smoke alarm. You may ignite and set fire to the smoke alarm and your home.
Test all smoke alarms weekly as follows:
1. Look at the Push-to-Test button. A light flashing about once a minute indicates the smoke alarm is receiving 120V AC power. See LED INDICATORS above.
2. Firmly depress the Push-to-Test button for at least five (5) sec­onds. The smoke alarm will sound its horn loudly. The alarm may sound for up to 10 seconds after releasing the Push-to­Test button.
3. If smoke alarm does not sound, replace the smoke alarm immediately. If the smoke alarm is under warranty, see warran­ty information at the end of this manual for more information.
REPLACE OR RETURN THE ALARM IF THE PUSH-TO-TEST FUNCTION DOES NOT OPERATE PROPERLY AFTER FOLLOWING THE PROCEDURES OUTLINED ABOVE (see REPAIR below).
being tested, the smoke alarm is sensing smoke. THE SOUND OF THE ALARM HORN REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION.
WARNING
CLEANING
In addition to weekly testing, this smoke alarm requires periodic cleaning. Periodic cleaning will remove dust, dirt, and debris.
DANGER: ELECTRICAL SHOCK HAZARD. Turn off power
at main service panel by removing fuse or switching appropriate circuit breaker to OFF position before cleaning smoke alarm.
CLEANING
Always turn off power to smoke alarm before cleaning. Clean the smoke alarm at least once a month to remove dust, dirt, or
debris as follows:
Using the wand attachment of a powerful vacuum cleaner, vacuum
all sides and the cover of smoke alarm. Be sure all the vents are free of debris.
If necessary, turn off power and use a damp cloth to clean smoke
alarm cover.
IMPORTANT: Do not attempt to remove the cover or clean inside the
smoke alarm. THIS WILL VOID YOUR WARRANTY.
REPAIR
CAUTION: Do not attempt to repair this smoke alarm.
If smoke alarm is not operating properly, see TROUBLESHOOTING on page 7. If you cannot solve the problem, and if the alarm is still under warranty, return smoke alarm to Invensys Controls Americas. Pack it in a well-padded carton, shipping prepaid, to:
If the smoke alarm is no longer under warranty, replace the smoke alarm immediately with a comparable Firex brand smoke alarm.
Doing so will void your warranty.
Invensys Controls Americas
Product Service Department 28C Leigh Fisher Blvd. El Paso, TX 79906
6
Page 7
Firex Replacement Guide
You Have You’ll Need
Model Model # Item #
G-6 G-6 or GC 406 or 41216
G-18, G-120, H or GC GC 41216
PG-40 PG-40 484
FXW-R, FX1014, FX1020 FXW-R 428
FXW-1A, or FX1106
PRACTICE FIRE SAFETY
Develop family escape plans, discuss them with ALL household members, and practice them regularly.
Expose everyone to the sound of a smoke alarm and explain
what the sound means. Determine TWO exits from each room and an escape route to
the outside from each exit. Teach all household members to touch the door. INSTRUCT
THEM NOT TO OPEN THE DOOR IF THE DOOR IS HOT. Tell them to use an alternative exit if the door is hot.
Teach household members to crawl along the floor to stay below
dangerous smoke, fumes, and gases. Determine a safe meeting place for all members outside the building.
Know how to call the nearest fire department in case of emergency.
Besides practicing and understanding fire safety rules, you should:
a.Install smoke alarms in every room of your residence. b.Test smoke alarms weekly. c.Maintain smoke alarms properly. d.Keep a supply of replacement batteries on hand. e.Replace nonworking smoke alarms immediately. f. Prevent hazardous conditions and follow fire safety rules:
Keep matches and cigarette lighters out of the hands of children.
Never smoke in bed.
Store flammables in proper, closed containers and do not use
them near flame or sparks.
Keep electrical appliances in good condition.
Make sure stoves, fireplaces, chimneys, barbeque grills, and
other appliances are clean and free of grease. Be sure they are properly installed and operating as designed.
Keep operating portable heaters and burning candles away from
combustible materials.Watch them carefully.
Do not overload electrical circuits.
WHAT TO DO IN CASE OF A FIRE
1. Don’t panic; stay calm. Notify every member in the resi­dence of the fire.
2. Have all residents leave the building as quickly as possible. Touch doors to feel if they are hot before opening them. Use an alternative exit if necessary. Crawl along the floor and cover your mouth and nose with a wet cloth, if possi­ble. DO NOT stop to collect anything. Follow pre-defined escape plans, if possible.
3. Meet at a prearranged meeting place outside the building.
4. Call the fire department from OUTSIDE the building.
5. DO NOT GO BACK INSIDE A BURNING BUILDING. Wait for the fire department to arrive.
These guidelines will assist you in the event of a fire. However, to reduce the chance that fires will start, practice fire safety rules and prevent hazardous situations.
TROUBLESHOOTING
!
DANGER: ELECTRICAL SHOCK HAZARD. Always
!
WARNING: DO NOT disconnect AC power to quiet
turn off power at main fuse box or cir­cuit breaker before taking trou­bleshooting action.
an unwanted false alarm. This will remove your protection. Fan the air around the smoke alarm or open a win­dow to remove the smoke, dust, or water vapor causing the false alarm.
7
Page 8
PROBLEM SOLUTION
Smoke alarm does not Check that AC power is sound when tested. turned on.
NOTE: Push and hold test button for at least five (5) seconds when testing.
LED blinks and alarm beeps Battery is low – REPLACE simultaneously every 60 IT IMMEDIATELY! seconds.
LED blinks and 30 seconds Unit inoperable. REPLACE later alarm beeps – repeats OR RETURN FOR REPAIR at 60 second intervals. IMMEDIATELY!
Smoke alarm sounds Move smoke alarm to a unwanted alarms when new location. See residents are cooking or SMOKE ALARM taking showers. PLACEMENT or replace
with model GC smoke alarm with False Alarm Control or model PG-40 photoelectric alarm.
Interconnected smoke Press and hold test alarms do not sound when button for at least system is tested. five (5) seconds.
The alarm sounds different The alarm is operating than I’m used to. It starts and correctly. This alarm features stops. the internationally recog-
nized horn signal for evacua­tion. The horn pattern is 3 short beeps followed by a 2 second pause and then repeats.
Smoke alarm sounds Clean smoke alarm unwanted alarms at (see page 6). intermittent times.
Smoke alarm is removed but Something other than the beeping sound still emits smoke alarm is emitting the from its ceiling location. beeping.
REPLACE OR RETURN THE ALARM IF THE PUSH-TO-TEST FUNCTION DOES NOT OPERATE PROPERLY AFTER FOLLOWING THE PROCEDURES OUTLINED ABOVE (see REPAIR on page 6).
Smoke alarms must be replaced every 10 years. See date code on back of smoke alarm to determine age.
WARRANTY
Invensys Controls Americas warrants to the original consumer purchaser each new smoke alarm to be free from defects in material and workmanship under normal use and service for a period of five (5) years from date of purchase. Invensys Controls Americas agrees to repair or replace, at its option, any defective smoke alarm, provided that it is returned with postage prepaid and with proof of purchase date to Invensys Controls Americas. This warranty does not cover damage resulting from accident, misuse or abuse or lack of reasonable care of the product. This warranty is in lieu of all other express warranties, obligations, or liabilities. THE IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF FIVE (5) YEARS FROM PURCHASE DATE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitations may not apply to you. IN NO CASE SHALL INVENSYS CONTROLS AMERICAS BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, WHATSOEVER, EVEN IF THE LOSS OR DAM­AGE IS CAUSED BY ITS NEGLIGENCE OR FAULT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other legal rights which vary from state to state.
191 E. North Avenue Carol Stream, Illinois 60188 USA www.invensyscontrols.com ©2006 Invensys Controls 110-427K
8
Loading...